Electric Equipment
MCB / MS / Mini-MC / EMPR / DMPR / MMS / MCCB / ACB / VCB
Low Voltage Circuit Breakers & Contactors
●1, 2, 3 and 4 pole series up to 125AF●B, C and D Characteristics
●2 and 4 pole series up to 63AF●Sensitivity up to 300mA●Overcurrent protection type available
Metasol/Meta-MEC series●3 and 4 pole series up to 800AF Mini-contactors available●AC/DC common use coil from 100AF●Thermal (Bimetallic) and electronic type overload relays are available●CE marked and UL approved
Page 4
Page 6
Page 8
Page 18
Susol /Meta-MEC series● 2, 3 and 4 pole series up to 1600AF ●Rated ambient temperature at 40℃ calibrated for 50℃ available●CE marked according to IEC standard and UL approved MCCBs
are also available.
Susol/Metasol series●65, 85 and 150kA breaking capacity●High functional digital trip relays ●CE marked and Marine classiflcation
Susol series
Page 20
Page 26
Page 32
4
Miniature circuit breakers1, 2, 3 and 4 pole series up to 125AF
3kA at 230VAC
6kA at 400VAC
6kA at 230/400VAC
1 changeover contact
6A at 240VAC, 3A at 415VAC
2A at 48VDC, 1A at 125VDC
Lug terminal
cable capacity 2.5㎟
9mm wide
Type BKP BKN
1A
2A
3A
4A
6A
10A
16A
20A
25A
32A
40A
50A
63A
80A
100A
125A
Auxiliary switch, AXOptional
Dimension See drawing 1 See drawing 2
Characteristic curve See curve 1 See curve 1
Protection Overload and short circuit Overload and short circuit
Rated current 3,6,10,16,20,25,32A 1,2,3,4,6,10,16,20,25,32,40,50,63A
Characteristic B, C, D curve B, C, D curve
Number of poles 1p+N 1p, 1p+N, 2p, 3p, 3p+N, 4p
Breaking capacity 1 pole 2~4 pole
Standard IEC 60898 IEC 60898
Type of trip Thermal magnetic release Thermal magnetic release Thermal magnetic release
Electrical endurance 20000 operations 6000 operations
Mount On 35mm DIN rail On 35mm DIN rail
Width 9mm per pole 17.8mm per pole
Terminal Lug type(cable up to 10㎟) Lug type(cable up to 25㎟)
Drawing 1 : Type BKP
17.8
8.9
60 82
60
37
455
45
68
(22)
(22)
(17)
Drawing 2 : Type BKN
5
37
4560
(14)
45
17.8
63
68
82
5
10kA at 400VAC
10kA at400VAC
10kA at 230/400VAC
10kA at 400VAC
BKN-b BKH
See drawing 3 See drawing 4
See curve 1 See curve 1
Overload and short circuit Overload and short circuit
1,2,3,4,6,10,20,25,32,40,50,63A 63, 80, 100, 125A
B, C, D curve C, D curve
1p, 1p+N, 2p, 3p, 3p+N, 4p 1p, 1p+N, 2p, 3p, 3p+N, 4p
1 pole 2~4 pole 1 pole 2~4 pole
IEC 60898 IEC 60947-2
Thermal magnetic release
8000 operations 6000 operations
On 35mm DIN rail On 35mm DIN rail
17.8mm per pole 27mm per pole
Lug type(cable up to 25㎟) Lug type(cable up to 50㎟)
Drawing 3 : Type BKN-b
17.8
(33)
(19)
4537
5 43.8
6860
65 82
Drawing 4 : Type BKH
Curve 1 : Type BKP, BKN, BKN-b, BKH, RKP
6
Residual current circuit breakers 2 and 4 pole series up to 63AF
Drawing 1 : Type RKP
35.6
8.9
8260
45
60
5
(22)
68
37
(22)
(17)
45
70
Drawing 2 : Type RKN
561
74
(13)45
36 45
22
72
68 82
36
68 82
1 3 5 N
2
1
24 6 N
N
N
Drawing 3 : Type KGR Drawing 4 : Type BKD
37
5
60
70
45
(10)
45
60
17.8
82
Drawing 5 : Type RKS
5523
18
18
Type RKP RKS RKN
Protection Ground fault and overcurrent Ground fault and overcurrent Ground fault Ground fault
Rated current, In 3(C,D),6,10,16,20,25,32A(B,C,D curve) 6, 10, 16, 20, 25, 32A (B, C curve) 25, 32, 40, 63A
Rated residual current
Operating, I△n 30, 100, 300mA(non-adjustable) 30, 100mA (non-adjustable) 30, 100, 300mA(non-adjustable)
Non-operating, I△no 0.5I△n 0.5I△n 0.5I△n
Number of poles 1P+N 1P+N 2, 4 pole
Rated voltage 230VAC 230VAC 230VAC(2p), 230/400VAC(4p)
Residual current off-time ≤ 0.1 sec. ≤ 0.3 sec. ≤ 0.1 sec.
Standard IEC 61009 IEC 61009 IEC 61008
Type of trip
Ground fault Electro-magnetic Electro-magnetic Electro-magnetic
Overcurrent Thermal-magnetic Thermal-magnetic N.A
Breaking capacity 4.5kA 10kA
Conditional short circuit capacity 6kA for In=25, 32, 40, 63A
Electrical endurance 20000 operations ≤ 4000 operations 6000 operations
Mount On 35mm DIN rail On 35mm DIN rail On 35mm DIN rail
Width 9mm per pole 9mm per pole 18mm per pole
Terminal Lug type(cable up to 10㎟) Lug type(cable up to 10㎟) Lug type(cable up to 35㎟)
Dimension See drawing 1 See drawing 5 See drawing 2
Characteristic curve See page 5 (curve 1)
7
Type BKDRated current, In 40, 50, 63, 80, 100, 125A
Number of poles 1p, 2p, 3p, 4p
Rated voltage 230/400VAC
Standard IEC 60947-3
Electrical 40, 50, 63A 20000 operationsendurance 80, 100, 125A 10000 operations
Mount On 35mm DIN rail
Width 17.8mm per pole
Terminal Lug type(cable up to 50㎟)
Dimension See drawing 4
32KGRb32KGRa
Curve 1 : Type 32KGRa, 32KGRb
Ground fault and overcurrent
15, 20, 30A
15, 30mA(non-adjustable)
0.5I△n
2 pole
110/220VAC
≤ 0.03 sec.
KS, JIS *(IEC61009)
Electronic
Bimetallic
1.5kA 2.5kA
6000 operations
On 35mm DIN rail
35mm
Screw clamp type(cable up to 25㎟)
See drawing 3
See curve 1
Note) * IEC61009 standard is applicable for 32KGRa only.
8
Contactors & Overload relaysMetasol MC 18 to 100A
MC type
Thermal Overload RelaysMT type
Magnetic Contactors
* The safety cover of magnetic contactor and thermal overload relay is optional.
MT-12/�
●
690V
690V
6kV
10A, 20
0.1~18A
0.17
45×73.2×63.7
Type
Screws clamp terminals
Rated operational voltage, Ue
Rated insulation voltage, Ui
Rated impulse withstand voltage, Uimp
Trip class
Setting range
Size Weight kg
and
weightSize(W×H×D) mm
WD
H
MC-6a MC-9a MC-12a MC-18a
● ● ● ●
3pole
690V
690V
50/60Hz
6kV
1800 operations per hour
15 mil. operations
2.5 mil. operations
25 25 25 32
2.5 2.5 3.5 4.5
9 11 13 18
3 4 5.5 7.5
7 9 12 18
3 4 7.5 7.5
6 7 12 13
3 4 7.5 7.5
4 6 9 9
1.5 1.5 2.2 3.7
7 8 11 16
2.2 2.2 4 4
5 6 9 11
0.33
45×73.5×82
0.47
45×83×113.7
1a or 1b
UA-1
AU-2, AU-4
18AF
Note) Minimum conduct current of Auxiliary contactor is DC 17V 5mA.
Type
screws clamp terminals
Number of poles
Rated operational voltage, Ue
Rated insulation voltage, Ui
Rated frequency
Rated impulse withstand voltage, Uimp
Maximum operating rate in operating cycles per hour(AC3)
Durability Mechanical
Electrical
Current AC-1, Thermal current A
and AC-3 200/240V kW
power A
380/440V kW
A
500/550V kW
A
690V kW
A
AC-4 200/240V kW
A
380/440V kW
A
Size AC Weight kg
and control Size(W×H×D) mm
weight DC Weight kg
control Size(W×H×D) mm
Auxiliary(standard)
Auxiliary Side mount
Front mount
Frame size
WD
H
MT-32/�
●
690V
690V
6kV
10A, 20
0.1~40A
0.17
45×75×90
MC-9b MC-12b MC-18b MC-22b*
● ● ● ●
3pole
690V
690V
50/60Hz
6kV
1800 operations per hour
15 mil. operations
2.5 mil. operations
25 25 32 40
2.5 3.5 4.5 5.5
11 13 18 22
4 5.5 7.5 11
9 12 18 22
4 7.5 7.5 15
7 12 13 20
4 7.5 7.5 15
6 9 9 18
1.5 2.2 3.7 3.7
8 11 16 18
2.2 4 4 5.5
6 9 11 13
0.46
45×73.5×86
0.47
45×73.5×117.7
1a1b
UA-1
AU-2, AU-4
22AF
9
MT-95/�
●
690V
690V
6kV
10A, 20
7~100A
0.48/0.5
70×97×110
MT-63/�
●
690V
690V
6kV
10A, 20
4~65A
0.31/0.33
55×81×100
100AF
MC-50a MC-65a
● ●
3pole
690V
1000V
50/60Hz
8kV
1800 operations per hour
12 mil. operations
2 mil. operations
70 100
15 18.5
55 65
22 30
50 65
30 33
43 60
30 33
28 35
7.5 11
35 50
15 22
32 47
1.05
79×106×122
1.3
79×106×149
2a2b
UA-1
AU-2, AU-4
65AF
MT-32/�
●
690V
690V
6kV
10A, 20
0.1~40A
0.17
45×75×90
MC-32a MC-40a
● ●
3pole
690V
1000V
50/60Hz
8kV
1800 operations per hour
12 mil. operations
2 mil. operations
50 60
7.5 11
32 40
15 18.5
32 40
18.5 22
28 32
18.5 22
20 23
4.5 5.5
20 25
7.5 11
17 24
0.55
69×83×93
0.77
69×83×120
2a2b
UA-1
AU-2, AU-4
40AF
MC-75a MC-85a MC-100a
● ● ●
3pole
690V
1000V
50/60Hz
8kV
1800 operations per hour
12 mil. operations
2 mil. operations
110 135 160
22 25 30
75 85 105
37 45 55
75 85 105
37 45 55
64 75 85
37 45 45
42 45 65
13 15 19
55 65 80
25 30 37
52 62 75
1.93
94×140×137
2.8
94×140×174
2a2b
UA-1
AU-2, AU-4
10
Contactors & Overload relaysMetasol MC 150 to 800A
MC type
Thermal Overload RelaysMT type
Magnetic Contactors
MT-150/�
●
690V
690V
6kV
10A, 20
34~150A
0.67
95×109×113
Type
Screws clamp terminals
Rated operational voltage, Ue
Rated insulation voltage, Ui
Rated impulse withstand voltage, Uimp
Trip class
Setting range
Size Weight kg
and
weightSize(W×H×D) mm
WD
H
MC-130a MC-150a
● ●
3pole
690V
1000V
50/60Hz
8kV
1200 operations per hour
5 mil. operations
1 mil. operations
160 210
37 45
130 150
60 75
120 150
60 75
90 100
55 55
60 60
22 30
93 120
45 55
90 110
2.1
95×158×132
2.1
95×158×132
UA-1
AU-2, AU-4
150AF
Type
screws clamp terminals
Number of poles
Rated operational voltage, Ue
Rated insulation voltage, Ui
Rated frequency
Rated impulse withstand voltage, Uimp
Maximum operating rate in operating cycles per hour(AC3)
Durability Mechanical
Electrical
Current AC-1, Thermal current A
and AC-3 200/240V kW
power A
380/440V kW
A
500/550V kW
A
690V kW
A
AC-4 200/240V kW
A
380/440V kW
A
Size AC Weight kg
and control Size(W×H×D) mm
weight DC Weight kg
control Size(W×H×D) mm
Auxiliary(standard)
Auxiliary Side mount
Front mount
Frame size
WD
H
MT-225/�
●
690V
690V
6kV
10A, 20
65~240A
2.5
147×141×184
MC-185a MC-225a
● ●
3pole
690V
1000V
50/60Hz
8kV
1200 operations per hour
5 mil. operations
1 mil. operations
230 275
55 75
185 225
90 110
185 225
110 132
180 200
110 140
120 150
37 45
150 180
75 90
150 180
5.4
138×203×181
AU-100 (Max.4NO4NC)
225AF
11
MT-400/�
●
690V
690V
6kV
10A, 20
85~400A
2.6
151×171×198
400AF
MC-265a MC-330a MC-400a
● ● ●
3pole
690V
1000V
50/60Hz
8kV
1200 operations per hour
5 mil. operations 2.5 mil. operations
1 mil. operations 0.5 mil. operations
300 350 450
80 90 125
265 330 400
132 150 200
265 330 400
140 160 200
225 280 350
160 200 250
185 225 300
50 55 75
200 220 300
102 110 150
200 220 300
9.2
163×243×198
AU-100 (Max.4NO4NC)
MT-800/�
●
690V
690V
6kV
10A, 20
200~800A
11.5
360×530×212
800AF
MC-500a MC-630a MC-800a
● ● ●
3pole
690V
1000V
50/60Hz
8kV
1200 operations per hour
2.5 mil. operations
0.5 mil. operations
580 660 900
147 190 220
500 630 800
250 300 400
500 630 800
250 300 400
400 500 720
300 400 500
380 420 630
90 110 160
350 400 630
176 200 300
350 400 630
22.4
285×312×242
AU-100 (Max.4NO4NC)
12
Contactors & Overload relays9 to 85A
2-poleSide mount
4-poleFront mount
2-poleFront mount
Types AC coil GMC-9 GMC-12 GMC-18 GMC-22
DC coil GMD-9 GMD-12 GMD-18 GMD-22
Ratings / IEC60947-4 kW A kW A kW A kW A
AC1 25 25 40 40AC3 200/240V 2.5 11 3.5 13 4.5 18 5.5 22
380/440V 4 9 5.5 12 7.5 18 11 22500/550V 4 7 7.5 12 7.5 13 15 22
690V 4 5 7.5 9 7.5 9 15 18
Ratings / UL508 hp A hp A hp A hp A
continuous current 20 25 30 32
single phase 115V 0.5 0.5 1 2
230V 1 2 3 3
three phase 200V 2 3 5 7
230V 2 3 5 7.5
460V 5 7.5 10 10575V 7.5 10 15 15
NEMA size 00 00 0 0
Types AC coil GMC-9/4 GMC-12/4 GMC-18/4 GMC-22/4
DC coil GMD-9/4 GMD-12/4 GMD-18/4 GMD-22/4
AC1(A) 20 20 25 32
Additional auxiliary contacts
3-pole Contactors
9A 12A 18A 22AFrame size
4-pole Contactors
Overload Relays
Bimetallic styleType GT
Base for separate mount
Settingranges (A)
Differential
Class10A Non-differential (3-heater)
Non-differential (2-heater)
Class 20 Differential
GTK-22GTH-22/3GTH-22
GTK-22/L
0.1 - 0.160.16 - 0.250.25 - 0.40.4 - 0.63
0.63 - 11 - 1.6
1.6 - 2.52.5 - 4
4 - 65 - 86 - 97 - 109 - 13
12 - 1616 - 22
Electronic styleType GMP
Class 1�30 adjustableSeparate mount type
GMP22
Setting ranges (A)
0.1 - 1.51 - 5
4.4 - 22
GT-22
13
Base for separate mount
Setting ranges(A) : 16 ~ 80A
Separate mountWiring by screw
GMP80
Setting ranges(A) : 5 ~ 60A
Separate mountWiring by CT tunnelGMP60
Setting ranges (A)4 - 20
8 - 40
GMC-32 GMC-40 GMC-50 GMC-65 GMC-75 GMC-85
GMD-32 GMD-40 GMD-50 GMD-65 GMD-75 GMD-85
kW A kW A kW A kW A kW A kW A
50 60 80 100 110 1357.5 32 11 40 15 55 18.5 65 22 75 25 85
15 32 18.5 40 22 50 30 65 37 75 45 8518.5 28 22 32 30 43 33 60 37 64 45 75
18.5 20 22 23 30 28 33 35 37 42 45 45
hp A hp A hp A hp A hp A hp A
45 50 70 80 90 100
2 3 3 5 5 7.5
5 5 7.5 10 15 15
7.5 10 10 15 20 25
10 10 15 20 25 30
20 25 30 40 50 5020 25 30 40 50 50
1 1 2 2 2 3
GMC-32/4 GMC-40/4 GMC-50/4 GMC-65/4 GMC-75/4 GMC-85/4
GMD-32/4 GMD-40/4 GMD-50/4 GMD-65/4 GMD-75/4 GMD-85/4
50 60 80 100 110 135
32A 40A 50A 65A 75A 85A
Base for separate mountGT-85
Setting ranges (A)
GTK-40
GTH-40/3
GTH-40
GTK-40/L
GTK-85
GTH-85/3
GTH-85
GTK-85/L
7 - 109 - 13
12 -1816 - 2218 - 2624 - 36
28 - 4034 -5045 - 6554 - 7563 - 85
GT-40
Setting ranges (A)
4 - 65 - 86 - 97 - 109 - 13
12 -1816 - 2218 - 2624 - 3628 - 40
separate mount
GMP40
2-poleSide mount
4-poleFront mount
2-poleFront mount
14
Contactors & Overload relays100 to 800A
Types AC/DC GMC-100 GMC-125 GMC-150 common coil
Ratings / IEC60947-4 kW A kW A kW A
AC1 160 160 210
AC3 200/240V 30 105 37 125 45 150
380/440V 55 105 60 120 75 150
500/550V 55 85 60 90 90 140
690V 55 65 60 70 90 100
Ratings / UL508 hp A hp A hp A
continuous current 160 160 210
single phase 115V 7.5 10 15
230V 15 20 25
three phase 200V 30 40 40
230V 30 40 50
460V 60 75 100
575V 60 75 100
NEMA size 3 3 4
Types AC/DC GMC-100/4 GMC-125/4 GMC-150/4common coil
AC1(A) 160 160 210
Additional auxiliary contacts
3-pole Contactors
100A 125A 150AFrame size
4-pole Contactors
Overload Relays
Bimetallic styleType GT
GT- 100
Setting ranges (A)
Differential
Class10A Non-differential (3-heater)
Non-differential (2-heater)
Class 20 Differential
GTK-100
GTH-100/3
GTH-100
GTK-100/L
GTK-150
GTH-150/3
GTH-150
GTK-150/L
34 - 50
39 - 57
43 - 65
54 - 80
65 - 100
85 - 125GT- 150
Setting ranges (A)
34 - 50
39 - 57
43 - 65
54 - 80
65 - 100
85 - 125
100 - 150
AU-1001NO+1NC, Side mount
15
GTK-220
GTH-220/3
GTH-220
GTK-220/L
GTK-400
GTH-400/3
GTH-400
GTK-400/L
GTK-600
GTH-600/3
GTH-600
GTK-600/L
GMC-180 GMC-220 GMC-300 GMC-400 GMC-600 GMC-800
kW A kW A kW A kW A kW A kW A
230 275 350 450 660 900
55 180 75 250 90 300 125 400 190 630 220 800
90 180 132 250 160 300 220 400 330 630 440 800
110 180 132 200 160 250 225 350 330 500 550 720
110 120 132 150 200 220 250 300 330 420 500 630
hp A hp A hp A hp A hp A hp A
230 275 350 450 660 900
15 15
30 40
60 60 100 125 150 250
60 75 100 150 200 300
125 150 200 300 400 600
125 150 200 300 400 600
4 4 5 5 6 7
GMC-180/4 GMC-220/4 GMC-300/4 GMC-400/4 GMC-600/4 GMC-800/4
230 275 350 450 660 900
180A 220A 300A 400A 600A 800A
GT- 220
Setting ranges (A)
65 - 100
85 - 125
100 - 150
120 - 180
160 - 240GT- 400
Setting ranges (A)
85 - 125
100 - 150
120 - 180
160 - 240
220 - 300
260 - 400
Setting ranges (A)
220 - 300
260 - 400
400 - 600
520 - 800
GT- 800
AU-1001NO+1NC, Side mount
16
Mini contactors6 to 16A
3NO main contacts
1 auxiliary contactsScrew clamp type Fast-on type Cage clamp type Solder pin type
Mini contactors
Overload Relays
Bimetallic styleType GT
Screw clamp type AC coil GMC-6M GMC-9M GMC-12M GMC-16M
DC coil GMD-6M GMD-9M GMD-12M GMD-16M
Fast-on type AC coil GMC-6MF GMC-9MF GMC-12MF GMC-16MF
DC coil GMD-6MF GMD-9MF GMD-12MF GMD-16MF
Cage clamp type AC coil GMC-6MC GMC-9MC GMC-12MC GMC-16MC
DC coil GMD-6MC GMD-9MC GMD-12MC GMD-16MC
Solder pin type AC coil GMC-6MP GMC-9MP GMC-12MP GMC-16MP
DC coil GMD-6MP GMD-9MP GMD-12MP GMD-16MP
Ratings / IEC60947-4 kW A kW A kW A kW A
AC1 20 20 20 20
AC3 200/240V 1.5 7 2.2 9 3 12 4 15
380/440V 2.2 6 4 9 5.5 12 7.5 16
500/550V 3 5 3.7 6 4 7 5.5 9
690V 3 4 4 5 4 5 4 5
Ratings / UL508 hp A hp A hp A hp A
continuous current Ith = 20A (maximum for cage clamp type is 10A)
single phase 120V 1/2 1/2 1 * -
230V/240V 1 1.5 2 * * -
three phase 240V 1.5 3 3 -
480V 3 5 7.5 * * * -
600V 3 5 7.5 -
Wire Range : Copper, 75°C, Stranded, 18-12AWG
NEMA size 00 00 00 0
Base for separate mountGT-12M
Setting ranges (A)
Differential
Non-differential (3-heater)
Non-differential (2-heater)
GTK-12M
GTH-12M/3
GTH-12M
0.1 - 0.160.16 - 0.250.25 - 0.40.4 - 0.63
0.63 - 11 - 1.6
1.6 - 2.52.5 - 4
4 - 65 - 86 - 97 - 109 - 13
12 - 16
Frame size 6A 9A 12A 16A
AU-2M
AU-1M
AU-4M
AU-2MF
AU-1MF
AU-4MF
AU-2MC
AU-1MC
AU-4MC AU-1MP
Additional auxiliary contacts
Note) * = 1/2 for cage clamp type, ** = 1.5hp for cage clamp type, *** = 5hp for cage clamp type16AF : not approved from UL
2-pole, Front mount
4-pole, Front mount
2-pole, Side mount
Fast-on type Cage clamp type Solder pin typeScrew clamp type
17
Digital motor protection relay
Model No. DMP06-S/Sa DMP60-S/Sa DMP06-T/Ta DMP06-T/Ta
Wiring Screw type Tunnel type
Panel mount Unit or Extension Note1)
Operation time Select either reverse time characteristics or definite time characteristics
Protection Over current According to the setting time
Phase failure 3 sec.
Reverse phase Within 0.1 sec.
Asymmetry 5 sec.
Stall 5 sec.
Lock Within 0.5 sec.
Under current 3 sec.
Ground fault Within 0.05~1 sec. Selectable (0.05~1.0sec)
Short circuit Note2) Within 50ms
Alarm Variable (60~110% of the setting current)
Current setting range (A) 0.5~6 5~60 0.5~6 5~60
Motor capacity 220~240V 0.09~0.75 1.1~11 0.09~0.75 1.1~11
(kW) 380~440V 0.12~1.5 2.2~22 0.09~1.5 2.2~22
Time setting Definite Delay in starting 0~60sec
range (sec) time Delay in operating 0~30sec
Inverse time 0~60sec
Reset Manual reset
Tolerance Current ±5%
Time ±5% (or±0.5sec)
Operating power Voltage AC 190~250V
Note3) Frequency 60Hz (50Hz)
Aux. contact OL 2-SPST 3A/250Vac Resistive load
AL SPST 3A/250Vac Resistive load
Insulation resistance Over DC500V 100㏁
Surge impulse voltage(IEC1000-4-5) 1.2×50㎲ 6kV (Apply standard wave form)
Fast transient burst(IEC1000-4-4) 2.5kV/5min
Environment Temperature Operation -25~70℃
Storage -30~80℃
Humidity 30~90% RH (No freezing)
Display 7-Segment 3 phase current, cause of a fault
Bar-Graph 60~110% of real load current
Mounting type 35mm Din-rail/Panel
Note1) In extension type, the digital EMPR is calibrated with combining the display past and main body so, please cautious not to combine the display part and main body with different part No.
Note2) Instantaneous short circuit protection is optional Note3) Operational voltage of AC 110V and 50Hz is optional
DMP�-S/Sa DMP�-T/Ta
18
Manual motor startersQuick selection table ... IEC rating
220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V
230V 400V 440V 500V 600V 230V 400V 440V 500V 600V
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 3 3100 100 100 100 100 100 50 38 3 3100 100 100 100 50 38 15 11 3 3100 100 100 100 15 11 10 8 3 3100 100 100 100 15 11 10 8 3 3100 100 50 38 15 11 6 5 3 3100 100 50 38 10 8 6 5 3 350 38 20 15 10 8 6 5 3 340 30 15 11 8 6 6 5 3 340 30 15 11 8 6 6 5 3 330 22 15 11 6 4 5 4 3 3- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 100 100100 100 100 100 100 100 100 100 8 8100 100 100 100 100 100 100 100 8 8100 100 100 100 100 100 100 100 6 6100 100 100 100 50 38 50 38 6 6100 100 100 100 50 38 50 38 6 6100 100 100 100 50 38 42 32 6 6100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4100 100 50 38 20 15 10 8 4 4- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
0.160.250.40.63
11.62.54681013172226324050637590100
TypeCurrent adjustable type MMS-32S MMS-32HInstantaneous type - MMS-32HIBreaking capacity Standard High breakingHandle Type Toggle Rotary
Number of poles 3 3Rated operational voltage (Ue) Up to 690V Up to 690VRated frequency 50/60 Hz 50/60 HzRated insulation voltage (Ui) 690V 690VRated impulse voltage (Uimp) 6kV 6kVUtilization category IEC 60 947-2 (Breaker) Cat. A Cat. A
IEC 60 947-4 (Motor starter) AC 3 AC 3Mechanical endurance (Operating) 100,000 100,000Electrical endurance (Cycles) 100,000 100,000Max operating frequency per hour (Ope./h) 25 25Temperature compensation (Operation) -20 ~ +60℃ -20 ~ +60℃Instantaneous short circuit release 13 × Ie max. 13 × Ie max.Overload protection � �
Phase failure function � �
Trip indicating function × ×
Test function � �
Weight (g) 320 360Rated Rated Thermal releasebreaking operational Adjustmentcapacity
current (Ie)range
(kA) (A)0.1~0.160.16~0.250.25~0.40.4~0.630.63~11~1.6
1.6~2.52.5~44~65~86~109~1311~1714~2218~2622~3228~4034~5045~6355~7570~9080~100
Frame 32AF
19
MMS-63S MMS-63H MMS-100S MMS-100H- MMS-63HI - MMS-100HI
Standard High breaking Standard High breakingRotary Rotary Rotary Rotary
3 3 3 3Up to 690V Up to 690V Up to 690V Up to 690V50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz1,000V 1,000V 1,000V 1,000V
8kV 8kV 8kV 8kVCat. A Cat. A Cat. A Cat. AAC 3 AC 3 AC 3 AC 3
50,000 50,000 50,000 50,00025,000 25,000 25,000 25,000
25 25 25 25-20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃
13 × Ie max. 13 × Ie max. 13 × Ie max. 13 × Ie max.� � � �
� � � �
× × � �
� � � �
1,000 1,000 2,200 2,200
63AF 100AF
220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V
230V 400V 440V 500V 600V 230V 400V 440V 500V 600V
220V 220V240V 415V 460V 525V 690V 240V 415V 460V 525V 690V
230V 400V 440V 500V 600V 230V 400V 440V 500V 600V
- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
100 100 100 100 15 12 10 8 4 3100 100 50 38 10 8 6 5 4 3100 100 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 350 38 25 19 10 8 6 5 4 3
- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
100100 100 100 50 38 50 38 6 5100100 100 100 50 38 42 32 6 5100100 50 50 50 38 12 9 5 5100100 50 50 50 38 12 9 5 5100100 50 50 35 27 12 9 5 5100100 50 50 35 27 10 8 5 5100100 50 50 35 27 10 8 5 5100100 50 50 35 27 10 8 5 5100100 50 50 35 27 10 8 5 5
- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 25 19 10 8100 100 50 38 40 30 15 11 10 8100 100 50 38 40 30 15 11 6 5100 100 50 38 40 30 12 9 6 5100 100 50 38 40 30 12 9 6 5100 100 50 38 40 30 8 6 5 4100 100 50 38 40 30 8 6 5 4100 100 50 38 40 30 8 6 5 4
Icu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu IcsIcu Ics Icu Ics Icu Ics Icu Ics Icu Ics
- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -- - - - - - - - - -
100100 100 100 50 38 35 27 12 9100100 100 50 50 38 35 27 12 9100100 100 50 50 38 35 27 12 9100100 100 50 50 38 25 19 12 9100100 100 50 50 38 20 15 12 9100100 100 50 50 38 15 11 10 8100100 100 50 50 38 15 11 8 6100100 75 50 50 38 12 9 6 6100100 75 50 50 38 12 9 6 6100100 75 50 50 38 12 9 6 6
20
Mold case circuit breakersSusol MCCB Series
TD100 TD160 TS100
♣ Applicable to MCCBs equipped with FTU, FMU, ATU★ 2 pole MCCB in 3pole frame size ★★ 700A only available for TS800FTU
★★★ Available for 3pole circuit breakers ★★★★ Under development★★★★★ Not applicable to 1pole
Frame size [AF]
Rated current, In ♣ [A]
No. of poles
Rated operational AC [V]
voltage, Ue DC [V]
Rated impulse withstand voltage, Uimp [kV]
Rated insulation voltage, Ui [V]
Rated ultimate short-circuit breaking capacity, Icu
AC 50/60Hz 220/240V [kA]
380/415V [kA]
440/460V [kA]
480/500V [kA]
660/690V [kA]
DC 250V [kA]
500V(2poles in series) [kA]
Rated service breaking capacity, Ics [%Icu]
Rated short-circuit making capacity Icm
AC 50/60Hz 220/240V [kA]
380/415V [kA]
440/460V [kA]
480/500V [kA]
660/690V [kA]
Category of utilization
Isolation behavior
Trip unit (release)
Thermal-Magnetic
●fixed-thermal, fixed-magnetic FTU
●adjustable-thermal, fixed-magnetic FMU
●adjustable-thermal, adjustable-magnetic ATU
●magnetic only MTU ★★★
Electronic
●LSI ETS ★★★
●LSI ETM ★★★
Option Earth-fault protection, Ig
Zone selective interlocking, ZSI
Ammeter
Communication
Earth-leakage protection module ★★★★
Connection fixed front-connection
rear-connection
plug-in front-connection
rear-connection
Mechanical life [operations]
Electrical life @ 415 V AC [operations]
Basic dimensions, W×H×D 1-pole [mm]
(front connection) 3-pole [mm]
4-pole [mm]
Weight 1-pole [kg]
(front connection) 3-pole [kg]
4-pole [kg]
Reference standard
100 160 100
16, 20, 25, 32, 40, 1P: 16, 20, 25, 32, 40, 50,
50, 63, 80, 10063, 80, 100, 125, 160 40, 50, 63, 80, 100
2, 3P: 100, 125, 160
2★, 3, 4 1, 2★, 3, 4 2★, 3, 4
690 240(1P), 690 690
500 250(1P), 500 500
8 8 8
750 750 750
N H L N H L N H L
30(1P) 50(1P)85 100 200
85 100 200 100 120 200
50 85 150 50 85 150 50 85 150
50 70 130 50 70 130 50 70 130
30 50 65 30 50 65 42 65 85
5 8 10 5 8 10 10 15 20
16(1P) 25(1P)42 65 100
42 65 100 50 85 100
42 65 100 42 65 100 50 85 100
100% 100% 100% 100% 100% 100% 100% 100% 100%
105(1P) 105(1P)187 220 440
187 220 440 220 264 440
105 187 330 105 187 330 105 187 330
105 154 286 105 154 286 105 154 286
63 105 143 63 105 143 88 143 187
8 14 17 8 14 17 17 30 40
A A A
● ● ●
● ● ●
● ●★★★★★ ●
- - -
- - ●
- - ●
- - -
- - -
- - -
- - -
- - -
- - -
● ● ●
● ●★★★★★ ●
● ●★★★★★ ●
● ●★★★★★ ●
25000 25000 25000
10000 10000 10000
- 35×140×86 -
90×140×86 90×140×86 105×160×86
120×140×86 120×140×86 140×160×86
- 0.57 -
1.5 1.5 2
1.8 1.8 2.6
IEC60947-2 IEC60947-2 IEC60947-2
21
TS160 TS250 TS400 TS630
1. The breakers with electronic trip units are available only at 3-pole version. (Only for AC supply)※ The trip unit ATU is available from 125A
TS800
160 250 400 630 800
(100)※, 125, 160 125, 160, 200, 250 300, 400 500, 630 700★★, 800
2★, 3, 4 2★, 3, 4 2★, 3, 4 2★, 3, 4 2★, 3, 4
690 690 690 690 690
500 500 500 500 500
8 8 8 8 8
750 750 750 750 750
N H L N H L N H L N H L N H L
100 120 200 100 120 200 100 120 200 100 120 200 100 120 200
50 85 150 50 85 150 65 85 150 65 85 150 65 100 150
50 70 130 50 70 130 65 85 130 65 85 130 65 100 130
42 65 85 42 65 85 42 65 85 42 65 85 42 85 100
10 15 20 10 15 20 10 20 35 10 20 35 10 20 35
50 85 100 50 85 100 50 85 100 50 85 100 50 85 100
50 85 100 50 85 100 50 85 100 50 85 100 50 85 100
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
220 264 440 220 264 440 220 264 440 220 264 440 220 264 440
105 187 330 105 187 330 143 187 330 143 187 330 143 220 330
105 154 286 105 154 286 143 187 286 143 187 286 143 220 286
88 143 187 88 143 187 88 143 187 88 143 187 88 187 220
17 30 40 17 30 40 17 40 74 17 40 74 17 40 74
A A A A A
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
25000 25000 20000 20000 10000
10000 10000 6000 6000 3000
- - - - -
105×160×86 105×160×86 140×260×110 140×260×110 210×320×135
140×160×86 140×160×86 186.5×260×110 186.5×260×110 280×320×135
- - - - -
2 2 5.4 5.4 15.1
2.6 2.6 7.2 7.2 19.6
IEC60947-2 IEC60947-2 IEC60947-2 IEC60947-2 IEC60947-2
22
Molded case circuit breakersMeta-MEC 30AF to 225AF Series
Note): 1. ● applicable or available2. ▲ available as a separate breaker3. (3) Breaking capacity(at 415VAC) of ABS32b 3A
ABS33b 3A is 2.5kA
Table 1.
Frame Size(AF)Frame TypeBreaking capacity(kA), Icu at 415VACNumber of polesType 2 pole
3 pole4 pole
Rated current (A)
Technical data conforming to IEC/EN60947-2Rated operational voltage(V), Ue(50/60Hz)Rated operational voltage(V), Ue(DC)Rated insulation voltage(V), Ui(50/60Hz)Rated impulse withstand voltage(kV), UimpUltimate breaking capacity(kA), Icu
AC 50/60Hz 220/240V380V415V440/460V480/500V600V
DC 125V250V
Service breaking capacity(%Icu), IcsCategory of useEndurance Mechanical(Number of operations) ElectricalType of trip unitThermal-magnetic releaseElectronic releasePre-alarm via LED Hydraulic-magnetic releaseMagnetic release only without thermal tripEarth leakage protection for 3 pole AccessoriesElectrical auxiliaries Auxiliary switch
Alarm switchShunt tripUndervoltage trip
External accessories Direct rotary handleExtended rotary handleTerminal shieldInsulation barrierRear connection Mechanical interlockPlug-in deviceMotor operator
Dimensions (W×H×Dmm) 3 pole breakerWeight(kg) 2 pole
3 pole4 pole
Derating chart : See tables
Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃
Calibrated for 40℃ In=15 to 30A 111.9% 111.3% 110.0% 108.0% 106.6% 104.9% 102.7% 100.0% 96.8% 93.3%
In=40 to 100A 110.2% 109.8% 108.7% 107.0% 105.8% 104.3% 102.4% 100.0% 97.2% 94.0%
Calibrated for 50℃ In=15 to 30A 113.1% 112.5% 111.3% 110.0% 109.1% 108.0% 106.6% 104.9% 102.7% 100.0%
In=40 to 100A 111.2% 110.7% 109.8% 108.7% 108.0% 107.0% 105.8% 104.3% 102.4% 100.0%
ABS ABH ABE ABS ABH5 10 5 10 25
2, 3 2, 3 2, 3 2, 3, 4 2, 3, 4ABS32b ABH32b ABE52b ABS52b ABH52bABS33b ABH33b ABE53b ABS53b ABH53b
ABS54b(3), 5, 10, 15, 20, 30 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50
600 600 600 600 600250 250 250 250 250690 690 690 690 6906 6 6 6 6
10 25 10 25 507.5 14 7.5 14 255 10 5 10 255 10 5 10 25
2.5 7.5 2.5 7.5 142.5 5 2.5 5 105 10 5 10 20
2.5 5 2.5 5 1450 50 50 50 50A A A A A
8500 8500 8500 8500 85001500 1500 1500 1500 1500
fixed.
fixed fixed fixed fixed
▲ ▲ ▲ ▲ ▲
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
- - - - -- - - - -- - - - -
0.45 0.45 0.45 0.45 0.70.65 0.65 0.65 0.65 1
- - - 0.85 1.2
30 50
See table 1
75×130×60 75×130×60 90×155×60
23
60 100 225
105×165×60
See table 2
Table 2.
Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃Calibrated for 40℃ In=100 to 225A 114.3% 113.2% 110.6% 107.5% 105.8% 140.0% 102.0% 100.0% 97.9% 95.6%Calibrated for 50℃ In=100 to 225A 116.3% 115.4% 113.2% 110.6% 109.1% 107.5% 105.8% 104.0% 102.0% 100.0%
ABE ABS ABE ABS ABH ABE ABS ABH5 10 10 25 35 18 25 35
2, 3 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4ABE62b ABS62b ABE102b ABS102b ABH102b ABE202b ABS202b ABH202bABE63b ABS63b ABE103b ABS103b ABH103b ABE203b ABS203b ABH203bABH54b ABS64b ABE104b ABS104b ABH104b ABE204b ABS204b ABH204b
60 5, 10, 15, 20, 30, 15, 20, 30, 40, 50 100, 125, 150, 175, 200, 22540, 50, 60, 60, 75, 100
75, 100
600 600 600 600 600 600 600 600250 250 250 250 250 250 250 250690 690 690 690 690 690 690 6906 6 6 6 6 6 6 6
10 25 25 50 65 35 50 657.5 14 14 25 35 18 25 355 10 10 25 35 18 25 355 10 10 25 35 18 25 35
2.5 7.5 7.5 14 25 10 14 252.5 5 5 10 18 7.5 10 185 10 10 20 25 15 20 25
2.5 5 5 14 18 10 14 1850 50 50 50 50 50 50 50A A A A A A A A
8500 8500 8500 8500 8500 7000 7000 70001500 1500 1500 1500 1500 1000 1000 1000
fixed fixed. fixed fixed. fixed
fixed fixed fixed
▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
- - - - - - - -- - - - - - - -- - - - - - - -
0.45 0.45 0.45 0.7 0.7 1.1 1.1 1.10.65 0.65 0.65 1.1 1.1 1.2 1.2 1.2
- 0.85 0.85 1.2 1.2 1.5 1.5 1.5
75×130×60 90×155×60
See table 1 See table 1
24
Mold case circuit breakersMeta-MEC 250AF to 1600AF Series
Note ;● applicable or available▲ available as a separate breaker
Table 3.Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃
Calibrated for 40℃ 110.0% 109.0% 107.0% 105.0% 104.0% 103.0% 101.5% 100.0% 98.5% 97.0%
Calibrated for 50℃ 113.0% 112.0% 110.0% 108.0% 107.0% 106.0% 104.5% 103.0% 101.5% 100.0%
Frame Size(AF) 400
Frame TypeBreaking capacity(kA), Icu at 415VACNumber of polesType 2 pole
3 pole4 pole
Rated current (A)
Technical data conforming to IEC/EN60947-2Rated operational voltage(V), Ue(50/60Hz)Rated operational voltage(V), Ue(DC)Rated insulation voltage(V), Ui(50/60Hz)Rated impulse withstand voltage(kV), UimpUltimate breaking capacity(kA), Icu
AC 50/60Hz 220/240V380V415V440/460V480/500V600V690V
DC 125V250V
Service breaking capacity(%Icu), IcsCategory of useEndurance Mechanical(Number of operations) ElectricalType of trip unitThermal-magnetic releaseElectronic releasePre-alarm via LED Hydraulic-magnetic releaseMagnetic release only without thermal tripEarth leakage protection for 3 pole AccessoriesElectrical auxiliaries Auxiliary switch
Alarm switchShunt tripUndervoltage trip
External accessories Direct rotary handleExtended rotary handleTerminal shieldInsulation barrierRear connection Mechanical interlockPlug-in deviceMotor operator
Dimensions (W×H×Dmm) 3 pole breakerWeight(kg) 2 pole
3 pole4 pole
Derating chart : See tables
250, 300, 350, 400Interchangeable via rating plug between
250 and 300350 and 400
See table 3
ABE ABS ABH ABL25 35 50 85
2,3,4 2,3,4 2,3,4 2, 3, 4ABE402b ABS402b ABH402b ABL402bABE403b ABS403b ABH403b ABL403bABE404b ABS404b ABH404b ABL404b
600 600 600 600250 250 250 250690 690 690 6906 6 6 6
35 50 85 12530 42 65 10025 35 50 85/50(Ics)25 35 50 8518 25 35 6518 22 25 30- - - -
20 30 50 6010 20 40 40100 100 50 50A A A A
4000 4000 4000 40001000 1000 1000 1000
fixed fixed fixed fixed
▲ ▲
▲ ▲ ▲ ▲
● ● ● ●
● ● ● ●
● ● ● ●
● ● ● ●
● ● ● ●
- - - -● ● ● ●
● ● ● ●
● ● ● ●
● ● ● ●
- - - -- - - -
140×257×1135.2 5.2 5.2 5.26.2 6.2 6.2 6.27.8 7.8 7.8 7.8
25
800 1200 1600
210×400×105 210×350×142.5
800Electronically adjustable :
(0.5-0.6-0.7-0.8-0.9-1.0)×InElectronically adjustable :
(0.5-0.6-0.7-0.8-0.9-1.0)×InSee table 3
ABE ABS ABL GBN(E) GBH(E) ABS ABS(electronic trip) GBN(E)35 50 85 35 50 65 65 65
2, 3, 4 2, 3, 4 2, 3, 4 3 3 3, 4 3 3ABE802b ABS802b ABL802bABE803b ABS803b ABL803b GBN803E GBH803E ABS1003 ABS1203 ABS1203E GBN1603EABE804b ABS804b ABL804b ABS1004 ABS1204
1000 1200 1200 1600
600 600 600 600 600 600 600 600250 250 250 - - 250 250 -690 690 690 690 690 690 690 6906 6 6 6 6 6 6 8
50 100 125 50 85 100 100 -42 65 100 35 50 65 65 -35 50 85/50(Ics) 35 50 65 65 6535 50 85 30 42 65 65 4525 45 65 22 35 50 50 2222 25 30 18 25 45 45 -- - - - - - - 20
30 50 60 - - - - -20 40 40 - - 40 - -100 50 50 50 50 50 50 50
A A A A A A A A2500 2500 2500 2500 2500 2500 2500 10000500 500 500 500 500 500 500 4000
fixed fixed fixed Adjustable-thermal, Fixed-magneticLSIA configuration LSIA configuration ●
● ● ● ●
▲
▲ ▲ ▲ ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● - - ●
- - - - - - - ●
● ● ● ● ● - - ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● - - -- - - - - - - ●
- - - - - - - ●
140×257×113 210×280×11311 11 11 - - - -
11.5 11.5 11.5 11.5 19.4 19.4 2318.2 18.2 18.2 - 27 - -
500, 600, 630, 700, 800Interchangeable via rating plug between 500 and 600, 500 and 630, 700 and 800
26
Air circuit breakersSusol ACB Series
Type
Ampere frame (AF)
Rated current(A) (In max) at 40℃
Setting current (A) Control trip relay ( ... × In max)
Rated current of neutral pole (A)
Rated insulation voltage(V) (Ui)
Rated operating voltage(V) (Ue)
Rated impulse withstand voltage (kV) (Uimp)
Frequency(Hz)
Number of poles (P)
Rated breaking capacity (kA sym)IEC 60947-2
220V/230V/380V/415V
AC 50/60Hz (Icu)KS C 4620
460V/480V/500V
550V/600V/690V
Rated service breaking capacity (kA) (Ics) ... %×Icu
Rated making capacity (kA peak)IEC 60947-2
220V/230V/380V/415V
AC 50/60Hz (Icm) KS C 4620
460V/480V/500V
550V/600V/690V
Rated short-time 1sec
withstand current (kA) (Icw) 2 sec
3 sec
Operating time (ms) Maximum total breaking time
Maximum closing time
Life cycle (time) Mechanical Without maintenance
With maintenance
Electrical Without maintenance
With maintenance
Connections Draw-out / Fixed Horizontal connection
Vertical connection
Front connection
Mixed connection
Weight (kg) Draw-out type Main body Motor charging type
(3P/4P) (With cradle) Manual charging type
Cradle only
Fixed type Motor charging type
Manual charging type
External dimensions (mm) Draw-out 3P
(H×W×D) type 4P
Fixed type 3P
4P
Trip relay
Certificate & Approval
Marine classiflcation
* Refer to trip relay specification. ** �: Standard, �: Option
AH-06D AH-08D AH-10D AH-13D AH-16D AH-20D
630 800 1000 1250 1600 2000
200 400
400 630 1000 1250 1600 2000
630 800
(0.4 ~ 1.0) × In max
400400
630 1000 1250 1600 2000630
800
1000
690
12
50/60
3, 4
85
85
65
100%
187
187
143
65
60
50
40
80
20,000
30,000
5,000
10,000
� -
� �
� -
� -
63/74 70/85
61/72 68/83
29/32 33/40
34/44 38/47
32/42 36/45
430×334×375
430×419×375
300×300×295
300×385×295
N, A, P, S type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
H
WD
*
**
27
AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E
630 800 1000 1250 1600 2000 2500 3200 4000
630 800 1000 1250 1600 2000 2500 3200 4000
(0.4 ~ 1.0) × In max
630 800 1000 1250 1600 2000 2500 3200 4000
1,000
690
12
50/60
3, 4
100
100
85
100%
220
220
187
85
75
65
40
80
15,000
20,000
5,000
10,000
� �
� �
� -
� -
87/103 104/147
85/101 102/145
44/55 58/70
44/55 63/100
42/53 61/98
430×412×375
430×527×375
300×378×295
300×493×295
N, A, P, S type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
AH-40G AH-50G AH-63G
4000 5000 6300
4000 5000 6300
(0.4 ~ 1.0) × In max
4000 5000 6300
1,000
690
12
50/60
3, 4
150
150
100
100%
330
330
220
100
100
100
40
80
10,000
15,000
2,000
5,000
�
�
-
-
181/223 186/230
179/221 184/228
97/117 102/124
98/123 103/130
96/121 101/128
460×785×375
460×1015×375
300×751×295
300×981×295
N, A, P, S type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
28
Air circuit breakersMetasol ACB Series
Type
Ampere frame (AF)
Rated current(A) (In max) at 40℃
Setting current (A) Control trip relay ( ... × In max)
Rated current of neutral pole (A)
Rated insulation voltage(V) (Ui)
Rated operating voltage(V) (Ue)
Rated impulse withstand voltage (kV) (Uimp)
Frequency (Hz)
Number of poles (P)
Rated breaking capacity (kA sym) (Icu) 220V/230V/380V/415V
AC 50/60Hz IEC 60947-2 460V/480V/500V
550V/600V/690V
Rated service breaking capacity (kA) (Ics) ... %×Icu
Rated making capacity (kA peak) (Icm) 220V/230V/380V/415V
AC 50/60Hz IEC 60947-2 460V/480V/500V
550V/600V/690V
Rated short-time 1 sec
withstand current (kA) (Icw) 2 sec
3 sec
Operating time (ms) Maximum total breaking time
Maximum closing time
Life cycle (time) Mechanical Without maintenance
With maintenance
Electrical Without maintenance
With maintenance
Connections Draw-out / Fixed Horizontal connection
Vertical connection
Front connection
Mixed connection
Weight (kg) Draw-out type Main body Motor charging type
(3P/4P) (With cradle) Manual charging type
Cradle only
Fixed type Motor charging type
Manual charging type
External dimensions (mm) Draw-out 3P
(H×W×D) type 4P
Fixed type 3P
4P
Trip relay
Certificate & Approval
Marine classiflcation
* Refer to trip relay specification. ** �: Standard, �: Option
H
WD
*
**
AN-06D AN-08D AN-10D AN-13D AN-16D AS-20D
630 800 1000 1250 1600 2000
200 400
400 630 1000 1250 1600 2000
630 800
(0.4 ~ 1.0) × In max
400400
630 1000 1250 1600 2000630
800
1000
690
12
50/60
3, 4
65 70
65 70
50 65
100% 100%
143 154
143 154
105 143
50 65
42 55
36 50
40
80
20,000
30,000
5,000
10,000
� -
� �
� -
� -
63/74 70/85
61/72 68/83
29/32 33/40
34/44 38/47
32/42 36/45
430×334×375
430×419×375
300×300×295
300×385×295
N, A, P type
KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK
29
AS-20E AS-25E AS-32E AS-40E AS-50F AS-40G AS-50G AS-63G
2000 2500 3200 4000 4000 5000 4000 5000 6300
630, 800
1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
(0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max (0.4 ~ 1.0) × In max
630, 800
1000, 1250 2500 3200 4000 4000 5000 4000 5000 6300
1600, 2000
1,000 1000 1,000
690 690 690
12 12 12
50/60 50/60 50/60
3, 4 3, 4 3, 4
85 100 120
85 100 120
85 85 100
100% 100% 100%
187 220 264
187 220 264
187 187 220
85 85 100
75 75 90
65 65 85
40 40 40
80 80 80
15,000 10,000 10,000
20,000 15,000 15,000
5,000 2,000 2,000
10,000 5,000 5,000
� � � �
� � � �
� - - -
� - - -
87/103 104/147 145/173 181/223 186/230
85/101 102/145 143/171 179/221 184/228
44/50 58/70 78/90 97/117 102/124
44/55 63/100 76/94 98/123 103/130
42/53 61/98 74/92 96/121 101/128
430×412×375 460×629×375 460×785×375
430×527×375 460×799×375 460×1015×375
300×378×295 300×597×295 300×751×295
300×493×295 300×767×295 300×981×295
N, A, P type N, A, P type N, A, P type
KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK
The trip relay of Susol ACB provides the additional protection functions for voltage, frequency, unbalance, andothers in addition to main protection functions for over current, short-circuit, ground fault. It supports theadvanced measurement functions for voltage, current, power, electric energy, harmonics, communicationfunction, and others.Analog trip function interlocked with mechanism enhanced a durability of devices as well as the breakingcapacity of ACB.Zone selective interlocking function makes the protective coordination more simple and thermal memory canbe applied to various loads.
Trip relay(OCR)Trip relay(OCR)
31
Trip relay types
Classification N type A type P type S type
Externals
Current �L / S / I / G / Thermal �L / S / I / G / Thermal �L / S / I / G / Thermal(Continuous) �P type
protection �ZSI(Protective coordination) �ZSI(Protective coordination)
� Earth leakage (Option) �Earth leakage(Option) �P type
Other�Over/Under current
protection�Over/Under frequency
�Unbalance(Voltage/Current)
�Reverse power
�Current (R / S / T / N) �3 Phase Voltage/Current �3 Phase Voltage/Current
RMS/Vector RMS/Vector
�Power(P, Q, S), PF(3-Phase) �Power(P, Q, S), PF(3-Phase)
�Energy(Positive/Negative) �Energy(Positive/Negative)
Measurement �Frequency, Demand �Frequency, Demand
function �Voltage/Current harmonics
(1st~63th)
�3 Phase Waveforms
�THD, TDD, K-Factor
Fine adjustment�Fine adjustment for long/short �P type
time delay/instantaneous/ ground
�Overload protection relays �P type
Pre Trip Alarm: DO (Alarm)
(Ground fault is not available
when using Pre trip alarm)
Digital Output�3DO (Fixed) �3DO (Programmable) �P type
�L, S/I, G Alarm �Trip, Alarm, General
IDMTL setting�Compliance with IEC60255-3 �P type
SIT, VIT, EIT, DT
Communication�Modbus/RS-485 �Modbus / RS-485 �Modbus / RS-485
�Profibus-DP �Profibus-DP �Profibus-DP
�Self Power �Self Power �AC/DC 100~250V �AC/DC 100~250V
-Power source - Power source works �DC 24~60V �DC 24~60V
works over 20% of over 20% of load current.
Power supply load current. - External power source are
required for comm.
�AC/DC 100~250V
�DC 24~60V
RTC timer �Available �Available �Available �Available
LED for�Long time delay �N type �N type �N type
trip info.�Short time delay/Instantaneous
�Ground fault
�10records �256records �256records
Fault recording (Fault/Current/Date and Time) (Fault/Current/Date and Time) �Last fault wave
recording (3 Phase)
Event recording �256 records(Content, Status, Date) �P type
Operating �Reset button �Reset, Menu �A type �A type
button Up/Down, Left/Right, Enter
Basic protection function(L / S / I / G)
is still under normal operation
without control power.
-
-
-
-
-
-
-
- -
-
-
-
32
Vacuum Circuit BreakersSusol VCB Series
Rated voltage (kV) 7.2 12
Rated short-circuit breaking current (kA) 8 12.5 20 25 31.5 40 50 20 25 31.5 40 50
Rated current (A) 400 630 630 630 1250 1250 1250 630 630 1250 1250 1250
1250 1250 2000 2000 2000 1250 1250 2000 2000 2000
2000 2000 3150 3150 3150 2000 2000 3150 3150 3150
4000 4000 4000 4000
Rated frequency (Hz) 50/60 50/60
Rated short-circuit breaking capacity (MVA) 100 160 250 310 390 500 620
Rated short-time withstand current (kA/3sec) 8 12.5 20 25 31.5 40 50 20 25 31.5 40 50
Rated short-circuit making current (kA) 20 32.5 52 65 82 104 130 52 65 82 104 130
Rated breaking time (Cycle) 3 3
Rated opening time (sec) ≤0.04 ≤0.04
No-load closing time (sec) ≤0.06 ≤0.06
Rated withstand Power frequency (kV/min) 20 28(42)
voltage Impulse (kV/1.2x50㎲㎲) 60 75
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Type test Mechanical M2 M2
Electrical E2 (List1) E2 (List1)
Capacitive current switching C2 C2
Lifetime Mechanical Without maintenance (time) 10000 10000
Maintenance (time) 20000 20000
Electrical Without maintenance (time) 10000 10000
Maintenance (time) 20000 20000
Installing Fixed ■■ ■■ ■■ ■■ ■■ ■■ - ■■ ■■ - - -
method Draw-out ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
Applied standard IEC 62271-100. JIS C 4603/JEC 2300 IEC 62271-100
Rated voltage (kV) 17.5 24 36 40.5
Rated short-circuit breaking current (kA) 20 25 40 50 12.5 25 31.5 40 25 31.5 40 25 31.5
Rated current (A) 630 630 1250 1250 630 630 1250 1250 360 630 1250 1250 1250
1250 1250 2000* 2000 1250* 1250* 2000 2000 1250 1250 2000 2000 2000
2000 2000 3150* 3150 2000* 3150 3150 2000 3150 2500
2500* 2500
Rated frequency (Hz) 50/60 50/60 50/60 50/60
Rated short-circuit breaking capacity (MVA)
Rated short-time withstand current (kA/3sec) 20 25 40 50 12.5 25 31.5 40 25 31.5 40 25 31.5
Rated short-circuit making current (kA) 52 65 104 130 32.5 65 82 104 65 82 104 65 82
Rated breaking time (Cycle) 3 3 3 3
Rated opening time (sec) ≤0.04 ≤0.04 ≤0.04 ≤0.04
No-load closing time (sec) ≤0.06 ≤0.06 ≤0.06 ≤0.06
Rated withstand Power frequency (kV/min) 38 50(65) 70(95) 95
voltage Impulse (kV/1.2x50㎲㎲) 95 125 170 185
Rated operating sequence O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO O-0.3s-CO-3min-CO
Type test Mechanical M2 M2 M2 M2
Electrical E2 (List1) E2 (List1) E2 (List1) E2 (List1)
Capacitive current switching C2 C2 C2 C2
Lifetime Mechanical Without maintenance (time) 10000 10000 10000 10000
Maintenance (time) 20000 20000 20000 20000
Electrical Without maintenance (time) 10000 10000 10000 10000
Maintenance (time) 20000 20000 20000 20000
Installing Fixed ■■ ■■ - - ■■ ■■ - - ■■ - - - -
method Draw-out ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■ ■■
Applied standard IEC 62271-100 IEC 62271-100. JEC 2300 IEC 62271-100. JEC 2300 GB11022
33
Dimensions Main Cradle
• Secondary trip coil • Mechanical position indicator• Under voltage trip release• Current trip coil• Position S/W• Keylock• Button padlock• Button cover• Mechanical position indicator
• Secondary trip coil • Earthing S/W• Under voltage trip release • Earthing with electromechanical interlock• Current trip coil • Earthing S/W with position S/W• Position S/W • Earthing S/W with keylock• Keylock • Door interlock• Button padlock • MOC• Button cover • TOC• Plug interlock • Shutter padlock• Mechanical position indicator • Emergency mechanical trip device
• Secondary trip coil • Earthing S/W• Under voltage trip release • Earthing with electromechanical interlock• Current trip coil • Earthing S/W with position S/W• Position S/W • Earthing S/W with keylock• Keylock • Door interlock• Button padlock • MOC• Button cover • TOC• Plug interlock • Shutter padlock• Mechanical position indicator • Emergency mechanical trip device
E type• No Shutter
• For MESG
F type• Insulation Shutter
• For MESG
G type• Bushing
• Insulation Shutter
• For MESG
H type• Bushing
• Metal Insulation Shutter
• Closed Compartment structure
• Earthing Switch & Interlock
• For MCSG
• Door Interlock
Accessories
Variouse type of Cradle
34
Memo
��For your safety, please read user's manual thoroughly before operating.
��Contact the nearest authorized service facility for examination, repair, or adjustment.
��Please contact qualified service technician when you need maintenance.Do not disassemble or repair by yourself!
��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions
�LS Industrial Systems (Middle East) FZE ��Dubai, U.A.E. Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E. Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected]
�Dalian LS Industrial Systems Co., Ltd. ��Dalian, ChinaAddress: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]
�LS Industrial Systems (Wuxi) Co., Ltd. ��Wuxi, ChinaAddress: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]
�LS-VINA Industrial Systems Co., Ltd. ��Hanoi, VietnamAddress: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]
�LS-VINA Industrial Systems Co., Ltd. ��Hochiminh , VietnamAddress: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]
�LS Industrial Systems Tokyo Office ��Tokyo, JapanAddress: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, JapanTel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: [email protected]
�LS Industrial Systems Shanghai Office ��Shanghai, ChinaAddress: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. ChinaTel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: [email protected]
�LS Industrial Systems Beijing Office ��Beijing, ChinaAddress: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]
�LS Industrial Systems Guangzhou Office ��Guangzhou, ChinaAddress: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. ChinaTel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: [email protected]
�LS Industrial Systems Chengdu Office ��Chengdu, ChinaAddress: 12Floor, Guodong Building, No52 Jindun Road Chengdu, 610041, P.R. ChinaTel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: [email protected]
�LS Industrial Systems Qingdao Office ��Qingdao, ChinaAddress: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. ChinaTel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: [email protected]
Specifications in this catalog are subject to change without notice due to continuous product development and improvement.
�� HEAD OFFICELS Tower, 1026-6 Hokyeh 1dong, Dongan-gu, Anyang, Kyonggi-Do, 431-848, KoreaTel. (82-2)2034-4887, 4873, 4918, 4148Fax. (82-2)2034-4648
�� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea
��Global Network
www.lsis.biz
2009. 07 LOW VOLTAGE CIRCUIT BREAKERS & CONTACTORS(E) 2004. 02/(22) 2009. 07 Printed in Korea STAFF
ⓒ 2004.2 LS Industrial Systems Co.,Ltd. All rights reserved.