Cast Resin Transformers T hE Up 3150 kVa, 12 kV, lossEs A...
Transcript of Cast Resin Transformers T hE Up 3150 kVa, 12 kV, lossEs A...
![Page 1: Cast Resin Transformers T hE Up 3150 kVa, 12 kV, lossEs A 0ocw.uniovi.es/pluginfile.php/5423/mod_resource/content/1/TRIHAL_Dry... · Trihal HE NRJED313576EN 02-2014 As standards,](https://reader031.fdocuments.us/reader031/viewer/2022021822/5b32256f7f8b9aed688bd175/html5/thumbnails/1.jpg)
Trihal HE - C3* E3 F1 5pCHigh Efficiency Cast Resin Transformer
StandardThese transformers comply with standards:• IEC60076-11andIEC60076-16• NFEN50541-1SchneiderElectricguaranteesthatitstransformersaresiliconefreeandcertified:• C3*Climaticclass• E3EnvironmentclassaccordingtoIEC60076-16• F1Firebehaviourclass• Almostpartialdischargefree-Acceptancelevel:-≤10pCRoutineTest-≤5pCSpecialTestaccordingtoIEC60076standard*C2Thermalshocktestcarriedoutat-50°C
DescriptionCastresin,50Hz,three-phaseddistributiontransformerswiththefollowingcharacteristics:• Indooruse/Outdoorusewithproperlydesigned
enclosure• ThermalclassF-Temperaturerise100K• Ambient≤40°C,altitude≤1000m• MVwindingsencapsulatedincastresin• Pre-impregnatedLVwindings• Naturalaircoolingsystem(ANtype)• Coreandframecoveredwithprotectivecoating• Anti-corrosionsurfacetreatment:corrositivitycategoryclassC2,“Medium”durability(accordingtoISO12944-2)
Standard fittingsTrihalwithoutenclosure(IP00):• HVvoltagevariationbyoffcircuittappinglinks• 4bi-directionalflatrollers• 4liftingholes• 4haulageholesontheunderbase• 2earthingpoints• 1ratingplate(onHVside)
TrihalwithIP31metalenclosure:• TrihalIP00asabove• IP31metalenclosure(exceptthebottom:IP21):-2liftinglugsfortransformerandenclosureassembly-1earthingpointonenclosure-accesstoHVtappingbyremovingaboltedpanel-enclosurefinalcolourRAL9002
Optional fittings• TemperaturesensorslocatedintheeLVwindings• Electronictemperaturemonitor• (ZconverterorTdigitalthermometer)• +40%AFcoolingsystemwithfans• Customenclosureswithspecialpaintcolors,IP
level(uptoIP44)oranti-corrosiontreatment• Earthingballs,Surgearrestors,Antivibrationspads• 3HVplug-inbushings(IP00orIP31)• Lockingdeviceforplug-inbushings(lockinoption)• 3mobileconnectorsforplug-inbushingsstraightor
elbow(cablecharacteristicsmustbespecified)
Theabovedescriptions/optionsconcernusualcasesandarenotrestrictive.Foranyotherrequests(specialsiteconditions,temperaturerise,housingdesign,etc..),pleaseconsultus.
Trihal hEUp To 3150 kVa, 12 kV, lossEs
PM102308
SM100141
SM100142
Cast Resin Transformers
A0 Ak
![Page 2: Cast Resin Transformers T hE Up 3150 kVa, 12 kV, lossEs A 0ocw.uniovi.es/pluginfile.php/5423/mod_resource/content/1/TRIHAL_Dry... · Trihal HE NRJED313576EN 02-2014 As standards,](https://reader031.fdocuments.us/reader031/viewer/2022021822/5b32256f7f8b9aed688bd175/html5/thumbnails/2.jpg)
Trihal HE
NRJED313576EN 02-2014
Asstandards,specificationsanddesignschangefromtimetotime,pleaseaskforconfirmationoftheinformationgiveninthispublication.
Design:SchneiderElectricIndustriesSASPhotos:SchneiderElectricIndustriesSAS
35,rueJosephMonierCS30323F-92506RueilMalmaisonCedex(France)Tél.:+33(0)141297000RCSNanterre954503439Capitalsocial896313776€www.schneider-electric.com
SchneiderElectricIndustriesSAS
©SchneiderElectric.A
llrig
htsreserved.
A0 AkCast Resin Transformers
Electrical characteristicsPower kVA 160 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150
Primary voltageSecondary voltage
10 kV400V
Isolation level 12kV
HV Tapping range ± 5 %
Vector group Dyn 11, Dyn 5, Dyn 1 (other vector groups upon request)
No-load losses (w)Load losses at 75°C (w) load losses at 120°C (w)
35022702600
50029703400
59034003900
70039204500
83049205650
100061807100
110069608000
130078309000
1500957011000
18001131013000
22001348015500
26001609018500
31501914022000
Impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6
Acoustic Level dB(A):- power LWA- pressure LPA (1m)
5443
5745
5947
60 48
6148
6249
6450
6551
6753
6854
7055
7156
7459
Rated power (kVA) 160 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150
Without enclosure IP00
Dimensions -A (mm) -B -C -D -E Masse totale (kg)
10806501280520715
800
11906601300520715
1020
12208001390670795
1160
13008001410670795
1360
13008001620670795
1540
13808001660670795
1900
15408001860670795
2640
15809501880820945
2820
16409501940820945
3360
16809502070820945
3760
18001200222010701195
4900
18001200217010701195
5160
19601200236010701195
6580
With IP31 metal enclosure
Dimensions -A1 (mm) -B1 -C1
Weight enclosure (kg)Total weight (kg)
16509501750
180980
16509501750
1801200
170010201900
2001360
170010201900
2001560
190011002300
2401780
170010201900
2002100
190011002300
2402880
200011702400
2403060
200011702400
2403600
200011702400
2804040
233012702650
3505250
233012702650
3605520
226010202760
4207000
TerminationsLV Terminations HV Terminations - EN 50180
Dimensions and weights
160 to 400 kVA*thickness 5
500 to 800 kVA*thickness 6
1000 to 1250 kVA*thickness 10
50100
4 x Ø 14
2550
80 40160
4 x Ø 16
3550
1600 kVA*thickness 12
*Valid for aluminium terminations.
2000 kVA* thickness 102500 kVA* thickness 2x10
40
Ø 14
1533
3380
4 x Ø 14
23.5
33
3370
4 x Ø 14
23.5
33
Routine fittings such as bar and cable supports, flexible connectors, etc. will be supplied by the contractor, who will ensure that the transformer terminals are not subject to mechanical stresses.
Without enclosure (IP00) With IP31 metal enclosure
D
C
ED
A
earthingterminal
tapping links
E/2
B
Ø 125 (160)
40 (50)
Ø 13
160 to 400 kVA*thickness 5
500 to 800 kVA*thickness 6
1000 to 1250 kVA*thickness 10
50100
4 x Ø 14
2550
80 40160
4 x Ø 16
3550
1600 kVA*thickness 12
*Valid for aluminium terminations.
2000 kVA* thickness 102500 kVA* thickness 2x10
40
Ø 14
1533
3380
4 x Ø 14
23.5
33
3370
4 x Ø 14
23.5
33
A1
earthingterminal
B1
C1