Cascade Tuning

18
1 Peter Thomas Control Specialists Ltd ExperTune User Conference – Austin Texas April 2007 How to Tune Cascade Loops www.controlspecialists.co.uk Established 1989 - British Standards Institute (BSI) ISO9001:2000 Tick IT registered “Certified Suppliers” of FDA / GAMP Validated Control Systems for AstraZeneca -international Pharmaceutical Manufacturer Approved Solutions Partner (Sales, Support & Training) of ExperTune Inc. Experience of working in Oil, Pharmaceuticals, Chemicals, Glass, Food and Water. Background

Transcript of Cascade Tuning

Page 1: Cascade Tuning

1

Peter ThomasControl Specialists Ltd

ExperTune User Conference –Austin Texas April 2007

How to Tune Cascade Loops

www.controlspecialists.co.uk

• Established 1989 - British Standards Institute (BSI) ISO9001:2000 Tick IT registered

• “Certified Suppliers” of FDA / GAMP Validated Control Systems for AstraZeneca -international Pharmaceutical Manufacturer

• Approved Solutions Partner (Sales, Support & Training) of ExperTune Inc.

• Experience of working in Oil, Pharmaceuticals, Chemicals, Glass, Food and Water.

Background

Page 2: Cascade Tuning

2

How to Tune Cascade Loops

• An overview of Cascade Control.

• Tuning Cascade Control Loops.

• Case Study.

Cascade Control

In the right circumstances, Cascade Control can greatly improve the performance of a control system.

In the right circumstances, Cascade Control can greatly improve the performance of a control system.

Page 3: Cascade Tuning

3

Temperature Control LoopSteam Header

TT

TIC

Heat Exchanger

To other User

Temperature Control LoopSteam Header

TIC

Heat Exchanger

To other User

TIC FLOW TEMP

Process SchematicTT

Page 4: Cascade Tuning

4

Temperature Control LoopSteam Header

TT

TIC

Response to a Load Change

Heat Exchanger

Steam Header

Temperature Control LoopSteam Header

TT

TIC

Heat Exchanger

To other User

TIC FLOW TEMP

Process Schematic

Page 5: Cascade Tuning

5

To other User

Steam Header

TT

TIC

FICFT

Temperature – Flow Cascade

Temperature – Flow Cascade

To other User

Steam Header

TT

TIC (Master)

FIC(Slave)

FTTIC FLOW TEMP

Process Schematic

FIC

The Cascade Loop

Page 6: Cascade Tuning

6

What's The Inner Loop For?

• Reduces phase lag of inner process• Disturbances to the inner loop are

compensated for before they upset the outer loop

• Prevents non-linearities in the inner loop from reaching the outer loop

Temperature – Flow CascadeSteam Header

TT

TIC (Master)

FIC(Slave)

FT

The Cascade Loop

Response to a Load Change

Page 7: Cascade Tuning

7

Master – Cascade Signals

MASTERPV SLAVEOP REM SP

OP

PV

Master – Cascade Signals

MASTERPV SLAVE

OP REM SP

OP

PV

REMTRK

When slave is NOT in Remote/Auto modeMaster OP is to track Slave Setpoint.

Page 8: Cascade Tuning

8

Master – Cascade Signals

MASTERPV SLAVE

OP REM SP

OP

PV

REMTRK

Integral action in Master is to be Inhibited when OP limit reached in Slave

OP LIMITINT

Other Examples of Cascade

• Batch Reactor Temperature Control (Batch Temperature onto Jacket Temperature)

• Level – Flow Control

Page 9: Cascade Tuning

9

Level Control

LT

Level loops are Integrating Processes

Level Control

LT

Level loops are Mass Balance Systems

IN > OUT: Level Rises

IN < OUT: Level Falls

IN = OUT: Level Holds

IN

OUT

Page 10: Cascade Tuning

10

Level Control Problems(Non Linear Responses)

LT LIC

Head Variations

IN

OUT

LT LIC

A failure of the control valve to reposition itself correctly following a reversal inthe control signal – level will cycle !!

Level Control Problems(Valve Hysteresis)

IN

OUT

Page 11: Cascade Tuning

11

Fixing the problemsLevel – Flow Cascade

LT LIC

FICFT

IN

OUT

How to Tune Cascade Loops

• An overview of Cascade Control.

• Tuning Cascade Control Loops.

• Case Study.

Page 12: Cascade Tuning

12

What happens when cascade loops are poorly tuned?

• Loops “fight” each other• Create oscillations• Neither variable is properly controlled• Operator puts loop in manual.

Tuning Cascade Loops1. Always check for measurement and

valve-related issues.2. Inner Loop Tuning - put slave into

Local Auto or Manual and tune the slave controller as a normal PID loop.

3. Outer Loop Tuning - put slave into Cascade and tune master controller as a normal PID loop.

4. Adjust outer loop tuning values to ensure that the RRT (Relative Response Time) of outer loop is 3-5 times slower than the inner loop.

Page 13: Cascade Tuning

13

Test Data - Inner Loop

Inner loop PV

Inner loop CO

Outer loop PV

Inner loop SP Change

Inner loop PVInner loop CO

Outer loop PVOuter loop SP change

Test Data - Outer Loop

Page 14: Cascade Tuning

14

Relative Response Time – What is it ?

1. An indication of the closed loop response of a control loop.

2. Loops with short RRT’s are fast loops

3. Loops with long RRT’s are slow loops.

4. The RRT approximately defines theperiod of any load disturbance initiated oscillations when thecontroller is in automatic.

Relative Response Time andCascade Loops

1. The closed loop response (i.e its RRT) of the outer loop MUST be 3 –5 times slower than the inner loop.

2. After tuning, adjust outer loop PID values to achieve this.

3. Our example:Inner: 38 secondsOuter: 400 seconds

Page 15: Cascade Tuning

15

Determining the Relative Response Time

Relative Response Time (RRT)

1/0.0677 = 15s

Page 16: Cascade Tuning

16

How to Tune Cascade Loops

• An overview of Cascade Control.

• Tuning Cascade Control Loops.

• Case Study.

Cascade Control – A Case Study

Waste Water Industry -Dissolved Oxygen Control

Page 17: Cascade Tuning

17

Dissolved Oxygen Control – As Found

• Oxygen Concentration controlled by QIC adjusting the flow of air.• PID Control implemented in a Siemens S7 PLC.• PIC used to control blower speed.• Flow measurement for information only.• If the blower speed exceeded 95% the second blower started (at the same speed) to assist the duty blower.• Poor control.

CASP 1 DO

0

10

20

30

40

50

60

70

80

90

100

Time

Val

ve p

ositi

on

0

0.5

1

1.5

2

2.5

3

3.5

4

DO

(m

g/l)

AV302

QI503

• Control Specialists Ltd modified the software at the request of the end user.• Flow loop quickly rejects disturbances due to duty-standby boosters coming on and off line.• Blower operating costs reduced.• Control dramatically improved.

CASP 1 DO

0

10

20

30

40

50

60

70

80

90

100

Time

Val

ve p

osi

tion

0

0.5

1

1.5

2

2.5

3

3.5

4

DO

(m

g/l)

AV302

QI503

Dissolved Oxygen Control – As Left

Page 18: Cascade Tuning