Cargo Compartment Fire Test Results
Impact of on-board fire protection capabilities
Sabatair Closing Event – 14 Nov 2019
Dr. André Freiling – Airbus Operations GmbH
Motivation
The goal of the full-scale fire tests is to
evaluate the effects that the implementation
of certain mitigating measures (FCCs, thermal
insulation) may have on the involvement of
cells/batteries in an external fire event
(i.e. starting from cargo items other than
cells/batteries)
Test Sequence
Cold Test:
Proof that the Halon
concentration is 3% at
the location of the
battery box
Commissioning Test:
Place half amount of
cells (400) next to the
ignition box – do not use
the Fire Suppression
System
No Fire Suppression test
800 cells
Halon
Fire Suppression test
800 cells
FCC + Halon
Fire Suppression test
800 cells
Full scale tests
Test Infrastructure
FAA MPS Test configuration
Pushed air inside the cargo compartment through
the Halon Nozzles by massflow controller 20l/s
FAA: Federal Aviation Administration (American Regulatority Authority)
MPS: Minimum Performance Standard for Aircraft Cargo Compartment Halon Replacement
Fire Suppression Systems (2012 Update), U.S. Federal Aviation Administration, DOT/FAA/TC-
TN12/11, May 2012
Cardboard burn box
filled with shredded paper
Test System Architecture
Fire Containment Cover
Test Batteries – Supplier 118650
Carboard paper dividers
between every cell
2 sub boxes stacked on top
of each other in one outer
cardboard box
96 Batteries in one sub-box
Test Batteries – Supplier 2
100 Batteries in one sub-box Corrugated Carboard dividers
between every second cell
2 sub boxes stacked side
by side in one outer
cardboard box
Full scale fire test setup
Legend
MPS requirements
followed as close as
possible for cardboard box
arrangement
100 cells @
100%SOC
100 cells @
50%SOC
100 cells @
100%SOC
100 cells @
50%SOC
Box 1
Box 2
These boxes are placed directly on the pallet
TC09
TC010
On the side of the boxe
Front facing the flames
100 cells @
50%SOC
50 cells @ 50%SOC
&
50 cells @100%SOC
50 cells @ 100%SOC
&
50 cells @50%SOC
100 cells @
50%SOC
TC
05
TC
08
TC
07
TC
06
Box 3
Box 4
TC011 on the
side of box 4
TC012 on the
side of box 3
The 50 cells @100%SOC are placed as shown in the picture.
Front facing the flames
These boxes are on the metallic support
Full scale fire test without Fire SuppressionT
[°C
]
t [hh:mm:sec]
Temperature inside the Battery Boxes
Full scale fire test without Fire Suppression
Ceiling Temperature at different sample points Oxygen concentration at different sampling points
Full scale fire test without Fire Suppression
Full scale fire test with Fire Suppression
Ceiling Temperatures93.3°C@ceiling
MPS Halon
Discharge
criterion
Actual Halon
Discharge
(145°C@Battery)
Full scale fire test with Fire Suppression
T [
°C]
t [hh:mm:sec]
Temperature inside the Battery Boxes
T [
°C]
t [hh:mm:sec]
93.3°C@ceiling
MPS Halon
Discharge
criterion
Actual Halon
Discharge
(145@battery)
Full scale fire test with Fire Suppression
93.3°C@ceiling MPS Halon Discharge
criterion
Actual Halon
Discharge
REMARK!!!!
Full scale fire test with Fire Suppression
Many batteries were involved
Full scale fire test with FCC and Fire Suppression
Test setupCardboard boxes coverd by FCC
Full scale fire test with FCC and Fire Suppression
Ceiling Temperatures
93.3°C@ceilingActual Halon
Discharge
93.3°C@ceilingActual Halon
Discharge
Full scale fire test with FCC and Fire Suppression
Temperature inside
the Battery Boxes
Full scale fire test with FCC and Fire Suppression
Boxes inside the FCC were impactedThe cover was impacted but not burnt through
Full scale fire test with FCC and Fire Suppression
Impact to the batteries was minimal
Conclusions
The Aircraft built-in fire
suppression system inhibits
further propagation of thermal
runaways for the tested batteries
under specific SoC.
For the tested scenario, a Fire
Containment Cover provides
significant protection against the
threats of an external fire event.
No Suppression Halon Fire Suppression Halon Fire Suppression + FCC
Thank you
o Questions / comments?
Brand LGChem MJ1 Samsung 35E
Nominal Capacity (based on manufacturer
Datasheet 3500mAh 3500mAh
Chemistry LiNiCoAlO2 LiNiCoMnO2
Dimensions 18650 18650
SOC 50% 50%
Backup