Capacitor Voltage Transformers for Outdoor Installation

download Capacitor Voltage Transformers for Outdoor Installation

of 4

description

Capacitor Voltage Transformers

Transcript of Capacitor Voltage Transformers for Outdoor Installation

  • Capacitor Voltage Transformers for Outdoor Installationfrom 72.5 kV to 800 kV

  • Instrument transformers and coupling capacitors for high-frequency telecommunication systems

    Characteristics:o Outdoor installationo Conformity to the main International Standardso Insulation: film(pp)-paper-synthetic fluido Mineral oil insulated electromagnetic unit contained in the transformers bottom tanko All external metallic parts in aluminium alloyo Hermetically sealed constructiono Constant accuracy in all service conditionso High fidelity of transient response and rapid damping of ferroresonance oscillationso Maintenance free

    Advantages:

    o No partial dischargeso Easy installation and commissioningo Long life cycle time

    Suitable for:

    o Carrier for high-frequency telecommunication (low-voltage terminal for H.F. coupling located inside secondary terminal box)o Line trap fixed on the top

    Special Optional availables on request:

    o Fuses or MCBs in secondary terminal boxo Composite Grey insulator (Standard is equipped with Porcelain Brown)o Carrier accessories (Drain Coil, Earth Switch, Surge Arrester)o Voltage Tap Grounding Switch

    Capacitor Voltage Transformers for Air Insulated High Voltage Substations (72,5 kV to 800 kV)

    Type

    ELECTRICAL CHARACTERISTICS OVERALL DIMENSIONSAND WEIGHTS

    Rated capacitance

    Highest system voltage

    Test voltages Rated primary voltages

    Maximumburdens

    Creepage distanceAccuracy classesPower

    frequency LIWL 0,2 0,5 1 Standard Long H (*) Total

    pF kV (r.m.s.) kV (r.m.s.) kV (peak) kV VA mm mm kg

    TCVT 72 1200024000 72.5 140 32560:3 66:3

    75150

    200300

    400600 1813 2248 1530 195

    TCVT 123 800016000 123 230 550110:3 115:3

    75150

    250350

    500700 3075 3815 1830 215

    TCVT 145 400012000 145 275 650130:3 132:3

    50100

    150300

    300600 3625 4495 2025 225

    TCVT 170 400010000 170 325 750 150:350

    100150250

    300500 4250 5270 2240 240

    TCVT 245 40008000 245 460 1050220:3230:3

    75150

    200350

    400700 6125 7595 2805 275

    TCVT 362 40006000 362 510 1175 330:3100150

    250350

    500700 9050 11222 3650 360

    TCVT 420 40005000 420 630 1425380:3 400:3

    100150

    300350

    600700 10500 13020 4285 415

    TCVT 550 40005000 525 (550) 680 1550 500:3150200

    350450

    700800 13125 16275 5000 430

    TCVT 800 Data supplied on request

    (*) for composite insulator

  • 1 - Fixing holes (28 DIA)2 - Earth terminal for 10 to 15 mm dia cable3 - Lifting holes4 - Secondary terminal box5 - Oil level gauge of electromagnetic unit6 - Threaded holes for line trap fi xing7 - High-voltage terminal8 - Oil draining plug of electromagnetic unit

    TCVTCapacitor Voltage Transformer

  • o Trench Italia S.r.l.Strada Curagnata, 3717014 Bragno-Cairo Montenotte (SV) - ItalyPhone +39 019 5161 111 Fax +39 019 5161 401E-Mail [email protected]

    o Trench Austria GmbHPaschinger Strasse 49A-4060 Linz-Leonding/AustriaPhone +43 (0)732 6793-0Fax +43 (0)732 671341E-Mail [email protected]

    o Trench Brasil LTDAVia Expressa de Contagem, 2685Contagem, MG - BrasilCEP: 32370-485Phone 55.31.391-5959Fax 55.31.391-1828E-Mail [email protected]

    o Trench LimitedCoil Product Division71 Maybrook Drive, Scarborough, OntarioCanada, M1V 4B6Phone (416) 298-8108Fax (416) 298-2209E-Mail [email protected]

    o Trench LimitedInstrument Transformer Division390 Midwest Road,Scarborough,OntarioCanada, M1P 3B5Phone (416) 751-8570Fax (416) 751-6952E-Mail [email protected]

    o Trench France S.A.16, rue du Gnral CassagnouB.P. 70F-68302 St-Louis Cedex/FrancePhone +33.3.89 70 23 23Fax +33.3.89 67 26 63E-Mail [email protected]

    o Trench Germany GmbH.Nrnberger Strasse 199D-96050 Bamberg/GermanyPhone +49.951.1803-0Fax +49.951.1803-224E-Mail [email protected]

    o Trench Switzerland AG.Lehenmattstrasse 353CH - 4028 Basel/SwitzerlandPhone +41.61.315 51 11Fax +41.61.315 59 00E-Mail [email protected]

    Data and characteristcs indicated in this publication may be varied without notice

    06-2009TI - 005 (draft)