nPage 1/05/03/12PVSYST V5.54
Grid-Connected System: Simulation parameters
Project : PV Syst Report for 100 KWp
Geographical Site Navi Mumbai Country INDIA
Situation Latitude 19.1°N Longitude 73.0°E
Time defined as Legal Time Time zone UT+5 Altitude 27 mAlbedo 0.20
Meteo data : Navi Mumbai, Synthetic Hourly data
Simulation variant : New simulation variant
Simulation date 05/03/12 17h55
Simulation parameters
Collector Plane Orientation Tilt 19° Azimuth 0°
Horizon Free Horizon
Near Shadings No Shadings
PV Array Characteristics
PV module Si-mono Model ELPS CS6P - 260MMManufacturer Canadian Solar Inc.
Number of PV modules In series 19 modules In parallel 20 stringsTotal number of PV modules Nb. modules 380 Unit Nom. Power 260 WpArray global power Nominal (STC) 98.8 kWp At operating cond. 87.5 kWp (50°C)Array operating characteristics (50°C) U mpp 517 V I mpp 169 ATotal area Module area 611 m² Cell area 545 m²
Inverter Model CI 100
Manufacturer Delta EnergyCharacteristics Operating Voltage 450-800 V Unit Nom. Power 100 kW AC
PV Array loss factorsThermal Loss factor Uc (const) 20.0 W/m²K Uv (wind) 0.0 W/m²K / m/s
=> Nominal Oper. Coll. Temp. (G=800 W/m², Tamb=20°C, Wind=1 m/s.) NOCT 56 °C
Wiring Ohmic Loss Global array res. 53 mOhm Loss Fraction 1.5 % at STCModule Quality Loss Loss Fraction 0.9 %Module Mismatch Losses Loss Fraction 2.0 % at MPPIncidence effect, ASHRAE parametrization IAM = 1 - bo (1/cos i - 1) bo Parameter 0.05
User's needs : Unlimited load (grid)
8/2/2019 Canadian With 100 Kw
http://slidepdf.com/reader/full/canadian-with-100-kw 2/3
E v a l u a t i o
nPage 2/05/03/12PVSYST V5.54
Grid-Connected System: Main results
Project : PV Syst Report for 100 KWp
Simulation variant : New simulation variant
Main system parameters System type Grid-Connected
PV Field Orientation tilt 19° azimuth 0°PV modules Model ELPS CS6P - 260MM Pnom 260 WpPV Array Nb. of modules 380 Pnom total 98.8 kWpInverter Model CI 100 Pnom 100 kW acUser's needs Unlimited load (grid)
Main simulation resultsSystem Production Produced Energy 143855 kWh/year Specific prod. 1456 kWh/kWp/year
Performance Ratio PR 73.5 %
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
0
1
2
3
4
5
6
7
8
N o r m a l i z e d E n e r g y [ k W h / k W p / d a y ]
Normalized productions (per installed kWp): Nominal power 98.8 kWp
Yf : Produced useful energy (inverter output) 3.99 kWh/kWp/day
Ls : System Loss (inverter, ...) 0.21 kWh/kWp/dayLc : Collection Loss (PV-array losses) 1.22 kWh/kWp/day
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
P e r f o r m a n c e R a t i o P R
Performance Ratio PR
PR : Performance Ratio (Yf / Yr) : 0.735
New simulation variant
Balances and main results
GlobHor T Amb GlobInc GlobEff EArray E_Grid EffArrR EffSysR
kWh/m² °C kWh/m² kWh/m² kWh kWh % %
January 147.0 24.00 180.3 175.2 14024 13337 12.72 12.10
February 155.0 24.90 177.8 173.1 13567 12914 12.48 11.88
March 196.0 27.10 208.5 203.0 15763 14992 12.37 11.76
April 202.0 28.80 197.5 191.6 14818 14089 12.28 11.67
May 208.0 30.00 193.0 186.6 14514 13801 12.31 11.70
June 148.0 29.30 137.0 132.0 10585 10007 12.64 11.95July 119.0 28.20 112.0 107.7 8731 8204 12.75 11.98
August 123.0 27.70 118.6 114.2 9304 8773 12.83 12.10
September 143.0 27.80 144.8 140.2 11239 10647 12.70 12.03
October 160.0 28.80 175.6 170.6 13361 12690 12.45 11.82
November 141.0 27.60 167.2 162.6 12704 12081 12.43 11.82
December 136.0 25.70 167.2 162.5 12942 12321 12.66 12.05
Year 1878.0 27.50 1979.7 1919.5 151552 143855 12.52 11.89
Legends: GlobHor Horizontal global irradiat ion
T Amb Ambient Temperature
GlobInc Global incident in col l. plane
GlobEff Effective Global, corr. for IAM and shadings
EArray Effective energy at the output of the array
E_Grid Energy injected into grid
EffArrR Effic. Eout array / rough area
EffSysR Effic. Eout system / rough area
8/2/2019 Canadian With 100 Kw
http://slidepdf.com/reader/full/canadian-with-100-kw 3/3
E v a l u a t i o
nPage 3/05/03/12PVSYST V5.54
Grid-Connected System: Loss diagram
Project : PV Syst Report for 100 KWp
Simulation variant : New simulation variant
Main system parameters System type Grid-Connected
PV Field Orientation tilt 19° azimuth 0°PV modules Model ELPS CS6P - 260MM Pnom 260 WpPV Array Nb. of modules 380 Pnom total 98.8 kWpInverter Model CI 100 Pnom 100 kW acUser's needs Unlimited load (grid)
Loss diagram over the whole year
Horizontal global irradiation1878 kWh/m²
+5.4% Global incident in coll. plane
-3.0% IAM factor on global
Effective irradiance on collectors1919 kWh/m² * 611 m² coll.
efficiency at STC = 16.20% PV conversion
Array nominal energy (at STC effic.)190121 kWh
-2.0% PV loss due to irradiance level
-15.1% PV loss due to temperature
-1.0% Module quality loss
-2.1% Module array mismatch loss
-1.1% Ohmic wiring loss
Array virtual energy at MPP151653 kWh
-5.1% Inverter Loss during operation (efficiency)
0.0% Inverter Loss over nominal inv. power
-0.0% Inverter Loss due to power threshold
0.0% Inverter Loss over nominal inv. voltage
-0.1% Inverter Loss due to voltage threshold
Available Energy at Inverter Output143855 kWh
Energy injected into grid143855 kWh