Laminated Wood Systems, Inc. Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications •Pole Classes 7 thru H-4 •Pole Lengths from 30 to 125 feet •Driving Systems, Tools, & Ordering Information 1327 285th Road Seward, NE 68434 Phone 800-949-3526 Fax 402-643-4374 www.lwsinc.com Canadian

Transcript of Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide...

Page 1: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

1

Laminated Wood Systems, Inc.

Strength Chart andSelection Guide

•CSA Grade “1” & “2” Construction•Semi-Thin & Thin Shell Applications•Pole Classes 7 thru H-4•Pole Lengths from 30 to 125 feet•Driving Systems, Tools, & Ordering Information

1327 285th Road • Seward, NE 68434Phone 800-949-3526 • Fax 402-643-4374www.lwsinc.com

Canadian

Page 2: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

2

WindLoad

AG

*ED

*

Leng

th

(or to refusalfor rock conditions)

508mm (20”) Max.

50mm - 100mm(2” to 4”)

Line Direction

Units11,12 & 13

Third Bandused on

WindLoad

AG

*ED

*

Leng

th

(or to refusalfor rock conditions)

Line Direction

Units11,12 & 13

Third Bandused on

Top Bolt required onsingle & doubleBig Foot Units

45o

45o

Due to longitudinal strength, steelmay be rotated up to 45 degreesin either direction

On double units the steelmay be oriented at anylocation with units postioned180o apart

508mm (20”) Max.

50mm - 100mm(2” to 4”)

50mm - 100mm(2” to 4”)

50mm - 100mm(2” to 4”)

Banding &Seals orderedseparately Banding &

Seals orderedseparately

305mm(12”) min.NO BAND

ZONE

305mm(12”) min.NO BAND

ZONE

Single & Double Installation

PoleEnforcer®

Unit Number**

Groundline TransverseStrength (N-m)

SingleUnit

DoubleUnit

GroundlineLongitudinal

Strength (N-m)SingleUnit

Unit Dimensions (mm)

Width Length Thickness

EmbedmentDepth(mm)

E D*AboveGround(mm)

A GUnit

Weight(Kg)

SingleUnit

PoleEnforcer®

Strength Chart

Driving depth is reduced when compared with the old standard

CPE - 35 - 10 47,400 94,800 36,000 127 3048 6 1524 1524 46 CPE - 47 - 10 63,600 127,200 54,000 146 3048 6 1524 1524 54 CPE - 56 - 10 75,800 151,600 47,000 181 3048 6 1524 1524 70 CPE - 75 - 10 101,600 203,200 63,000 181 3048 6 1524 1524 70 CPE - 91 - 11 124,200 248,400 75,000 203 3352 8 1676 1676 95CPE - 108 - 11 146,300 292,600 84,000 229 3352 8 1676 1676 101CPE - 148 - 11 200,500 401,000 108,000 254 3352 9.5 1676 1676 130CPE - 169 - 11 229,600 459,200 117,000 279 3352 9.5 1676 1676 134CPE - 191 - 12 259,400 518,800 128,000 305 3658 9.5 1829 1829 153CPE - 211 - 12 286,500 573,000 139,000 330 3658 9.5 1829 1829 160

**Banding & seals ordered separately. See page 8 for details.

Page 3: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

3

0” to 1” minimum shellthickness required for

the first 12” AGL

1” minimum shellthickness required

Var

ies

12”

4” minimum shellthickness required 12”

below top of steel

Minimum Shell Thickness

Single Units(or double units)

Double Units(only)

12”

1” minimum shellthickness required for

the first 12” AGL

2” minimum shellthickness required

Var

ies

12”

4” minimum shellthickness required 12”

below top of steel

12”

Semi Thin Shell Thin Shell

Effective shell thickness

NOBANDZONE

NOBANDZONE

PhaseRaiser® Test ... “Zero Thin Shell”

Tests conducted on thepatented PhaseRaiser®

structure lifting system(whose steel design isbased on the patentedPoleEnforcer®) provedthe remarkable strengthof the PoleEnforcer® inthin shell applications.The test simulated theequivalent of 8’-0” ofZERO SHELL THICK-NESS. PoleEnforcer® + crossbolts = PhaseRaiser®

50’-0” Class 3 Pole

PoleFailure ....... 3,550 lbs

Loaded ...... 48’-0” AGL

GroundlineMomentFailure ....... 170,400 ft-lbs

No permanentdeformation of steel.

8’-0”ZEROSHELL

Page 4: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

4

Pole Class

CSA (Canadian Standards Association) C22.3 No. 1 - M87Overhead Systems Canadian Electric Code

Outside Wiring

GRADE 1 CONSTRUCTION1.25 / 2 Transverse Loading

Semi-Thin Shell Criteria - Single and Double Units

PoleEnforcer® Selection Guide - Per CSA-015

30 Ft.35 Ft.40 Ft.45 Ft.50 Ft.55 Ft.60 Ft.65 Ft.70 Ft.75 Ft.80 Ft.85 Ft.90 Ft.95 Ft.

100 Ft.105 Ft.110 Ft.115 Ft.120 Ft.125 Ft.

PoleLength H-4 H-3 H-2 H-1 1 2 3 4 5 6 7

75-10 56-10 47-10 35-10 35-10 35-10 35-10

108-11 91-11 91-11 75-10 56-10 47-10 35-10 35-10 35-10

191-12 169-11 148-11 108-11 91-11 75-10 75-10 56-10 47-10 35-10

211-12 191-11 148-11 148-11 108-11 91-11 75-10 56-10 47-10 35-10

148-11D 211-12 169-11 148-11 148-11 108-11 91-11 75-10 56-10

148-11D 108-11D 191-12 169-11 148-11 108-11 91-11 75-10

148-11D 148-11D 211-12 169-11 148-11 148-11 108-11 75-10

169-11D 148-11D 148-11D 191-12 169-11 148-11 108-11 91-11

169-11D 148-11D 148-11D 211-12 169-11 148-11 148-11 91-11

191-12D 169-11D 148-11D 108-11D 191-12 148-11 148-11

191-12D 169-11D 148-11D 148-11D 211-12 169-11 148-11

211-12D 191-12D 148-11D 148-11D 211-12 169-11 148-11

211-12D 191-12D 169-11D 148-11D 148-11D 191-12 148-11

211-12D 169-11D 148-11D 148-11D 191-12

211-12D 191-12D 148-11D 148-11D 211-12

211-12D 169-11D 148-11D 211-12

211-12D 169-11D 148-11D 148-11D

211-12D 191-12D 148-11D 148-11D

191-12D 169-11D 148-11D

191-12D 169-11D 148-11D

Page 5: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

5

Pole Class

CSA (Canadian Standards Association) C22.3 No. 1 - M87Overhead Systems Canadian Electric Code

Outside Wiring

GRADE 1 CONSTRUCTION1.25 / 2 Transverse Loading

Thin Shell Criteria - Double Units Required

PoleEnforcer® Selection Guide - Per CSA-015

30 Ft.35 Ft.40 Ft.45 Ft.50 Ft.55 Ft.60 Ft.65 Ft.70 Ft.75 Ft.80 Ft.85 Ft.90 Ft.95 Ft.

100 Ft.105 Ft.110 Ft.115 Ft.120 Ft.125 Ft.

PoleLength H-4 H-3 H-2 H-1 1 2 3 4 5 6 7

35-10D 35-10D 35-10D 35-10D 35-10D 35-10D 35-10D

56-10D 56-10D 47-10D 35-10D 35-10D 35-10D 35-10D 35-10D 35-10D

91-11D 75-10D 75-10D 56-10D 56-10D 35-10D 35-10D 35-10D 35-10D 35-10D

108-11D 91-11D 75-10D 75-10D 56-10D 47-10D 35-10D 35-10D 35-10D 35-10D

148-11D 148-11D 91-11D 75-10D 75-10D 56-10D 47-10D 35-10D 35-10D

148-11D 108-11D 91-11D 91-11D 75-10D 56-10D 47-10D 35-10D

148-11D 148-11D 108-11D 91-11D 75-10D 75-10D 47-10D 35-10D

169-11D 148-11D 148-11D 108-11D 91-11D 75-10D 56-10D 47-10D

169-11D 148-11D 148-11D 108-11D 91-11D 75-10D 56-10D 47-10D

191-12D 169-11D 148-11D 108-11D 91-11D 75-10D 75-10D

191-12D 169-11D 148-11D 148-11D 108-11D 91-10D 75-10D

211-12D 191-12D 148-11D 148-11D 108-11D 91-10D 75-10D

211-12D 191-12D 169-11D 148-11D 148-11D 91-10D 75-10D

211-12D 169-11D 148-11D 148-11D 108-11D

211-12D 191-12D 148-11D 148-11D 108-10D

211-12D 169-11D 148-11D 108-10D

211-12D 169-11D 148-11D 148-10D

211-12D 191-12D 148-11D 148-10D

191-12D 169-11D 148-10D

191-12D 169-11D 148-10D

Page 6: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

6

Pole Class

CSA (Canadian Standards Association) C22.3 No. 1 - M87Overhead Systems Canadian Electric Code

Outside Wiring

GRADE 2 CONSTRUCTION1.1 / 1.3 Transverse Loading

Semi-Thin Shell Criteria - Single and Double Units

PoleEnforcer® Selection Guide - Per CSA-015

30 Ft.35 Ft.40 Ft.45 Ft.50 Ft.55 Ft.60 Ft.65 Ft.70 Ft.75 Ft.80 Ft.85 Ft.90 Ft.95 Ft.

100 Ft.105 Ft.110 Ft.115 Ft.120 Ft.125 Ft.

PoleLength H-4 H-3 H-2 H-1 1 2 3 4 5 6 7

91-11 75-10 75-10 47-10 47-10 35-10 35-10

148-11 148-11 108-11 918-11 75-10 56-10 47-10 35-10 35-10

148-11D 211-12 191-12 148-11 148-11 91-11 108-11 75-10 56-10 47-10

148-11D 148-11D 211-12 169-11 148-11 148-11 108-11 75-10 75-10 47-10

169-11D 148-11D 148-11D 191-12 169-11 148-11 108-11 91-11 75-10

169-11D 148-11D 148-11D 211-12 191-12 148-11 148-11 108-11

191-12D 169-11D 148-11D 148-11D 191-12 169-11 148-11 108-11

211-12D 191-12D 148-11D 148-11D 211-12 191-12 148-11 148-11

211-12D 191-12D 169-11D 148-11D 148-11D 191-12 169-11 148-11

211-12D 191-12D 148-11D 148-11D 211-12 169-11

191-12D 169-11D 148-11D 108-12 191-12

211-12D 169-11D 148-11D 148-11D 191-12

211-12D 191-12D 148-11D 148-11D 211-12

191-12D 169-11D 148-11D

211-12D 169-11D 148-11D

211-12D 191-12D 148-11D

191-12D 169-11D

191-12D 169-11D

211-12D 169-12D

211-12D 191-12D

Page 7: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

7

Pole Class

CSA (Canadian Standards Association) C22.3 No. 1 - M87Overhead Systems Canadian Electric Code

Outside Wiring

GRADE 2 CONSTRUCTION1.1 / 1.3 Transverse Loading

Thin Shell Criteria - Double Units Required

PoleEnforcer® Selection Guide - Per CSA-015

30 Ft.35 Ft.40 Ft.45 Ft.50 Ft.55 Ft.60 Ft.65 Ft.70 Ft.75 Ft.80 Ft.85 Ft.90 Ft.95 Ft.

100 Ft.105 Ft.110 Ft.115 Ft.120 Ft.125 Ft.

PoleLength H-4 H-3 H-2 H-1 1 2 3 4 5 6 7

47-10D 47-10D 35-10D 35-10D 35-10D 35-10D 35-10D

75-10D 75-10D 56-10D 47-10D 35-10D 35-10D 35-10D 35-10D 35-10D

148-11D 108-11D 91-11D 75-10D 75-10D 56-10D 47-10D 35-10D 35-10D 35-10D

148-11D 148-11D 108-11D 91-11D 75-10D 75-10D 47-10D 47-10D 35-10D 35-10D

169-11D 148-11D 148-11D 108-11D 91-11D 75-10D 56-10D 47-10D 35-10D

169-11D 148-11D 148-11D 148-11D 91-11D 75-10D 75-10D 47-10D

191-12D 169-11D 148-11D 148-11D 108-11D 91-11D 75-10D 56-10D

211-12D 191-12D 148-11D 148-11D 108-11D 91-11D 75-10D 56-10D

211-12D 191-12D 169-11D 148-11D 148-11D 108-11D 75-10D 75-10D

211-12D 191-12D 148-11D 148-11D 108-11D 91-11D

191-12D 169-11D 148-11D 108-11D 91-11D

211-12D 169-11D 148-11D 148-11D 108-11D

211-12D 191-12D 148-11D 148-11D 108-11D

191-12D 169-11D 148-11D

211-12D 169-11D 148-11D

211-12D 191-12D 148-11D

191-12D 169-11D

191-12D 169-11D

211-12D 169-12D

211-12D 191-12D

Page 8: Canadian Strength Chart and Selection Guide · 2020-04-10 · Strength Chart and Selection Guide •CSA Grade “1” & “2” Construction •Semi-Thin & Thin Shell Applications

8

Banding • Seals • Tools • Accessories • Options

51mm (2”) Wide Galvanized Banding

Part Number Description Weight PEB2G85 51mm x 1.3mm (2” x .050”) Steel Banding 43Kg

(approx. 85.4M [280 ft.]) 53,393N (95 lbs.)(12,000 lbs.) ultimate tensile strength. per coil

Galvanized Seals

Part Number Description Weight

PEOS2GL 51mm x 108mm (2” x 4-1/4”) Open Crimp 23KgSeal (250 per box) (50 lbs.)

Safety Caps†

Part Number Description Weight

PE2SC Safety Cap for 35mm to 148mm units 0.45Kg (6” to 10”) (1 lb.)

PE3SC Safety Cap for 169mm to 211mm units 0.45Kg (11” to 13”) (1 lb.)† Nails included

Complete Tool & Driving Systems*

Includes the PE90HHB-B-D Air Hammer & BracketAssembly, the PE90WP Sectional Winch Pole Assemblyand the PE90TWB Pull Down Winch Assembly.

• PE90PDS Pneumatic Driving System

May be operated using either a truck mounted or polemounted capstan hoist. Includes the PE250DS DrivingShank and ten PE25WW 11.4Kg (25lb.) Wafer Weights. Thedrop weight driving system is recommended for hard drivingsoil conditions.

• PE500DWS Drop Weight Driving System

Available upon request.• Hydraulic Driving System

Includes the PE90PDS Pneumatic Driving System and nineother specialized tools, everything needed to install thePoleEnforcer® groundline reinforcement system.

• PE90PDS Pneumatic Driving System Tool Package

Optional “Big Foot”

Uplift & Thrust System

H-frame and guyed angle struc-tures can be reinforced using thePoleEnforcer® BIG FOOT internalfooted system. The installationprocedure is essentially the samewith the exception that theBIG FOOT unit is driven anadditional 125mm (6”) intothe ground. A hydrau-lic uplift cylinder isthen used to raisethe unit to thestandard settingdepth. Raising theBIG FOOT unit causes the“foot” to rotate and engagethe bottom of the pole.

1327 285th Road • Seward, Nebraska 68434Phone: 800-949-3526 • Fax: 402-643-4374

E-mail: [email protected] • www.lwsinc.com

Laminated Wood Systems, Inc.

*Refer to the PoleEnforcer® Driving Systems & Tool brochure for complete ordering information.