Calculation of Altitude Correction

download Calculation of Altitude Correction

of 3

Transcript of Calculation of Altitude Correction

  • 8/16/2019 Calculation of Altitude Correction

    1/3

    1/4/2016 Calculation of Altitude Correction

    http://nepsi.com/resources/calculators/altitude-correction.htm 1/3

    Calculator-1

    Known variables: Equipment E levation (meters or feet), Standard Equipment Impulse Voltage (kV), and Power Frequency Withstand Voltage (kV)

    Formulas and Variables

    IEC Correction Factor IEEE / ANSI Correction Factor  

    Where:

    Up = Rated lightning impule withstand voltage [kV (peak value)]

    Ud = Rated short-duration power-frequency withstand voltage (kV (r.m.s. value))

    Ur  = Rated voltage (kV (r.m.s. value))

    ALTITUDE CORRECTION FOR METAL-ENCLOSED CAPACITOR

    BANKS AND HARMONIC FILTER BANKS

    The following calculator computes the altitude correction factor and resulting sea-level impulse withstand and power frequency withstand voltage

    requirements for electrical equipment being applied at altitudes greater than 1000 meters (3300 feet) in accordance with IEC and IEEE/ANSI

    standards.

     ANSI/IEEE and IEC standards differ slightly on the standard available voltage ratings for components and equipment, impulse withstand voltage,

    and power frequency withstand voltage, as well as the methodology for de-rating these voltage ratings due to high altitude application. The following

    calculator provides both calculations based on the standards.

    Be sure to use tables 1 and 2 to determine "industry standard" sea level withstand and impulse levels for IEC standards, and Table 3 for ANSI

    standards for your rated equipment voltage.

     

    Input Equipment Details*  

    Input Equipment Elevation (in meters or feet): 1500 meters  

    Input Sea Level Impulse Volage Based On System Voltage (kV ): 95  

    Input Sea Level Withstand Voltage Based on System Voltage  (kV): 36  

    * Obtain Impulse and Withstand Voltage Values from Tables 1 and 2 for IEC Standards, an d 

    Table 3 for ANSI Standards 

    IEC Calculation Results  

    IEC Correction Factor: 1.06  

    Required Sea Level Impulse Voltage (kV): 101.01  

    Required Sea Level Withstand Voltage (kV): 38.28  

    ANSI/IEEE Calculation Results  

    ANSI/IEEE Correction Factor: 1.05  

    Required Sea Level Impulse Voltage (kV): 100.00  

    Required Sea Level Withstand Voltage (kV): 37.89  

    http://nepsi.com/http://nepsi.com/http://nepsi.com/http://nepsi.com/http://nepsi.com/

  • 8/16/2019 Calculation of Altitude Correction

    2/3

    1/4/2016 Calculation of Altitude Correction

    http://nepsi.com/resources/calculators/altitude-correction.htm 2/3

    Ka = altitude correction factor

    H = altitude above sea level in meters

    Note: the correction factors should only be applied to the impulse and withstand voltages and not to the rated voltages.

    Background

    Medium-voltage metal-enclosed harmonic filter banks are designed and built with components that are based on application under "usual service

    conditions" as defined by IEC and ANSI standards. Generally, the "usual service conditions" defined in standards encompass ambient temperature,

    altitude, solar radiation, and environmental considerations.

    The insulating property of air decreases as the altitude increases, therefore this phenomenon must be taken into account for air insulated

    components applied at altitudes greater than 1000 meters (3300 feet). ANSI/IEEE and IEC standards provide a methodology for determining the

    impulse withstand voltage, and power frequency withstand voltage for medium-voltage components used in metal-enclosed harmonic filter banks at

    high altitude.

    IEC STANDARDS

    In accordance with IEC 60694, the rated insulation level for switchgear and control gear is selected from the values given in tables 1 and 2,

    depending on location. In these tables, the withstand voltages are based on a standardized reference atmosphere (i.e. sea level). The standards

    state the rated withstand voltage values for lightning impulse voltage (Up) and power-frequency withstand voltage (Ud) shall be selected without

    crossing the horizontal marked lines based on the rated voltage of the switchgear or control gear, or in NEPSI's case, the harmonic filter or 

    capacitor bank.

    For most of the rated voltages, several rated insulation levels exists to allow for application of different overvoltage performance criteria. The choiceof insulation level for a give rated voltage should be made considering the degree of exposure to fast-front and slow-front over-voltages, the type of 

    neutral earthing of the system, and the type of overvoltage limiting devices. Medium-voltage metal-enclosed harmonic filter banks equipped with

    lightning arresters are considered to have a lower degree of exposure and therefore the lower withstand voltage is most often chosen. Metal-

    enclosed banks are considered to have lower exposer.

    Table 1 - IEC Rated Insulation Levels for Rated Voltages

    Non-North American Apparatus

    Table 2 - IEC Rated Insulation Levels for Rated Voltages

    For North American Apparatus

  • 8/16/2019 Calculation of Altitude Correction

    3/3

    1/4/2016 Calculation of Altitude Correction

    http://nepsi.com/resources/calculators/altitude-correction.htm 3/3

    ANSI / IEEE STANDARDS

     ANSI standards are similar to IEC standards in that they both use a multiplying factor and both have standard voltage withstand ratings based on

    equipment voltage rating. Table 3 provides the standard voltage ratings for equipment rated in accordance with ANSI/IEEE standards. Table 3 can

    also be used in a similar manor to 1 and 2. The first column on the left is the Rated maximum Voltage (Ur ). The second is the Power-frequency

    withstand voltage (Ud). The final column is the Impulse withstand (Up).

    Table 4 is utilized to determine altitude correction factors in accordance altitude. The table shows a 1% decrease in withstand voltages for each 100

    meters above 1000 meters. The voltage factors shown in Table 4 should be applied to both the power frequency withstand voltage and the impulse

    withstand voltage.

    Table 3 - Standard Voltage and Insulation Levels for Components Rated in Accordance With ANSI/IEEE Standards

    Table 4 - Altitude Correction Factors