Page 1: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

..........................................................................

Cahier technique n° 179

LV surges and surge arrestersLV insulation co-ordination

C. Séraudie

Collection Technique

Page 2: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

"Cahiers Techniques" is a collection of documents intended for engineersand technicians, people in the industry who are looking for more in-depthinformation in order to complement that given in product catalogues.

Furthermore, these "Cahiers Techniques" are often considered as helpful"tools" for training courses.They provide knowledge on new technical and technological developmentsin the electrotechnical field and electronics. They also provide betterunderstanding of various phenomena observed in electrical installations,systems and equipments.Each "Cahier Technique" provides an in-depth study of a precise subject inthe fields of electrical networks, protection devices, monitoring and controland industrial automation systems.

The latest publications can be downloaded from the Schneider Electricinternet web site.Code: http://www.schneider-electric.comSection: Experts' place

Please contact your Schneider Electric representative if you want either a"Cahier Technique" or the list of available titles.

The "Cahiers Techniques" collection is part of the Schneider Electric’s"Collection technique".

ForewordThe author disclaims all responsibility subsequent to incorrect use ofinformation or diagrams reproduced in this document, and cannot be heldresponsible for any errors or oversights, or for the consequences of usinginformation and diagrams contained in this document.

Reproduction of all or part of a "Cahier Technique" is authorised with theprior consent of the Scientific and Technical Division. The statement"Extracted from Schneider Electric "Cahier Technique" no. ....." (pleasespecify) is compulsory.

Page 3: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

ECT 179 first issue, March 1999

no. 179LV surges and surge arrestersLV insulation co-ordination

Christophe SERAUDIE

Having graduated from the Centre d’Etudes Supérieures desTechniques Industrielles (CESTI: Centre for the Advanced Study ofIndustrial Techniques) in 1986, he then obtained his PhD in ceramicmaterials in 1990 (thesis prepared at Limoges University under aCeramics and Composites CNRS contract). He joined Merlin Gerin’s“LV breaking” research group that same year, and then in 1992assumed responsibility for development of surge arresters in theLV Final Distribution Division.

Page 4: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.2

Lexicon

Common mode (disturbances):which are applied and propagated between liveconductors and frames or the earth.

Differential mode (disturbances):which are superimposed on network voltageand propagated between the various liveconductors.

Filter:equipment particularly designed to eliminateswitching and power frequency surges.

Holding current Is:current delivered by the network and which flowsoff via the surge arrester after passage of thedischarge current (this phenomenon only existsfor spark-gap-based technologies).

Leakage current I f:current flowing in the surge arrester whenit is supplied at its maximum steady statevoltage.

Level of protection:the highest value of residual voltage andmaximum arcing voltage.

Lightning rod:a metal device designed to intercept lightning inorder to flow it off to earth.

Maximum arcing voltage:peak voltage in 1.2/50 µs wave (characteristicspecific to spark-gap type components).

Nominal In or maximum Imax discharge current:peak value of the current in 8/20 µs wave(see fig. 9 ) used for operating tests.

Residual voltage U r:voltage appearing at the terminals of a surgelimiter (component or switchgear) duringdischarge current flow.

Surge limiter:device used to attenuate or clip certain types ofsurge. In France this term is particularly reservedfor MV surge protection devices in LV installationsusing IT earthing systems.

Surge arrester:a device designed to limit transient surges,including lightning surges, and to redirect currentwaves. It contains at least one non-linearcomponent (as per NF C 61-740).

Page 5: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.3

LV surges and surge arrestersLV insulation co-ordination

Contents

1 Surges p. 41.1 Lightning surges p. 5

1.2 Surges by electrostatic discharges p. 8

1.3 Switching surges p. 8

1.4 Power frequency surges p. 9

2 Surge protection devices 2.1 The protection principles p. 10

2.2 The components p. 13

2.3 Implementation of the components p. 14

3 Standards and applications 3.1 “Product” standards p. 16

3.2 Horizontal standards p. 17

3.3 Surge arrester installation guides p. 17

3.4 Implementation of surge arresters p. 19

4 Conclusion p. 22

Bibliography p. 23

Low voltage insulation co-ordination consists of matching the surge levelsthat may appear on an electrical network (or installation) with the surgewithstand of the industrial or domestic equipment that it supplies, bearing inmind the possibility of including surge limiting devices in the networkstructure.This discipline contributes to increased safety of equipment and increasedavailability of electrical power.

Insulation co-ordination control therefore requires:c estimation of surge level and energy,c knowledge of the characteristics and location of the devices installed,c selection of appropriate protection devices, bearing in mind that fora device, there is only one surge withstand (normally defined by itsconstruction standard).

This “Cahier Technique” deals with the aspects relating to standards andimplementation of disturbances, protection devices and in particular surgearresters.

It mainly concerns LV installations (< 1000 V) in the industrial, tertiary anddomestic sectors.

Page 6: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.4

1 Surges

There are four different types of surge:c lightning,c electrostatic discharge,c switching,c power frequency.

Their main characteristics are described in thetable in figure 1 , and are defined in theIEC 1000-4 publications.

These disturbances which are superimposed onnetwork voltage can be applied in two modes:

c common mode, between the live conductorsand the earth,c differential mode, between the various liveconductors.In both cases the resulting damage comes fromdielectric breakdown and leads to destruction ofsensitive equipment and in particular of electroniccomponents.

Installations are regularly subjected to acertain number of non-negligible surges(see fig. 2 ) which cause malfunctioning and

Home (living roomon 1st floor)

kV0.1 0.2 0.3 0.70.5 1 2 3 5 7 10 20 40 50 700.010.02

0.10.2

12

1020

100200

10002000

Landis andGyr factory(furnace room)

Home (service entrance)underground distribution

Landis and Gyr factory (laboratory)

Bank in Basel (service entrance)

Farm supplied byoverhead lines

Composite curve inUSA, 120 V distribution

Number oftransients/year

Surge Duration Steepness of rising edge, Damping accordingor frequency to distance

Lightning Very short (µs) Very high (1000 kV/µs) Strong

Electrostatic Very short (ns) High Very strongdischarge (≈ 10 MHz)

Switching Short (ms) Average Average(1 to 200 kHz)

At power Long (s), Network frequency Zerofrequency or very long (h)

Fig. 1: the four types of surge present on the electrical networks.

Fig. 2 : frequencies of occurrence and peak values of surges (recorded by Landis and Gyr and published by the IEEE).

Page 7: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.5

1.1 Lightning surges

Lightning is a natural phenomenon withspectacular and destructive consequences.

In France two million lightning strokes causeeach year the death of 40 people and20000 animals, 15000 fires, 50000 power cutson electrical and telephone networks and thedestruction of countless transformers andthousands of electronic household appliances.The total cost of the effects of lightning isestimated at around one thousand million francsa year. Not all regions have the same degree ofexposure. Although a map normally exists

showing the lightning densities for each country,in order to determine in greater detail theexposure of a site, preference should be given tothe maps published by firms specialising in thedetection of storms and related phenomena(see fig. 3 ).

Lightning is linked to the formation of stormclouds which combine with the ground to form agenuine dipole. The electrical field on the groundmay then reach 20 kV/m. A leader developsbetween the cloud and the ground in a series of

even destruction of equipment, resulting indowntime.Protection devices, such as HV and LV surgearresters, are available. However, in order to

ensure correct protection against the surgesoccurring on the network, detailed knowledge oftheir nature and characteristics is necessary.This is the purpose of this chapter.

( Copyright 1985 METEORAGE).

Fig. 3 : reading of lightning impacts in France. Each colour corresponds to a lightning striking density.

Bastia

Ajaccio

Nancy

Dijon

Strasbourg

Rouen

Rennes

Brest

Nantes

Orléans

Paris

Limoges

Bordeaux

Toulouse

Lyons

Marseilles

Lille

Page 8: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.6

leaps, creating the ionised channel in which thereturn arc or lightning stroke flows (see fig. 4 ).According to the polarity of the cloud withrespect to the ground, the stroke is eithernegative (negative cloud) or positive (positivecloud), and according to the origin of the leader,the stroke is either ascending or descending.

It has been observed that in countries with atemperate climate (including France), themajority of lightning strokes are negative, butthat the most energetic are positive.Their effects form the subject of two approaches:when the element studied is the one receivingthe stroke, we refer to a direct lightning stroke,and when the element studied only suffers theeffects of the stroke, we refer to an indirectlightning stroke.When lightning falls on a structure, the lightningcurrent generates an impulse surge.

The direct lightning stroke

In the electrotechnical field, the “direct” lightningstroke is the one directly striking the electricalinstallations (overhead lines, substations, etc.).Its energy is considerable as 50 % of lightningstrokes exceed 25 kA peak and 1 % exceed180 kA (see table in figure 5 ).The steepness of these discharges can reach100 kA/µs. Moreover, a lightning stroke is rarelyunique, but several impulses (discharges),separated by dozens of milliseconds, can bedetected (see fig. 6 ). Fig. 4 : diagram showing a lightning stroke.

Overrun Current Load Slope i dt2∫ Total Number of

possibility peak duration discharges

P (%) I (kA) Q (C) S (kA/µs) (KA2.s) T (s) n

50 26 14 48 0.54 0.09 1.8

10 73 70 74 1.9 0.56 5

1 180 330 97 35 2.7 12

Fig. 5 : main characteristics for lightning strokes (source: Soulé).

The destructive effects of a direct lightning strokeare well known: electrocution of living beings,melting of components and fires in buildings. Theinstallation of a lightning rod on a constructionlimits these risks, as do also the guard wiresprotecting EHV lines.

Fig. 6 : form of the negative ground/cloud lightning current.

+ + + + + + +

--

--

-- -

+ + + + + + +

Leap leader

Continuous leaderReturnarc

Current (A)

First current arc 30000

1000

50 µs

30 ms

Slope 30 kA/µs

Second return arc15 kA

Total load Q: 30 coulombs

Subsequent arcs

0.5 s Time

Page 9: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.7

The indirect lightning stroke

This is the manifestation at a distance of a directlightning stroke.Three aspects of its effects are covered:conducted surges, rise in earthing potential andradiation.

c Conducted surges are the result of an impacton overhead lines, and may reach severalhundred kilovolts.If the impact occurs on an MV network, thetransmission by the transformer to LV takesplace by capacitive coupling (see fig. 7 ). As arule less than 4 % of surge amplitude on theMV side is found on the LV side. A statisticalstudy carried out in France shows that 91 % ofsurges at a LV consumer do not exceed 4 kVand 98 % do not exceed 6 kV.

c A rise in earthing potential occurs when thelightning current flows off through the ground.This variation in earthing potential affectsinstallations when the lightning strikes the

ground near their earthing connections(see fig. 8 ). Thus, at a given distance D from thepoint of impact of the lightning, the potential U isexpressed by the equation:U 0.2 s / D≈ I ρwhereI: lightning current,ρs: ground resistivity.

If this formula is applied to the case of figure 8whereI = 20 kA,ρs = 1000 Ohm.m,D/neutral = 100 m,D/installation = 50 m,the potential of the neutral earthingconnection rises to 40 kV, whereas that ofthe installation earthing connection is 80 kV,i.e. a potential difference -pd- between theneutral and installation earthing connections of40 kV. However, this example is purelyacademic since in reality the values attained inthe installation seldom exceed 10 kV.

Fig. 7 : transmission of a lightning surge, from MV to LV, takes place by capacitive coupling of the transformerwindings.

Fig. 8 : diagram explaining the rises and differences in potential of the earths of an electrical installation.

Uf

Uf

ZpnUf

M

Lightningsurge

100 m

Distance oflightning stroke

50 m0 m

∆U

D

Page 10: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.8

Naturally this surge also depends on groundresistivity.This often accounts for the phenomenon ofanimals that are indirectly struck by lightning:even 100 m away from the point of impact, ahorse in a meadow may receive a difference inpotential of 500 V between his rear and forelegs.

c Radiation is another effect, as an indirectlightning stroke can generate an extremely rapidvariation in the electromagnetic field, responsiblefor the voltages induced in the loops.Consequently, it is common to find, in the vicinityof storms, induced voltages of some hundredvolts per square metre of loop.

Fig. 9 : standardised lightning waveforms.

1.2 Surges by electrostatic discharges

In a very dry environment, human beingselectrostatically charged by friction (particularlyon a synthetic carpet) frequently attain a voltageof several dozen kilovolts. Its discharge is animpulse current of a few dozen amperes.

1.3 Switching surges

This type of phenomenon occurs on electricalnetworks undergoing rapid modifications totheir structure (opening of protection devices,opening and closing of control devices). Thesurges generated are normally propagated in theform of high frequency waves with rapiddamping.

Switching of inductive currents

On making or breaking of inductive currents,impulses with a high amplitude and a very smallrise time may occur. Thus, a switch controllingan electric motor, an LV/LV transformer, acontactor, or even a simple relay, etc. generatesa differential mode surge whose amplitude mayexceed 1000 V with rising edges of a fewmicroseconds.

Switching surges caused by the switching ofinductive currents may also stem from MV.

Switching of capacitive circuits

Whereas electrical networks tend to be moreinductive, the presence of capacitances(capacitor banks or simply off-load lines) formsan LC resonant circuit. Switching then causessurges of the oscillating kind. A surge factor ofthree can be observed in the event of re-arcingafter breaking.

Breaking a strong current by a breaking device

The breaking of a short-circuit current generatessurges if breaking is very quick and withoutenergy consumption by the arc. Surges may begreat when certain fuses are blown

The associated electric fields, radiated by theflash, may reach 50 kV/m, and can induce highvoltages in the open circuits which act like aerials.A very steep front and a rapid damping arecharacteristic of such phenomena. A statisticalstudy of surges and overcurrents due to lightninghas resulted in the standardisation of the wavesshown in figure 9 .Characterisation of equipment according to thiswave type is a reference for its lightningwithstand.The answer to these various effects of lightningis dealt with in a “protection device” approachdeveloped in chapter 3.

Perforation of electronic components has beenobserved after such discharges, whose risingedges are extremely steep (a few nanosecondsat most).

a) “Current” 8/20 µs wave b) “Voltage” 1.2/50 µs wave

i

tµs

208

50 %

u

tµs501,2

50 %

Page 11: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.9

Fig. 10 : standardised waveforms representing switching surges.

(of around 1.5 kV). A similar well known case isthe current breaking accompanying arc welding:the surges observed reach a dozen kilovolts.A statistical study of switching surges hasresulted in standardisation of the waves shownin figure 10 .

1.4 Surges at power frequency

The main characteristic of these surges is theirfrequency which assumes that of the network:generally 50, 60 or 400 Hz.

MV spark-gap holding current

Lightning falling on an MV line causes arcing ofthe spark-gaps which then flow off to earth acurrent, at network frequency, until the protectiondevices of the main substation trip. This currentgenerates, for a fraction of a second, a rise inearthing potential of the LV network as well as arisk of breakdown in return of the LV equipmentif the earthing connection of the spark-gaps isthe same as that of the LV neutral.

This surge may appear several times insuccession, for example during re-energisationattempts while the insulation fault is still present(case of automatic reclosing cycles on overheadnetworks in rural distribution). This risk is notpresent with zinc oxide surge arresters which donot have a holding current.Such a rise in earthing potential of the LV networkalso occurs in the event of MV/frame breakdown

Characterisation of equipment according to thiswave type is a reference for its switching surgewithstand.

of an MV/LV transformer if the frame of thetransformer is connected to the neutral earth.

Breaking of neutral continuity

Although distribution networks are normallythree-phase, many switchgear items aresingle-phase. Depending on the needs of eachLV consumer, voltage unbalances may occur.The most problematic case is breaking of theneutral which may generate a rise in potentialthat is harmful for devices programmed tooperate at single-phase voltage and which thenfind themselves operating at a voltage close tophase-to-phase voltage.

The insulation fault

In the case of a three-phase network withunearthed or impedant neutral, one earthedphase subjects the two other phases tophase-to-phase voltage with respect to earth.The most dangerous of all these surges are thosewhich are propagated in common mode, eitherlightning or power frequency, when the MV zerophase-sequence current is strong.

50 %

2.50.25

t

ms

va) “Long dampened” 250/2500 µs wave

b) “Recurrent pulse” 5/50 ns wave (simulating fuseblowing for example)

c) “Dampened sinusoidal” 0.5 µs /100 kHz wave

t

ns

v

50 %

505

v

t

10

U

0.1 U

0.5µs

0.9 U

Page 12: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.10

Degree of pollution Construction Surge categoryrequirement I II III IV

For devices connected For energy consuming For devices in fixed For devicesto circuits in which devices, supplied installations and if used at themeasurements are from the fixed reliability and installationtaken to limit transient installation availability of the originsurges to an device are covered byappropriate low level specific specifications

Rated impulse withstand 1.5 2.5 4 6voltage (kV)

1.2/50 µs test voltage at 1.8 2.9 4.9 7.4sea level (kV)

1 = No pollution, or only Minimum clearance 0.5 1.5 3 5.5dry non-conductive in air (mm)pollution

2 = Normal presence of Minimum clearance 0.5 1.5 3 5.5non-conductive in air (mm)pollution only

3 = Presence of Minimum clearance 0.8 1.5 3 5.5conductive pollution in air (mm)or of a dry non-conductive pollutionwhich becomesconductive as a resultof condensation

4 = Persistent high Minimum clearance 1.6 1.6 3 5.5conductivity due to in air (mm)pollution caused, forexample, by conductivedust or by snow and rain

2 Surge protection devices

In order to ensure safety of people, protection ofequipment and, to a certain extent, continuity ofsupply, insulation co-ordination aims at reducingthe likelihood of equipment dielectric failure.Several components can be used to limit and/or

eliminate the surges described earlier. Thesecomponents, used to manufacture the surgeprotection devices, are sometimes includedin certain LV devices, particularly of theelectronic kind.

2.1 The protection principles

The level of surge that a device is able towithstand depends on its two main electricalcharacteristics which are:c clearance in air,c length of creepage distance on the insulatorsor tracking.

The surge protection devices are classedaccording to their function:c the primary protection devices which deal withdirect lightning strokes,c the secondary protection devices whichcomplete the first kind and deal with all othersurge phenomena.

It should be noted that all these devices and theirinstallation must also take account of theelectromagnetic disturbances due to currents ofhigh strength and/or high di/dt (e.g. lightningdischarge currents).

Clearance

Clearance is the shortest distance between twoconductors. This distance, in air, plays an impor-tant role in the breakdown phenomenon. The riskof arcing depends on the voltage applied and thedegree of pollution. For this reason electricaldevices must satisfy standards (see fig. 11 )

Fig. 11: impulse withstand voltages and clearances (as in IEC 947-1) applicable for equipment installed on LV 230/400 V networks.

Page 13: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.11

which particularly define four categories of surgeand four degrees of pollution.Assessment of the degree of “normal pollution”varies according to the application:c for industrial applications, unless otherwisespecified in the relevant equipment standard,devices for industrial applications are normallydesigned to be used in an environment with adegree of pollution 3,c for domestic applications, unless otherwisespecified in the relevant equipment standard,devices for domestic and similar applications arenormally designed to be used in an environmentwith a degree of pollution 2.

Length of creepage distance on theinsulators

Creepage distance is the shortest distance,along the surface of an insulating material,between two conductive parts.Electrical devices must also satisfy standards inthis area (see fig. 12 ).

However, in an electrical installation theseconstruction arrangements (clearance andcreepage distance) may prove insufficient,particularly for loads. The use of the protectiondevices described below is thus often advisable.

The primary protection devices

These devices consist of a sensor, a specificelectrical conductor and an earth. They perform

three functions: intercepting lightning strokes,flowing them off to earth and dissipating them inthe ground.

The interception devices are the lightning rodswhich are available in different forms such asguard wires on HV overhead lines or Franklinantennae at the top of steeples.They are earthedin order to flow off the lightning currents, either byone conductor (often a copper strip) or by several(which is preferable). The earth, which must beparticularly well made, is often formed by several,separately buried, copper conductors.Installation and choice of a lightning rod aredetermined on the basis of a maximumacceptable lightning current for the installationand the area to be protected. According to thismaximum current (or peak current of the firstimpulse), the electrogeometrical model is used tocalculate critical arcing distance. This distance isused as the radius of a fictitious sphere rollingalong the ground and which knocks up againstthe buildings to be protected. Only the areaunder the sphere is protected for lightningcurrents of a strength greater than or equal tothe reference value. All elements in contact withthis sphere are exposed to being directly struckby lightning (see fig. 13 ).

The secondary protection devices

These devices provide protection against theindirect effects of lightning and/or switching andpower frequency surges.

Fig. 12 : lengths in millimetres of creepage distances for electrical devices (extracted from publication IEC 947-1).

Fig. 13 : principle of the electrogeometrical model used to define the zone protected by a surge arrester.

Degree of pollution 1 2 3 4

Comparative tracking u 100 u 600 u 400 u 100 u 600 u 400 u 100 u 600 u 400 u 175index to 600 to 400 to 600 to 400 to 600 to 400

Rated insulationvoltage (V) 400 1 2 2.8 4 5 5.6 6.3 8 10 12.5

500 1.3 2.5 3.6 5 6.3 7.1 8 10 12.5 16

630 1.8 3.2 4.5 6.3 8 9 10 12.5 16 20

����������

Fictitioussphere

Leader

d = Critical arcingdistance

Lightning rod

Protected zone

Page 14: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.12

These devices sometimes contain several of thedevices described above, and as such are partof the secondary protection devices.

The other protection typesTelephony and switched networks are affectedby surges like LV, the only difference being thatthe acceptable surge level is normally lower.

There are two types of telephone protectiondevices:c modules plugged into boards for telephoneexchanges,c modular cases to be mounted on symmetricalrail, designed to protect one or more telephonepairs (see fig. 15 ) for users (tertiary and domestic),c mixed “LV supply/telephony” extensions forMinitel type applications.In actual fact all information transmissionequipment can be affected and disturbed bysurges. Therefore suitable surge arresters mustbe specified for domotic installations (of theBatiBUS type) as well as for computer andaudiovisual equipment.

Fig. 14 : installation diagram of a surge limiter.

Fig. 15 : a surge arrester for telephone network(Merlin Gerin PRC surge arrester).

This category contains:v surge arresters for LV networks,v filters,v wave absorbers.

Under some conditions, other devices may alsoperform this function:v transformers,v surge limiters,v network conditioners and static UninterruptiblePower Supplies (UPS).

In practice these devices have two effects: eitherthey limit the impulse voltage (these are the“parallel” protection devices) or they limit thepower transmitted (these are the “serial”protection devices).c Surge arrestersIn LV, this type of switchgear has considerablyprogressed in terms of safety with reinforcedstandardised tests: nominal withstand to20 lightning impulses instead of the previous 3,and specific tests at power frequency surges.

Furthermore, with the latest standards, surgearresters can be forgotten once installed, sinceany deterioration due to serious faults must bereported (remote transfer, technical alarm, etc.).

An entire range of surge arresters is thusavailable: modular arresters for mounting on asymmetrical rail, arresters that can be installed ina main LV board or in a subdistribution enclosureand even “flush-mountable” models placed insocket boxes. They all enable flow off of variouscurrents (from 1 to 65 kA) with a varyingprotection level (from 1500 to 2000 V).

c Filters and transformersA filter uses the RLC circuit principle, and iseasily calculated once the disturbance to befiltered has been properly identified. It isparticularly used to attenuate switching surges.A transformer can also act as a filter: its reactorattenuates surges and reduces the steepness oftheir wave front.c Wave absorbersA wave absorber is a “super” surge arrester/filterin that it can dissipate important energies (due tosurge) and that its protection level is ideal forelectronic equipment.However, these devices have one major defect,namely their filters which, due to theirserial-connection, impose a sizing directly linkedto the nominal current which will pass throughthem. They are therefore used more in finaldistribution.c Surge limitersThese devices defined in French standardNF C 63-150 are used on unearthed or impedantnetworks (IT earthing system) and installed atthe MV/LV transformer outlet (see fig. 14 ). Theyenable the flow off to earth of high energy surgesand withstand the “earth” fault current of theMV network.c The network conditioners and the StaticUninterruptible Power Supplies

Surge limiter asper French standardNF C 63-150

Permanentinsulationmonitor: PIM

Earthing system: IT

PIM

MV/LV

Page 15: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.13

2.2 The components

networks), insulator bypass by surface trackingof a dielectric, or gas within a sealed tube.Its advantages are that it allows high energies toflow through, combined with a very small straycapacitance.

Its disadvantages are as follows:c its high conduction voltage dependent on wavefront steepness,c its long response time linked to wave frontsteepness,c the existence of a holding current (hard toextinguish),c potential drift of its threshold voltage.In the case of air spark-gaps (LV indoor), arcingvoltage also depends on atmospheric conditions(degree of hygrometry and pressure) and thuson the installation site (damp premises andaltitude): variations of 40 % have been observed.

Silicon componentsThis designation covers a variety of electroniccomponents (diode, thyristor, triac, etc.).Their low energy withstand means that thesecomponents are mainly used in LV andparticularly on telephone lines. Their responsetime and residual voltage are low.As a rule destruction of these components takesthe form of a short-circuit, which is an easilydetectable electrical fault.

How to choose a componentSurge arrester manufacturers base their choiceon a variety of characteristics:c threshold voltage Us or conduction voltage,c residual voltage Ur when the disturbance occurs,c leakage current I f at mains voltage,c response time,c stray capacitance,c energy withstand,c failure mode, etc.For information, some of these are quoted in thetable in figure 16 .

Protection devices are designed with a variety ofcomponents, some of which, such as reactors,resistors and capacitors are already well known toelectricians, and others, such as varistors, spark-gaps and silicon components, whose behaviour isdescribed below. These explanations are given,for LV surge arresters, for devices with virtuallyidentical volumes (as a guideline of the size ofmodular switchgear), as overall dimension is alsoan important choice criterion for the user.

The varistor

This component is also known as MOV whichstands for “Metal Oxide Varistor” (GEMOV for theGeneral Electric brand and SIOV for the Siemensbrand), or simply variable resistor as it has anon-linear behaviour. Presented most commonlyin the form of a cylindrical lozenge, it is a ceramicsolid originally made of silicon carbide (SiC) andtoday made of zinc oxide (ZnO). Lozengethickness defines its voltage characteristic, andits surface the amount of energy that it candissipate. Its main advantage is its energyloss / cost ratio which makes it an essentialcomponent in the manufacture of surge arresters.

The main problem stems from its implementationas:c a series of low energy impulses causes tempe-rature rise and speeds up the ageing process,c excessive energy implies destruction of thecomponent by short-circuiting,c a very high energy may in some cases result inexplosion of the varistor.

Today, these disadvantages are minimised bythe know-how of surge arrester manufacturers:c a disconnection system prevents thermalrunaway and cuts out the faulty component,c coating with a fireproof resin is used to containthe high energies to be dissipated.

The spark-gapThe following types are available: air (such asthe former horn gap placed on MV overhead

Fig. 16 : the main characteristics of the components for surge protection devices.

Characteristic U/ I Component Leakage current I f Holding current Is Residual voltage U r Conducted energy E Conduction time t

Ideal device 0 0 Weak High Weak

Spark-gap 0 Strong Weak High Strongbut strong US

Varistor Weak 0 Weak High Medium

Diode Weak 0 Weak Weak Weak

U

IU

IU

IU

I

Page 16: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.14

These characteristics are evaluated by testsaccording to various constraints (voltage,current, energy).

Standardised waves reproducing thedisturbances and surges described in theprevious chapter are used for this purpose. Inparticular, for studying varistor ageing, the10/1000 µs wave, applied several times, hasbeen chosen (see fig. 17 ).

Fig. 17 : 10/1000 µs wave, particularly used to studyvaristor ageing.

2.3 Implementation of components

In order to benefit from the various advantagesof these components, the obvious solution is tocombine them.A diagram is thus required to implement themwithin devices designed to be placed simply onelectrical installations. However there is nostandard diagram, and only a diagram tailored to aspecific need can satisfy the operator. In practice,well designed and properly tested assemblies areable to suitably combine the advantages descri-bed above, taking account of input data (lightning,etc.) and output data (low residual voltage, etc.).

This diagram is also used to make the technical/economic compromise able to satisfy the user interms of value for money.

The main surge protection devices onLV networks are:c filters,c surge arresters,

c wave absorbers,c and, for telephone networks, specific surgearresters.

FilterBased on combinations of reactors andcapacitors, a large number of diagrams arepossible (see fig. 18 ).Its attenuation varies according to the diagram,in L, T or π.To ensure proper adaptation of the device,choice of components, based on a calculationusing the pass-bands of the disturbances to becontrolled, therefore requires sound knowledgeof installation impedances.

LV surge arresterThe diagram of a simple, effective LV surgearrester is described in figure 19 : the three

Fig. 18 : standard diagrams of filters used in LV.

Fig. 19 : diagram and photograph of a single-phase LV surge arrester (Merlin Gerin PF15 middle-range surge arrester).

Ph N

i

t

100010 µs

50 %

c) in πb) in Ta) in L

Page 17: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.15

varistors thus combined protect the installation inthe common and differential modes.

To obtain a better energy withstand/residualvoltage ratio, another combination of thecomponents is used, performed for a singlephase (as shown in the diagram in figure 20 ):c the spark-gap dissipates the energy,c the serial-connected reactors “flatten” the wavefronts: the “sensitive” components are thusseparated with reduced electrical stresses whensurges occur,c and the varistor fixes the residual voltage.

The reactors are sized according to thecharacteristics of the components and thenominal current of the line to be protected. Thislast point often results in a large volume and highcost for these protection devices.

Wave absorber

Based on combined filter/surge arresterdiagrams, it effectively eliminates energy surges.It may also contain an earthed screentransformer in order to block differential mode HFdisturbances and common mode LF voltages.

Reserved for sensitive installations, it normallytakes the form of a large-sized enclosure.

Surge arrester for information and telephonecircuits

The gas discharge tube is ideal for the protectionof telephone lines:c the permanent supply voltage is sufficiently lowto prevent holding current on the discharge tubeafter a surge,c its clipping voltage is greater than ringinggenerator voltage.

In this area, the devices used have recourse toseveral electronic diagrams. A distinction mustbe made between:c those used in information exchange centres,for example in radio relays,c those designed for installation in telephoneexchanges,c those designed for the protection of simpletelephone lines, for example implemented on thetelephone incoming line in a home.

All these devices have virtually the sameelectrical characteristics (conduction voltage,response time, leakage current), as theoperating voltages on these networks are small.However their installation and energy flow offcapacity are different.

In a home, a surge arrester designed to protecta telephone incoming line can be installed inthe consumer switchboard and may usethe earthing connection of the electricalinstallation.

Figure 21 shows two internal diagrams ofthis type of surge arrester for a simpletelephone line, one grouping three spark-gapsand the other showing their integration in a“3 terminal” version. The latter is preferable, asit allows better balancing of common modeprotection devices and a reduction in arcingvoltage by bringing the electrodes closertogether.

Fig. 20: complete diagram of a LV surge arrester withserial-mounted reactors: more than just a filter.

Fig. 21: use of gas discharge tubes on a telephonenetwork, either from 2P devices or from a single 3P device.

(+) (-) (+)

(-)

Page 18: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.16

3 Standards and applications

The increasing need for availability of electricalpower together with the upgrading of electricalequipment and installations (strong currents andin particular weak currents) are responsible forthe development of surge arresters. Theselightning protection devices were firststandardised in France, but European andinternational standards should be publishedbefore the end of the century.

The standards dealing with this subject can bedivided into three main categories:

c product standards, for the design andmanufacture of surge arresters,c horizontal standards, which concern the designand/or implementation of various devices,c implementation guides, specific to LV surgearresters.

A global approach to the above texts, followedby some implementation examples, completethis chapter.

3.1 “Product” standards

Product approval is a guarantee for its user interms of operation and safety.

The vast majority of electrical switchgear have tosatisfy specific manufacturing standards.Consequently, for electrical power distribution,circuit-breakers satisfy standard IEC 947-2(NF C 63-120) for industry and standard IEC 898(NF C 61-410) for domestic applications.Contactors and switches have to satisfy otherparts of standard IEC 947. Likewise,switchboards and cubicles also have to complywith standards, such as IEC 439-1.

These texts specify all components of electricalnetworks, right down to loads, with respect toinsulation and surge withstand (see fig. 22 ).

The purpose of the surge arresters is protectionof the various electrical equipment.

A “product” standard specific to LV surgearresters has been available in France since1987: the NF C 61-740. The requirement toconform to this standard increases dependabilityof installations and safety of the people operatingthem.

The 1995 version of standard NF C 61-740defines the normal operating conditions, therated characteristics, the classification, etc. Thisstandard particularly describes certain testsguaranteeing safety. In addition to the“conventional” tests (connection, case, etc.),other more specific tests are scheduled:c verification of the level of residual voltage Ur atnominal discharge current In (8/20 µs wave) andof maximum impulse arcing voltage (1.2/50 µswave). The highest of these values forms theprotection level of the surge arrester (forexample 1500 V);c proper operation after 20 impulses at nominaldischarge current In, for example 20 kA (without

disconnection or any changes in surge arrestercharacteristics);c proper operation after 1 impulse at maximumdischarge current Imax, for example 65 kA(a rechargeable disconnection can take placebut without any changes in surge arrestercharacteristics);c verification of disconnection in event of surgearrester thermal runaway;c testing withstand to disconnection faultcurrents in the event of surge arrester short-circuiting. This disconnection can be performedby fuses or circuit-breakers external to the surgearresters;c testing withstand to transient surges at powerfrequency (50 Hz, 1500 V, 300 A, 200 ms): nophenomena external to the surge arrester shouldbe generated (flames, projections, etc.);c testing ageing by verification for 1000 hours ofequipment withstand at maximum steady statevoltage Uc;

Fig. 22 : representation of curve U = f(I) of a surge arrester

Ι (kA)

Ιmax (15)

Ιn(5)

< 1 mA

Ur(1800)

U(V)

Ur (440)

Page 19: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.17

3.2 Horizontal standards

This category of standard texts contains two“reference” texts: the IEC 364 (NF C 15-100)and IEC 664. Standard IEC 364 concernsthe electrical installations of buildings, andIEC 664 insulation co-ordination ofLV equipment.

IEC 364

This standard only defines two situations, a“natural” and a “controlled” situation:c the “natural” situation concerns installationssupplied by a fully underground LV networkwhere impulse withstand of devicesconforming to their manufacturing standard issufficient,c the “controlled” situation concerns installationssupplied by bare or twisted overhead LV lines inwhich devices have a withstand compatible withforeseeable surges.

However, in both cases, surge arresters need tobe installed as:c in “natural” situations, surges may occur as aresult of a rise in earthing potential further to anindirect lightning stroke (see fig. 8 ) or a fault inthe MV/LV transformer,c the “controlled” situation is not always feasibleas a result of the diversity in equipmentwithstand levels, and nor is it lasting as additionsare always possible.

In France, standard NF C 15-100 uses thesedefinitions. In particular paragraph 443 also usesthe definition of surge categories, referringreaders to paragraph 534 for choice ofequipment and its installation.

IEC 664For general application in low voltage, thisstandard is divided into four parts:c part 1: principles, specifications and tests,c part 2: specifications for clearances, creepagedistances and solid insulation,c part 3: use of coating of electronic deviceprinted circuit boards,c part 4: application guide.

All the tests and measures guaranteeing fullysafe operation of the equipment are described inthis standard.

The table in figure 11 gives the values fixed bystandard IEC 664 for clearance in air, for themanufacture of the different types of electricalswitchgear. This table shows that surgewithstand varies according to the position of thedevices in the installation.This standard also stipulates certain creepagedistance lengths in order to verify the trackingwithstand required for manufacture of the variouselectrical switchgear types (see fig. 12 ).Although the standard takes account of the riskof pollution (various levels are scheduled), theclimatic effects, combined with equipment andcomponent ageing, reduce equipment withstandwith time.

Today, the withstand of electronic and computerdevices does not always correspond to theminimum level given by class l (1500 V).Moreover, these devices may be connected tothe electrical network at the installation origin, aplace where only class III and IV devices shouldbe installed. Surge arresters therefore need tobe fitted at the installation origin.

3.3 Surge arrester installation guides

A variety of documents deal with the subject ofsurge arrester installation: in France, standardNF C 15-531 focuses on the installation rules ofLV surge arresters, and standard NF C 15-100covers all the LV electrical installations.

At international level, a standard is currentlybeing drafted. Its equivalent will be standardNF C 15-443 (to be published in replacement ofstandard NF C 15-531) which treats three mainsubjects differently:c evaluation of the risk of lightning,c selection of surge arresters,c implementation of surge arresters.

To evaluate the risk, a formula based onscientific criteria is proposed to engineering anddesign departments.This formula takes accountof the characteristics of the site and theenvironment:c lightning density,c type of distribution network,c site topography,c presence of lightning rods, if any.

Selection of surge arresters depends on:c the importance of the risk,c the susceptibility of the devices,

c testing temperature rise, necessary when thesurge arrester contains components such asresistors or reactors.

The above tests have been defined to guaranteethe dependability of all conform surge arresters.These tests will normally form part of theinternational standard currently being drafted.

Page 20: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.18

c the earthing system of the electrical network.Whatever system is used, if a lightning risk ispresent, all electrical installations must be fitted

with surge arresters (see fig. 23 ), whosecomposition may vary according to the type ofearthing system.

Fig. 23: choice of surge protection mode (common or differential) according to the electrical installation earthing system as per NF C 15-443 .

Main LV boardL1

L2L3N

Earthing strip(main earthing terminal)

M

Time-delayed

Optional component

Surge arrester

Earth bar

Main LV boardL1

L2L3N

Earth bar

Earthing strip(main earting terminal)

M

Optional component

Surge arrester

PE

Main LV boardL1

L2L3

PEN

Earth bar

Earthing strip(main earting terminal)

M

Surge arrester

b) IT system d) TN-C system

a) TT system c) TN-S system

Main LV boardL1

L2L3N

M

PIM

Earthing strip(main earting terminal)

Surge arrester

Earth bar

Page 21: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.19

These differences are due to:

c whether or not differential mode surges aretreated,

c the maximum steady state voltage Uc:v between live conductors and the earth:- Uc > 1.5 Un in the TT and TN earthing systems,- Uc > e Un in the IT earthing system;v between phases and neutral, Uc > 1.1 Unwhatever earthing system is used.

3.4 Implementation of surge arresters

A variety of rules are defined (importance ofequipotential bonding, staggered or cascadingprotection devices, use of residual currentdevices), application of which may sometimesvary according to the installation sector (tertiaryand industrial or domestic).

Importance of the equipotential bondings

EMC principles state that LV installations musthave only one earthing connection for their loads.This connection is close to the origin of theinstallation, and it is at this level that the “main”surge arrester must be installed (see fig. 24 ):care must be taken to minimise the impedance ofits circuit (reduction of its connections to the liveconductors and earth, as well as the impedanceof the disconnection device). In this manner, ifthe surge arrester begins to conduct, the loadsare subjected at most to the protection voltageUp equal to the residual voltage of the surgearrester plus the voltage drop in its connections

Note 1 : Earthing the neutral does not preventsurges from affecting the phase conductors.

Note 1 : Surge limiters, use of which iscompulsory in the IT earthing system, replacesurge arresters for protection against 50 Hz MVsurges. As these two devices do not have thesame functions, surge arresters continue to berequired for lightning surges.

and in the disconnection device. Hence theimportance of a properly constructed installationconform to proper practices.

Reminder: one metre of cable has an inductanceof 1 µH: application of the formula ∆U = L di/dtwith the 8/20 µs wave and a 10 kA currentresults in a voltage of approximately 1000 voltspeak/metre: hence the importance of minimisingsurge arrester connecting cable length.

Cascading protection devices

When a high amplitude lightning stroke occurs,the importance of the current flown off by thesurge arrester means that protection voltagemay exceed the withstand voltage of sensitivedevices. These devices must therefore beprotected by use of “secondary” surge arresters(see fig. 24 ). To ensure their effectiveness,these “secondary” surge arresters must beinstalled more than 10 metres away from the“main” surge arrester. This connection is

NB: For increased efficiency of protection, the cable lengths L1+L2+L3 must be reduced when installing a surge arrester.Up = protection voltage downstream of the main surge arrester.Ups = protection voltage after the secondary surge arrester.* = surge arrester disconnection device at end of life (in short-circuit).

Fig. 24 : positions of surge arresters in an LV installation.

M

*

“Secondary”surge arrester

“Main”surge arrester

MV/LV

Outgoers(loads)

L1

L2

L3

Up Ups*

Page 22: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.20

important as cable impedance performs adecoupling between the two protection levels (asshown in figure 25 ).

It is important to bear in mind that the supply ofmany electrical devices, and in particularelectronic devices, is protected against surge bydifferential mode varistors. “Cascading” is thusalso applied between the surge arrester of theinstallation responsible for protecting thesensitive device and the latter, and calls for astudy of the protection levels.

Note 1: presence of surge arresters on theMV close to those placed on the LV is anothercase of “cascading” using the differences in arcingvoltage of MV and LV surge arresters and thedecoupling performed by the MV/LV transformer.

Note 2 : when electronic devices containingcommon or differential mode filters areconnected near the installation origin, thesefilters must be able to withstand the protectionvoltage Up (see fig. 24 ).

Cohabitation of residual current devices andsurge arresters

In installations whose origin is equipped with anRCD, it is preferable to place the surge arresterupstream of the latter (see fig. 26a ). However,some electrical utilities do not allow interventionat this distribution level: this is the case ofLV consumers in France. A time-delayed orselective RCD is then necessary to preventcurrent flow off via the surge arrester fromcausing nuisance tripping (see fig. 26b ).

This length was defined for surge arresters equipped with varistors* = surge arrester disconnection device at end of life (in short-circuit).

Fig. 25 : example of two surge arresters installed in cascade.

* = surge arrester disconnection device at end of life (in short-circuit)** = residual current device for protection of people, in this case associated with the disconnection device.

Fig. 26 : position of a surge arrester on the installation of a LV consumer, for electrical distribution in TT earthing system.

M

*Outgoers(normalloads)

“Main”surge arresterUr = 2000 V at 5 kAIn = 15 kA

Outgoers(sensitiveloads)

PE

L > 10 mN3LIncomer

* “Secondary”surge arresterUr = 1500 V at 5 kAIn = 5 kA

a) Simplest connection(forbidden in France by EDF)

b) Recommended connection: also enables discriminationwith high sensitivity RCDs placed on the outgoers

***

Incomingpower circuit-breaker, withnormal RCD

*

Incomingpower circuit-breaker with S type RCD

Circuit-breaker inassociation with ahigh sensitivity RCD selective with S type RCD

Page 23: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.21

Likewise, if surge arresters have to be installednear high sensitivity RCDs (10 or 30 mA), theymust be placed just upstream of them.

In short

In tertiary, industry and the domestic sector,installation of a surge arrester must alwayscomply with the following requirements:c all surge arresters must be equipped with adisconnection device (de-energised when it isshort-circuited): a fuse or a circuit-breaker. Thisdevice must be adapted to the surge arresterand its connections (by its rating and tripping orblowing curve) as well as to its installation point(by its breaking capacity). As a rule,

manufacturers specify the characteristics of thedevice to be provided for each type of surgearrester;c the connections from the surge arrester to thelive conductors and from the surge arrester tothe main equipotential bonding must be as shortas possible: 50 cm is the maximum value (seechapter 2 and fig. 24 );c surge arrester cabling must not create a loopsurrounding devices sensitive to electromagneticphenomena (electronic clocks, programmers, etc.).

Note : Both for initial choice of surge arrester andfor its installation requirements, it is vital toconsult the manufacturers’ technical documents.

Page 24: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.22

4 Conclusion

Nowadays, maximum availability of electricalpower is required for a variety of reasons,whether purely economic (search for maximumproductivity) or for safety purposes, or yet againsimply for comfort in domestic applications. It isthus obvious that the ability to eliminate or atleast greatly reduce the risks and hence theconsequences of surges has become aprofessional reference.

This reference calls for control of insulationco-ordination in low voltage, first by applying asimple investigation method resulting incombination and choice of devices and surgearresters. The latter (the surge arresters) mustlimit the foreseeable surges on the network to alevel acceptable by the former (the devices).

This calls for the following:c estimation of surges (lightning, switching orpower frequency) which may appear on theelectrical network (see chapter 1),c knowledge of the characteristics of the devicesinstalled and more particularly of their impulsewithstand (see chapter 2),c selection of protection devices, taking thesetwo points into account, as well as the earthingsystem of the electrical network.

However, this “theoretical approach” must becompleted by the contractor’s know-how. Aswe explained earlier in this document, failure

to respect a few basic rules will make even thebest surge arresters useless (see chapter 4). Inthis context, it is important to recall theimportance of:c shortening surge arrester connections,c having a single earthing connection for allloads,c respecting the minimum distance between twosurge arresters,c choosing a selective or time-delayed RCDwhen it is placed upstream of a surge arrester.

Surge arrester standards have been stabilised,and standards concerning insulationco-ordination in LV electrical installations shouldshortly be so also. Consequently, there is noescaping the fact that electricity-relatedprofessions need to quickly adapt if they are tosatisfy operators.To ensure the success of this adaptation,the importance of surge arrestermanufacturers’ documents should beemphasised (see the Merlin Gerin SurgeArrester Guide), as they contain both:c simplified explanations of surge andelectromagnetic disturbance phenomena,c the technical information essential for makingthe right choices and combinations (as describedabove).

Page 25: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.23

Bibliography

Standards

c IEC 364: electrical installations in buildings(French application: NF C 15-100).c IEC 439-1: LV switchgear – 1st part: Typetested assemblies and part tested assemblies.c IEC 664: insulation co-ordination of equipmentin LV systems (networks).c IEC 898: Circuit-breakers for domesticinstallations (French application: NF C 61-410).c IEC 947-1: LV switchgear – 1st part: Generalrules (French application: NF C 63-001).c IEC 947-2: LV switchgear – 2nd part: Circuit-breakers (French application: NF C 63-120).c UTE C 15-443 Juillet 1996: Protection of low-voltage electrical installations againstovervoltages of atmospheric origin. Selectionand installation of surge protective devices.c NF C 61-740 – 1995: Equipment for installationsdirectly supplied by a LV public distributionnetwork – Surge arresters for LV installations.

Others publications

c Lightning protection for electrical installationSchneider Electric

Cahiers Techniques Schneider Electric

c Les pertubations électriques en BTCahier Technique n° 141R. CALVASc EMC: Electromagnetic compatibilityCahier Technique no 149F. VAILLANTc Lightning and HV electrical installationsCahier Technique no 168B. DE METZ-NOBLAT

Page 26: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Cahier Technique Schneider Electric no. 179 / p.24

Page 27: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types
Page 28: Cahier technique n 179studiecd.dk/cahiers_techniques/LV_surges_and_surge... · 2020-01-29 · Cahier Technique Schneider Electric no. 179 / p.4 1 Surges There are four different types

Schneider Electric Direction Scientifique et Technique,Service Communication TechniqueF-38050 Grenoble cedex 9Télécopie : (33) 04 76 57 98 60

DTP: SODIPE - ValenceEdition: Schneider ElectricPrinting: Imprimerie du Pont de Claix - Claix - France - 1000- 100 FF - ©

199

9 S

chne

ider

Ele

ctric

03-9917918