Cables Facts and Figures
-
Upload
foulques0404 -
Category
Documents
-
view
2.205 -
download
136
Transcript of Cables Facts and Figures
Cables Facts and Figures
Revised 012008
Preview
This booklet has been revised several times to meet the demands of an ever-changing market, as well as specification changes as the result of improvingtechnology. It is not a treatise on electrical technology, but it is published to givesupplementary information to engineers, technicians and electricians involvedin cable selection and installation.
Aberdare hopes that users find it useful and invites any constructive (orcorrective) criticism.
PURPLE PEACH 09/2007
Aberdare Power Cables“with Compliments from Aberdare Cables”
1.0 How to Select a Cable
2.0 Useful Electrical Formulae
3.0 Transport, Handling and Installation of Electric Cables
1.1 Load to be supplied1.2 Permissible Voltage Drop1.3 Prospective Fault Current1.4 Environmental Conditions of Installation1.4.1 Cables Laid Direct in the Ground1.4.2 Cables Installed in Air1.4.3 Cables installed in Ducts1.4.4 Composite Cable Routes1.4.5 Intermittent Operation1.4.6 Solar Heating
2.1 Volt Drop2.2 Charging Current2.3 Per Unit System2.4 Load Growth2.5 Load Factor2.6 Capacitor Voltage Rise2.7 Load Sharing2.8 Conductor Resistance2.9 Lead Resistance2.10 Wire Armour Resistance
3.1 Cables on Wooden Drums3.2 Cable Transportation3.3 Cable Storage3.4 Mechanical Forces on Cables during Installation3.5 Pulling Cables through Pipes or Ducts3.6 Preparation for Cable Laying3.7 Backfilling and Reinstatement3.8 Repairs to PVC Oversheaths
1
12
16
115789
10101011
12131313131314141515
1617181819202626
Contents
4.0 Paper Insulated and Lead Covered 6.35/11kV Cables
5.0 Medium Voltage XLPE Insulated, PVC Bedded, SWA,
PVC sheathed 6.35/11kV Cables
6.0 Low Voltage PVC and XLPE insulated 600/1000V
Power Cables
7.0 ElastomericTrailing Cables
8.0 Overhead Aluminium Conductors
9.0 Innovative products
4.1 Notes on impregnating compound4.2 Moisture in Paper cables4.3 Derating factors for non-standard conditions4.4 Short circuit ratings for PILC cables4.5 Earth fault ratings
5.1 Notes on XLPE insulation5.2 Derating factors for non-standard conditions5.3 Short circuit ratings for XLPE insulated 6.35/11kV
cables5.4 Earth fault current
6.1 Notes on PVC and XLPE insulation6.2 Cable cross section6.3 Derating factors for non-standard conditions6.4 Short circuit ratings for PVC and XLPE insulated
600/1000V cables
- INTERDAC 3
ContentsContinuation ...
27
32
37
46
50
52
2727293031
323435
36
373744
46
1.0 How to Select a Cable
1.1 Load to be supplied
The following formulae apply:
1.2 PermissibleVoltage Drop
When selecting a cable for your specific application, a number of variablesrequire attention.These are:(a) Size and type of load to be supplied(b) Permissible voltage drop(c) Prospective fault current(d) Circuit protection(e) Environmental conditions of installation
In order to select the appropriate cable, it is necessary to know the voltageand the load current in amps. This information will be available eitherdirectly in amps or as kW or kVA.
= x 1000 Amps3 xV x Cos
Amps
Use this value of current to determine the cable size by reference to therelevant tables given in Section 4 (Paper insulated), Section 5 (XLPE insu-lated medium voltage) or Section 6 (PVC and XLPE insulated low voltage)for Copper or Aluminium conductors.
A slightly larger conductor size may be chosen for safety aspects, and toprovide for the higher than usual current which may be experienced duringstarting of electric motors.
Suppose it is required to supply a 3 phase, 400 volt, 100kW motor con-nected in star/delta, over a distance of 50m buried direct in ground. Themotor load is known to have a power factor of 0,9 lagging. The full load linecurrent, IFL can be calculated as follows:
We now refer to table 6.2 on pg 38 and note that the smallest copperconductor, PVC insulated cable, that can supply a current of 161 amps inthe ground, is a 50 mm² rated area cable. This cable can carry 169 ampscontinuously if installed under standard conditions.
Calculate the highest current drawn by the load, by multiplying the currentas calculated in 1.1 by an appropriate factor. If a Star/Delta motor starter isused on a motor, this factor is 3. If the motor is started direct on line, thenuse a factor of 6. Where the load is resistive heating, lighting or atransformer, it is not necessary to increase the current as calculated in 1.1.
IFL kW if we know kW, voltage, as well as power factor
if we know the kVA rating as well as the voltage
f
I
I
FL = x 10003 xV
= 100 x 10003 x 400 x 0,9
= 161 Amps
kVA
Example of Cable Selection for LowVoltage
FL
1
Calculate the volt drop which will be experienced at the load terminals byreference to table 6.2 or 6.3 on pg 38 or pg 39. The maximum volt dropallowed by SANS 10142-1 during full load running condition. There is nohard and fast rule as to the allowable volt drop under starting conditions.Depending on the type of load to be started, there is the possibility that thetorque may be compromised during starting, if the motor is subjected todifficult starting conditions. A reasonable volt drop should be chosen inthese cases
The volt drop may be calculated in two different ways:
Using Method (b)
Note:
(a) Multiplying the current by the impedance of the length of cable.Calculate the percentage volt drop by reference to the phase to earthvoltage.
(b) Multiply the current by the length of cable, and then multiply the resultby the volt drop per amp per metre figure as given in table 6.2 or 6.3 onpage 38 or page 39, depending on the type of conductor.
Starting Current = 3 x Running Current= 3 x 161 Amps= 483 Amps
Impedance of 50m of 50mm² Cable (Table 6.2) pg 38= 0,4718 x 50
1000= 0,02359 ohms
Volt Drop = 483 x 0,02359= 11,394 x 100
230 1= 4,95% (Acceptable)
Starting Current = 3 x 161 Amps= 483 Amps
Volt Drop per amp per metre = 0,817 mV/A/m (Table 6.2) pg 38Volt Drop = 0,817 x 10 x 483 x 50
= 19,73 voltsPercentageVolt Drop = 19,73 x 100
400 1= 4,93% (Acceptable)
It often happens on long runs of electric cable that a larger conductorthan that calculated in 1.1 is required for volt drop reasons.
Previous example using method (a)
-3
2
Example of Cable Selection for MediumVoltage (11kV)We wish to supply a 2MVA 11kV transformer from an Eskom supply pointwhich is 3km away. We are to use an underground paper insulated, copperconductor cable. The depth of burial of the cable is 1,25m. Ground thermalresistivity is 2K.m/W. The ground temperature is 25°C and there are noother cables in the trench.
Short circuit level may be assumed to be 250 MVA, and the earth fault level100 MVA, and it may be assumed that a fault will be cleared in half asecond.
= 2 000 0003 x 11 000
= 105 Amps before derating for nonstandard conditions
Derating factor for Depth of Burial at 1,25 m is 0,96.Derating factor for SoilThermal Resistivity at 2 K.m/W is 0,84.Derating factor for GroundTemperature of 25°C is 1,00.
Total Derating = 0,96 x 0,84 x 1,00
= 0,8064
Standard = 1050,8064
= 130 Amps
Table 4.2 on pg 28 shows that a 35 mm² Copper conductor cable would becapable of carrying this load (130A). This is confirmed by reference to thePaper Insulated Cable brochure (Page 13).
The cable size required is thus 35 mm² Copper conductor, 3 Core Generalpurpose belted cable. (Table 17 SANS 97).
Volt Drop = Z x 3 x x distance1000
= 0,6371 x 1,73 x 105 x 30001000
= 347,6 volts (3,2% of 11kV)
Volt drop is seldom a problem at Medium Voltage, even for long runs ofsmall conductor size as shown above.
Using the previous formulae:
Checking for volt drop:
I
I
FL
3
Prospective Symmetrical (Short Circuit) Current= 250 000 000
3 x 11 000
= 13,122 kA
= Cross Section x Kt
K is 115A/mm² for copper conductors, paper insulated.
0,5
Checking for fault current
Cable short circuit current with stand is
Isc
35 x 115 = 5,692 kA0,5
This cable will not survive the prospective short circuit current.
x 115 = 13,122 kA
= 80 mm²
Nearest standard size is a 95 mm² Copper conductor.This has a current rating of 235 Amps under standard conditions.
Lead area for a 95 mm² x 3 Core PILC cable is approximately 200 mm²
= 200 x 0,0240,5
= 6,8 kA for half a second
= 100 000 0003 x 11 000
= 5,25 kA for half a second
In many cases, the cable conductor size is larger than dictated by the fullload current, and is chosen in order to survive the prospective short circuitcurrent. The use of large conductors can be avoided by improving thespeed of protection, (fuses for example) and in the case of earth faultcurrent, by the use of sensitive earth fault protection.
The half second rating is thus:
Conductor size required is thus:
Earth fault current for half a second:
Cable earth fault current withstand is:
Required earth fault current:
x
\x
IEF
4
5
1.3 Prospective Fault CurrentElectric cables are designed to operate below a certain maximum temp-erature, this being dependent on the conductor material and the type andthe thickness of the insulation.
Cable selection for a particular installation must therefore be made on thebasis of not exceeding these temperature limits.
Suppose the 400 volt distribution board from which a cable is fed has a faultlevel of 5 MVA. This translates to a fault current of 7,22 kA, and the cablemust be capable of passing this current without damage until the fault iscleared.
The smallest cable that can safely handle this fault current for a 1 secondfault, is a 70 mm² copper conductor cable, or a 95 mm² aluminiumconductor cable. Suppose now that the fault clearance time (including anymechanical delays on the tripping mechanism) is closer to 2 seconds, thenthe smallest cable would be a 95 mm² copper conductor(10,925 ÷ 2=7,725 kA for 2 seconds) or a 150 mm² aluminium conductor (11,400 ÷ 2 =8,061kA for 2 seconds). Likewise, a fault duration less than 1 second willallow the use of smaller conductors than were calculated for the1secondrating.
impedance
Consider the following diagram:Diagrammatically, the system is:-
p.u. source = Base MVAFault Level MVA
p.u. transformer = Base MVA x Transformers % Impedanceimpedance Transformer MVA
p.u. cable = Z (ohms) x Base MVAimpedance V (kV)
(1) + (2) + (3) = p.u. impedance
Another Example:
We are required to calculate the fault current at the sub dist board.
P.U. SYSTEM
(1)
(2)
(3)2
11kV
11kVRing
FaultLevel250MVA
Main LV Dis Board
Sub Dis Board
TRANSFORMER
Board500 kVA
Z=0,05 p.u.
100 metres50 metres 100kW Motor185mm² Copper
Cable 70mm² CopperCable
Pf 0.9
/
X
X
X X
X
X
X
Fault Level = Base MVA MVAp.u. impedance
Fault Current = Fault Level (MVA) x 1 000 0003 x Voltage (V)
Source 100 = 0,4 p.u.250
Transformer 100 x 0,05 = 10 p.u.0,5
Example 1: Using a base of 100 MVA and the per unit method, theimpedance of the system at the sub-dist board can be determined:
FromTable 6.2 on pg 38 the impedance of 185 mm² cable = 0,1445 /kmThus the impedance of 100 m = 0,01445
Z.p.u. = Z (ohms) c MVA = 0,01445 x 100 = 9,03 p.u.V2 (kV) (0,400)2
Fault Level at Sub Board = 100 = 5,147 MVA0,4 + 10 + 9,03
Fault Current at = 5,147 x 1 000 000 = 7,429 kASub-Dist Board 3 x 400
Source 250 = 1 p.u.250
Transformer 250 x 0,05 = 25 p.u.0,5
Cable 0,01445 x 250 = 22,578 p.u.(0,400)2
Total Impedance = 48,578
Fault Level = 250 = 5,146 MVA48,578
Fault Current = 5,146 x 1 000 0003 x 400
= 7,428 kA
WW
The fault level at the sub-dist board is then found by dividing the baseMVA by the total per unit impedance:
Example 2: Using a Base of 250 MVA, the same result is obtained:
6
From the above illustration, it is clear that whatever may be the value ofBase MVA, short circuit current is the same. However, in the interest ofsimplicity a numerical convenient value of the Base MVA should bechosen.
Where k = 115A/mm² for PVC / Copper cables, shows that a 70 mm²copper cable can withstand a short circuit current of 8.05 kA for 1 second.This is above the potential fault level of the system. Moreover, the durationof the fault or the time taken by the protective device to operate has to beconsidered.The circuit supplying the motor would very likely be protectedby a 200 amp fuse or a circuit breaker. Both these devices would operatewell within 1 second, the actual time being read from the curves showingshort circuit current / tripping time relationships supplied by the protectiveequipment manufacturer. Suppose the fault is cleared after 0,2 seconds.We need to determine what short circuit current the cable can withstandfor this time
This can be found from the expression = A x Kt
and where A is the conductor cross sectional area in mm² and t the durationof the fault in seconds
So in our example = 70 x 115 = 18 kA0,2
This is well in excess of the system potential fault level and so it can beconcluded that a 70 mm² cable is suitable for this example. During theperiod of short circuits, the forces acting upon individual cores of a 3 phasesystem are enormous. These are forces of repulsion and attraction, andhence cause the cores to move if inadequately restrained. In the case of 3core armoured cables, the fact that the cores are laid up, and therestraining effect of the armour wires is such as to limit the coremovement. Bursting strengths are, however, still important in the case ofPILC cables where the effect of the resultant voids left in the insulation(even after small movement) may be detrimental to the long term life of thecable so affected.
The data used for determining the current ratings given in this publicationare based on calculations according to IEC 287. Ratings for multicorecables are given for a single cable run. Where groups of cables run in acommon route the appropriate derating factors are given in the tables onpages 29 ; 34 and 44 depending on the type of cable being used.
Similarly when the installation conditions differ from standard, the deratingfactors in the appropriate sections must be used.
I
I
sc
sc
where K = 115 for PVC / Copper cables (70°C - 160°C)K = 143 for XLPE / Copper cablesK =76 for PVC / Aluminum (solid or stranded) cables (70°C - 160°C)K = 92 for XLPE / Aluminum (solid or stranded) cablesK = 115 for PILC / Copper cables (70°C - 160°C)K = 76 for PILC / Aluminum (stranded) cables (70°C - 160°C)
(90°C - 250°C)
(90°C - 250°C)
1.4 Environmental Conditions of Installation
7
A qualitative assessment of the conditions immediately surrounding thecable should be made. Factors such as the need for a fire retardantsheath, additional mechanical protection, safeguards against chemicalattack and corrosion should be considered in this category. Theseinfluences affect mainly the external finish of the cable, the armouringand serving.
Cables are sometimes specified with a termite repellent sheath. It isworth mentioning that no sheath will repel insects since sheath materialhas to be ingested by the termite to be fatal. Thus, the statement ‘cablewith a termite repellant sheath’ is somewhat erroneous.
In the case of paper lead cables there are several alternative sheathmetals available, pure lead is prone to fatigue when subjected tovibration. Alloy E sheath can be supplied which will resist deteriorationthrough fatigue.
The foregoing notes are by no means an exhaustive treatment of thepoints to consider when choosing a cable for a particular application butare ratherguidelines to the salient points which need consideration.
1.4.1 Cables Laid Direct in the Ground
Suitability of soils for bedding and backfill
Clay:
Sand:
Sand clay:
The ratings given are based on a ground thermal resistivity (g) of 1,2K.m/W. The factor (g), varies considerably with differing groundconditions and has a pronounced effect on a cable’s current carryingcapacity. The only sure way to determine (g) is to measure it along thecable route. This practice is normally reserved for supertension cables,but there could be other applications where soil thermal resistivity iscritical.
Clay is a dense, compact material, greasy to the touch when wetand which has a low Thermal Resistivity even in the fully dried-outcondition. Most clays however, shrink when drying and can thus not beused as a bedding for the cable. They can be used as backfill and shouldbe consolidated by rolling rather than tamping.
Sand is a crumbly material with particle grains easily distinguishedand gritty to the touch even when wet. Particle sizes larger than 2mm areknown as gravel. Sea sand or sand obtained from a river bed usuallyconsists of spherical particles and has a very high Thermal Resistivitywhen dry. Some quarried sands and man-made sands as used formaking concrete, have irregularly shaped particles of varying size andcan be compacted to a high density. These can be used as a beddingmaterial especially when 5-10% clay is added and will have asatisfactorily low Thermal Resistivity in the dried-out state. Sand/gravelmixes should be used with care as sharp particles can damage the cableserving.
Sand clay is, as its name implies, a mixture of sand and clay.It is an ideal material for use as bedding and backfill and is bestcompacted by rolling. It rarely dries out to lower than 6% moisturecontent.
8
9
Loam:
Chalk:
Ouklip:
Peat:
Loam can vary in colour from reddish brown to dark brown andmay contain quantities of organic matter. It crumbles well, even whendry, and can be well compacted to achieve satisfactory values ofThermalResistivity. It is very suitable as a bedding material.
Chalk is a soft white or grey porous material having a lowerThermal Resistivity when wet, but drying out to very high values and isunsuitable for use as bedding or backfill in any area where drying out islikely.
Ouklip is decomposed rocky material, varying in particle size andhaving very low Thermal Resistivity in the undisturbed state. It can beused as a backfill material when mixed with loam or clay but should notbe used as a cable bedding.
Peat or humus is composed mainly of organic material and is blackor dark brown in colour. It should not be used as bedding or backfill asdried-out Thermal Resistivity values of over 4 K.m/W are usuallyobtained. It should be removed and alternative material used for bothbedding the cables and backfilling the trench.
Make-up soil:
Mine sand:
This is a general term for the soil in any area, the level ofwhich has been raised artificially using imported fill which may consist ofbricks, concrete, cinders, ash, slag, stones, other refuse or any of thematerial considered above. If any doubt exists as to suitability, it is bestremoved completely and a suitable material imported.
Mine sand is thermally very satisfactory, but is highlycorrosive and should therefore not be used.
Material
Sandy Soil
Clay
Chalky Soil
Concrete
Water logged ground
Gravel
1,20
1,60
1,80
0,90
0,50
1,00
Thermal Resistivity (g) K.m/W
Table 1.1
The thermal resistivity of a substance is greatly influenced by themoisture content at a given time. The higher the quantity of retainedmoisture the lower will be the thermal resistivity. A heavily loaded cablewill dry out the soil around the cable and cause an increase in (g). Thisprocess is cumulative and damage could be done to the cable insulationthrough over-heating.
Impurities such as slag, ash and the like increase the value of (g), as doesintense vegetation on the cable route, by drawing moisture from theground.
Multicore cables should be installed with a space of 0,3 x overall1.4.2 Cables Installed inAir
>
10
diameter and single core cables with a space of 0,5 x overalldiameter between themselves and the vertical wall or surface sup-porting them as per IEC 287 If they are installed in direct contact withthe wall then the current rating given should be reduced by 5% as arough guide line provided there is a space of 150mm or six times theoverall diameter of the cable whichever is the greater between adjacentcables or cable groups in the case of single core cables. If the installationfails to comply with this requirement then the derating factors in therelevant sections should be applied.
Where the ambient temperature along a route varies, the highest valueshould be taken to select the cable size.
The air within a pipe or duct will increase the thermal resistance of theheat dissipation path. Consequently the current rating or a cable run in aduct (pipe) is lower than that for an equivalent cable in the ground or infree air. The ratings given can be applied to cables laid in concrete,asbestos,
>
1.4.3 Cables Installed in Ducts
pitch fibre, PVC, earthenware or cast iron pipes which are the morecommon materials encountered. It should be noted that single corecables forming a part of an a.c. system should not be individuallyinstalled in cast iron pipes due to the heavy losses incurred by eddycurrent induction.
Generally the size of the duct (pipe) chosen should depend upon theease of pulling in, or out, the cable. It should be borne in mind that alarger cable may be required in the future to cater for increased loadgrowth. Common pipe sizes used in South Africa are 100mm and150mm internal diameters. When groups of cables are run in pipesalong the same route, they should be derated according to the factorsgiven in the relevant tables.
It frequently happens that a cable run is made partly in air, partly direct inthe ground and partly in ducts. The latter conditions lead to the lowestrating and it is here that attention must be focused. Very little heattravels longitudinally along the cable, the main dissipation being verti-cally through the duct wall and surrounding ground. Any rating where theroute is part ground, part duct must therefore be treated with care.
Where the length of ducting does not exceed 5 metres per 100m ofroute length, the cable rating may be assumed to be that for direct burialin the ground.
Certain types of loads have an intermittent characteristic where the loadis switched on and off before the cable has time to cool completely.Depending upon the load cycle it may be possible to select a smallercable for intermittent operation than would be the case if the load werecontinuously applied. When a current in excess of the normal ratedcurrent is applied, the heating of the cable will be a correspondinglyquicker operation than the cooling.
1.4.4 Composite Cable Routes
1.4.5 Intermittent Operation
Thus a continuous current of 76 amps flowing over the 10 minute cycletime would produce the same heating effect as the individual cycliccurrents, and the size of cable could be selected based on 76 amps.
When cables are installed in direct sunlight, an appreciable heating dueto solar absorption takes place. This results in a significant reduction inthe cables current carrying capacity and for this reason it is stronglyrecommended that cables be protected from direct sunlight. Themaximum intensity of solar radiation measured in South Africa variesbetween 1000 and 1250 /m² depending upon location.
1.4.6 Solar Heating
W
11
Thus
( )²tIn n
n = N
n = 1n = N
n = 1
( )tn
I =
( )²tIn n
n = N
n = 1n = N
n = 1
(t )n
I =
57 50010
=
= 75,83 Amps
• 150 Amps for 1 minute • 50 Amps for 2 minutes• 100 Amps for 3 minutes • 0 Amps for 4 minutes
Then applying the expression for RMS current.
ExampleSuppose a process cycle is as follow:
Generally = Equivalent RMS current= Current flowing during th period (Including
periods of zero current).t = Duration of nth periodN = Number of periods, (includes periods of zero
current)
I
In n
n
2.0 Useful Electrical Formulae
2.1 Volt Drop
The voltage drop in a single phase circuit is given by:Volt Drop = 2 x ( cos x sin )
Induction Reactance X = 2 fL ohms
Capacitive Reactance X = 12 fC
Where a, b and c are the distance in mm between the centres of the threephases conductors.
X I R
where I = Line current ampsR = Circuit resistance ohms/phaseX = Circuit reactance ohms/phase
= Angle of lead or lag between current andvoltage
where f = supply frequency HertzL = circuit inductance HenrysC = circuit capacitance Farads
+f f
w
w p
f
p
Î m
Î
f
p
p
L
C
Impedance Z = R + ( L) ohms
Power Factor cos = RZ
Admittance Y = G-jB ohms
Capacitive Susceptance B = 2 fC (Siemens)
L = 0,0516 + 0,46 log mH/km/phaser
C = 0,024 l r F/km/phaselog
r
GMD = abc
2 2
3
Where = 2 f
Where G = conductance (Siemens)B = susceptance (Siemens)
GMD
andGMD
where GMD = Geometric mean diameter mmr = Conductor radius mmr = Relative permittivity of dielectric
For a 3 Core Screened Underground Cable or Overhead Line:
12
13
2.2 Charging Current
2.3 Per Unit System
2.4 Load Growth
2.5 Load Factor
2.6 CapacitorVoltage Rise
Charging current = 2 f amps/km3 x 10
In the case of an underground cable with shaped conductors, C is increa-sed by 8%.
Per unit impedance Z = x Z (ohms)E
Per unit impedance referred to a given base MVA
= Actual Z p.u. x Base MVAFull Load MVA
Z p.u. on given MVA base
= MVA Base x Z (ohms)E
Load growth L in n year at (g) % per annum
Ln = Lo (1 + ) MW
where Lo = Load in first year in MW.
Monthly Load Factor = kWh Sold per MonthNumber of Hours per Month x M.D. kW
Monthly Diversity Factor =Individual Consumers M.D.’s
Per unit voltage rise in a circuit due to capacitorsV p.u. =
3 Phase Capacitor kVAR3 Phase Fault Level kVA
p
m
C E
where C = Capacitance per phase FE = Line to line voltage
6
2
th
n
I
SSimultaneous M.D. Recorded during the Month
g100
14
2.7 Load Sharing
2.8 Conductor Resistance
Natural load sharing between 2 parallel feeders
= Amps+
= Amps+
+
Change of conductor resistance with temperature
= (1 + (T -T ) ohms
The a.c. resistance of a conductor is given by:
= R (1+ + )
I I
I I
I I I
1 2 2
1 1 2 2
2 1 1
1 1 2 2
t o t o
t
o
a d 1
d
1
ZZ Z
ZZ Z
where == Angle of load current= Angle of transmission line 1= Angle of transmission line 2
R R
where R = d.c. resistance at temperatureT °CR = Initial d.c. resistance at temperatureT °C
= Temperature co-efficient of resistance ofconductor material
R y y
where R = d.c. resistancey = skin effect factory = proximity effect factor
Ðq ÐfÐq Ðq
Ðq ÐfÐq Ðq
fqq
a
a
1 2
1
2
t
t
[ ]
(1 + + )y y1
3 Core
Up to 185
240
300
400
500
630
800
1000
1,027
1,041
1,068
1,115
1,175
-
-
-
1,019
1,027
1,048
1,087
1,136
1,208
1,315
1,516
Single Core
Conductor Area
mm²
Table 2.1 : Values of (1 + + ) for 1000 volt cablesy y1
2.9 Lead Resistance
2.10 WireArmour Resistance
Resistance = 238,1 ohms/kmarea of PipeWall
Resistance = 185,03 ohms/kmd N
where d = wire diameterN = Number of wires
2
Volume Resistivity ohm/mm²/km
Specific Gravity
Temperature co-efficient of Resistance per °CCo-efficient of linear Expansion per C
Specific Heat cals/g
Melting Point C
°
°
Copper Annealed
17,2414
8,89
3,93 x 10
17 x 10
0,093
1065
-3
-6
Aluminium Annealed
28,03
2,703
4,03 x 10
23 x 10
0,24
659
-3
-6
Property
15
Table 2.2 : Characteristics of Copper and Aluminium conductors
It can be shown that aluminium has 78% of the current carrying capacity ofan equivalent size copper conductor. The current rating of a cable dependsupon the thermal dissipation of the conductor I²R losses. Using thesuffixes ‘c’ for copper and ‘a’ for aluminium, equal conductor losses aresatisfied by:
x R = x R
= R xR
= 17,2414 x28,03
= 0,61 x
= 0,61 x
= 0,78
I I
I I
I
I
I I
I
c2
c a2
a
a2
c c2
a
c2
c2
a c
c
16
3.0 Transport, Handling and Installation of Electric Cables
3.1 Cables onWooden Drums
Figure 1
(a) The cable drum is manufactured from carefully selected locally grownwood with a low moisture content (typical not more than 15%) (Fig. 1)if they are required to be treated it shall be done in accordance withSANS 05 with a Class C preservative or with chromate copperarsenate. Saligna, which is a hardwood, does not require treatment.
(b) Marking on drum flanges should be clear, stencilled or burned into thewood and should include the following information:
(i) Manufacturer’s name or trade mark.(ii) Rated voltage, rated area, number of cores and specification.(iii) Length of the cable in metres.(iv) Year of manufacture.(v) Gross mass in kilograms.(vi) The instruction“NOTTO BE LAID FLAT”.(vii) Serial number or other identification.(viii) On each flange an arrow with the words“ROLLTHISWAY”.(ix) SABS Mark (if applicable).
(c) Both ends of the cables on the drum should be sealed and the innerend fixed to the flange of the cable drum to prevent loose coiling. Theouter end is fixed to the flange as well, for the same reason.
(d) Cable drums should stand on firm, well-drained surfaces.
(e) In the past, it was common practice to rotate stored cable drumsthrough 180° to re-distribute the rosin impregnation oil through thedielectric. The use of MIND cables has obviated this reason forrotating drums. However, it is still recommended that wooden cabledrums that are stored in the open, irrespective of the type of cablecontained, should be periodically rotated to avoid the drum timberrotting through rising damp.
98-1999
163010 063
MASS E894 KG
rollthisway
CP 11/6
3.2 CableTransportation
Preparation
Figure 2
Loading
Securing
Off loading
(a)(i) The truck must match the drum size.(ii) Do not overload the trucks.(iii) Cable ends must be sealed, secured and protected(iv) Use special cable trailers for depot to site transportation if
possible (See fig. 2).
(b)(i) Check drums for correct cable and size, serial number, mass
and possible damage.(ii) Select correct forklift/crane.(iii) Select correct slings and spindle and check sling condition.(iv) If a crane is to be used, ensure that a spreader is incorporated
to prevent damage to drum flanges.(v) If the drum is to be rolled, observe correct rolling direction by
referring to arrows on flanges.(vi) Ensure that the drum bolts are tight.(vii) Ensure that truck surface is clear of obstructions, nails etc.(viii) Do not drop drums onto truck loading bed.
(c)(i) Secure drums to the truck bed to prevent sliding and rolling,
using adequate steel chains and chocks.(ii) Always try to pack drums flange-to-flange.(iii) Do not lay drums flat.(iv) Stop the vehicle during transportation and check that the load
is secure.
(d)(i) Check for damage to cable drums.(ii) Select correct spindle slings for the drum size and mass and
ensure that same are in good order, ensure that a spreader isused.
(iii) Do not drop drums but lower gently onto firm and relativelylevel surfaces.
(iv) Off load drums in such a way that they are easily accessible.(v) If using a fork-truck, ensure that it is of adequate size relative to
the task at hand.(vi) Ensure that the fork-truck tyres lateral spacing is correct.(vii) Take care that the protruding tyres do not damage other
equipment or drums.(viii) There are two methods of rolling drums from loading beds if
cranes are not available (See fig.3)
Cable Trailer
17
18
Figure 3
Method 1:
Method 2
3.3 Cable storage
Indoors
Outdoors
3.4 Mechanical Forces on Cables during Installation
Hole excavated maximum slope 1 in 10 to receive
: Ramp constructed maximum slope 1 in 4
(a)(i) Stack flange-to-flange and preferably not one on top of the
other.(ii) Stack so that drums are easily accessible.(iii) Observe fire prevention rules.(iv) Cable ends must be sealed at all times.(v) Despatch on“first in - first out” basis.(vi) Rotate Paper insulated cable drums one complete revolution
per annum.
(b)(i) Drums should stored on a hard surface at a slight angle and the
area should(ii) Drums should be released on a“first in - first out” basis.(iii) Cable ends should be sealed at all times.(iv) Stack flange-to-flange but if this is not possible limit vertical
stacking practice to smaller drums only.(v) Stack in such a way that drums are easily accessible.(vi) Observe fire protection rules.(vii) Cable racks are ideal for storage but take care not to overload.(viii) Cables must be identifiable at all times.(ix) If drums are expected to be stored for a long time they must be
specially treated or made of hard wood.(x) Rotate Paper insulated cable drums one complete revolution
per annum.
Any cable has a maximum pulling force which should not be exceededduring installation. The cable construction imposes the limitation on thepulling-in force. When a cable stocking is used the maximum force can berelated to overall cable diameter in mm as follows:
have a drainage system.
Drum stop
19
SteelWire Armoured Cables F = 0.94 d x 10 kN
Attempts should be made to limit the pulling force required to a minimumto avoid stretching the outer layers of the cable. This is particularly relevantwhere control and communication cables are concerned since instancesare known where the cores have finished 2-3 metres inside the sheath andinsufficient overlap at straight joint positions has necessitated re-layingsome lengths.
An increase in the pulling force is permissible when the cable is laid bymeans of a pulling eye attached to the conductors. As a rule of thumb, thefollowing forces may be applied to a conductor:-
Copper 4.9 x 10 kN/mm²
Then, for example the maximum force that should be applied via a pullingeye to a 70mm² 3 core copper cable is:-
70 x 3 x 4.9 x 10 = 10.29 kN
Generally when cables are installed using well-oiled rollers and jacks, thefollowing forces can be expected:-
straight route15 - 20% of cable weight2 - 90° bends 20 - 40% of cable weight
Cables laid in open trenches should be left slightly “snaked” so that anylongitudinal expansion or contraction can be accommodated. Similarlywhen cables are installed in cleats or on hangers a slight sag betweenfixing points is recommended.
When a cable is pulled through a pipe, friction between the cable servingand the pipe material increases the longitudinal force requirements.Representative values for the co-efficient of friction ( ) between the morecommon cable servings and pipe materials are given below:-
4 -6
-2
SteelTape Armoured or Unarmoured Cable F = 0.39 d x 10 kNControl and Communication Cables F = 0.26 d x 10 kN
Aluminium 2.94 x 10 kN/mm²
4 -6
4 -6
-2
-2
3.5 Pulling cables through Pipes or Ducts
m
Table 3.1
Serving Material Pipe Material
PVC
PVC
PVC
PVC
Bitumenized
Hessian
or Jute
Asbestos
Metal (Steel)
Pitch Fibre
PVC
Asbestos
Metal (Steel)
Pitch Fibre
PVC
0,65
0,48
0,55
0,35
0,97
0,76
0,86
0,55
20
This information can readily be used to determine the maximum length ofcable that can be pulled through a given pipe without exceeding themaximum permissible pulling force. Take for example the 70 mm² x 3 corecable previously quoted, if this is a low voltage cable with a PVC sheath andit is desired to know the maximum length of PVC pipe it can be pulledthrough then:-
Maximum force = 10.29 kN (by pulling eye)for PVC to PVC = 0.35But force = x Reactive force
= x Cable weight= x Cable mass
102
mass of cable = 10.29 x 102 = 2 998 kg0,35(1 kN = 102 kg)
From the table the mass of 70 mm² x 3 Core copper cable is 3,6 kg/m.
Thus the maximum length of cable that can be pulled through a PVC pipe is:
2 998 = 832 metres3,6
If there are any bends in the route then these will create additional loadingand reduce the theoretical length of cable that can be installed.
In certain instances when long runs in pipes or ducts are encountered itmay be beneficial to grease the cable with petroleum jelly or some othernon aggressive compound to facilitate the pulling-in.
Considerable damage can be done to cable serving at the mouth of a pipeand precautions should be exercised at such points. This point is achievingmore importance with the present day trend towards impermeable anticorrosive sheaths which have to withstand periodic pressure tests.Included among the protective measures that can be adopted are thefitting of a rubber grommet to the mouth of the pipe and inserting areasonable thickness of rag.
When unarmoured cables are pulled into pipes it will be beneficial toensure that there is no foreign matter present which could cause damageto the sheath before pulling. Pushing a draw rod through the pipe willusually clear any obstruction.
mmm
3.6 Preparation for Cable Laying
Planning(a)When planning a cable route there are several factors to beconsidered, among the most important of these are:
(i) GroundThermal resistivity (TR) tests.(ii) Position of joint bays.(iii) Provision to indicate on the ‘as laid’ drawings, the serial or
drum number of the cable installed.
(iv) The use of mass or pre-impregnated non-draining Paperinsulated cables, XLPE and PVC dielectrics has all buteliminated the need for special precautions when layingcables on steep slopes in shafts.
(b)
(i) Always use the best hoisting equipment available.
(ii) Do not drop drums of cable onto the ground as this not onlydamages the drum but will damage the cable as well(especially Paper insulated cable).
(iii) It is most important that a minimum of rolling of the drums onthe ground be allowed and then only in the direction of thearrows painted on the flanges.
(iv) When rolling a drum of cable, to change direction use 2 steelplates with grease between them, and by standing one flangeon these plates the cable drum may then be swivelled in thedesired direction.
(v) Position the drum prior to cable-pulling so that the cable ispulled from the top of the drum.
(vi) Note that a drum of power cable can weigh up to 10 tons somake sure that adequate cable drum jacks are used, that thespindle is strong enough to hold the drum and that the jacksstand on firm ground and that they hold the spindle horizontal.
(vii) Site the drum at the most convenient place for cable-pulling,usually at the start of a reasonably straight section near thecommencement of the trench work.
(viii) Allow for drum braking.
( c)
(i) This often governs the rating of a power cable buried directly, asdoes the temperature of the soil. Losses for cables running atthe maximum temperature at which the dielectric system canfaithfully operate for a maximum life of say, 25 years, areconsiderable, ranging from 15 W/m for normal distributioncables. Cable conductor temperature and the soil surroundingthe cable must be able to dissipate this heat effectively orthermal instability (runaway)will result. For example an XLPEinsulated 11 kV cable with conductors running at 90°C could endup with a surface temperature of about 80°C resulting in drying-out of the soil. Depth of burial plays an important factor here andhas been set at 800 mm. Most MV Cable current ratings arecalculated with ground temperatures at 25°C at depths of burialof 800 mm.
Drum Handling
GroundThermal Resistivity
21
22
LV cables are normally buried at 500 mm. Soil thermal resis-tivity (the ability of the soil to conduct or dissipate heat) isstandard at 1.2K.m/W.
(ii) The actual soil thermal resistivity along the proposed routeshould be measured either by means of an ERA needle probeor the SABS needle probe, but these are outside the scope ofthis paper, suffice it to say that different soil compositionsalong the route will have different rates of heat dissipation andcould result in“hot spots”.
(iii) To overcome this, bedding and backfill soils may have to be“imported”.
(d)
Ensure that there is sufficient working space, consider passing trafficand other obstructions. If it is not possible to position the joint bays atstandard cable length distances, remember that the cable can beordered in specific lengths. Consider drainage for large bays and tryto construct the bays prior to cable pulling to prevent any damage tothe cable at a later stage.
(e)In the unlikely event of a cable failure in the future, quoting the cabledrum serial number will assist the cable manufacturer in his qualitycontrol, as this serial number is related to the manufacturing and rawmaterial management in the factory.
(f)
The following“VITALACTIONS”must be observed prior to a cable pull.
(i) Cable rollers must be placed between 2 and 3 m apart in thetrench(depending on size of cable) (See fig. 4a on page 23).
(ii) Ensure that graphite lubricants have been applied wherenecessary.
(iii) Check that skid plates are secure and in position, corner rollersare a good alternative (See fig. 4b on page 23).
(iv) Ensure that each member of the pulling gang knows exactlywhat he is to do and that communication signals betweenmembers are clear.
(v) The trench floor must be clear of stones and otherobstructions and the cable bedding correctly dispersed.
Positioning of Joint Bays
Recording Cable Drum Serial Numbers on“As Laid”Drawings
Preparing for Cable Laying
23
Ensure that:
(vi) Cable covers are available at convenient points.
(vii) Any objects that may fall into the trench and damage the cableduring the pull and prior to backfilling have been removed.
(viii) If the ambient temperature is below 10°C or has been so forthe past 24 hours, the cable on the drum will have to becovered with a tarpaulin and heated with suitable lamps orheaters for at least 24 hours under close supervision. Ensurethat sufficient ventilation exists, and pay the cable off the drumslowly and carefully. The drum should be lagged with only afew of the bottom lags removed during the heating process.
(ix) Place the drum at a convenient point prior to the pull on strongjacks and on sound footing (as mentioned earlier) with thearrow on the drum flanges POINTING IN THE OPPOSITEDIRECTION to the rotation when the cable is being pulled.
(x) Before pulling, cut the inner end of the cable free.
(xi) Remove the drum battens carefully and from the bottom.
(xii) Inspect the cable ends for any sign of leakage (especially Paperinsulated cables). If a leak is suspected, it can be proved byheating the cap until just too hot to touch and insulating oil willexude out, the cap should then be removed and the extent ofthe damage assessed, by means of the dielectric test (SeeSection 4.2). Cables with extruded dielectrics should besealed and free from moisture.
(xiii) The cable must be payed off from the top of the drum but takecare not to bend it too sharply.
(a) Cable Roller
(c) Cable Stocking
(b) Corner Roller
(d) Pulling Eye
Figure 4
24
(xiv) Cable pulling stockings should be examined and placed overthe nose of the cable with care (see fig. 4c & d on pg 23). Thepulling rope or wire must be attached to the stocking in such away that the cable cap will not be damaged during the pull.Theuse of swivels is recommended to prevent twisting of thestocking. The use of stockings is preferable to tying a ropedirectly to the cable for pulling-in.
(xv) For permissible mechanical forces see Section 3.4.
(xvi) Bending radius of cables as recommended by the manufac-turer should not be exceeded. They are:
CableTypeBending
Radius up to& including
11kV
22 kV&
33 kV
• Single Core
• Multicore
• Multi and Single Core 16-50 sq mm
• Armoured Multi & Single Core 70 sq mm and greater
• Single Core
• Multicore
Paper Insulated Cables
PVC Insulated Cables 1000 Volt
XLPE Insulated Cables
Table 3.2 : Recommended Bending radii
20 x d
12 x d
8 x d
10 x d
17 x d
15 x d
25 x d
15 x d
-
-
17 x d
15 x d
Where is the diameter over the outer sheath.d
(xvii) One man should remain at the drum and “brake” the drum inorder to maintain the correct tension on the cable during thepull.
(xviii) Cables should be pulled to their final position in a continuousmanner.
(xix) If a winch is being used to pull the cable and unavoidable sharpbends are encountered, a snatch block could be used to assistthe pulling tension at bend (See fig. 5).
Skid plates
Cable pulled to a position as nearsnatch block as possible. Thencable and bond detached fromblock and positioned around skidplatesas shown.
Figure 5
25
(xx) Heavy lead-sheathed Paper insulated cables in long lengthsmay need very large gangs of men if no winch is used; lighterXLPE insulated cables require fewer men.
(g)Once the cable pull is completed, the nose-end of the cable iscarefully lifted off the rollers and placed on the bottom of the trench,leaving enough slack to terminate the cable and observing theminimum bending radius. Immediately after cutting, the cable shouldbe suitably sealed on both ends of the cut to prevent the ingress ofmoisture. Examine the nose cap and make good any damage thatmay have occurred during pulling.
(h)These techniques are applied when heavy cables are to be laid or thetrench undergoes many changes of direction or very long lengths ofcable have to be laid, or a combination of these.
As in the previously mentioned methods of cable pulling, the trenchwould have been prepared with cable rollers, corner rollers and skidplates. Snatch blocks would have been anchored to the sides of thetrench at bends and a winch placed at the far end of the section. Atthe near end a mobile bond carrier is placed conveniently adjacent tothe cable drum, ensuring that its braking system is adequate and thatit has rewinding facilities. A steel rope, more than twice the length ofthe cable to be pulled, is wound onto the bond carrier drum and its endfed over the rollers and through the snatch blocks and then secured tothe drum of the winch.
The cable end is manhandled onto the first rollers and tied to the steelrope (See fig. 6) at intervals of about 2 metres. Start the winch and asthe nose of the cable arrives at the snatch block untie it from the steelcable, take it around the corner roller and retie on the straight.
Once the nose has reached the winch end, and allowing thenecessary slack, the cable can be untied, the steel rope rewound ontothe bond carrier. Further preparation for backfilling may then becommenced.
Sealing of Cable Ends
Bond Pulling
Figure 6 : Bond Pulling
Ties Applied at not Greaterthan 2 Metre Intervals
Steel wire bond
Mobile Bond Carrier
Cable drum Cable tied
Cable re-tied
Cable re-tied
Cable untied
Cable untied
Snatch block
Skid plate
Joint bay
joint bay
Winch
Cable
Cable
Bond wire
Cable tied to bond
26
3.7 Backfilling and Reinstatement
3.8 Repairs to PVC oversheaths
Superficial Damage
Holes or Slits in the PVC Sheath
Removal of a complete section of oversheath
Once the cables have been laid, and before commencing with backfillingcarry out a visual inspection of the installation to ensure that:
(a) The cables are properly bedded.(b) Correct spacing between cables if there is more than one in the
trench.(c) Cable entrances at ducts are suitably protected against the possibility
of vermin gaining entrance.(d) Laying and pulling equipment has been removed.(e) That there is no obvious damage to cable sheaths. Up to 90% of the
service failures experienced in any cable system can be avoided ifappropriate action is taken at this stage.
As mentioned above PVC sheaths damaged ‘during pulling’ should berepaired taking every care to do a workmanlike job.
(a)Generally the local area damaged should be removed, the remainingsheath chamfered for 25 mm at the edges. A EPR self-amalgamatingtape is then applied after cleaning the affected area thoroughly witha suitable solvent (i.e. Genklene). The PVC tape should be approxi-mately 30 mm wide and is applied under tension with a 50% overlapcontinuing up the chamfer until the top is reached plus 4 layersextending 75 mm beyond the chamfer.
(b)Chamfer the edges of the damaged area for a distance of 30 mm andabrade the area with Carborundum strip for a further 20mm.
Clean the area with a solvent and apply a filling putty (B sealing tape)followed by a layer of EPR self-amalgamating tape applied at hightension extending 50 mm from the patch, followed by 3 layers of PVCtape extending 100 mm from the edges of the EPR tape.
(c )Upon removal of the damaged ring, chamfer the remaining edges fora distance of 30 mm, clean with the solvent and apply 4 layers of EPRtape at high tension to 50 mm beyond the chamfer. Apply PVC self-adhesive tape at one third overlap to a level corresponding to theoriginal over sheath diameter. Five layers of PVC self-adhesive tapeare then applied, each one extending 5 mm further along the cable.
The repair is then completed with a resin poultice reinforcementconsisting of 6 layers of ribbon gauge or bandage, impregnated andpainted with an approved grade of freshly mixed epoxy resin. Allow12 hours to cure.
27
4.0 Paper InsulatedAnd Lead-covered 6.35/11kV Cables
4.1 Notes on impregnating compound
4.2 Moisture in Paper cables
MoistureTest
The following chapter generally covers 6.35/11kV PILC cables. For highervoltages or single core applications please consult our application engi-neers for specialised technical or installation information. The cablesdescribed in this section are manufactured according to SANS 97. (Forgreater details see brochure covering this product).
Present day paper insulated cable are mass impregnated with non-drainingcompound (MIND). This Poly-Iso-Butylene compound remains in a solidstate at normal operating temperatures and melts at a p p r o x i m a t e l y100°C.
Compound migration, as was experienced in earlier rosin-oil impregnatedcables installed vertically or on inclines, has thus been eliminated by theuse of this non-draining compound.
If cable is damaged and the lead sheath or end cap is punctured, moisturealmost invariably penetrates into the insulation and, if not detected imm-ediately and removed, may cause trouble at a later date. In every suchcase, therefore, a moisture test should be carried out and the cable cutback until all traces of dampness are removed. The following simple, butreliable test is recommended:
Heat about 1 litre of oil compound (or melted paraffin wax)in a saucepan toa temperature of 150°C (check by thermometer). Remove individual papertapes from the cable under test and immerse them in the hot compound.If any moisture is present, it will boil out of the paper and form bubbles orfroth, which will rise to the surface of the liquid. If no moisture is present,the hot compound will be undisturbed.
When carrying out the above test do not handle the portion of the papertapes to be immersed in the compound, as moisture from the hands maygive rise to false conclusions. As moisture is most likely to travel along thecable under the lead sheath or along the conductors, the papers next to thesheath and conductors are those most likely to contain moisture.
To minimise the penetration of moisture into the cable from the atmos-phere or other sources, the cores should be moisture-blocked at each end,by sweating them solid or using solid centre ferrules.
Table 4.1 : Current Rating Parameters
Maximum sustained conductor temperatureGround TemperatureAmbient air temperature (free air-shaded)Ground Thermal ResistivityDepth of laying to top of cable or duct
70°C
25°C
30°C
1,2K.m/W
800mm
28
25 35 50 70 95 120
150
185
240
300
31,3
8
33,6
4
33,4
9
36,5
0
39,3
3
41,7
3
44,3
6
47,4
2
52,1
4
56,1
5
105
130
160
195
235
265
295
335
380
425
4890
5710
6020
7080
8260
9440
1077
0
1229
0
1448
0
1694
0
80 100
125
155
185
210
235
265
305
340
1,44
21
1,04
92
0,77
77
0,54
23
0,39
72
0,31
83
0,26
40
0,21
66
0,17
34
0,14
72
1,90
0
2,66
0
3,80
0
5,32
0
7,22
0
9,12
0
11,4
00
14,0
60
18,2
40
22,8
00
31,3
8
33,6
4
33,4
9
36,5
0
39,3
3
41,7
3
44,3
6
47,4
2
52,1
4
56,1
5
4415
5055
5195
5790
6505
7225
7980
8870
1005
0
1141
5
0,87
79
0,63
71
0,47
51
0,33
65
0,24
99
0,20
53
0,17
39
0,14
81
0,12
45
0,11
06
2,87
5
4,02
5
5,75
0
8,05
0
10,9
25
13,8
00
17,2
50
21,2
75
27,6
00
34,5
00
Tab
le 4
.2E
lect
rical
and
Phy
sica
l Pro
pert
ies
of 3
cor
e Pa
per
insu
late
d an
d le
ad c
over
ed d
oubl
e st
eel t
ape
arm
oure
d Ju
te S
erve
d 6.
35/1
1kV
cab
les
to S
AN
S 9
7Ta
ble
17 (G
ener
al p
urpo
se b
elte
d)
(mm
)(m
m)
(kg
/km
)(A
)(A
)(
/km
)W
(/k
m)
W(k
g/k
m)
(mm
²)(k
A)
(kA
)
Ele
ctr
ical P
rop
ert
ies
Ele
ctr
ical P
rop
ert
ies
Ph
ysic
al P
rop
ert
ies
Ph
ysic
al P
rop
ert
ies
Cab
le
Siz
e
CO
PP
ER
CO
ND
UC
TO
RS
ST
RA
ND
ED
ALU
MIN
IUM
CO
ND
UC
TO
RS A
pp
rox.
Cab
leM
ass
Dia
mete
ro
ver
lead
1 s
eco
nd
sh
ort
cir
cu
itra
tin
g
Imp
e-
dan
ce
Cu
rren
tra
tin
g(G
rou
nd
)
Ap
pro
x.
Cab
leM
ass
Dia
mete
ro
ver
lead
1 s
eco
nd
sh
ort
cir
cu
itra
tin
g
Imp
e-
dan
ce
Cu
rren
tra
tin
g(G
rou
nd
)
(Sho
rt c
ircui
t ra
tings
bas
ed o
n te
mpe
rat u
re r
ise
of 7
0°C
to
1 60°
C)
29
4.3 Derating factors for non-standard conditions
Table 4.3.4 : Ground Temperature derating factors
MaximumConductor
Temperature (70°C)
GroungTemperatures (°C)
25
1,00
30
0,95
35
0,90
40
0,85
45
0,80
Table 4.3.3 : Grouping of PILC cables in Horizontal Formation at standard soilconditions (multicore cables)
No ofCables
inGroup
Direct in Ground In Single Way Ducts
Axial Spacing (mm) Axial Spacing (mm)
Touching 150 300 300450 450600 600Touching
2
3
4
5
6
0,80
0,69
0,63
0,57
0,55
0,88
0,80
0,75
0,71
0,69
0,85
0,75
0,70
0,66
0,63
0,91
0,84
0,81
0,77
0,75
0,89
0,80
0,77
0,73
0,71
0,90
0,84
0,80
0,78
0,76
0,92
0,86
0,84
0,81
0,80
0,94
0,89
0,87
0,85
0,84
0,93
0,87
0,84
0,82
0,80
Ground Thermal Resistivity (Multicore PILC cables)Table 4.3.2 :
1,0
1,2
1,5
2,0
2,5
1,07
1,00
0,92
0,84
0,75
1,03
1,00
0,95
0,88
0,82
Thermal Resistivity(K.m/W)
Direct in Ground In Single Way Ducts
Depth of Laying (mm) Direct in Ground In Single Way Ducts
800
1000
1250
1500
2000
1,00
0,98
0,96
0,95
0,92
1,00
0,99
0,97
0,96
0,94
Table 4.3.1 : Depth of laying - multicore PILC cables (up to 300 mm²)
30
4.4 Short circuit ratings for PILC cables
Short circuit ratings do not lend themselves to rigid treatment due tounknown variables, and wherever possible conservative values should beapplied.
With the continued growth of power system fault capacity, attention mustbe given, when selecting a cable, to its short circuit capacity as well as tothe continuous current rating.
Other limiting effects in avoiding damage during subsequent short circuitconditions are as follows:-
(a) Weakening of joints due to softening of solder at conductor tempera-tures above 160°C.
MaximumConductor
Temperature (70°C)
AirTemperatures (°C)
25
1,10
30
1,00
35
0,94
40
0,87
45
0,79
Table 4.3.5 : Air Temperature derating factors
Solar Radiation
Correction FactorsCross-SectionalArea of Conductor
1250 W/m² (Highveld)1000 W/m² (Coastal)mm²
0,62
0,57
0,53
0,49
0,44
1,5 - 10
16 - 35
50 - 95
120 - 185
240 - 400
0,70
0,68
0,65
0,62
0,59
Table 4.3.6 : Correction factors for direct solar radiation
Note:
Horizontal formation
Vertical formation
Note:
PILC Cables may be grouped in air without derating providing thatthe cables are installed on cable ladders, and that for:
(a)The clearance between cables is not less than 2 x the overalldiameter of the largest cable (or 150 mm) whichever is least.
(b)(i) The clearance from a supporting wall is greater than 20 mm,
and(ii) The vertical clearance between cables is greater than 150 mm.
If the number of cables > 4, they are to be installed in a horizontal plane.
31
(b) If crimped or welded ferrules and lugs are used (see A - 1.2 ofannex A SANS 97) temperatures of 250°C can be tolerated.
(c) Bursting effects are only of concern with unarmoured screenedcables larger than 150 mm². Multicore wire armoured cables are onlylikely to burst at currents in excess of 33 kA for cable sizes below70mm², in excess of 39 kA for cables below 150 mm² and in excessof 22 kA for cables below 300 mm².
Cable short circuit ratings are based on the adiabatic performance of theconductors and may thus be regarded as “internal ratings” which are notaffected by external factors as in the case of current ratings. Therefore, noderating factors are needed.
Ratings are derived from temperature limits as follows:-
The values of K for copper and aluminium conductors of 6.35/11 kV PILCcables are 115 & 76 amps/mm² respectively, for a conductor temperaturerising from 70°C to 160°C.
on pg 28 provides 1 second short circuit ratings.
Some systems make provision for reducing earth fault currents by theinclusion of a neutral earthing resistor (NER) at the star point of thedistribution transformer.
Where this is not the case, the resultant high earth fault current under afault condition will be carried by the lead sheath and by the galvanised steelwire armour. The bitumised steel tape armour is expected to rust in timeand should not be included in any calculation to carry fault current.
The value of K for lead sheaths and galvanised steel wire armour is 24 & 44amps/mm² respectively. The following formula must be applied:
The area of the lead sheath and the armour wires of the cable must beobtained.
Reference to SANS 97 will provide the necessary information.
where I = short circuit rating in AmpsK = constant combining temperature limits and conductor
material propertiesA = area of conductort = duration of short circuit in seconds
Table 4.2
4.5 Earth Fault Ratings
I =
K x AAmps
t
I =
K x AAmps
t
32
5.0 Medium Voltage XLPE Insulated, PVC Bedded, SWA, PVC sheathedcables
QualityAssurance
5.1 Notes on XLPE Insulation
The following chapter generally covers 6.35/11kV XLPE cables. For highervoltages or single core applications please consult our applicationengineers for specialised technical or installation information. The cablesdescribed in this section are manufactured according to SANS 1339. (Forgreater details see brochure covering this product).
MV XLPE cable manufactured by Aberdare Cables is required to undergo apartial discharge test at our Standford Road Port Elizabeth factory. Thepartial discharge measurement technique involves scanning of everymetre of every drum of cable using the only such scanner installed in theSouthern Hemisphere. The technique has been in use since the intro-duction of XLPE by Aberdare Cables and has given superb performanceover the past 20 years.
The advantage of the scanning technique is that non-complying XLPEcores can be re-insulated before they are further processed (application ofcopper tape screen, laying up of 3 cores, application of PVC bedding,application of Steel Wire Armour and extrusion of outer sheath). Althoughthis is a expensive operation, it is dramatically cheaper than rectification offaults at final test or after installation on the customer premises. Infactories where partial discharge detection is carried out only as a finaltest, and assuming a non-complying partial discharge is detected, thedecision to scrap the cable or alternatively to strip and replace an XLPEcore will be very costly.
The advantage to the customer of the above testing is that he is assured ofquality cable with an acceptable level of partial discharge.
Aberdare’s unrivalled quality record in experiencing only one field failure ofXLPE cable during its twenty years of manufacture of this product isadequate proof of the superiority of this testing method.
For XLPE insulated conductors, continuous conductor temperatures of90°C are permissible with overload excursions up to 130°C for a maximumof 8 hours continuous per event, with a maximum total of 125 hours perannum. In the case of short circuits the insulation can withstand conductortemperatures of up to 250°C for 1 second.
Maximum sustained conductor temperatureGround TemperatureAmbient air temperature (free air-shaded)Ground Thermal ResistivityDepth of laying to top of cable or duct
90°C
25°C
30°C
1,2K.m/W
800mm
Table 5.1 : Current ratings are based on these parameters
33
Tab
le 5
.2E
lect
rical
and
Phy
sica
l Pro
pert
ies
of 3
cor
e X
LPE
insu
late
d P
VC b
edde
d, s
teel
wire
arm
oure
d, P
VC s
heat
hed
6.35
/11k
V c
able
s to
SA
NS
133
9Ty
peA
(Indi
vidu
ally
scr
eene
d)
(mm
)(m
m)
(kg
/km
)(A
)(A
)(
/km
)W
(/k
m)
W(k
g/k
m)
(mm
²)(k
A)
(kA
)
Ele
ctr
ical P
rop
ert
ies
Ele
ctr
ical P
rop
ert
ies
Ph
ysic
al P
rop
ert
ies
Ph
ysic
al P
rop
ert
ies
Cab
le
Siz
e
CO
PP
ER
CO
ND
UC
TO
RS
ST
RA
ND
ED
ALU
MIN
IUM
CO
ND
UC
TO
RS A
pp
rox.
Cab
leM
ass
Dia
mete
ro
ver
lead
1 s
eco
nd
sh
ort
cir
cu
itra
tin
g
Imp
e-
dan
ce
Cu
rren
tra
tin
g(G
rou
nd
)
Ap
pro
x.
Cab
leM
ass
Dia
mete
ro
ver
lead
1 s
eco
nd
sh
ort
cir
cu
itra
tin
g
Imp
e-
dan
ce
Cu
rren
tra
tin
g(G
rou
nd
)
25 35 50 70 95 120
150
185
240
300
47,3
49,7
52,6
56,3
60,5
64,2
68,8
72,8
79,1
85,6
140
170
200
240
290
325
360
410
470
520
4655
5215
5895
6995
8170
9370
1124
0
1277
5
1495
5
1786
5
0,93
53
0,67
83
0,50
67
0,35
81
0,26
65
0,21
87
0,18
47
0,15
71
0,13
17
0,11
60
155
190
225
255
285
320
370
420
3,57
5
5,00
5
7,15
0
10,0
10
13,5
85
17,1
60
21,4
50
26,4
55
34,3
20
42,9
00
0,82
84
0,57
67
0,42
13
0,33
75
0,27
95
0,22
85
0,18
21
0,15
35
4,60
0
6,44
0
8,74
0
11,0
40
13,8
00
17,0
20
22,0
80
27,6
00
52,6
56,3
60,5
64,2
68,8
72,8
79,1
85,6
5015
5635
6340
7045
8350
9245
1058
0
1207
0
34
Table 5.2.4 : Ground Temperature derating factors
25
1,0
30
0,96
35
0,92
40
0,88
45
0,84
MaximumConductor
Temperature (90°C)
Ground Temperatures (°C)
5.2 Derating factors for non-standard conditions
Table 5.2.3 : Group of XLPE cables in horizontal formation at standard depthsof laying and in standard soil conditions (multicore cables)
No ofCables
in Group
Direct in Ground In Single Way Ducts
Axial Spacing (mm) Axial Spacing (mm)
Touching 250 700 Touching 250 700
0,79
0,69
0,63
0,58
0,55
0,87
0,80
0,75
0,72
0,69
0,85
0,75
0,68
0,64
0,60
0,91
0,86
0,80
0,78
0,74
0,87
0,79
0,75
0,72
0,69
0,93
0,91
0,87
0,86
0,83
2
3
4
5
6
Ground thermal resistivity - multicore XLPE cables(up to 300 mm²)
Table 5.2.2 :
Thermal Resistivity(K.m/W)
Direct in Ground In Single Way Ducts
0,7
1,0
1,2
1,5
2,0
2,5
3,0
1,23
1,08
1,00
0,90
0,80
0,72
0,66
1,28
1,12
1,00
0,93
0,85
0,80
0,74
Depth of Laying (mm) Direct in Ground In Single Way Ducts
Table 5.2.1 : Depth of laying - multicore XLPE cables (up to 300 mm²)
500 - 800
850 - 1000
1050 - 1200
1250 - 1400
1450 - 1600
1,00
0,97
0,95
0,93
0,92
1,00
0,96
0,95
0,95
0,94
35
Note:
Horizontal formation
Vertical formation
Note:
Cables may be grouped in air without derating provided that the cablesinstalled on cable ladders, and that for:
(a)The clearance between cables is not less than 2 x the overalldiameter of the largest cable (or 150 mm) whichever is least.
(b)The clearance from a supporting wall is greater than 20 mm, andThe vertical clearance between cables is greater than 150 mm.
If the number of cables > 4, they are to be installed in a horizontalplane.
5.3 Short circuit ratings for XLPE insulated 6.35/11 kV cables
Short circuit ratings do not lend themselves readily to rigid treatment dueto unknown variables. Wherever possible conservative values should beapplied. As the growth of a power system increases so do the systemfault levels. When selecting a cable attention must be given to it’s shortcircuit capability, as well as to the continuous current ratings.
Other limiting effects in avoiding damage during short circuit conditions areas follows:-
(a) Weakening of joints due to softening of the solder at a conducttemperature of 160°C and above, although most conductor joiningnowadays is done by compression fittings, particularly on XLPEinsulated cables.
Solar Radiation
Correction FactorsCross-SectionalArea of Conductor
1250 /m² (Highveld)W1000 /m² (Coastal)Wmm²
0,62
0,57
0,53
0,49
0,44
1,5 - 10
16 - 35
50 - 95
120 - 185
240 - 400
0,70
0,68
0,65
0,62
0,59
Table 5.2.6 : Correction factors for direct solar radiation
MaximumConductor
Temperature (90°C)30
1,0
35
0,95
40
0,89
45
0,84
50
0,78
Table 5.2.5 : Air Temperature derating factors
AirTemperatures (°C)
(b) Bucking of the conductors in joint boxes due to longitudinal expansionof cables laid direct in ground.
Cables short circuit ratings are based on the adiabatic performance of theconductors. This assumes no heat loss from the cable during the period ofthe fault. No derating factors are necessary with regard to soiltemperature, depth of burial etc.
Ratings are derived from temperature limits as follows:-
Where I = Short circuit rating in AmpsK = constant combining temperature limits and conductor
material propertiesA = area of Conductort = duration of short circuit in seconds
The value of K for copper and aluminium conductors of 6.35/11 kV XLPEcables is 143 & 92 amps/mm² respectively, for a conductor temperaturerising from 90°C to 250°C.
Some systems provide for reducing earth fault currents by the inclusion ofa neutral earthing resistor (NER) at the star point of the distributiontransformer, to typically 300 A.
Where this is not the case, the resistance of the copper tapes and steelwire armour should be included in the calculation.
Typical 1 second Earth Fault ratings for XLPE insulated 6.35/11 kVType A cables manufactured to SANS 1339 - 1991 are shown in table 5.3
5.4 Earth Fault Current
36
Cable Size Earth Fault Rating
Table 5.3 : Earth fault ratings
mm² kA/s
25
35
50
70
95
120
150
185
240
300
10,4
12,2
13,1
17,6
18,7
19,7
20,8
25,0
26,8
28,6
I =
K x AAmps
t
37
6.2 Physical dimensions of the cables are given in terms of the sketchbelow and these abbreviations are used in the tables.
C/S OF SINGLE CORE CABLE
D1 = diameter over bedding
d = diameter of armour wires
D2 = diameter over outer sheath
6.0 Low Voltage PVC and XLPE Insulated 600/1000V Power Cables toSANS 1507
6.1 Note on PVC insulation
Note of XLPE insulation
For PVC insulation continuous conductor temperatures up to 70°C arepermissible. Care must be exercised in matching the cable to the circuitprotection. Under short circuit conditions, a maximum conductortemperature of 160°C is allowed for a maximum period of 1 second.
For XLPE insulation, continuous conductor temperature up to 90°C arepermissible with excursions of up to 130°C or a maximum of 8 hourscontinuous per event, with a maximum total of 125 hours per annum.
D1
d
D2
Table 6.1 : Current rating parameters
Maximum sustained conductor temperature
Ground temperature
Ambient air temperature (free air shaded)
Ground Thermal Resistivity
Depth of laying to top of cable or duct
PVC XLPE
70°C
25°C
30°C
1,2 K.m/W
500mm
90°C
25°C
30°C
1,2 K.m/W
500mm
38
Tab
le 6
.2E
lect
rical
and
Phy
sica
l Pro
pert
ies
of 3
and
4 c
ore
PVC
Insu
late
d P
VC b
edde
d S
WA
PVC
she
athe
d 60
0/10
00V
cab
les
man
ufac
ture
d to
SA
NS
150
7-3
CO
PP
ER
CO
ND
UC
TO
RS
Cu
rren
t R
ati
ng
No
min
al
Dia
me
ters
Ph
ysic
al
Pro
pe
rtie
sE
lectr
ical P
rop
ert
ies
Ap
pro
x.M
ass
3 Vo
ltd
rop
f
(mV
/A/m
)
1 Vo
ltd
rop
f
(mV
/A/m
)(m
m)
D1
dD
2
(mm
)(m
m)
(mm
)(m
m)
(mm
)(k
g/k
m)
Gro
un
d
(A)
Du
cts
(A)
Air
(A)
Imp
e-
dan
ce
(/k
m)
W(k
g/k
m)
1,5
2,5 4 6 10 16 25 35 50 70 95 120
150
185
240
300
24 32 42 53 70 91 119
143
169
210
251
285
320
361
416
465
20 26 34 43 58 75 96 116
138
171
205
234
263
298
344
385
14,4
8
8,87
5,52
3,69
2,19
1,38
0,87
49
0,63
35
0,47
18
0,33
25
0,24
60
0,20
12
0,16
98
0,14
45
0,12
20
0,10
90
25,0
80
15,3
63
9,56
1
6,39
1
3,79
3
2,39
0
1,51
5
1,09
7
0,81
7
0,57
6
0,42
7
0,34
8
0,29
4
0,25
0
0,21
1
0,18
9
28,9
56
17,7
34
11,0
34
7,37
4
4,38
4
2,75
9
1,74
9
1,26
7
0,94
4
0,66
5
0,49
2
0,40
2
0,33
9
0,28
9
0,24
4
0,21
8
8,51
9,61
11,4
0
12,5
8
14,5
9
16,5
5
19,4
6
20,8
9
24,2
6
27,0
7
31,1
9
33,3
8
36,6
8
40,8
2
46,4
3
51,1
0
9,33
10,5
6
12,5
7
13,9
0
16,1
4
19,1
8
21,3
4
23,9
7
28,1
4
31,2
9
35,8
2
38,1
0
42,0
5
46,7
5
53,0
6
58,5
3
1,25
1,25
1,25
1,25
1,25
1,25
1,60
1,60
1,60
2,0
0
2,0
0
2,0
0
2,0
0
2,50
2,50
2,50
1,25
1,25
1,25
1,25
1,25
1,60
1,60
1,60
2,0
0
2,0
0
2,0
0
2,0
0
2,50
2,50
2,50
2,50
14,1
3
15,2
3
17,0
2
18,4
0
20,4
1
22,3
7
26,4
6
27,8
9
31,4
6
35,4
7
39,9
9
42,1
8
45,9
8
51,1
2
57,1
3
62,2
0
14,9
5
16,1
8
18,3
9
19,7
2
21,9
6
25,9
2
28,3
4
31,1
7
36,5
4
40,0
9
44,6
2
47,4
0
52,6
5
57,4
5
64,1
6
70,1
3
448
522
667
790
996
1295
1838
2215
2871
3617
4901
5720
6908
8690
1076
7
1295
0
19 26 35 45 62 83 110
135
163
207
251
290
332
378
445
510
501
597
762
910
1169
1768
2196
2732
3893
4837
6115
7269
9250
1103
9
1372
6
1654
4
Cab
le
Siz
e
(mm
²)
3c
3c
3c
3c
4c
4c
4c
4c
39
Tab
le 6
.3E
lect
rical
and
Phy
sica
l Pro
pert
ies
of 3
and
4 c
ore
PVC
Insu
late
d P
VC b
edde
d S
WA
PVC
she
athe
d 60
0/10
00V
cab
les
man
ufac
ture
d to
SA
NS
150
7-3
ALU
MIN
IUM
CO
ND
UC
TO
RS
Cu
rren
t R
ati
ng
No
min
al
Dia
me
ters
Ph
ysic
al
Pro
pe
rtie
sE
lectr
ical P
rop
ert
ies
Ap
pro
x.M
ass
3 Vo
ltd
rop
f
(mV
/A/m
)
1 Vo
ltd
rop
f
(mV
/A/m
)(m
m)
D1
dD
2
(mm
)(m
m)
(mm
)(m
m)
(mm
)(k
g/k
m)
Gro
un
d
(A)
Du
cts
(A)
Air
(A)
Imp
e-
dan
ce
(/k
m)
W(k
g/k
m)
Cab
le
Siz
e
(mm
²)
3c
3c
3c
3c
4c
4c
4c
4c
25 35 50 70 95 120
150
185
240
90 108
129
158
192
219
245
278
324
73 87 104
130
157
179
201
229
268
80 99 119
151
186
216
250
287
342
1,44
46
1,04
65
0,77
49
0,53
88
0,39
34
0,31
48
0,26
07
0,21
33
0,17
08
2,50
2
1,81
3
1,34
2
0,93
3
0,68
1
0,54
5
0,45
2
0,36
9
0,29
6
2,88
9
2,09
3
1,54
9
1,07
8
0,78
7
0,62
9
0,52
1
0,42
7
0,34
2
17,7
6
19,3
3
21,8
7
24,7
6
28,6
8
31,0
9
33,9
9
37,8
0
42,6
0
20,6
5
21,9
3
25,0
5
29,2
7
33,7
3
35,4
4
39,3
9
44,5
1
50,0
4
1,60
1,60
1,60
1,60
2,0
0
2,0
0
2,0
0
2,0
0
2,50
1,60
1,60
1,60
1,60
2,0
0
2,0
0
2,50
2,50
2,50
24,7
6
26,3
3
29,0
7
31,9
6
37,0
8
39,8
9
42,7
9
47,1
0
52,9
27,6
5
29,1
3
32,2
5
37,6
7
42,5
3
44,2
4
49,6
9
54,8
1
61,1
4
1301
1477
1782
2132
2908
3328
3837
4557
5977
1554
1757
2150
2930
3647
4023
5276
6231
7550
70°C
70°C
70°C
90°C
90°C
90°C
26 34 45 55 75 94 123
148
177
216
258
293
329
371
428
482
30 40 52 64 87 110
143
172
206
252
302
344
387
435
498
558
21 28 36 44 60 76 98 119
142
175
209
238
268
302
349
401
25 32 42 52 70 89 116
139
167
205
248
282
318
359
413
471
16 21 28 35 48 60 107
132
163
206
251
291
334
383
453
520
22 30 39 49 68 85 132
163
200
253
312
362
416
478
557
634
Tab
le 6
.4E
lect
rical
and
Phy
sica
l Pro
pert
ies
of 3
and
4 c
ore
XLP
E In
sula
ted
PVC
bed
ded
SW
A P
VC s
heat
hed
600/
1000
V c
able
s m
anuf
actu
red
to S
AN
S 1
507-
4
CO
PP
ER
CO
ND
UC
TO
RS
Cu
rren
t R
ati
ng
No
min
al
Dia
me
ters
Ph
ysic
al
Pro
pe
rtie
sE
lectr
ical P
rop
ert
ies
Ap
pro
x.M
ass
3 Vo
ltd
rop
f
(mV
/A/m
)
1 Vo
ltd
rop
f
(mV
/A/m
)(m
m)
D1
dD
2
(mm
)(m
m)
(mm
)(m
m)
(mm
)(k
g/k
m)
Gro
un
dD
ucts
Air
Imp
e-
dan
ce
(/k
m)
W(k
g/k
m)
Cab
le
Siz
e
(mm
²)
3c
3c
3c
3c
4c
4c
4c
4c
1,5
2,5 4 6 10 16 25 35 50 70 95 120
150
185
240
300
15,4
3
9,45
5,88
3,93
2,33
1,46
0,93
13
0,67
38
0,50
09
0,35
21
0,25
89
0,21
09
0,17
75
0,15
00
0,12
47
0,10
99
26,7
26
16,3
68
10,1
84
6,80
7
4,05
3
2,54
6
1,61
3
1,16
7
0,86
8
0,61
0
0,44
8
0,36
5
0,30
7
0,26
0
0,21
6
0,19
0
30,8
61
18,9
00
11,7
61
7,86
2
4,66
3
2,92
4
1,86
3
1,34
8
1,00
2
0,70
4
0,51
8
0,42
2
0,35
5
0,30
0
0,24
9
0,21
9
8,08
9,18
10,0
6
11,2
5
13,2
5
15,2
1
18,1
3
19,5
6
22,4
9
25,7
4
28,7
6
31,3
9
34,6
9
39,0
5
44,2
2
48,4
5
8,85
10,0
8
11,0
7
12,4
0
14,6
4
17,6
8
19,8
6
22,3
2
25,7
6
29,8
1
33,1
35,8
7
40,1
2
44,7
7
50,5
8
55,5
6
1,25
1,25
1,25
1,25
1,25
1,25
1,60
1,60
1,60
2,00
2,00
2,00
2,50
2,50
2,50
2,50
1,25
1,25
1,25
1,25
1,25
1,25
1,60
1,60
1,60
2,00
2,00
2,00
2,50
2,50
2,50
2,50
13,7
0
14,8
0
15,6
8
16,8
7
19,0
7
21,0
3
25,1
3
26,5
6
29,6
9
32,9
4
37,1
6
40,1
9
43,4
9
49,3
5
54,5
2
58,3
5
14,4
7
15,7
0
16,6
9
18,0
2
20,4
6
24,4
2
26,8
6
29,5
2
32,9
6
38,2
1
41,9
0
44,6
7
50,4
2
55,0
7
61,6
8
67,1
6
416
487
566
683
890
1191
1693
2025
2606
3323
4442
5335
6403
8184
1007
3
1207
6
453
521
650
778
1033
1544
2018
2511
3242
4503
5650
6731
8708
1034
3
1293
2
1557
5
40
41
Tab
le 6
.5E
lect
rical
and
Phy
sica
l Pro
pert
ies
of 3
and
4 c
ore
XLP
E In
sula
ted
PVC
bed
ded
SW
A P
VC s
heat
hed
600/
1000
V c
able
s m
anuf
actu
red
to S
AN
S 1
507-
4
ALU
MIN
IUM
CO
ND
UC
TO
RS
Cu
rren
t R
ati
ng
No
min
al
Dia
me
ters
Ph
ysic
al
Pro
pe
rtie
sE
lectr
ical P
rop
ert
ies
Ap
pro
x.M
ass
3 Vo
ltd
rop
f
(mV
/A/m
)
1 Vo
ltd
rop
f
(mV
/A/m
)(m
m)
D1
dD
2
(mm
)(m
m)
(mm
)(m
m)
(mm
)(k
g/k
m)
Gro
un
d
(A)
Du
cts
(A)
Air
(A)
Imp
e-
dan
ce
(/k
m)
W(k
g/k
m)
Cab
le
Siz
e
(mm
²)
3c
3c
3c
3c
4c
4c
4c
4c
108
131
160
200
245
285
328
378
438
1,54
08
1,11
59
0,82
58
0,57
36
0,41
78
0,33
37
0,27
56
0,22
47
0,17
85
2,66
9
1,93
3
1,43
0
0,99
4
0,72
4
0,57
8
0,47
7
0,38
9
0,30
9
3,08
2
2,23
2
1,65
2
1,14
7
0,83
6
0,66
7
0,55
1
0,44
9
0,35
7
15,5
3
18,0
0
20,0
9
23,4
3
25,8
5
29,0
9
32,1
5
36,0
2
40,3
9
19,1
6
20,4
4
23,0
6
27,3
8
30,9
9
33,2
0
36,7
5
42,5
2
50,4
0
1,25
1,60
1,60
1,60
1,60
2,0
0
2,0
0
2,0
0
2,50
1,60
1,60
1,60
1,60
2,0
0
2,0
0
2,0
0
2,50
2,50
21,5
3
25,0
0
27,0
9
30,6
3
33,0
5
37,4
9
40,9
5
45,3
2
50,6
9
26,1
6
27,4
4
30,2
6
34,9
8
39,3
9
42,0
0
46,0
5
52,8
2
61,5
0
925
1307
1550
1911
2254
2929
3457
4132
5375
1377
1549
1872
2371
3158
3584
4274
5650
7024
25 35 50 70 95 120
150
185
240
115
138
164
199
238
272
306
344
392
92 111
132
161
194
221
249
283
325
42
Tab
le 6
.6E
lect
rical
and
Phy
sica
l Pro
pert
ied
ofS
ingl
e co
re u
narm
oure
d P
VC in
sula
ted
PVC
she
athe
d 60
0/10
00V
cab
les
man
ufac
ture
d to
SA
NS
150
7-3
ST
RA
ND
ED
CO
PP
ER
CO
ND
UC
TO
RS
(/k
m)
W(m
m)
(mm
)(k
g/k
m)
mV
Gro
un
dG
rou
nd
Cu
rren
t R
ati
ng
Cu
rren
t R
ati
ng
Air
Du
ct
Air
mV
(A)
(A)
(A)
(mm
²)(A
)(A
)
Cab
leS
ize
1C
ab
les
AC
or
DC
f
Ele
ctr
ical P
rop
ert
ies
Ph
ysic
al P
rop
ert
ies
Vo
lt D
rop
per
am
pp
er
mV
Vo
lt d
rop
pe
r a
mp
pe
r m
V
No
min
al
Mass
No
min
al D
iam
ete
rs3
Cab
les in
Tre
foil F
orm
ati
on
.f
Imp
e-
dan
ce
25 35 50 70 95 120
150
185
240
300
400
500
630
800
1000
118
156
186
232
281
324
370
424
498
566
651
740
836
931
1041
126
156
191
246
300
349
404
463
549
635
742
835
953
1086
1216
1,75
1,27
0,95
0,67
0,50
0,41
0,35
0,30
0,25
0,23
0,21
0,19
0,18
0,17
0,16
127
153
180
221
265
301
338
381
442
499
565
634
718
792
856
111
132
155
190
226
256
287
323
372
419
472
532
603
689
741
112
141
172
223
273
318
369
424
504
584
679
778
892
1020
1149
1,52
1,10
0,82
0,58
0,43
0,36
0,30
0,26
0,22
0,20
0,18
0,17
0,15
0,15
0,14
0,87
67
0,63
56
0,47
45
0,33
56
0,25
0,20
54
0,17
34
0,14
99
0,12
68
0,11
31
0,10
28
0,09
63
0,08
9
0,85
2
0,08
19
5,95
7,00
8,15
9,79
11,5
4
12,9
6
14,3
9
16,1
0
18,7
1
21,4
5
24,3
0
26,5
1
33,1
5
37,7
0
42,2
5
11,9
1
12,9
6
15,1
5
16,5
7
19,0
4
20,2
4
22,0
7
24,0
8
27,8
1
30,7
5
34,1
0
37,1
3
43,6
2
49,0
0
53,4
5
366
469
632
880
1160
1413
1734
2145
2725
3375
4395
5299
6965
9118
1105
0
D1
D2
Not
e: (1
) D1
is t
he d
iam
eter
ove
r th
e co
nduc
tor .
(2
) D2
is t
he d
iam
eter
ove
r th
e sh
eath
.
43
Tab
le 6
.7E
lect
rical
and
Phy
sica
l Pro
pert
ied
ofS
ingl
e co
re u
narm
oure
d X
LPE
insu
late
d P
VC s
heat
hed
600/
1000
V c
able
s m
anuf
actu
red
to S
AN
S 1
507-
4
ST
RA
ND
ED
CO
PP
ER
CO
ND
UC
TO
RS
(/k
m)
W(m
m)
(mm
)(k
g/k
m)
mV
Gro
un
dG
rou
nd
Cu
rren
t R
ati
ng
Cu
rren
t R
ati
ng
Air
Du
ct
Air
mV
(A)
(A)
(A)
(mm
²)(A
)(A
)
Cab
leS
ize
1C
ab
les
AC
or
DC
f
Ele
ctr
ical P
rop
ert
ies
Ph
ysic
al P
rop
ert
ies
Vo
lt D
rop
per
am
pp
er
mV
Vo
lt d
rop
pe
r a
mp
pe
r m
V
No
min
al
Mass
No
min
al D
iam
ete
rs3
Cab
les in
Tre
foil F
orm
ati
on
.f
Imp
e-
dan
ce
25 35 50 70 95 120
150
185
240
300
400
500
630
800
1000
169
205
245
302
366
422
480
554
656
766
902
1040
1229
1366
1486
174
211
257
236
404
475
542
629
753
881
1045
1182
1417
1603
1790
1,86
6
1,35
2
1,00
7
0,71
0
0,52
6
0,43
1
0,36
3
0,30
9
0,25
9
0,22
9
0,20
7
0,19
2
0,17
8
0,17
1
0,16
6
151
181
213
260
312
355
397
449
522
589
668
750
848
942
1025
137
164
192
235
281
319
356
402
466
524
592
664
746
823
892
137
167
203
257
318
372
426
494
594
692
807
925
1094
1254
1400
1,61
6
1,71
0
0,87
2
0,61
5
0,45
6
0,37
3
0,31
5
0,26
8
0,22
4
0,19
9
0,17
9
0,16
7
0,15
4
0,14
8
0,14
4
0,93
32
0,67
60
5,36
00
0,35
52
0,26
31
0,21
54
0,18
18
0,15
45
0,12
95
0,11
49
0,10
35
0,09
63
0,88
90
0,08
56
0,08
31
5,95
7,00
8,15
9,79
11,5
4
12,9
6
14,3
9
16,1
0
18,7
1
21,4
5
24,3
0
26,5
1
33,1
5
37,7
0
42,2
5
11,8
1
12,8
6
14,3
8
16,2
2
17,9
7
19,3
2
21,4
2
23,6
3
26,6
9
30,0
5
33,3
0
36,3
3
42,7
9
48,8
4
54,2
1
328
426
567
824
1071
1304
1628
1995
2461
3182
4117
5032
6641
8535
1067
6
D1
D2
Not
e: (1
) D1
is t
he d
iam
eter
ove
r th
e co
nduc
tor .
(2
) D2
is t
he d
iam
eter
ove
r th
e sh
eath
.
44
6.3 Derating factors for non-standard conditions
No ofCables
inGroup
Direct in Ground
Axial Spacing (mm)
Touching
In Single Way Ducts
Axial Spacing (mm)
150 300 450 600 Touching 300 450 600
2
3
4
5
6
0,81
0,70
0,63
0,59
0,55
0,90
0,82
0,78
0,75
0,72
0,87
0,78
0,74
0,70
0,67
0,93
0,87
0,85
0,82
0,81
0,91
0,84
0,81
0,78
0,76
0,95
0,90
0,89
0,87
0,86
0,93
0,87
0,86
0,83
0,82
0,96
0,93
0,91
0,90
0,90
0,94
0,90
0,89
0,87
0,86
Table 6.3.3 : Derating factors for grouping of cables in horizontal formation, atstandard depths of laying and in standard soil conditions.Multi-core cables (up to 300 mm²)
Table 6.3.2 : Derating factors for ground thermal resistivity(multicore cables)
Direct in ground In single way ductsThermal Resistivity
(K.m/W)
1,0
1,2
1,5
2,0
2,5
1,08
1,00
0,93
0,83
0,78
1,04
1,00
0,96
0,88
0,87
Depth of laying (mm) Direct in ground In single way ducts
Table 6.3.1 : Derating factors for depth of laying - multicore cables(up to 300mm²)
500
800
1000
1250
1500
2000
1,00
0,97
0,95
0,94
0,93
0,92
1,00
0,97
0,96
0,95
0,94
0,93
45
Note: Cables may be grouped in air without derating, provided that the cablesare installed on ladders, and that for:-
(a)The clearance is greater than 2x the cable overall diameter (or 150mm,whichever is the least).
Horizontal formation
(b)(i) The clearance from a vertical wall is greater than 20 mm, and(ii) The vertical clearance between cables is greater than 150mm.
If the number of cables > 4, they are installed in the horizontal plane.
Vertical formation
Note:
D* is the overall diameter of one cable
Table 6.3.6 : Derating factors for grouping of multicore cable installedhorizontally in air
No. of cables
Condition
Cable touching
Clearance D* between Cables
1
1
1
2
0,9
0,95
3
0,84
0,9
6
0,80
0,88
9
0,75
0,85
Derating Factor
Table 6.3.5 : Air Temperature derating factors
Maximum ConductorTemperature (°C)
70 (PVC)
90 (XLPE)
Air Temperatures (°C)
30
1,00
1,00
35
0,94
0,95
40
0,87
0,89
45
0,79
0,84
Table 6.3.4 : Ground Temperature factors - multicore cables (up to 300 mm²)
Maximum Conductor
Temperature (°C)
70 (PVC)
90 (XLPE)
GroundTemperatures (°C)
25
1,00
1,00
30
0,95
0,96
35
0,90
0,92
40
0,85
0,88
45
0,80
0,82
50
0,70
0,76
Solar Radiation
Correction Factors
1250 /m² (Highveld)W1000 /m² (Coastal)W
Cross-SectionalArea of Conductor
mm²
0,62
0,57
0,53
0,49
0,44
1,5 - 10
16 - 35
50 - 95
120 - 185
240 - 400
0,70
0,68
0,65
0,62
0,59
Table 6.3.7 : Correction factors for direct solar radiation
46
Insulationmaterial
Conductormaterial
OperatingTemperature
°C
Short CircuitTemperature
°CK factor
PVC
PVC
XLPE
XLPE
Copper
Aluminium
Copper
Aluminium
70
70
90
90
160
160
250
250
115
76
143
92
Table 6.9 : Values of conductor/temperature constant K
6.4 Short circuit ratings for PVC and for XLPE insulated 600/1000V cablesto SANS 1507.
With PVC and with XLPE insulated cables, care must be taken to limit theconductor temperature for continuous operation and for short circuitconditions as indicated inTable 6.9.
Short circuit ratings are regarded as internal ratings. Their calculation isbased on an adiabatic equation and is not affected by external consi-deration. Due to unknown variables, short-circuit ratings do not lendthemselves readily to rigid treatment, so whenever possible conservativevalues should be applied.
Ratings are derived from temperature limits as follows:
where = Short circuit rating in ampsK = A constant combining temperature limits and properties
of conductor materialsA = area of conductort = duration of short circuit in seconds
Isc
Isc =
K x A Ampst
7.0 ElastomericTrailing Cables
Features ofAberdare’s trailing cables
The following chapter generally coversType 41 and 61 elastomeric trailingcables. For other elastomeric cables or different voltages please consultour application engineers for specialised technical or installationinformation. The cables described in this section are manufacturedaccording to SANS 1520 part 2 (for greater details see brochure coveringthis product).
Aberdare’s mining trailing cables are manufactured according to SANS1520 part 1 and 2 and bear the SANS mark up to 33 kV. The sheath isreinforced by means of an open-mesh braid in order to limit cut-spread.Theelastomers used for the sheaths are carefully selected to ensure that theproduct will withstand even the highest levels of ultraviolet radiation foundin South Africa.
47
Type 41Trailing Cable
Conductors :
Insulation :
Screens :
Sheath :
RatedVoltage :
Specification :
Tinned soft copperCo-Extrusion of EPM/CSM3 Power cores individually screenedwith copper/textile braid.Pilot core unscreened.Extra-Heavy-Duty CR640/1 100VSANS 1520 Part 1
Self-propelled electrically driven machines, movable electricapparatus in hazardous areas (Minerals Act,1991), typically,• Type 41; 4 mm² for small pumps, drills, fans etc.• Type 41; 10 and 16 mm² for shuttle-cars.
Applications
Type 61A and 61BTrailing Cable
Conductors :
Insulation :
Screens :
Sheath :
Rated Voltage :
Specification :
Tinned soft copperCo-Extrusion of EPM/CSM3 Power cores individually screenedwith copper/textile braid. 3 Pilotcores unscreened..Extra-Heavy-Duty CR640/1 100VSANS 1520 Part 1
Applications
Self-propelled electrically driven machines, portable electric apparatusand movable electric apparatus in hazardous areas (Minerals Act,1991), typically,• Type 61A 25 mm² for LHD's 70 mm² for Shearer and reeling
applications.• Type 61B 70 mm² for Continuous Miners and non-reeling
applications where a lighter cable is required.
48
Tab
le 7
.164
0/1
100V
Trai
ling
Cab
leTe
chni
cal D
ata
(A)
(mm
)(x
PC
D)
(mm
)(
/km
)W
(/k
m)
W(
/km
)W
(kg
/km
)
Cab
le
Siz
e
(mm
²)
Po
we
rP
ow
er
Pil
ot
Pil
ot
4 6 10 16 25 35 50 70 95 16 **35
**50 70 95
**12
0
4 6 10 16 10 10 16 16 16 6 6 6 10 16 16
5,5
3,66
2,11
1,34
0,85
90,
610,
424
0,29
90,
227
1,34
0,61
0,42
0,29
0,22
0,17
5,5
3,66
2,11
1,34
2,26
2,26
1,44
1,44
1,44
3,66
3,66
3,66
2,23
1,44
1,44
3,5
3,6
2,0
1,6
1,1
1,2
1,4
0,7
0,85 1,6
1,2
1,4
0,7
0,85 0,8
7,01
4,67
2,69
1,71 1,1
0,77
80,
553
0,38
70,
301
1,71
0,78
30,
550,
389
0,30
10,
243
45 57 77 100
130
160
200
245
295
105
160
200
245
295
315
25 28 32 33 41 46 51 55 60 31 38 43 48 54 58
27 30 34 36 44 50 55 59 64 33 41 46 52 58 60
0,9
1,4
1,8
2,2
2,9
4,2
5,2
6,2
7,6
2,1
3,3
3,9
5,5
6,9
7,7
8 8 8 8 8 8 8 8 8 8 12 12 12 12 12
150
180
190
200
240
280
300
330
360
185
315
350
390
430
470
Typ
e 4
1Tra
ilin
g c
ab
le (
3xin
d.s
cr.
Po
wer
plu
s 1
x P
ilo
t co
res)
Ty
pe
61
ATra
ilin
g c
ab
le (
3x
ind
.scr.
Po
we
r p
lus 3
x P
ilo
t co
res)
Ty
pe
61
BTra
ilin
g c
ab
le (
3x
ind
.scr.
Po
we
r p
lus 3
x P
ilo
t co
res)
Ma
xim
um
co
nd
ucto
rre
sis
tan
ce
(dc a
t 2
0°C
)
Ma
xim
um
co
mb
ine
dscre
en
resis
tan
ce
(dc a
t 2
0°C
)
Imp
ed
an
ce
( Z
)
Cu
rre
nt
rati
ng
(at
90
°C)
*
Ove
rall
dia
me
ter
min
ma
x
Ca
ble
ma
ss
(ap
pro
x)
Lay
rati
o
Be
nd
ing
rad
ius
(min
)
Ph
ysic
al
Pro
pe
rtie
sE
lectr
ical P
rop
ert
ies
No
te:
1 .L
ow
-Vo
ltag
eTra
ilin
gC
ab
les
with
lay
ratio
so
fm
ore
than
8are
No
tsu
itab
leF
or
Co
ntin
uo
us
Re
elin
g.
* **
Cu
rren
tra
tin
gs
insh
ad
eat
am
bie
nt
tem
pera
ture
of3
0°C
.N
ot
co
vere
db
yS
AN
S1
52
0P
art
1
49
Tested to SANS Test Methods statement 503, 504 and 506
Physical Properties of Sheathing Materials
Property UNITS
MPa
%
N/mm
GP
8
250
5
HD
11
250
7,5
EHD
15
250
10
Tensile Strength (min.)Elongation at Break (min.)Tear Resistance (min.)
Derating Factors for Number of Layers on a Reeling Drum
Number of layers
Factor
1
0,84
2
0,65
3
0,45
Derating Factors for AmbientTemperatures (Mining Cables)
Ambient Temperature (°C)
Factor
25
1,10
30
1,00
35
0,90
40
0,80
45
0,70
Based on an initial conductor temperature at 90°C and a final temperatureof 200°C
1 Second Short-circuit Ratings
Cable Size Current Cable Size Current
(mm² ) (kA) (mm² ) (kA)
16
25
35
50
70
2,0
3,1
4,3
6,1
8,5
95
120
150
185
240
11,6
14,6
18,3
22,6
29,3
8.0 OverheadAluminium Conductors
Aluminium conductors have achieved wide acceptance all over the worldfor use in overhead transmission and distribution lines. Generally a steelcore is used with the aluminium to give the conductor mechanicalstrength. This arrangement is termed Aluminium conductor steelreinforced or ACSR. Conductors comprised entirely of aluminium areknown as All aluminium conductors or AAC. These conductors areextensively used for busbars in outdoor substations where spans areshort. All aluminium alloy conductors or AAAC consist of an alloy ofaluminium to give a tensile strength in excess of that of AAC, allowinglonger spans.These conductors are recommended for coastal areas wheresevere corrosion is a problem.
Hard drawn aluminium in H9 temper is used in both ACSR and AAC. Highstrain steel wire is used in ACSR and this is sometimes protected fromcorrosion by an application of grease. Such measures are particularlyadopted when the conductor is intended for use in aggressive environ-ments as encountered in coastal regions.
Aberdare Cables manufacture a wide range of AAC, ACSR and AAAC tocustomers’ requirements or national specifications. The informationcontained in table 8.2 relates to the more popular sizes and standardsunder the following conditions:
50
Sag and tension charts are available on request. The following informationneeds to be supplied:
• Span length
• Maximum design load (45% of UTS if not specified)
• Stringing temperature.
Ambient Temperature
Maximum Conductor Temperature
Wind Speed
Normal Stringing Temperature
Solar Radiation
Solar Absorption Co-efficient
30°C
75°C
0.44 m/s
25°C
0,089 W/cm²
1
Table 8.1 : Current Rating parameters
51
Tab
le 8
.2P
hysi
cal a
nd E
lect
rical
Dat
a fo
r po
pula
r AC
SR
siz
es
Alu
min
ium
(mm
)(m
m)
(N)
(Am
ps)
(/k
m)
W(m
m²)
Ste
el
Tota
l
Sq
uir
rel
Go
ph
er
Fox
Ferr
et
Rab
bit
Min
k
Har
e
Do
g
Wo
lf
Pan
ther
Bea
r
Go
at
12,9
0
16,3
0
22,5
8
25,8
1
32,2
6
38,7
1
64,5
2
64,5
2
96,7
7
129,
00
161,
30
193,
50
6,33
7,08
8,37
9,00
10,0
5
10,9
8
14,1
6
14,1
5
18,1
3
21,0
0
23,4
5
25,9
7
57,7
0
72,2
0
101
117
145
174
289
289
438
588
733
899
27,5
0
34,4
0
48,1
0
55,6
0
69,4
0
82,8
0
138
100
292
391
488
598
85,2
0
107
149
173
214
257
427
389
730
970
1220
1500
8020
9610
1310
0
1520
0
1850
0
2190
0
3600
0
3470
0
6920
0
9080
0
1120
00
1360
00
1,36
77
1,09
33
0,78
22
0,67
66
0,54
26
0,45
46
0,27
33
0,27
33
0,18
28
0,13
63
0,10
93
0,08
91
130
150
190
210
240
260
360
360
470
560
650
730
6/1/
2,11
6/1/
2,36
6/1/
2,79
6/1/
3,00
6/1/
3,35
6/1/
3,66
6/1/
4,72
6/4,
72+7
/1,5
7
30/7
/2,5
9
30/7
/3,0
0
30/7
/3,3
5
30/7
/3,7
1
Co
de
Nam
e
Eq
uiv
al.
Co
pp
er
Are
a
Sta
nd
ing
/w
ire d
iam
.O
vera
llD
iam
ete
rM
ass (
kg
/km
)U
ltim
ate
ten
sile
str
en
gth
DC
resis
tan
ce
at
20°C
Cu
rren
tra
tin
g
52
9.0 Innovatice Products (INTERDAC 3)
Intermediate voltage 3 phase 4 wire 1900/3300V underground supplycable
Construction
Mechanical forces during installation
(a) Use of intermediateVoltage allows increased power transfer over longdistances with smaller conductor sizes, eg for loads typically 25 kVAthis represents a considerable saving when compared to conventionalsystems.
(b) Underground cable - with a specially adapted tractor, the cable can beburied with minimum labour, and thus least cost.
(c) Screened cable construction for ease of fault location.(d) Buried cable results in a“clean” landscape - no poles or overhead lines
to hinder farm vehicles.
The maximum pulling force that should be applied to the conductor ofINTERDAC 3 Cable during installation is 200 kg.
3 Circular stranded plain soft copper conductors,XLPE insulated, layed up with one circularstranded tinned soft copper earthing conductor,collectively screened with an aluminiumpolyethylene laminate (APL) tape, polyethylenesheathed 1900/3300V underground supply cable.
* DC at 20°C** In ground. Soil temperature 25°C. Depth of lay 500 mm.
Soil thermal resistivity 1,2 K.m/W. Operating temperature 90°C
10
1,83
1,83
2,34
80
0,82
16
1,15
1,15
1,47
105
2,29
25
0,73
0,73
0,93
135
3,57
Cable Size (mm²)
Phase Conductor Resistance*
Earth Conductor Resistance*
Impedance (Z)
Current Rating**
1 Second Short Circuit Rating
( /km)
( /km)
( /km)
(A)
(kA)
W
W
W
Table 9.1 : Electrical properties
Phase Conductor Construction (no. x diam.)
Earth Conductor Construction (no. x diam.)
Insulation Thickness (nominal)
Aluminum Screen Thickness
Sheath Thickness (nominal)
Cable Diameter (nominal)
Approximate Cable Mass
Minimum Bending Radius
Cable Size (mm²) 10
7 x 1,33
7 x 1,33
2,1
0,15
1,45
20,5
545
205
16
7 x 1,67
7 x 1,67
2,2
0,15
1,6
21,3
990
210
25
19 x 1,38
19 x 1,38
2,2
0,15
2,0
26,4
1100
260
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
(kg/km)
(mm)
Table 9.2 : Physical properties
The Aberdare Group's product range and services are wide but specialised. Tried andtested and carrying South African Bureau of Standards (SABS) marks and complying withInternational Standards, we stand by our products.
• Screened or belted• Fully impregnated or drained• Copper or Aluminium conductors up to400mm² (3 core) & 1000mm² (singlecore)
• Individually screened• Copper or aluminium conductors up to
300mm² (3 core) & 500mm² (single core)
• Flexible Cable (Types H05 RN-F, H07 RN-F)• Welding Cable• Mining Trailing Cable (Up to 33kV)
• AAC (All Aluminium Conductor)• AAAC (All Aluminium Alloy Conductors)• ACSR (Aluminium Conductor Steel
Reinforced)• PHDC (Plain Hard Drawn Copper)
• PVI Panel Flex (Single Core Flexible Wiring)• HRQ Insulated Wire (High Temperature
Insulated Wire 105°C)• Cabtyre (Flexible Wiring)• Ripcord (Flexible Wiring)• Monster (Flexible Wiring)• Illumination (PVC/ Rubber)• PVI House Wire (Single Core General
Purpose)• Flat Twin & Earth (Innovative Wiring)• Surfix (Innovative Wiring)• Submersible Pump Cable (3 & 4 Core
Flexible)
• Nitrile Trailing Cable (Flexible PVC - 4 Core)• PVC Nitrile Cable (Welding)• General Welding Cable (EPM/CM) &
(EPM/CR)
• PVDAC (Low Voltage PVC Cable)• Multicore (Low Voltage PVC Cable)• ABC (Aerial Bundle Conductor)• Airdac SNE (House Service Connecting
Cable)• Airdac II CNE (House Service Connecting
Cable)• Intermediate Voltage Cable (1,9 / 3,3kV)
• Silicone Cabtyre (Flexible Wiring)• Silicone (Single Core Flexible Wiring)• Special Silicone (Polyester & Glass Fibre
Braided Cable)
• RAYCHEM joints and terminations up to132kV
• RAYCHEM heat shrink tubing and mouldedparts
• RAYCHEM wraparound repair sleeves andcable marking systems
• BOWTHORPE surge arrestors• RAYCHEM & ZIBO insulators
(Distribution and Station class)• AMP wedge technology overhead line
connector systems• SIMEL lugs, ferrules and ABC hardware
including torque shear connectors• DULMISON spacers, dampers, heliformed
fittings• DURACAST low voltage cable jointing kits
and resin systems• ABERDARE cast iron joints for PILC cables
POWER
Paper Insulated Cables up to 42 kV
XLPE Insulated Cables up to 66 kV
Elastomeric Insulated Cables
Overhead Aluminium Conductors
GWI (General Wire Insulated)
Electrodac
Silicone
ACCESSORIES
Product RangeOur Services are Wide but Specialised
53
POSSIBLE SPECIFICATION CHANGES:
Aberdare’s policy of continuous product improvement may result in changes to the finished product, the parameters of which may differ fromthe published parameters in this brochure. Aberdare reserves the right to change product specifications from time to time to effectimprovements and / or enhancements and accepts no liability arising from any differences between the published parameters of this brochureand the finished product, unless by prior written agreement.©ABERDARE CABLES (PTY) LTD. Unauthorised duplication by any means strictly prohibited
www.aberdare.co.za