PRODUCT SPECIFICATION EPB18135 DEP 2014-12-16 Page 1/5 Power Distribution Cable for Signalling Systems Enhanced unarmoured cables Rodent Protected Construction and testing according standards NetworkRail NR/L2/ELP/27408 BS EN 60228 BS 7655-1.3 and BS 7655-4.2 IEC 60502-1 Rated Voltage (1) 0,6/1kV Outer sheath colour BLACK Conductor Identification Brown, Black Marking on the outer sheath On the outer sheath by embossing on two primary lines with the following information (example) : Legend 1 (line 1): CABELTE ELECTRIC CABLE 600/1000 V NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR Railway Catalogue number” Property of Network Rail M.M. Legend 2 (line 2): CABELTE ELECTRIC CABLE 600/1000 V NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR Railway Catalogue number” Property of Network Rail Year - Year of manufacture M.M. - Metric Marking (shall be printed) Line 1 and line 2 are spaced ~180º. The distance between the end of one element of marking and the beginning of the next identical element of marking is ≤ 550mm. (1) - Whilst the rated voltage is 600/1000V, the reinforced insulation thickness permits an insulation level suitable for voltages 1000/1730V (Uo/U). SAC/XLPE/FGT/PVC Circular conductors schematic design Shaped conductors schematic design 1 Conductor Solid Aluminium Conductors (SAC), circular (≤ 35mm 2 ) or shaped (> 35mm 2 ), class 1, according to BS EN 60228. 2 Insulation XLPE type GP 8 according to BS 7655-1.3. The two insulated conductors are stranded. 3 Bedding (only in circular conductors design) PVC. 4 Identification tape Polypropylene tape with a printed legend: “Property of Network Rail CABELTE YEAR”, applied over the stranded cores. Thickness = 50μm | Minimum width = 5mm. 5 Rodent protection Fibreglass tape, helically applied with a minimum overlap of 15%. Weaving design: plain weave 1/1 (272 tex). Nominal thickness of tape = 0,65mm. Optional tape - Polypropylene plastic tape applied under the fiber glass tape, helically with overlap. Nominal thickness of the tape =0,05mm 6 Outer sheath PVC type 9 according to BS 7655-4.2. 7 Fillers PVC. 5 4 2 1 6 4 3 2 1 5 6 7

description

Cable refrence see details

Transcript of Cable refrence see details

Page 1: Cable refrence see details

PRODUCT SPECIFICATION

EPB18135

DEP 2014-12-16 Page 1/5

Power Distribution Cable for Signalling Systems Enhanced unarmoured cables Rodent Protected

Construction and testing according standards

NetworkRail NR/L2/ELP/27408

BS EN 60228 BS 7655-1.3 and BS 7655-4.2

IEC IEC 60502-1

Rated Voltage

(1)

0,6/1kV

Outer sheath colour

BLACK

Conductor Identification

Brown, Black

Marking on the outer sheath

On the outer sheath by embossing on two primary

lines with the following information (example) : Legend 1 (line 1):

CABELTE ELECTRIC CABLE 600/1000 V

NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR

“Railway Catalogue number” Property of Network Rail M.M.

Legend 2 (line 2):

CABELTE ELECTRIC CABLE 600/1000 V

NR/L2/ELP/27408 PVC 2x50 Al YEAR H NMR

“Railway Catalogue number” Property of Network Rail

Year - Year of manufacture

M.M. - Metric Marking (shall be printed)

Line 1 and line 2 are spaced ~180º.

The distance between the end of one element of marking

and the beginning of the next identical element of marking

is ≤ 550mm.

(1) - Whilst the rated voltage is 600/1000V, the reinforced

insulation thickness permits an insulation level suitable for

voltages 1000/1730V (Uo/U).

SAC/XLPE/FGT/PVC

Circular conductors schematic design

Shaped conductors schematic design

1 – Conductor Solid Aluminium Conductors (SAC), circular

(≤ 35mm2) or shaped (> 35mm2), class 1, according to

BS EN 60228.

2 – Insulation

XLPE type GP 8 according to BS 7655-1.3.

The two insulated conductors are stranded.

3 – Bedding (only in circular conductors design)

PVC.

4 – Identification tape

Polypropylene tape with a printed legend: “Property of Network Rail CABELTE YEAR”, applied over the

stranded cores.

Thickness = 50µm | Minimum width = 5mm.

5 – Rodent protection

Fibreglass tape, helically applied with a minimum

overlap of 15%. Weaving design: plain weave 1/1

(272 tex). Nominal thickness of tape = 0,65mm.

Optional tape - Polypropylene plastic tape applied

under the fiber glass tape, helically with overlap.

Nominal thickness of the tape =0,05mm

6 – Outer sheath

PVC type 9 according to BS 7655-4.2.

7 – Fillers

PVC.

5

4

2

1

6

4

3

2

1

5

6

7

Page 2: Cable refrence see details

PRODUCT SPECIFICATION

EPB18135

DEP 2014-12-16 Page 2/5

Technical Characteristics

Cable designation SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC

Voltage U0/U (kV) 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1 0,6/1

Nº of cores x conductor size (mm2) 2x16 2x25 2x35 2x50 2x70 2x95 2x120

Conductor class and material Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1 Al Class 1

Max. cond. dc resist. at 20°C (Ω/km) 1,91 1,20 0,868 0,641 0,443 0,320 0,253

Nominal core to core capacitance (F/km) 0,125 0,141 0,153 0,184 0,217 0,243 0,271

Nominal core to earth capacitance (F/km) 0,130 0,150 0,165 0,179 0,205 0,228 0,247

Zero sequence impedance (Ω/km) (1) 2,50+j2,29 1,59+j2,26 1,16+j2,24 0,87+j2,22 0,62+j2,19 0,46+j2,16 0,37+j2,14

Positive sequence impedance (Ω/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770

Negative sequence impedance (Ω/km) (1) 2,45+j0,100 1,54+j0,0936 1,11+j0,0898 0,82+j0,0864 0,57+j0,0820 0,41+j0,0792 0,32+j0,0770

Inductance (mH/km) 0,319 0,298 0,286 0,275 0,261 0,252 0,245

Reactance (Ω/km) 0,100 0,0936 0,0898 0,0864 0,0820 0,0792 0,0770

Impedance (cos = 0,8) (Ω/km) 1,96 1,23 0,890 0,660 0,457 0,332 0,264

Insulation material XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8 XLPE GP8

Insulation nom. thickness (mm) 2,0 2,0 2,0 2,0 2,0 2,0 2,0

Core identification colours BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK BR-BK

Sheath material PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9 PVC 9

Sheath min. average thickness (mm) 2,4 2,4 2,6 2,7 2,9 3,0 3,2

Rodent protection FGT FGT FGT FGT FGT FGT FGT

Internal identifying tape Yes Yes Yes Yes Yes Yes Yes

Approximate overall diameter (mm) 25 27 29 27 29 32 34

Bend Radius (mm) 200 216 232 216 232 256 272

Weight of cable (kg/km) 660 810 970 810 1010 1220 1450

Maximum drum length (m) (2) 4000 3000 3000 3000 2000 1500 1500

Maximum pulling force – per cond. (daN) 48 75 105 150 210 285 360

BR - Brown

BK - Black

FGT- Fibre Glass Tape

(1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100Ω.m) .

(2) These values may suffer slight changes.

Page 3: Cable refrence see details

PRODUCT SPECIFICATION

EPB18135

DEP 2014-12-16 Page 3/5

Technical Characteristics (cont.)

Cable designation SAC/XLPE/FGT/PVC SAC/XLPE/FGT/PVC

Voltage U0/U (kV) 0,6/1 0,6/1

Nº of cores x conductor size (mm2) 2x150 2x185

Conductor class and material Al Class 1 Al Class 1

Max. cond. dc resist. at 20°C (Ω/km) 0,206 0,164

Nominal core to core capacitance (F/km) 0,307 0,321

Nominal core to earth capacitance (F/km) 0,269 0,284

Zero sequence impedance (Ω/km) (1) 0,32+j2,12 0,26+j2,11

Positive sequence impedance (Ω/km) (1) 0,27+j0,0751 0,21+j0,0738

Negative sequence impedance (Ω/km) (1) 0,27+j0,0751 0,21+j0,0738

Inductance (mH/km) 0,239 0,235

Reactance (Ω/km) 0,0751 0,0738

Impedance (cos = 0,8) (Ω/km) 0,217 0,175

Insulation material XLPE GP8 XLPE GP8

Insulation nom. thickness (mm) 2,0 2,0

Core identification colours BR-BK BR-BK

Sheath material PVC 9 PVC 9

Sheath min. average thickness (mm) 3,4 3,6

Rodent protection FGT FGT

Internal identifying tape Yes Yes

Approximate overall diameter (mm) 36 39

Bend Radius (mm) 288 312

Weight of cable (kg/km) 1680 1950

Maximum drum length (m) (2) 1400 1200

Maximum pulling force – per cond. (daN) 450 555

BR - Brown

BK - Black

FGT- Fibre Glass Tape

(1) Should be take only as approx. value. It is assumed that cable is installed in the ground (earth resistivity 100Ω.m) .

(2) These values may suffer slight changes.

Page 4: Cable refrence see details

PRODUCT SPECIFICATION

EPB18135

DEP 2014-12-16 Page 4/5

Current carrying capacity according to BS 7671:

Page 5: Cable refrence see details

PRODUCT SPECIFICATION

EPB18135

DEP 2014-12-16 Page 5/5

Voltage drop according to BS 7671: