Busbar Protection

90
PROTECTION 2 SUBSTATION SOMPOL C.

Transcript of Busbar Protection

Page 1: Busbar Protection

PROTECTION 2SUBSTATION

SOMPOL C.

Page 2: Busbar Protection

Busbar Protection

Page 3: Busbar Protection

Busbar ProtectionBus arrangement

1. Radial bus2. Main and transfer3. Double breaker double bus4. Ring bus5. Breaker and a half

Page 4: Busbar Protection

Busbar ProtectionMain Bus

DisconnectSwitch

Circuit Breaker

Circuit

Radial bus

Page 5: Busbar Protection

Busbar Protection1. Radial busAdvantages

Lowest costSmall land area requiredEasy to expandSimple to operateSimple protective relay

Page 6: Busbar Protection

Busbar Protection1. Radial busDisadvantages

Low reliabilityLow flexibility of operation for maintenanceBus fault and failure of breaker requires substationbe removed from service

Page 7: Busbar Protection

Busbar Protection

DisconnectSwitch

Circuit Breaker

Circuits

Main Bus

Transfer Bus

TransferCircuit

Breaker(N.O.)

Circuits

N.O

.

N.O

.

N.O

. TransferSwitch

Main and transfer

Page 8: Busbar Protection

Busbar Protection2. Main and transferAdvantages

Small land area requiredEasy to expandIncreased flexibility of operation over radial busAny breaker can be removed from service without an outage

Page 9: Busbar Protection

Busbar Protection 2. Main and transfer Disadvantages Increased cost over radial bus Increased complexity of operation over radial bus Increased complexity of protection over radial bus Low reliability

Page 10: Busbar Protection

DisconnectSwitch

Circuit Breaker

Circuits

Bus No. 1

Bus No. 2

Circuits

Circuit Breaker

Busbar Protection

Double breaker double bus

Page 11: Busbar Protection

Busbar Protection3. Double breaker double busAdvantages

Very high reliabilityVery flexibility operation Any breaker can be removed from service without an outage

Page 12: Busbar Protection

Busbar Protection 3. Double breaker double bus Disadvantages High cost Large land area required Complex protective relaying and control

Page 13: Busbar Protection

Circuit Breaker

Source

Load

Source

Load

Line DisconnectSwitch

DisconnectSwitch

Busbar Protection

Ring bus

Page 14: Busbar Protection

Busbar Protection4. Ring busAdvantages

High reliabilityFlexibility operationLow costAny breaker can be removed from service without outageExpandable to breaker and a half configuration

Page 15: Busbar Protection

Busbar Protection 4. Ring bus Disadvantages Complex protective relaying and control Failed breaker during fault caused outage of one additional circuit

Page 16: Busbar Protection

Line DisconnectSwitch

Main Bus No. 1

Main Bus No. 2

Circuit Breaker

Disconnect Switch

Circuits

Circuits

Busbar Protection

Breaker and a half

Page 17: Busbar Protection

Busbar Protection5. Breaker and a halfAdvantages

Very high reliabilityVery flexibility operation Any breaker can be removed from service without an outage

Page 18: Busbar Protection

Busbar Protection 5. Breaker and a half Disadvantages Large land area required High cost Complex protective relaying and control

Page 19: Busbar Protection

Busbar Protection

Approximate per unit cost Reliability

Radial 1 5Main and transfer 1.2 4Ring bus 1.25 3Breaker and a half 1.45 2Double breaker double bus 1.75 1

Page 20: Busbar Protection

Busbar Protection

Radial bus

Page 21: Busbar Protection

Busbar Protection

Main and transfer

Page 22: Busbar Protection

Busbar Protection

Double breaker double bus

Page 23: Busbar Protection

Busbar Protection

Breaker and a half

Page 24: Busbar Protection

- What kind of bus arrangement in single line diagram 1 and 2 ?

- Where is the zone of protection of 87B1 and 87B2 ?

Practice 0

Page 25: Busbar Protection

Busbar Protection

Criteria of Bus Differential relay (87B) Check the difference current between

the current flow in and out of the protected bus ( vector summation at relay = 0 )

Page 26: Busbar Protection

Busbar Protection

Bus differential has 2 types1. High impedance2. Low impedance

Page 27: Busbar Protection

Busbar ProtectionHigh impedance bus differential

1. Every bay must use same class and CT ratio2. Suitable for non switching substation3. Easy to expand4. Easy to use

Page 28: Busbar Protection

Because of fault current at bus bar is very high, so some CT may saturate and make 87B misoperation on external fault…..

Page 29: Busbar Protection

Assume one CT saturate on external fault

saturateVoltage = 0 at 87B

Page 30: Busbar Protection

CT saturation- Equivalent circuit ( saturate )

E

Ip/n Is

Im

Lm

IfE

saturatesaturateRct

Ip/n Is

EIm = ∞Lm = 0

Rct

Rct

Equivalent circuit = Rct

Page 31: Busbar Protection

Assume one CT saturate on external fault

Rct 87B

Voltage > 0 at 87B

Page 32: Busbar Protection

Ex Calculation of 87BData- 3 phase fault current at bus = 25000 A ( If - 3phase )- 1 phase fault current at bus = 23600 A ( If - 1phase )- CT ratio 2000/5 ( N )- Rct = 1.2 Ω- RL = 1.5Ω ( lead resistance between relay and CT )- Relay setting range ; 175, 225, 275, 325 v- Vk = 800 v

Page 33: Busbar Protection

Vs3 >= ( If / N )* ( Rct + RL ) ; 3 phase fault

Vs1 >= ( If / N )* ( Rct + 2RL ) ; 1phase fault

Setting of 87B ( Vs )

Vs1 = 249.6 v Vs3 = 169.8 v

So set Vs = 325 v;( Vk >= 2Vs )

Page 34: Busbar Protection

- From single line diagram 2, if- 3phase fault =17000 A- 1phase fault = 13000 AWhat is the setting of Vs ?

Practice 1

Page 35: Busbar Protection

Busbar ProtectionLow impedance bus differential

1. Can use difference CT ratio for each bay2. Suitable for switching substation3. Not easy to expand

Page 36: Busbar Protection

Busbar ProtectionFunction of bus differential

Trip all circuit breakers that connected to the fault bus via 86B ( bus differential lockout relay ) and interlock all circuit breakers also.

Page 37: Busbar Protection

From single line diagram 2- Which circuit breaker should be tripped if 87B1

operated?- What is the operating time of 87B?

Practice 2

Page 38: Busbar Protection

Transmission line Protection

Page 39: Busbar Protection

Transmission line protection Since the impedance of a transmission line

is proportional to its length, for distance measurement it is appropriate to use a relay capable of measuring the impedance of a line up to a predetermined point. Such a relay is called distance relay ( 21 ).

Page 40: Busbar Protection

Transmission line protection The basic principle of impedance measurement

( Z ) involves the comparison of the fault current ( I ) with the voltage ( V ) “ seen ” by the relay at the relaying point.

Zr = Vr / Ir

Page 41: Busbar Protection

Transmission line protection

Impedance seen by relay Zr = Zline + Zload

Z load Zr Vr

Z line ZS

Vs

Ir

Relay point

Page 42: Busbar Protection

Transmission line protection

Basic operation of distance relayOperating condition :

Page 43: Busbar Protection

Transmission line protection Since the relay see current via CT and voltage

via VT, so actual impedance that relay seen is :

Z relay = Zr * CT ratio / PT ratio

Page 44: Busbar Protection

Transmission line protection We use R-X diagram to represent the line

impedance:

Z = R + jX Ω

Page 45: Busbar Protection

Relation between rectangular and polar form

R = P cos ƟPolar form

Rectangular form Z = R + jX Ω

X = P sin Ɵ

P Ɵ

P =√ R2 + X2

Ɵ = tan-1 X/R

Page 46: Busbar Protection

Transmission line protection We use R-X diagram to represent the line

impedance:

Z = R + jX Ω

Page 47: Busbar Protection

Transmission line protection

R-X diagram

R

jX

Z1=R1+jX1 Z2=R2+jX2

Load area

P1 Ɵ1 P2 Ɵ2

Ɵ1Ɵ2

Page 48: Busbar Protection

Transmission line protection

Plain impedance

R

jX

Page 49: Busbar Protection

Transmission line protection

Plain impedance has no direction !

Page 50: Busbar Protection

Transmission line protection

Plain impedance with direction

Page 51: Busbar Protection

Transmission line protection jX

Mho

R

Page 52: Busbar Protection

Transmission line protection

Offset mho R

jX

Page 53: Busbar Protection

Transmission line protection Quadrilateral

Page 54: Busbar Protection

Transmission line protection Stepped distance protection - 3 zone of protection, zone1, zone2, zone3 - 3 difference tripping time

A B C Z1A

Z2A Z3A

Z1B

Z1B

Z1C Z2C

Z3C

T2A

T3A

T2C

T2B

T2B

T3C

Page 55: Busbar Protection

Transmission line protection

Zone1 = 85 % line , instantaneous trip Zone2 = 120 % line , delay trip T2 Zone3 = 100 % line+120 % next line delay trip T3

Example criteria

Page 56: Busbar Protection

Ex Calculation of 21Data- Base voltage =115 kV- Base MVA = 100 MVA- CT ratio = 800/5- PT ratio 115/115 kV/V- Conductor type : 477 MCM AAC – 590 A

Page 57: Busbar Protection

Data- Length of line AB = 70 km, line BC = 30 km, line BD = 50 km- Impedance data :

AB : z1= z2 = 9.7 + j29.1 Ωp , z0 = 25.4 + j101 ΩpBC : z1= z2 = 5.8 + j16.9 ΩpBD : z1= z2 = 8 + j25 Ωp

C

A B21 D

Page 58: Busbar Protection

Multiply by 0.16, soAB : z1= z2 = 1.55 + j4.65 Ωs , z0 = 4 + j16.1 Ωs

= 4.91 71.5° Ωs BC : z1= z2 = 0.92 + j2.7 ΩsBD : z1= z2 = 1.28 + j4 Ωs

Setting Zone 1 = 85% line AB = 4.17 71.5° Ωs Zone2 = 120% line AB = 5 71.5° Ωs , 0.5 secZone3 = 100% line AB + 120% line AB = 9.17 71.5° Ωs ,1 sec

Page 59: Busbar Protection

R

jX

A

B

71.5°

zone1

zone2

zone3

Page 60: Busbar Protection

Earth fault compensate

Kn = ( z0 – z1 ) / 3z1

= 2.51 + j11.51 = 11.78 77.6°4.67 + j13.97 14.73 71.5°

= 0.799 6.15°

Page 61: Busbar Protection

From single line diagram 2- Which circuit breaker should be tripped if 21

line 1 operated ( both primary and back up )?- Which circuit breaker should be reclosed?- Where is the zone of protection of 21?

Practice 3

Page 62: Busbar Protection

Transmission line protection Zone1 can over trip due to : - CT, PT error - Impedance data and calculation error - Relay error

So zone1 should not set 100 % line

Page 63: Busbar Protection

Tele Protection

Page 64: Busbar Protection

Transmission line protection Because zone 1 cannot clear fault at the end

of line ( 15 % ), fault must be cleared by zone 2 with delay time T2. Too slow!

To solve this problem ‘ communication system ’is required.

Page 65: Busbar Protection

Transmission line protection Teleprotection scheme 1. Permissive underreach transfer trip ( PUTT )

2. Permissive overreach transfer trip ( POTT )

Page 66: Busbar Protection

Transmission line protection

- Send carrier by zone 1 1. Permissive underreach transfer trip ( PUTT )

- High speed trip ( by pass T2 ) when zone 2 start and carrier received

Page 67: Busbar Protection

Transmission line protection

- Send carrier by zone 2 2. Permissive overreach transfer trip ( POTT )

- High speed trip ( bypass T2 ) when zone 2 start and carrier received

Page 68: Busbar Protection

Transmission line protection

- clear fault 100% line as fast as zone 1Benefit of teleprotection

- on more over trip - also initiate recloser as zone 1

Page 69: Busbar Protection

Transmission line protection Other functions in distance relay * Power swing blocking * Fuse failure * Switch onto fault ( SOTF )

Page 70: Busbar Protection

Transmission line protection Power Swing Blocking distance relay operate by detect impedance in its

zone, and sometime voltage and current in the system are disturb by fault. System impedance also change and if impedance move into relay’s zone, It’s trip. Wrong operation!

Page 71: Busbar Protection

Transmission line protection

To prevent this situation, relay use PSB. By detect rate of change of the impedance, relay will know which one is fault which one is power swing and block itself to trip…

Page 72: Busbar Protection

Transmission line protectionFuse failure

Distance relay calculate impedance by the ratio of voltage to current. If voltage goes to zero, impedance will be zero also. Zero impedance means fault is very close to distance relay and should trip the transmission line.

Page 73: Busbar Protection

Transmission line protectionPT fuse blows can make distance relay see

‘zero impedance’ in spite of no fault in high voltage system. Distance relay use ‘ zero sequence concept’ to protect itself from misoperation

Page 74: Busbar Protection

Transmission line protectionSwitch OnTo Fault ( SOTF )

For safty in transmission line maintenance, the line should be grounded for all 3 phases. Afterfinish the job, sometime ground are forgotten to remove from line. When CB is closed, it closed to fault.

Page 75: Busbar Protection

Transmission line protectionDistance relay use healthy voltage for

reference, so when close into 3 phase fault , no voltage reference at all. It’s possible that all the zones are not trip!. Memory feature is now used to make high speed trip instead. It’s SOTF….

Page 76: Busbar Protection

Transmission line protection Auto recloser relay ( 79 )

- Close circuit breaker after tripped by distance relay( only trip by high speed zone )

- Single or multi shots - Single or three poles - Dead time and reclaim time should be set properly - Helpful for temporary fault

Page 77: Busbar Protection

Trip & reclose

Dead time

Page 78: Busbar Protection

Transmission line protection Synchrocheck relay ( 25 )

- Supervise recloser relay befor close circuit breaker by check voltage level, frequency, and phase angle at both sides of circuit breaker ( sync. Function ,

BH-LH or LL-LB) - Only check voltage level for charge line function

( voltage check Function, BH-LD or DL-LB )

Page 79: Busbar Protection

Back up Protection

Page 80: Busbar Protection

Back up Protection In protection system, each equipment

should have 2 sets of protective relay. One set we call ‘primary protection’ and the another is call ‘back up protection’.

Page 81: Busbar Protection

Back up ProtectionExample :TransformerPrimary – 87K, self protection, Back up – 51T, BFFeederPrimary – 51/51G, Back up – 51T, BF

Page 82: Busbar Protection

Back up ProtectionTransmission linePrimary – zone1, Back up – zone2, zone3

and others distance relay ( 115 kV ), BFPrimary – protection primary, Back up –

protection back up and others distance relay ( 230 kV ) , BF

Page 83: Busbar Protection

Back up ProtectionBus barPrimary – 87B, Back up – zone2, zone3 of

others distance relay at remote end substation ( 115 kV ), BF

Page 84: Busbar Protection

Back up Protection Principle of Breaker failure Measure the duration of fault current from the

instance at which any relay operates to trip circuit breaker. If current is still flowing after preselected time delay, it is considered that the circuit breaker has failed to trip.

Page 85: Busbar Protection

Back up Protection Principle of Breaker failure Normally breaker failure timer should less than

zone 2 timer of distance relay at remote end substation to limit the tripping area only in substation that breaker fail.

Page 86: Busbar Protection

Back up Protection Element of Breaker failure 1. Main protection operate 2. Current detector operate ( 50BF) 3. Breaker fail timer operate ( 62BF) 4. On this function by cut off switch ( BFCO)

Page 87: Busbar Protection

Back up Protection Function of Breaker failure When breaker fail to trip, the tripping and

interlocking of all other circuit breakers connected to the failed circuit breaker will be initiated. Another lockout relay, 86BF, is required.

Page 88: Busbar Protection

From single line diagram 2- If circuit breaker 80722 fail to trip, which circuit

breakers should be tripped?

Practice 4

From single line diagram 1- If circuit breaker 7052 fail to trip, which circuit

breakers should be tripped?

Page 89: Busbar Protection

Question ?

Page 90: Busbar Protection

Have a nice day!

The end