Bus-Bar Protection Schemes Bus-Bar Protection Schemes. 500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme. - Differential Protection For each section of bus- bar. - SF6 Pressure low Trip. 66 and 33 KV. Bus-Bar Protection Scheme. - Differential Protection For each section of bus- bar or Arc protection or Micro switch protection. - SF6 Pressure low Trip. 22 and 11 KV BUS-Bar Protection Scheme. - Arc protection or Micro switches protection. 500, 400, 275, and 220 KV BB section & BB couplers protection scheme. - I.D.M.T Non Directional O/C & E/F Relay. - C.B Fail to Trip. - SF6 Pressure Trip. - Inter Trip (through pilot cable). 132 KV BB section & BB couplers protection scheme. - I.D.M.T Non Directional O/C & E/F Relay. - C.B Fail to Trip.

Transcript of Bus bar protection

Page 1: Bus bar protection

Bus-Bar Protection Schemes

 Bus-Bar Protection Schemes.

•    500, 400, 275, 220 and 132 KV. Bus-Bar Protection Scheme.   - Differential Protection For each section of bus-bar.   - SF6 Pressure low Trip.                                  

•    66 and 33 KV. Bus-Bar Protection Scheme.   - Differential Protection For each section of bus-bar or Arc protection or

Micro switch protection.-         SF6 Pressure low Trip. 

•     22 and 11 KV BUS-Bar Protection Scheme.

   - Arc protection or Micro switches protection.

 •     500, 400, 275, and 220 KV BB section & BB couplers protection scheme.       - I.D.M.T Non Directional O/C & E/F Relay.       - C.B Fail to Trip.       - SF6 Pressure Trip.       - Inter Trip (through pilot cable).

 •     132 KV BB section & BB couplers protection scheme.       - I.D.M.T Non Directional O/C & E/F Relay.       - C.B Fail to Trip.

 •     33 KV BB section & BB couplers protection scheme.        - I.D.M.T Non Directional O/C & E/F Relay. •     11 KV BB section & BB couplers protection scheme.        - I.D.M.T Non Directional O/C & E/F Relay.

 Shunt Reactor Protection Scheme.

275 &132 KV. Shunt Reactor Protection Scheme.•     I.D.M.T Non Direction O/C & E/F relay.

Page 2: Bus bar protection

•     Inter Trip (through pilot cable – SHR connected through cable C.B. “for 132 kV only”).

•     Buchhols Trip.

•     Oil Temperature Trip.

•     Winding Temperature Trip.

•     Cable oil pressure Low Trip. (For cable tails)

•     SF6 pressure Low Trip.

•     C.B Fail to trip. (For 132 KV. C.B only).

 33 KV. Shunt Reactor Protection Scheme for both connected to 33 KV Bus-Bar or to tertiary of 300 MVA Transformer.

•     I.D.M.T Non Direction O/C & E/F relay.•     Buchhols Trip.•     Oil Temperature Trip.•     Winding Temperature Trip.