S&C VistaUnderground Distribution Switchgear
Outdoor Distribution, 15.5 kV through 38 kV
Featuring
Manual,
Remote Supervisory, and
Source-Transfer Models
-
8/3/2019 Bulletin 680-30 - EDOC_001773
2/16
2
Vista Underground Distribution Switchgear Addresses Your Concerns
Areyouwastingmoneyandresourcesontime-
consuming,labor-intensiveroutineoperationofyour
switchgear?
Hascoordinatingupstreamprotectivedeviceswith
downstreamfusingbecomeaheadache?
Areyourcustomerscomplainingthattheydont
wantobtrusivegreenboxesontheirproperty?
S&CsVistaUndergroundDistributionSwitchgear
istheanswertotheseandmanyotherunderground
distributionsystemproblems.S&Cworkedclosely
withelectricutilitiesandpoweruserstoidentifyand
satisfyneedsthatwerenotbeingmetbyconventional
undergrounddistributionequipment.VistaUDSisan
exceptionalproductthatmeetsalloftheseneeds.
VistaUndergroundDistributionSwitchgear
isavailableinmanual,remotesupervisory,and
source-transfermodels.Allmodelsfeatureload-
interrupterswitchesandresettable,vacuumfault
interruptersorarcspinnersinserieswithdisconnect
switches,elbow-connectedandenclosedinasubmersible,SF6-insulated,weldedsteeltank.Vista
UDSisavailablewithuptosixways,inratings
through38kVand25kAsymmetricalshort-circuit.
Largewindowsinthetankprovideaclearviewofthe
opengap,groundposition,andgroundbus.
Remote Supervisory Pad-Mounted Style Vista UDS installation.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
3/16
3
15-kV UnderCover Style Model 422.
Switch terminalsequipped with600-A bushings or 900-A bushings
Bushings and bushing wells arelocated on one side of the gear,reducing operating space requiredfor elbows and cables
Large viewing windows let you seeopen gap and grounded positionson load-interrupter switches and faultinterrupters. Trip indicators are easilychecked too
Optional voltage indicator withliquid-crystal display. You can checkthe integrity of the voltage indicatorby shining a flashlight on the photo-cell-powered test circuit, while placinga gloved finger over the test button.See page 8. No flashlight needed indaylight
Operating panel islocated near grade levelso UnderCover Stylegear is easily operatedfrom a standing position.See page 4
Overcurrent controlreadily programmedwith your PC
Fault interrupterterminalsequippedwith 200-A bushingwells, 600-A bushings,or 900-A bushings
-
8/3/2019 Bulletin 680-30 - EDOC_001773
4/16
4
Compact welded-steel tank protectsswitching and protection components fromthe environment. Stainless-steel constructionstandard in UnderCover Style
Operating panel of Vista UDS gear. Viewing windows, for confirming open gap and grounded position on load-interrupter switches and fault interrupters, are located under hinged covers of voltage indicators.
Pressure gauge(locatedunder window) temperatureand altitude compensated
Operating mechanismsfor switches and faultinterrupterspadlockablein any position
Microprocessor-basedovercurrent controlhoused in watertightenclosure. CTs (not visible)provide power and signal
inputs
Operation selectorprevents inadvertentoperation from closedposition directly togrounded position and
vice versa
Gas-fill port
Theload-interrupterswitchesprovidethree-pole
liveswitchingof600-ampereor900-ampere
three-phasecircuits.Theswitcheshavethree
positions(closed-open-grounded)andprovidea
clearlyvisiblegapwhenopen.The200-ampere,
600-ampere,and900-amperefaultinterrupters
offer40-msfaultclearing,havethree-position
(closed-open-grounded)disconnects,andare
availablewitheithersingle-poleorthree-pole
switching.MostmodelsofVistaUDSusein-series
vacuumfaultinterruptersforfaultclearing.
However,thepopular15-kV,12.5-kAmanualmodels
nowfeaturearc-spinningtechnologyforfault
interruption...reducingtheheightofthetankby
nearlyafoot!
Optional voltage indicatorwith liquid-crystaldisplay. Includes self-test feature
-
8/3/2019 Bulletin 680-30 - EDOC_001773
5/16
5
VistaUDSisavailableinuptosixways.This
meansitcanaccommodateanycombinationofup
tosixbustaps,load-interrupterswitches,orfault
interrupters.Withconventionalpad-mountedgear,
foraloopedfeederwithfourtaps,twounitsofgear
arenecessary.ButwithVistaUDS,onlyonesix-way
unitisneeded.VistaUDSsimplifiesinstallationand
improvesaestheticsbyreducingthenecessary
realestate.
Themodelnumberindicatesthetotalnumberofways,aswellasthenumberofload-interrupterand
fault-interrupterways.Forexample,Model321has
3ways2load-interrupterswitchwaysand1
fault-interrupterway,asshownbelow.
TYPICAL CONFIGURATIONS OF MANUAL AND REMOTE SUPERVISORY VISTA UDS
TYPICAL CONFIGURATIONS OF SOURCE-TRANSFER VISTA UDS
422201
514 624
VT
VT
321
VT
VT
523
VT
VT
532 (split-bus)
321
LOAD
1
LOAD
2
LOAD
3
LOAD
4
LOAD
1
LOAD
2
LOAD
3
LOAD
4
Conventional
pad-mounted
gear
Vista
UndergroundDistribution
Switchgear
-
8/3/2019 Bulletin 680-30 - EDOC_001773
6/16
6
Vista UDS Offers Numerous UnobtrusiveInstallation OptionsOneoptionisthelow-profilepad-mountedstyle.At
15,25,andeven34.5kV,pad-mountedVistaUDSis6
to14inchesshorterthantheaverageSF 6-insulated
gear.AndVistaUDSstotalreal-estaterequirement
islessthanone-thirdthatofatypicalSF 6-insulated
design.ThismeansthatVistaUDSiseasiertositeand
allowsmoreroomforlandscapingoptionsthatfurther
improveaesthetics.VistaUDSsmostinnovativeinstallationofferingis
theUnderCoverstyle.TheUnderCoverstyleisideal
forareaswithstringentreal-estaterestrictionsor
whereaestheticsareextremelyimportant.TheVista
UDSgearisinstalledunderground,butalloperations
areeasilyperformedbyoneoperatoraboveground.
UnderCoverstyleinstallationscanalsosavemoney
byreducingcostsassociatedwithtrenchingandlong
cableruns.
VistaUDSisalsoavailableforfloor-mountedor
wall-mountedvaultinstallations,andinaman-hole
style.Withitscompactdesign,ruggedconstruction,
andinternalvisibleopenpoint,man-holestyleVista
UDSisperfectforapplicationswhereinstallation
spaceislimited.
UnderCover Style.
Vault-Mounted Styleavailable for floor andwall-mounting.
Pad-Mounted Style.
Man-Hole Style.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
7/16
7
1.Rotatetheswitchoperatingshafttotheopen
position,thenconfirmtheopengapthroughthe
largeviewingwindow.SeeFigures1and2.With
ordinaryelbowgear,ontheotherhand,specially
trainedoperatorsneedtoremovetheelbowsfrom
theirbushingsusingashotgunclampsticka
tedioustaskthatmustbecarefullyperformed.See
Figure3.
Vista UDS Operation Is Quicker,Easier, SaferVistaUDSwasspecificallydesignedtosimplify
operatingtasks,enhancesafety,andminimize
thedurationofoutages.VistaUDSiscertified
arc-resistantperIEC298AppendixAA,forcurrents
upto12.5kAsymmetricalfor15cycles(25kA
symmetricalfor15cycles,formodelsrated25kA
short-circuit).Intheeventofaninternalfault,the
enclosurewillretainitsintegrity.JustonepersonisneededtooperateVista
UDS.Theresnoexposuretomediumvoltage.The
procedureissimple:
Figure 3. Operation of typical dead-front gear can beawkward and time-consuming.
Figure 1. Opening load-interrupter switch (or fault
interrupter).
Figure 2. Window cover lifts for viewing switch-bladepositions of load-interrupter switch or fault interrupter.
Fault interrupter furnished on all Vista UDS except 15-kVmanual models.
Groundedpositioncontact
Switch blade inopen position
Closedpositioncontact
Vacuum bottle
Fault interrupter furnished on 15-kV, 12.5-kA manualmodels.
Groundedpositioncontact
Arc-spinningcontact
Closed positioncontact
Switch bladein openposition
-
8/3/2019 Bulletin 680-30 - EDOC_001773
8/16
8
2.Confirmthatthecableisde-energizedsoitcanbe
safelygrounded.Withtraditionalgear,themedium-
voltagecablesmustbetesteddirectlyusinga
clampstick-mountedtester.Butvoltagetestingwith
VistaUDScanbeaccomplishedsimplyandeasily
withouteveraccessingthecables.Simplyusethe
voltageindicatorsshowninFigure4.Thevoltage
indicatorisevenequippedwithaself-testfunction,
soyoucantestthetester.SeeFigure5.
3.Groundthecables.Insteadoftheawkwardtaskof
havingtomovetheelbowstoparkingstands,alongwiththegroundingbushingsorelbows,withVista
UDSyouneedonlyrotatetheswitchoperatingshaft
tothegroundedposition.SeeFigure6.Grounding
caneasilybeconfirmedbylookingthroughthe
viewingwindow.
Thereareevenmorebenefits:Thevoltageindicator
canbefurnishedwithalow-voltagephasingoption.
SeeFigure7.Thisfeatureallowsconfirmationof
properphasingwithouteveraccessingthecables.
VistaUDSallowsfault-locatingandhi-pottingtests
tobeperformedwiththecablesattachedandthe
busenergized.
Photocell forenergizing self-test feature
Test window
Test button
LCD display
Test circuitry can be powered byflashlight or bright sun
Place gloved finger overtest button to begin testing
Figure 4. Voltage indicator.
Figure 5. Testing the voltage indicator.
Figure 6. Grounding load-interrupter switch (or faultinterrupter).
Figure 7. Measuring phase-to-phase voltagePhase1 to Phase 1.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
9/16
9
Overcurrent Controlfor Superior CoordinationVistaUDSutilizesauniquemicroprocessor-based
overcurrentcontrol,housedinawatertightenclosure
mountedonthegear.Theovercurrentcontrol
featuresavarietyofTCC(time-currentcharacteristic)
curveswithselectableinstantaneousanddefinite-
timedelayattributes,forsuperiorcoordinationwith
upstreamprotectivedevicesanddownstreamfusing.
TheparametersfortheTCCcurvesaresetusingapersonalcomputerconnectedtothedataportofthe
overcurrentcontrol.Therearenoknobsordials,
sothesettingscannotbeinadvertentlychangedor
alteredbyunauthorizedpersonnel.Integralcurrent
transformersprovidepowerandcurrentsensing.
Thereisevenaneventrecorderthatcaptures
informationonthelasttwelveoperationsofeach
faultinterrupter.
User-supplied personal computer is attached to the overcurrent control for programming the relay in the field.
Coordinating-speed tap curve with definite-timedelay eliminates miscoordination problemsfrequently encountered with transformer fuses.
1000
Vista TapInterrupter (Phase)Min. Pickup Current: 400ADef. Time Delay: 4 cycle
Phase
Overcurrent Relay
Type: CO-9
Time Dial: 3
Min. Pickup Current:
720ACTI: 0.15 sec.
Transformer-
Primary Fuse
(100E, Standard
Speed)
10
100
.1
1TIME
IN
SECONDS
10
100
1,000
10,000
100,000
CURRENT IN AMPERES
.01
-
8/3/2019 Bulletin 680-30 - EDOC_001773
10/16
10
Remote Supervisory Vista UDSFordistributionautomationapplications,S&Coffers
RemoteSupervisoryVistaUDS.RemoteSupervisory
VistaUDSprovidesautomatedswitchingandfault
protection,andcanalsoperformauto-sectionalizing
withouttrippingthemainbreaker.Automation
featuresarealsoretrofittabletoexistingManualVista
UDS.Motoroperators,currentandvoltagesensors,
andlow-voltagecompartmentareeasilyinstalledin
thefield.
Eachmotoroperatorincludesacontrolboardthat
provideslocalpush-buttonandremoteoperation
betweentheclosed,open,andgrounded
positions.Uptosixcontrolboardscanbe
accommodatedwithinthelow-voltagecompartment,
soanyorallload-interrupterswitchesorfault
interrupterscanbemotoroperated.Themotor
Operatorselector
Padlock featurePosition indicator
Details of motor operator.
15-kV Remote Supervisory Pad-Mounted Style Model 422.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
11/16
11
operatorsmaybebatterypoweredor,optionally,
self-poweredusinginternalvoltagetransformers.
Thelow-voltagecompartmentmayalsocontain
auser-specifiedremoteterminalunitand
communicationdevice,providingacompletely
automatedswitchingandprotectionpackage.
Optionalvoltageandcurrentsensingroundoutthe
RemoteSupervisoryVistaUDSoffering.
AvarietyofRTUshavebeensuccessfully
integratedinRemoteSupervisoryVistaUDS,
including:ACS,HarrisDART,ValmetPoleCAT,
QEI/Quindar,Hathaway/SystemsNorthwest,
MotorolaMOSCAD,andDAQ.
Andthesetransceivershavebeenintegrated:
MetricomUtilinet,MDS,Dymec,H&L,andMotorola.
RTUsandcommunicationdevicesofother
manufacturecanbeaccommodatedtoo;contactyour
nearestS&CSalesOffice.
Details of low-voltage compartment of RemoteSupervisory Vista UDS Model 422.
Push-to-test lamps
Operation counter
Operationpush buttons
Position-indicatinglamps
Connector for portablemotor operator control
Vista motor controls for installation with two motor-operated ways.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
12/16
12
WhenRemoteSupervisoryVistaUDSisfurnished
withanEnergyLine5800SeriesSwitchControl,itcan
beamemberofanIntelliTEAM,usingEnergyLines
revolutionarypeer-to-peercommunications.
IntelliTEAMsoftwaresupportsautomatic
sectionalizingandreconfiguration,significantly
reducingoutagetime.IntelliTEAMspeer-to-peer
communicationnetworkusesdistributedintelligence,
eliminatingtheneedfor,butstillfullysupporting,
aSCADAmasterstation.And,whenRemote
SupervisoryVistaUDSisfittedwithanEnergyLine
switchcontrol,thegearcanbeusedforautomatic
sourcetransfer,withremotecontrolandmonitoring.
RemoteSupervisoryVistaUDSalsoallowstheuser
toremotelytripthevacuumbottlesofanythree-phase
faultinterrupterwayusingexternal,user-specified
relays.Thisadditionalshunt-tripcapabilitypermits
advancedapplicationslikesensitiveearth-groundfault
detection,aswellasprotectiverelayschemesusing
high-speedcommunicationforclosed-loopandopen-
loopsystems.
Portable Motor OperatorLocalmotoroperationofVistaUDSgearisalso
availableforuserswhodonotrequireacomplete
automationpackage.Theportablemotoroperator
includescablingandhand-heldcontrol,allinaneasily
portable,durablecase.
Theoperatoreasilyattachestoanyload-interrupter
switchorsingle-poleorthree-polefaultinterrupter.
Thensimplypluginthepowercableandthecontrol
cable.Thehand-heldcontrolfeaturesopen,close,andgroundpushbuttons,anenablebutton
topreventinadvertentoperation,andaready
indicatinglight.Remote Supervisory Vista UDS with 5800 SeriesSwitch Control.
Vista UDS Portable Motor Operator. Inset shows hand-held control.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
13/16
13
Micro-AT Source-Transfer Control.
Source-Transfer Vista UDSSource-TransferVistaUDSprovidesfullyautomatic
primary-selectiveserviceforone,two,orthree
criticalloadcircuits.Thispackageincludesall
thefeaturesofManualVistaUDS,plustheS&C
Micro-ATSource-TransferControl,three-phase
voltagesensingonsourceways,andinternalpower
providedbyvoltagetransformers.Itisavailablein
common-busandsplit-busconfigurations.
TheMicro-ATSource-TransferControl,locatedin
thelow-voltagecompartment,ensuresahighdegree
ofcritical-loadcontinuitybyminimizinginterruptions
resultingfromthelossofonesource.Excludingthe
intentionaltimedelaytocoordinatewithupstream
protectivedevicesand/ortransitiondwelltime,
transferisachievedin6secondsmaximum.
TheMicro-ATSource-TransferControlutilizes
anadvancedmicroprocessortoperformcontrol
operations,asdirectedbysettingsprogrammed
intothedeviceatthefactoryandinthefield.
Suchsettings,consistingofthecontrolsoperating
characteristicsandvoltage-,current-,andtime-related
operatingparameters,areenteredintothecontrolby
meansofakeypadonthefrontpanel.
Anunbalancedetectionfeaturemaybe
field-programmedintheMicro-ATSource-Transfer
Control.Thisfeatureprotectstheloadsfromany
source-sideopen-phaseconditionatthesamevoltage
astheVistaUndergroundDistributionSwitchgear.
Ifthevoltageunbalanceexceedsapresetreference
levelforaperiodoftimesufficienttoconfirmthat
thelossisnottransient,anoutputsignalisproduced
whichinitiatesautomatictransfertotheothersource.Anovercurrent-lockoutfeaturemaybefurnished
whichpreventsanautomatictransferoperationthat
wouldcloseasourceload-interrupterswitchintoa
fault.Alight-emittingdiodelampindicateswhen
lockouthasoccurred.Testkeysareprovidedfor
simulatinganovercurrentconditiononeachsource.
Case for Vista UDS Portable Operator.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
14/16
14
Standard Three-Phase Ratings123
ApplicableStandard
Amperes, RMS
Frequency,
Hertz
Fault Interrupter Load-Interrupter Switch
Short-
Circuit,Sym.
Main Bus
Continuous
Current7
Continuous,Load
Dropping, andLoad Splitting
(Parallel orLoop
Switching)
456
Fault-Closing,
Sym.
Fault
Inter-rupting,
Sym.
Continuous,
LoadDropping, and
Load Splitting(Parallel or
Loop
Switching)
456
Fault-Closing,
Sym.
Momen-
tary,
Sym.
1 Sec.,Sym.
IEC 50 or 60200 or 630 12 500 12 500 200 or 630 12 500 12 500 12 500 12 500 600
630 25 500 25 000 630 25 500 25 000 25 000 25 000 600
ANSI 50 or 60200 or 630 12 500 12 500 200 or 630 12 500 12 500 12 500 12 500 600
600 25 500 25 000 600 25 500 25 000 25 000 25 000 600
1Refer to the nearest S&C Sales Office for other ratings.
2 IEC ratings have been assigned in accordance with the applicableportions of IEC 265-1 for a Class A switch.
3 ANSI ratings have been assigned in accordance with the applicableportions of ANSI C37.71, C37.72, and C37.73.
4 Fault interrupters and load-interrupter switches are rated 600 amperes(630 amperes IEC) continuous, load dropping, and loop splitting when fur-
nished with 600-ampere bushings (standard for load-interrupter switchesand 25-kA fault interrupters, optional for 12.5-kA fault interrupters). Therating is limited to 200 amperes if 200-ampere bushing wells are used
(standard for 12.5-kA fault interrupters, optional for 12.5-kA load-inter-rupter switches). Models rated 25-kA are only available with 600-amperebushings.
5 Fault interrupters and load-interrupter switches can switch the magne-tizing current of transformers associated with the load-dropping rating. Inaddition, unloaded cable switching ratings are as follows: 10 amperes at
15.5 kV and 20 amperes at 29 kV and 38 kV.
6 900 ampere is also available.
7 1200 ampere is also available.
32,500-ampere peak ten-time duty-cycle rating.
65,000-ampere peak three-time duty-cycle rating. Ten-time duty-cyclefault-clearing rating is 16,000 amperes symmetrical, 41,600 amperes
peak.
-
8/3/2019 Bulletin 680-30 - EDOC_001773
15/16
-
8/3/2019 Bulletin 680-30 - EDOC_001773
16/16
Offi W ld id d
Descriptive Bulletin 680-30June 1, 2004