Building Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary Program Type Classroom Facilities Assistance Program (CFAP) - Regular Setting Suburban Assessment Name Elizabeth Price Elementary (10215) 10-02-14 - EEA Assessment Date (on-site; non-EEA) 2015-01-06 Kitchen Type Full Kitchen Cost Set: 2015 Building Name Elizabeth Price Elementary Building IRN 10215 Building Address 2610 Delmore Street Building City Cuyahoga Falls Building Zipcode 44221 Building Phone (330) 920-3635 Acreage 8.50 Current Grades: K-5 Teaching Stations 23 Number of Floors 1 Student Capacity 293 Current Enrollment 386 Enrollment Date 2009-04-13 Enrollment Date is the date in which the current enrollment was taken. Number of Classrooms 21 Historical Register NO Building’s Principal Mr. John Musat Building Type Elementary Next Page Report Generated at 21 Jul 2015 12:51 Building Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary Page 1

Transcript of Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate...

Page 1: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Building Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary

Program Type Classroom Facilities Assistance Program (CFAP) - Regular

Setting Suburban

Assessment Name Elizabeth Price Elementary (10215) 10-02-14 - EEA

Assessment Date (on-site; non-EEA) 2015-01-06

Kitchen Type Full Kitchen

Cost Set: 2015

Building Name Elizabeth Price Elementary

Building IRN 10215

Building Address 2610 Delmore Street

Building City Cuyahoga Falls

Building Zipcode 44221

Building Phone (330) 920-3635

Acreage 8.50

Current Grades: K-5

Teaching Stations 23

Number of Floors 1

Student Capacity 293

Current Enrollment 386

Enrollment Date 2009-04-13

Enrollment Date is the date in which the current enrollment was taken.

Number of Classrooms 21

Historical Register NO

Building’s Principal Mr. John Musat

Building Type Elementary

Next Page

Report Generated at 21 Jul 2015 12:51Building Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary Page 1

Page 2: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Building Pictures - Cuyahoga Falls City(43836) - Elizabeth Price Elementary(10215)

North elevation photo: East elevation photo:

South elevation photo: West elevation photo:

GENERAL DESCRIPTION

36,585 Total Existing Square Footage

1953,1963 Building Dates

K-5 Grades

386 Current Enrollment

23 Teaching Stations

8.50 Site Acreage

Elizabeth Price Elementary School, which is not on the National Register of Historic Buildings, and originally constructed in 1953, is a one story, 36,585 square foot brick schoolbuilding located in a suburban residential setting. The existing facility features a conventionally partitioned design, and does not utilize modular buildings. The structure of theoverall facility contains a brick veneer on a masonry bearing wall type exterior wall construction, with painted concrete masonry units, glazed block, plaster and metal framedpartitions with gypsum board type wall construction in the interior. The base floor system of the overall facility consists of concrete slab-on-grade type construction. The floorsystem of the Stage Storage areas is wood deck on wood joist type construction. There are no intermediate floors in this single story structure. The roof structure of the overallfacility, except over the Multipurpose space, is 2’’ gypsum plank deck over on steel joist type construction. The roof structure of the Multipurpose space is 2’’ gypsum plank deckover on steel beam type construction. The roofing system of the overall facility, except for over the Kindergarten Classroom, is an asphalt built-up roof with gravel wear coat roofthat was installed in 1999. The roofing system over the Kindergarten Classroom is a granulated asphalt rolled roof that was installed in 1999. The ventilation system of the buildingis adequate to meet the needs of the users. The Classrooms are undersized in terms of the current standards established by the State of Ohio. Physical Education and StudentDining spaces consist of one Multipurpose space. The electrical system for the facility is inadequate. The facility is equipped with a non-compliant security system. The buildinghas a non-compliant automatic and manual fire alarm system. The facility is not equipped with an automated fire suppression system. The building contains asbestos and otherhazardous materials. The overall building is not compliant with ADA accessibility requirements. The school is located on an 8.5 acre site adjacent to residential properties. Theproperty, playgrounds, and play areas are partially fenced for security. Access onto the site is unrestricted. Site circulation is fair. There is dedicated space for school buses to loadand unload on the site, but is not separated from vehicular traffic. Parking for staff, visitors and community events is adequate.

No Significant Findings

Report Generated at 21 Jul 2015 12:51Building Pictures - Cuyahoga Falls City(43836) - Elizabeth Price Elementary(10215) Page 2

Page 3: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Previous Page

Next Page

Report Generated at 21 Jul 2015 12:51Building Pictures - Cuyahoga Falls City(43836) - Elizabeth Price Elementary(10215) Page 3

Page 4: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Building Construction Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215)

Name Year Handicapped Access Floors Square Feet Non OSDM Addition

Original Construction 1953 no 1 32,418 no

Classroom Addition 1963 no 1 4,167 no

Previous Page

Next Page

Report Generated at 21 Jul 2015 12:51Building Construction Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) Page 4

Page 5: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Building Component Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215)

AdditionAuditorium

Fixed Seating

CorridorsAgriculturalEducation

Lab

PrimaryGymnasium

MediaCenter

VocationalSpace

StudentDining

Kitchen NatatoriumIndoorTracks

AdultEducation

BoardOffices

OutsideAgencies

AuxiliaryGymnasium

Original Construction (1953)

4625 4600 735 789

Classroom Addition (1963)

635

Total 0 5,260 0 4,600 735 0 0 789 0 0 0 0 0 0

Master Planning Considerations There is an area of approximately 20,000 SF to the east of the building where a small athletic field is located.

Previous Page

Next Page

Report Generated at 21 Jul 2015 12:51Building Component Information - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) Page 5

Page 6: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Existing CT Programs for AssessmentNext Page

Previous Page

Program Type Program Name Related Space Square Feet

No Records Found

Legend:

Not in current design manual

In current design manual but missing from assessment

Report Generated at 21 Jul 2015 12:51<Untitled> Page 6

Page 7: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Main Assessment Menu - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215)

Building Summary - Elizabeth Price Elementary (10215)

District: Cuyahoga Falls City

Name: Elizabeth Price Elementary

Address: 2610 Delmore Street

Cuyahoga Falls,OH 44221

Bldg. IRN: 10215

County: Summit Area: Northeastern Ohio (8)

Contact: Mr. John Musat

Phone: (330) 920-3635

Date Prepared: 2015-01-06 By: Bernie Merritt

Date Revised: 2015-01-22 By: Dave Gandee

Current Grades K-5 Acreage: 8.50

Proposed Grades N/A Teaching Stations: 23

Current Enrollment 386 Classrooms: 21

Projected Enrollment N/A

Addition Date HA Number of Floors Current Square Feet

Original Construction 1953 no 1 32,418

Classroom Addition 1963 no 1 4,167

Total 36,585

*HA = Handicapped Access

*Rating =1 Satisfactory

=2 Needs Repair

=3 Needs Replacement

*Const P/S = Present/Scheduled Construction

FACILITY ASSESSMENTCost Set: 2015 Rating

Dollar Assessment C

A. Heating System 3 $1,248,280.20 -

B. Roofing 3 $581,880.00 -

C. Ventilation / Air Conditioning 2 $18,292.50 -

D. Electrical Systems 3 $593,774.55 -

E. Plumbing and Fixtures 3 $391,295.00 -

F. Windows 2 $446,608.00 -

G. Structure: Foundation 1 $0.00 -

H. Structure: Walls and Chimneys 2 $225,559.10 -

I. Structure: Floors and Roofs 2 $23,220.00 -

J. General Finishes 3 $1,018,792.10 -

K. Interior Lighting 3 $182,925.00 -

L. Security Systems 3 $104,267.25 -

M. Emergency/Egress Lighting 3 $36,585.00 -

N. Fire Alarm 3 $54,877.50 -

O. Handicapped Access 2 $276,391.00 -

P. Site Condition 2 $401,751.74 -

Q. Sewage System 1 $0.00 -

R. Water Supply 1 $0.00 -

S. Exterior Doors 2 $1,250.00 -

T. Hazardous Material 3 $128,208.50 -

U. Life Safety 3 $152,692.00 -

V. Loose Furnishings 3 $182,925.00 -

W. Technology 3 $482,190.30 -

- X. Construction Contingency /Non-Construction Cost

- $1,600,615.78 -

Total $8,152,380.52

CEFPI Appraisal Summary

Section Points Possible Points Earned Percentage Rating Category

Cover Sheet — — — —

1.0 The School Site 100 72 72% Satisfactory

2.0 Structural and Mechanical Features 200 95 48% Poor

3.0 Plant Maintainability 100 58 58% Borderline

4.0 Building Safety and Security 200 113 57% Borderline

5.0 Educational Adequacy 200 103 52% Borderline

6.0 Environment for Education 200 127 64% Borderline

LEED Observations — — — —

Commentary — — — —

Total 1000 568 57% Borderline

Enhanced Environmental Hazards Assessment Cost Estimates

C=Under Contract

Renovation Cost Factor 104.05%

Cost to Renovate (Cost Factor applied) $8,482,551.93

The Replacement Cost Per SF and the Renovate/Replace ratio are only provided when this summary isrequested from a Master Plan.

Previous Page

Report Generated at 21 Jul 2015 12:51Main Assessment Menu - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) Page 7

Page 8: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Main Assessment Menu - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215)

Original Construction (1953) Summary

District: Cuyahoga Falls City

Name: Elizabeth Price Elementary

Address: 2610 Delmore Street

Cuyahoga Falls,OH 44221

Bldg. IRN: 10215

County: Summit Area: Northeastern Ohio (8)

Contact: Mr. John Musat

Phone: (330) 920-3635

Date Prepared: 2015-01-06 By: Bernie Merritt

Date Revised: 2015-01-22 By: Dave Gandee

Current Grades K-5 Acreage: 8.50

Proposed Grades N/A Teaching Stations: 23

Current Enrollment 386 Classrooms: 21

Projected Enrollment N/A

Addition Date HA Number of Floors Current Square Feet

Original Construction 1953 no 1 32,418

Classroom Addition 1963 no 1 4,167

Total 36,585

*HA = Handicapped Access

*Rating =1 Satisfactory

=2 Needs Repair

=3 Needs Replacement

*Const P/S = Present/Scheduled Construction

FACILITY ASSESSMENTCost Set: 2015 Rating

Dollar Assessment C

A. Heating System 3 $1,106,102.16 -

B. Roofing 3 $516,333.60 -

C. Ventilation / Air Conditioning 2 $16,209.00 -

D. Electrical Systems 3 $526,144.14 -

E. Plumbing and Fixtures 3 $356,126.00 -

F. Windows 2 $424,368.00 -

G. Structure: Foundation 1 $0.00 -

H. Structure: Walls and Chimneys 2 $201,098.60 -

I. Structure: Floors and Roofs 2 $23,220.00 -

J. General Finishes 3 $934,547.80 -

K. Interior Lighting 3 $162,090.00 -

L. Security Systems 3 $92,391.30 -

M. Emergency/Egress Lighting 3 $32,418.00 -

N. Fire Alarm 3 $48,627.00 -

O. Handicapped Access 2 $256,391.00 -

P. Site Condition 2 $363,118.28 -

Q. Sewage System 1 $0.00 -

R. Water Supply 1 $0.00 -

S. Exterior Doors 2 $1,250.00 -

T. Hazardous Material 3 $106,491.80 -

U. Life Safety 3 $139,357.60 -

V. Loose Furnishings 3 $162,090.00 -

W. Technology 3 $427,269.24 -

- X. Construction Contingency /Non-Construction Cost

- $1,440,323.40 -

Total $7,335,966.92

CEFPI Appraisal Summary

Section Points Possible Points Earned Percentage Rating Category

Cover Sheet — — — —

1.0 The School Site 100 72 72% Satisfactory

2.0 Structural and Mechanical Features 200 95 48% Poor

3.0 Plant Maintainability 100 58 58% Borderline

4.0 Building Safety and Security 200 113 57% Borderline

5.0 Educational Adequacy 200 103 52% Borderline

6.0 Environment for Education 200 127 64% Borderline

LEED Observations — — — —

Commentary — — — —

Total 1000 568 57% Borderline

Enhanced Environmental Hazards Assessment Cost Estimates

C=Under Contract

Renovation Cost Factor 104.05%

Cost to Renovate (Cost Factor applied) $7,633,073.58

The Replacement Cost Per SF and the Renovate/Replace ratio are only provided when this summary isrequested from a Master Plan.

Report Generated at 21 Jul 2015 12:51Main Assessment Menu - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) Page 8

Page 9: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Main Assessment Menu - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215)

Classroom Addition (1963) Summary

District: Cuyahoga Falls City

Name: Elizabeth Price Elementary

Address: 2610 Delmore Street

Cuyahoga Falls,OH 44221

Bldg. IRN: 10215

County: Summit Area: Northeastern Ohio (8)

Contact: Mr. John Musat

Phone: (330) 920-3635

Date Prepared: 2015-01-06 By: Bernie Merritt

Date Revised: 2015-01-22 By: Dave Gandee

Current Grades K-5 Acreage: 8.50

Proposed Grades N/A Teaching Stations: 23

Current Enrollment 386 Classrooms: 21

Projected Enrollment N/A

Addition Date HA Number of Floors Current Square Feet

Original Construction 1953 no 1 32,418

Classroom Addition 1963 no 1 4,167

Total 36,585

*HA = Handicapped Access

*Rating =1 Satisfactory

=2 Needs Repair

=3 Needs Replacement

*Const P/S = Present/Scheduled Construction

FACILITY ASSESSMENTCost Set: 2015 Rating

Dollar Assessment C

A. Heating System 3 $142,178.04 -

B. Roofing 3 $65,546.40 -

C. Ventilation / Air Conditioning 2 $2,083.50 -

D. Electrical Systems 3 $67,630.41 -

E. Plumbing and Fixtures 3 $35,169.00 -

F. Windows 2 $22,240.00 -

G. Structure: Foundation 1 $0.00 -

H. Structure: Walls and Chimneys 2 $24,460.50 -

I. Structure: Floors and Roofs 2 $0.00 -

J. General Finishes 3 $84,244.30 -

K. Interior Lighting 3 $20,835.00 -

L. Security Systems 3 $11,875.95 -

M. Emergency/Egress Lighting 3 $4,167.00 -

N. Fire Alarm 3 $6,250.50 -

O. Handicapped Access 2 $20,000.00 -

P. Site Condition 2 $38,633.46 -

Q. Sewage System 1 $0.00 -

R. Water Supply 1 $0.00 -

S. Exterior Doors 2 $0.00 -

T. Hazardous Material 3 $21,716.70 -

U. Life Safety 3 $13,334.40 -

V. Loose Furnishings 3 $20,835.00 -

W. Technology 3 $54,921.06 -

- X. Construction Contingency /Non-Construction Cost

- $160,292.38 -

Total $816,413.60

CEFPI Appraisal Summary

Section Points Possible Points Earned Percentage Rating Category

Cover Sheet — — — —

1.0 The School Site 100 72 72% Satisfactory

2.0 Structural and Mechanical Features 200 95 48% Poor

3.0 Plant Maintainability 100 58 58% Borderline

4.0 Building Safety and Security 200 113 57% Borderline

5.0 Educational Adequacy 200 103 52% Borderline

6.0 Environment for Education 200 127 64% Borderline

LEED Observations — — — —

Commentary — — — —

Total 1000 568 57% Borderline

Enhanced Environmental Hazards Assessment Cost Estimates

C=Under Contract

Renovation Cost Factor 104.05%

Cost to Renovate (Cost Factor applied) $849,478.35

The Replacement Cost Per SF and the Renovate/Replace ratio are only provided when this summary isrequested from a Master Plan.

Report Generated at 21 Jul 2015 12:51Main Assessment Menu - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) Page 9

Page 10: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

A. Heating System

Description: The existing system for the 1953 Original Construction is a natural gas fired heated water boiler type system, installed in 1953, and is in fair topoor condition. The system in the 1963 Addition is an extension of that found in the 1953 Original Construction. 2-pipe vs. 4-pipe designations arenot applicable in this facility, as no central air conditioning is provided. The two (2) cast iron boilers, manufactured by American-Standard, wereinstalled in 1953 and are in poor condition. Heating water is distributed to terminal units consisting of unit ventilators, cabinet heaters, unitheaters, air handlers, and fin tubes. The terminal equipment is original to each addition and is in fair to poor condition. The system does notcomply with the 15 CFM per person fresh air requirements of the Ohio Building Code mechanical code and Ohio School Design Manual. Thepneumatic type system temperature controls are original to each addition, with upgrades in 1999, and are in fair condition. The system does notfeature individual temperature controls in all spaces required by the OSDM. The overall system does not feature any central energy recoverysystems. The facility is not equipped with louvered interior doors to facilitate Corridor utilization as return air plenums. The existing system is notducted, except for the Multi-Purpose Room (Student Dining / Gymnasium), and floor to structural deck heights in the 1953 Original Constructionwill not accommodate the installation of properly sized ductwork for a future Ohio School Design Manual approved system. Floor to structuraldeck heights in the 1964 Addition and the remainder of the 1953 Original Construction will accommodate the installation of properly sizedductwork for a future Ohio School Design Manual approved system. The existing system in the Multi-Purpose Room (Student Dining /Gymnasium) is ducted, but the ductwork cannot be integrated into a possible future system due to arrangement, air volume, and routing ofexisting ductwork. The overall heating system is evaluated as not being in safe and efficient working order, and long term life expectancy of theexisting system is not anticipated. The structure is not equipped with a central air conditioning system. The site does not contain underground fueltanks.

Rating: 3 Needs Replacement

Recommendations: Provide new overall heating, ventilating, and air conditioning system to achieve compliance with Ohio Building Code and Ohio School DesignManual standards. Convert the overall facility, except for the Multi-Purpose Room (Student Dining / Gymnasium) to a ducted system to facilitateefficient exchange of conditioned air. Replace existing ductwork in the Multi-Purpose Room (Student Dining / Gymnasium) to facilitate efficientexchange of conditioned air with pricing included in conversion to ducted system replacement. Provide architectural soffits in the 1953 OriginalConstruction Corridors to accommodate the installation of ductwork, with funding provided in conversion to ducted system replacement.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

HVAC System Replacement:

$26.12sq.ft. Required Required $955,600.20(includes demo of existing system and reconfiguration of piping layout and newcontrols, air conditioning)

Convert To Ducted System

$8.00sq.ft. Required Required $292,680.00(includes costs for vert. & horz. chases, cut openings, soffits, etc. Must be usedin addition to HVAC System Replacement if the existing HVAC system isnon-ducted)

Sum: $1,248,280.20$1,106,102.16 $142,178.04

Natural Gas Fired Heated Water Boilers Unit Ventilator

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 10

Page 11: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

B. Roofing

Description: The roof over the overall facility, except for over the Kindergarten Classroom, is an asphalt built-up roof with gravel wear coat system that wasinstalled in 1999, and is in fair condition. The roof over the Kindergarten Classroom is a granulated asphalt rolled roofing system that wasinstalled in 1999, and is in fair condition. There are no District reports of current leaking. Signs of past leaking were observed during the physicalassessment. Access to the roof was gained by roof access door that is in poor condition. Fall safety protection cages are not required, and arenot provided. There were no observations of standing water on the roof. Metal cap flashings are in fair condition. Roof storm drainage isaddressed through a system of roof drains, which are properly located, and in good condition. The roof is not equipped with overflow roof drains,though they are not required. No problems requiring attention were encountered with any roof penetrations. There are not any covered walkwaysattached to this structure.

Rating: 3 Needs Replacement

Recommendations: The roof over the overall facility requires replacement to meet Ohio School Design Manual guidelines due to condition. The roof access doorrequires replacement due to condition. Install new exterior roof access ladder required for access to upper roof. 10-02-14 Update: Existing roofwas installed over 2 previous roofs. Provide budget for additional roof tear-off. Coping will need replaced as part of roof tear-off and replacement.Provide budget for coping replacement.

Item Cost Unit Whole Building

Original Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Built-up Asphalt: $13.20sq.ft. (Qty)

32,418 Required 4,167 Required $482,922.00

Repair/replace cap flashing and coping:

$18.40ln.ft. 1,200 Required 120 Required $24,288.00

Other: Add Roof Ladder $50.00ln.ft. 10 Required $500.00Provide new roof access ladder forMultipurpose space

Other: Replace Roof Access Door $1,000.00each 1 Required $1,000.00Replace roof access door, frame, andhardware.

Other: Tear-off Additional Roofing System

$2.00sq.ft. (Qty)

32,418 Required 4,167 Required $73,170.00Tear-off Additional Roofing System

Sum: $581,880.00 $516,333.60 $65,546.40

Typical Roof On the Overall Facility Typical Roof With Roof Over the Kindergarten Classroom Beyond

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 11

Page 12: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

C. Ventilation / Air Conditioning

Description: The overall facility is not equipped with a central air conditioning system. Window units are provided in the Principal’s Office, Teacher Lounge,and Administrative Offices locations. The ventilation system in the overall facility consists of unit ventilators, original to each addition and in faircondition, providing fresh air to Classrooms, and unit ventilators and air handlers, original to each addition and in fair condition, providing fresh airto other miscellaneous spaces such as the Multi-Purpose Room (Student Dining / Gymnasium) and Media Center. Relief air venting is providedby transfer grilles from the Classrooms, unit ventilators, air handlers, ceiling plenums, and central relief fans. The ventilation system does notmeet the Ohio Building Code 15 CFM per occupant fresh air requirement. The overall system is not compliant with Ohio Building Code and OhioSchool Design Manual requirements. Dust collection systems are not required in this facility. Exhaust systems for Restrooms, Storage Rooms,Custodial Closets, Maintenance Workrooms, Kitchen Dry Food Storage, Locker Rooms, P.E. Workroom & Storage, and Art Rooms areinadequately placed, and in poor condition. The Art Program is equipped with a kiln located in the Mechanical Room, and the existing kilnventilation system is adequate.

Rating: 2 Needs Repair

Recommendations: Provide an air conditioning system to meet with Ohio Building Code and Ohio School Design Manual requirements. Pricing included in Item A.Replace the existing general building exhaust system.

Item Cost Unit Whole Building

Original Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Other: General Building Exhaust System

$0.50sq.ft. Required Required $18,292.50Replace the existing general building exhaustsystem.

Sum: $18,292.50 $16,209.00 $2,083.50

Window AC Unit Restroom Ventilation System

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 12

Page 13: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

D. Electrical Systems

Description: The electrical system provided to the 1953 Original Construction is a 120/208 volts, 400 amp, 3 phase and 4 wire system installed in 1953, and isin poor condition. The system in the 1964 Addition is an extension of that found in the 1953 Original Construction. Power is provided to the schoolby multiple City of Cuyahoga Falls owned, pad-mounted transformers located in a concrete vault outside the Mechanical Room, and in faircondition. The panel system, installed in 1953, is in poor condition, and cannot be expanded to add additional capacity. The Classrooms are notequipped with adequate electrical outlets. The typical Classroom contains five (5) general purpose outlets, zero (0) dedicated outlets for eachClassroom computer, and zero (0) dedicated outlets for each Classroom television. Some Classrooms are equipped with as many as six (6)general purpose outlets, while others are equipped with as few as thee (3) general purpose outlets. There are not any spaces that have noelectrical outlets. The Corridors are not equipped with adequate electrical outlets for servicing. Adequate GFI protected exterior outlets are notprovided around the perimeter of the building. The facility is not equipped with an emergency generator. Adequate lightning protection safeguardsare not provided. Stage lighting power system including control panel, breakers, and dimmers is inadequately provided, in poor condition anddoes not meet OSDM requirements. The overall electrical system does not meet Ohio School Design Manual requirements in supporting thecurrent needs of the school, and will be inadequate to meet the facility’s future needs.

Rating: 3 Needs Replacement

Recommendations: The entire electrical system requires replacement to meet Ohio School Design Manual guidelines for overall capacity and Classroom capacitydue to age, condition, lack of OSDM-required features, and to accommodate the addition of an air conditioning system. Provide new transformerdue to age and condition, with funding to be coordinated with the City of Cuyahoga Falls owned utility company. Provide an emergencygenerator, with funding included in the electrical system replacement. Provide adequate lightning protection safeguards in the overall facility,including associated grounding system, with funding included in the electrical system replacement.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

System Replacement:

$16.23sq.ft. Required Required $593,774.55(Includes demo of existing system. Includes generator for life safety systems. Does notinclude telephone or data or equipment) (Use items below ONLY when the entiresystem is NOT being replaced)

Sum: $593,774.55 $526,144.14 $67,630.41

Main Electrical Distribution Panel Pad Mounted Transformer Vault

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 13

Page 14: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

E. Plumbing and Fixtures

Description: The service entrance is equipped with two (2) reduced pressure backflow preventers in fair condition. A water treatment system is not provided,though none is needed. The domestic water supply piping in the overall facility is galvanized and copper, is original to each addition, and is in faircondition. The waste piping in the overall facility is cast iron with some galvanized, is original to each addition, and is in fair condition. The facilityis equipped with one (1) A.O. Smith natural gas domestic water boiler, installed in 1994, in fair condition, with one (1) separate 450 gallon storagetank, installed in 1969, and in poor condition. The overall facility contains 2 Large Group Restrooms for boys, 2 Large Group Restrooms for girls,1 Locker Room Restroom for boys, 1 Locker Room Restroom for girls, 0 Locker Room Restrooms for staff, 1 Kitchen Restroom, 1 Health ClinicRestroom, 1 Restrooms associated with Kindergarten / Pre-K Classrooms / Specialty Classrooms, and 2 Restrooms for staff. Boys’ Large GroupRestrooms contain 6 non-ADA wall mounted flush valve toilets, 8 non-ADA (4 wall / 4 floor) mounted (4 flush valve / 4 central flush) urinals, aswell as 4 non-ADA wall mounted lavatories. Girls’ Large Group Restrooms contain 11 non-ADA wall mounted flush valve toilets, as well as 4non-ADA wall mounted lavatories. Boys’ Locker Room Restroom contains 1 non-ADA wall mounted flush valve toilet, 1 non-ADA wall mountedlavatory, as well as 4 non-ADA showers. Girls’ Locker Room Restroom contains 1 non-ADA wall mounted flush valve toilet, 1 non-ADA wallmounted lavatory, as well as 4 non-ADA showers. Staff Restrooms contain 2 non-ADA wall mounted flush valve toilets, as well as 2 non-ADA wallmounted lavatories. Condition of fixtures is fair to poor. The facility is equipped with 2 non-ADA drinking fountains, as well as 1 ADA electric watercooler, in fair to poor condition. Elementary Classrooms are inadequately equipped with the required lavatory mounted type drinking fountains,which are not ADA compliant, and are in fair to poor condition. Special Education Classroom is not equipped with the required Restroom facilities.Kitchen is equipped with the required Restroom which contains 1 non-ADA wall mounted flush valve toilet, as well as 1 non-ADA wall mountedlavatory, and fixtures are in fair to poor condition. Health Clinic is equipped with the required Restroom which contains 1 non-ADA wall mountedflush valve toilet, as well as 1 non-ADA wall mounted lavatory, and fixtures are in fair to poor condition. Kindergarten / Pre-K Classrooms areequipped with Restroom facilities which contain 1 non-ADA floor mounted flush valve toilet, as well as 1 non-ADA wall mounted lavatory, andfixtures are in fair to poor condition. Kitchen fixtures consist of one (1) double-compartment sink and one (1) dishwashing unit with built-in Hatcowater booster heater, which are in fair condition. The Kitchen is not equipped with a satisfactory grease interceptor due to age, condition,insufficient capacity. The Kitchen is not provided the required 140 degree hot water supply. The school meets the OBC requirements for fixtures,except for electric water coolers. Per OBC and OSDM requirements this facility should be equipped with 14 toilets, 4 urinals, 14 lavatories, and 4electric water coolers, and at present it is equipped with 24 toilets, 8 urinals, 15 lavatories, and 1 electric water cooler. ADA requirements are notmet for fixtures and drinking fountains (see Item O). Custodial Closets are properly located and are adequately provided with required servicesink or floor drain sink, which is in fair condition. Science Classroom / Lab utility sinks, gas connections, compressed air connections, and safetyshower / eyewash are not provided, but are not required due to existing grade configuration. Due to existing grade configuration, no Biology orChemistry Classroom acid waste systems are required. CONTINUED

Rating: 3 Needs Replacement

Recommendations: Replace galvanized water supply piping in the overall facility with copper piping due to age and condition. Replace sanitary waste piping in theoverall facility due to age and condition. To facilitate the school’s compliance with OBC and OSFC requirements, provide 13 lavatory mountedtype drinking fountains and 3 new electric water coolers. Due to age, condition, and OSFC standards, replace 8 lavatory mounted type drinkingfountains, 15 lavatories, 24 toilets, 8 urinals, and 1 electric water cooler. See Item O for replacement of fixtures related to ADA requirements. SeeItem J for provisions on Kitchen related equipment. Replace the service entrance reduced pressure back flow preventers due to age andcondition. Replace the domestic hot water boiler and 450 gallon storage tank due to age and condition. Replace the Kitchen grease trapinterceptor due to age, condition, and insufficient capacity. Provide the Kitchen with a water booster heater. Replace the existing Custodial Closetservice sinks due to age and condition.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

Back Flow Preventer: $5,000.00unit 2 Required $10,000.00Domestic Supply Piping: $3.50sq.ft. Required Required $128,047.50(remove / replace) Sanitary Waste Piping: $3.50sq.ft. Required Required $128,047.50(remove / replace) Domestic Water Heater: $5,100.00per

unit 1 Required $5,100.00(remove / replace)

Toilet: $1,500.00unit 24 Required $36,000.00(remove / replace) See Item O Urinal: $1,500.00unit 8 Required $12,000.00(remove / replace) Sink: $1,500.00unit 15 Required $22,500.00(remove / replace) Electric water cooler: $3,000.00unit 4 Required $12,000.00(double ADA) Other: Domestic Hot WaterStorage Tank

$3,000.00per unit

1 Required $3,000.00Replace the domestic 450 gallon hot water storage tank due toage and condition.

Other: Kitchen Grease Trap $5,000.00per unit

1 Required $5,000.00Replace the Kitchen grease trap interceptor due to age,condition, and insufficient capacity.

Other: Kitchen Water Heater $5,100.00per unit

1 Required $5,100.00Provide the Kitchen with a water booster heater.

Other: Lavatory Mounted TypeDrinking Fountain

$1,500.00per unit

9 Required 4 Required $19,500.00To facilitate the school’s compliance with OBC and OSFCrequirements, provide 13 lavatory mounted type drinkingfountains.

Other: Lavatory Mounted TypeDrinking Fountain Replacement

$500.00per unit

8 Required $4,000.00Due to age, condition, and OSFC standards, replace 8 lavatorymounted type drinking fountains.

Other: Service Sink $500.00per unit

2 Required $1,000.00Replace the existing Custodial Closet service sinks due to ageand condition.

Sum: $391,295.00 $356,126.00 $35,169.00

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 14

Page 15: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Floor Mounted Flush Valve Urinals Domestic Hot Water Boiler and Storage Tank

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 15

Page 16: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

F. Windows

Description: The 1953 Original Construction is equipped with thermally broken aluminum frames with double glazed insulated glazing and insulated panel typewindow system, which was installed in 2000, and is in good to fair condition. One window opening in the 1953 Original Construction containsKalwall panels and thermally broken aluminum frames with double glazed insulating glazing, which was installed in 1998, and is in fair condition.The 1963 Addition is equipped with thermally broken aluminum frames with double glazed insulated glazing and insulated panel type windowsystem, which was installed in 2004 and is in good to fair condition. Window system seals are in good condition, with no air and water infiltrationbeing experienced. Window system hardware is in good condition. The window system features surface mounted shades, which are in good tofair condition. The window system is equipped with insect screens on operable windows, which are in good to fair condition. This facility is notequipped with any curtain wall systems. This facility does not feature any glass block windows. The exterior doors in the overall facility areequipped with thermally broken, aluminum frame sidelights and transoms with double glazed insulated glazing, in good condition. The schooldoes not contain skylights. Window security grilles are not provided for ground floor windows. There is no Greenhouse associated with thisschool.

Rating: 2 Needs Repair

Recommendations: Replace broken window glazing as required through the overall facility. Replace damaged insect screens as required through the overall facility.Replace damaged surface mounted window shades as required through the overall facility. Replace 1998 windows and Kalwall panels in the1953 Original Construction. Replace single pane vision panels in exterior doors of the overall facility with approved insulating safety glass.10-02-14 Update: Exterior finish on windows deteriorated and chalking. Operable sashes not working and seals broke. Revise WindowReplacement line item from 0 sf to 6,344 sf at 1953 Original Building and from 0 sf to 288 sf at 1963 Addition.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

Insulated Glass/Panels: $60.00sq.ft. (Qty)

6,344 Required 288 Required $397,920.00(includes blinds)

Other: Replace Damaged Insect Screens

$8.00sq.ft. (Qty)

748 Required 120 Required $6,944.00Replace damaged insect screens as required through theoverall facility.

Other: Replace Damaged SurfaceMounted Blinds

$8.00sq.ft. (Qty)

1,496 Required 240 Required $13,888.00Replace damaged surface mounted window shades asrequired through the overall facility.

Other: Replace DefectiveInsulating Glass Panels

$28.00sq.ft. (Qty)

374 Required 60 Required $12,152.00Replace broken window glazing as required through theoverall facility.

Other: Replace Kalwall Panels $28.00sq.ft. (Qty)

468 Required $13,104.00Replace 1998 windows and Kalwall panels in the 1953Original Construction.

Other: Replace Single PaneExterior Door Vision Panels

$200.00each 11 Required 2 Required $2,600.00Replace single pane vision panels in exterior doors of theoverall facility with approved insulating safety glass.

Sum: $446,608.00 $424,368.00 $22,240.00

Typical Classroom Windows in the 1953 Original Construction Window Opening in the 1953 Original Construction with Kalwall Panels

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 16

Page 17: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

G. Structure: Foundation

Description: The overall facility is equipped with concrete masonry unit foundation walls on concrete footings, which displayed no locations of significantdifferential settlement, cracking, or leaking, and are in good condition. The District reports that there has been no past leaking. No grading or sitedrainage deficiencies were noted around the perimeter of the structure that are contributing or could contribute to foundation / wall structuraldeterioration.

Rating: 1 Satisfactory

Recommendations: Existing conditions require no renovation or replacement at the present time.

Item CostUnitWhole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

SumComments

Sum: $0.00 $0.00 $0.00

Condition of Exterior Wall at Sidewalk Typical Condition of Exterior Wall at Grade

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 17

Page 18: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

H. Structure: Walls and Chimneys

Description: The overall facility has a brick veneer on a masonry bearing wall system, which displayed locations of deterioration, and is in good to faircondition. The exterior masonry does not contain control joints. The school does have sufficient expansion joints, and they are in good condition.The exterior masonry has not been cleaned and sealed in recent years and shows evidence of mortar deterioration and locations ofefflorescence, graffiti and staining. Architectural exterior accent material consists of stone, which is in fair condition. Interior walls are paintedconcrete masonry units, glazed block, plaster and metal framed partitions with gypsum board and are in good to fair condition. Interior masonrydoes not contain control joints. Interior masonry appears to have inadequately spaced and caulked control joints in fair condition. The window sillsin the 1953 Original Construction are an element of the aluminum window system, and are in good condition. The window sills in the 1963Addition are stone and in fair condition. The exterior lintels are steel, and are rusting and in fair condition. The chimney is in fair condition andrequires masonry tuckpointing, cleaning and sealing. Soffits at window openings and building entrances are corrugated transite material typeconstruction, and are in fair to poor condition. A loading dock has not been provided to facilitate unloading of trucks and receipt of product /supplies / foodstuffs. The school does have sufficient expansion joints, and they are in good to fair condition.

Rating: 2 Needs Repair

Recommendations: Provide tuckpointing in all areas of mortar deterioration as required through the overall facility. Provide masonry cleaning, sealing and caulking asrequired through the overall facility. Sawcut and caulk new appropriately spaced control joints in existing masonry through the overall facility. Prepand paint exposed steel lintels through the overall facility. Repoint stone sills in the 1963 Addition. Provide masonry repairs as required throughthe overall facility. Provide masonry infill for existing unit ventilator openings in exterior walls. Replace existing transite soffits in the 1953 OriginalConstruction. Repair masonry chimney as required. H - Structures Walls and Chimneys: 10-02-14 Update: Corrugated Transite Facia atGymnasium East Elevation in disrepair. Replace corrugated facia at Gymnasium North Elevation @ Gymnasium. Lintels @ Gymnasiumdeteriorated. Replace lintels @ gymnasium (40 lf). Significant deterioration of brick veneer @ NE Corner of 1963 Addition. Remove and rebuildNE corner of 1963 Addition (300 sf)

Item Cost Unit Whole Building

Original Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Tuckpointing: $5.25sq.ft. (Qty)

3,640 Required 456 Required $21,504.00(wall surface)

Exterior Masonry Cleaning: $1.50sq.ft. (Qty)

14,564 Required 1,827 Required $24,586.50(wall surface)

Exterior Masonry Sealing: $1.00sq.ft. (Qty)

14,564 Required 1,827 Required $16,391.00(wall surface)

Exterior Caulking: $5.50ln.ft. 4,384 Required 832 Required $28,688.00(removing and replacing) Replace Brick Veneer System: $35.00sq.ft.

(Qty) 300 Required $10,500.00(total removal and replacement including pinning and

shoring) Lintel Replacement: $250.00ln.ft. 40 Required $10,000.00(total removal and replacement including pinning and

shoring) Install Control Joints $60.00ln.ft. 243 Required 96 Required $20,340.00Other: Chimney Repair $15.00sq.ft.

(Qty) 260 Required $3,900.00Repair masonry chimney as required.

Other: Masonry Infill $12.75sq.ft. (Qty)

124 Required 24 Required $1,887.00Provide masonry infill for existing unit ventilatoropenings in exterior walls.

Other: Masonry Repairs $15.00sq.ft. (Qty)

2,185 Required 274 Required $36,885.00Provide masonry repairs as required through the overallfacility

Other: Paint Steel Lintels $5.00sq.ft. (Qty)

707 Required 134 Required $4,205.00Prep and paint exposed steel lintels through the overallfacility.

Other: Prep and Paint Steel Lintels

$8.00sq.ft. (Qty)

707 Required 134 Required $6,728.00Prep and paint exposed steel lintels through the overallfacility.

Other: Replace CorrugatedTransite Facia

$16.80sq.ft. (Qty)

432 Required $7,257.60Replace Corrugated Transite Facia @ Gymnasium EastElevation

Other: Replace Transite Soffits $14.60sq.ft. (Qty)

2,170 Required $31,682.00Replace existing transite soffits in the 1953 OriginalConstruction.

Other: Repoint Stone Window Sills

$7.50ln.ft. 134 Required $1,005.00Repoint stone sills in the 1963 Addition.

Sum: $225,559.10 $201,098.60 $24,460.50

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 18

Page 19: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Exterior Soffits and Walls in the 1953 Original Construction Typical Condition of Stone Window Sill Joints

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 19

Page 20: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

I. Structure: Floors and Roofs

Description: The floor construction of the base floor of the overall facility is concrete slab-on-grade type construction, and is in good condition. There is nocrawl space. The floor construction of the Stage Storage areas is wood deck on wood joist type construction, and is in good condition. There areno intermediate floors in this single story structure. Ceiling to structural deck spaces are sufficient to accommodate HVAC, electrical, andplumbing scopes of work in required renovations. The roof construction of the overall facility, except over the Multipurpose space, is 2’’ gypsumplank deck over on steel joist type construction, and is in good condition. The roof construction of the Multipurpose space is 2’’ gypsum plankdeck over on steel beam type construction, and is in good condition.

Rating: 2 Needs Repair

Recommendations: Provide funding for removal and replacement of non-compliant OBC wood floor structure at the Stage.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Replace Wood Floor System$45.00sq.ft. (Qty) 516 Required $23,220.00Sum: $23,220.00 $23,220.00 $0.00

Typical Roof Structure Of the Overall Facility Non-Compliant OBC Wood Floor Construction

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 20

Page 21: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

J. General Finishes

Description: The overall facility features conventionally partitioned Classrooms with VAT and VCT flooring, acoustical tile ceilings, as well as glazed andpainted block wall finishes, and they are in fair to poor condition. The overall facility has Corridors with terrazzo flooring, acoustical tile ceilings, aswell as plaster and glazed block wall finishes, and they are in fair condition. The overall facility has Restrooms with terrazzo flooring, plasterceilings, as well as glazed block wall finishes, and they are in fair to poor condition. Toilet partitions are metal, and are in poor condition.Classroom casework in the overall facility is wood type construction with plastic laminate tops, is inadequately provided, and in poor condition.The typical Classroom contains 8 lineal feet of casework, and Classroom casework provided ranges from 4 to16 feet. Classrooms are providedadequate chalkboards, markerboards, and tackboards, which are in fair condition. The lockers, located in the Corridors, are adequately provided,and in fair condition. The Classroom storage cubbies, located in the Classroom, are adequately provided, and in poor condition. The Art programis equipped with a kiln located in the Boiler Room in fair condition, and existing kiln ventilation is adequate. The facility is equipped with woodnon-louvered interior doors that are partially recessed without proper ADA hardware and clearances, and in fair to poor condition. TheGymnasium space has VCT flooring, acoustical tile ceilings, as well as glazed and painted block wall finishes, and they are in fair to poorcondition. Gymnasium telescoping stands are wood type construction in fair to poor condition. Gymnasium basketball backboards are fixed type,and are in fair to poor condition. The Media Center, located in the 1953 Original Construction, has carpet flooring, acoustical tile ceilings, as wellas painted block, glazed block and gypsum board partitions wall finishes, and they are in fair condition. Student Dining shares the Gymnasiumspace. OSDM-required fixed equipment for Stage is inadequately provided, and in fair to poor condition. The existing Kitchen is full service, isundersized based on current enrollment, and the existing Kitchen equipment, installed in 1953 with incremental upgrades, is in fair to poorcondition. The Kitchen hood is in poor condition, and is not equipped with the required UL 300 compliant wet chemical fire suppression system.The required 6’’ overhang on all three exposed sides of the cooking equipment is not provided by the hood. Kitchen hood exhaust ductwork is notof proper construction material and/or installed as required by the OSDM and OBMC. Reach-in coolers and freezers are located within theKitchen spaces, and are in fair condition.

Rating: 3 Needs Replacement

Recommendations: Provide complete replacement of finishes and casework due to installation of systems outlined in Items A, C, D, E, I, K, L, M, N, T, U, and due tocondition. Provide for the replacement of interior doors due to condition. Other doors are funded in Item O due to opening expansion. Provide forthe replacement of Kitchen equipment due to age and condition. Provide for the replacement of the Kitchen exhaust hood due to age andcondition. Provide for the replacement of toilet partitions due to condition. Provide for the replacement of toilet accessories due to condition.Provide for the replacement of Gymnasium seating due to condition. Provide for the replacement of Basketball goals due to condition. J - GeneralFinishes: 10-02-14 Update: Exterior walls are 8’’ block with 4’’ clay fired brick and no air cavity or insulation. Provide insulation of exterior walls tomeet LEED energy requirements.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

Complete Replacement ofFinishes and Casework (Elementary):

$15.90sq.ft. Required Required $581,701.50(elementary, per building area, with removal of existing)

Toilet Partitions: $1,000.00per stall

22 Required $22,000.00(removing and replacing)

Toilet Accessory Replacement $0.20sq.ft. Required $6,483.60(per building area) Door, Frame, and Hardware: $1,300.00each 21 Required 4 Required $32,500.00(non-ADA) Basketball Backboard Replacement

$6,500.00each 2 Required $13,000.00(electric)

Bleacher Replacement $110.00per seat

386 Required $42,460.00(based on current enrollment)

Kitchen Exhaust Hood: $56,000.00per unit

1 Required $56,000.00(includes fans, exhaust & ductwork)

Total Kitchen Equipment Replacement:

$190.00sq.ft. (Qty)

789 Required $149,910.00(square footage based upon only existing area of food preparation,serving, kitchen storage areas and walk-ins. Includes demolitionand removal of existing kitchen equipment)

Other: Insulation for Exterior Walls

$7.00sq.ft. (Qty)

14,564 Required 1,827 Required $114,737.00Furring of exterior walls to meet LEED energy requirements(includes furring, insulation and abuse resistant GWB up to roofdeck)

Sum: $1,018,792.10$934,547.80 $84,244.30

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 21

Page 22: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Typical Corridor Finishes Lockers located in the Corridors

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 22

Page 23: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

K. Interior Lighting

Description: The typical Classrooms in the 1953 Original Construction are equipped with some T-8 1x4 suspended and T-8 2x4 lay-in direct fluorescentfixtures with single level switching. Classroom fixtures are in fair condition, providing an average illumination of 58 FC, thus complying with the 50FC recommended by the OSDM. The typical Classrooms in the 1964 Addition are equipped with T-8 1x4 surface mount fluorescent fixtures withsingle level switching. Classroom fixtures are in fair condition, providing an average illumination of 38 FC, which is less than the 50 FCrecommended by the OSDM. The typical Corridors in the overall facility are equipped with T-8 1x4 lay-in direct fluorescent fixtures with singlelevel switching. Corridor fixtures are in fair to poor condition, providing an average illumination of 10 FC, which is less than the 20 FCrecommended by the OSDM. The Multi-Purpose Room (Student Dining / Gymnasium) spaces are equipped with recessed and surface mountmetal halide type lighting, in poor condition, providing an average illumination of 20 FC, which is less than the 50 FC recommended by theOSDM. The Media Center is equipped with T-8 2x4 lay-in direct fluorescent fixture type lighting in fair condition, providing an average illuminationof 61 FC, thus complying with the 50 FC recommended by the OSDM. The Student Dining and Gymnasium spaces are incorporated into theMulti-Purpose Room (Student Dining / Gymnasium). The Kitchen spaces are equipped with T-8 2x4 lay-in direct fluorescent fixture type lightingwith single level switching. Kitchen fixtures are in good condition, providing an average illumination of 76 FC, thus complying with the 75-80 FCrecommended by the OSDM. The Service Areas in the overall facility are equipped with incandescent and T-8 1x4 surface mount fluorescentfixture type lighting in fair condition, providing inadequate illumination. The typical Administrative spaces in the overall facility are equipped withT-8 2x4 lay-in direct fluorescent fixture type lighting in good condition, providing adequate illumination based on OSDM requirements. The overalllighting systems of the facility are not compliant with Ohio School Design Manual requirements due to age, condition, inadequate lighting levels,lack of multi-level switching, and the utilization of incandescent fixtures.

Rating: 3 Needs Replacement

Recommendations: Provide complete replacement of lighting system due to age, condition, inadequate lighting levels, lack of multilevel switching, the utilization ofincandescent fixtures, and installation of systems outlined in Items A, C, J, and U.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Complete Building Lighting Replacement$5.00sq.ft. Required Required $182,925.00Includes demo of existing fixtures Sum: $182,925.00 $162,090.00 $20,835.00

Corridor Fluorescent Light Fixtures Multi-Purpose Room (Student Dining / Gymnasium) Light Fixtures

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 23

Page 24: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

L. Security Systems

Description: The overall facility contains a Honeywell motion sensor and door contact type security system in fair to poor condition. Motion detectors areinadequately provided in main entries, central gathering areas, offices, main Corridors, and spaces where 6 or more computers are located.Exterior doors are adequately equipped with door contacts. An automatic visitor control system is not provided. Compliant color CCTV camerasare not provided at main entry areas, parking lots, central gathering areas, and main Corridors. A compliant computer controlled access controlsystem integrating alarms and video signals, with appropriate UPS backup, is not provided. The system is not equipped with card / biometricreaders. The security system is inadequately provided throughout, and the system is not fully compliant with Ohio School Design Manualguidelines. Existing playground fencing is not fully compliant with Ohio School Design Manual guidelines. The exterior site lighting system isequipped with surface mounted HID high pressure sodium / mercury vapor entry lights in fair condition. Pedestrian walkways are not illuminated.Parking and bus pick-up / drop off areas are not illuminated. The exterior site lighting system provides inadequate coverage.

Rating: 3 Needs Replacement

Recommendations: Provide complete replacement of security system to meet Ohio School Design Manual guidelines. Provide complete replacement of exterior sitelighting system to meet Ohio School Design Manual guidelines. Provide additional playground fencing to meet Ohio School Design Manualguidelines, funding included in complete replacement of security system.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Security System: $1.85sq.ft. Required Required $67,682.25(complete, area of building) Exterior Site Lighting:$1.00sq.ft. Required Required $36,585.00(complete, area of building) Sum: $104,267.25 $92,391.30 $11,875.95

Security System Motion Detection Device Surface Mounted HID High Pressure Sodium / Mercury Vapor Light Fixture

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 24

Page 25: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

M. Emergency/Egress Lighting

Description: The overall facility is equipped with an emergency egress lighting system consisting of non compliant plastic construction exit signs, as well asOSDM compliant red lettered, cast aluminum construction, and LED illuminated exit signs and the system is in fair condition. The facility is notadequately equipped with emergency egress floodlighting and the system is in fair to poor condition. The system is not provided with appropriatebattery backup and emergency generator on separate circuits. The system is inadequately provided throughout, and does not meet Ohio SchoolDesign Manual and Ohio Building Code requirements.

Rating: 3 Needs Replacement

Recommendations: Provide complete replacement of emergency / egress lighting system to meet Ohio School Design Manual guidelines.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Emergency/Egress Lighting:$1.00sq.ft. Required Required $36,585.00(complete, area of building) Sum: $36,585.00 $32,418.00 $4,167.00

Compliant Illuminated Exit Sign Emergency Egress Light Fixture

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 25

Page 26: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

N. Fire Alarm

Description: The overall facility is equipped with an addressable Gamewell Flex 610 fire alarm system, installed in 1999, and in good to fair condition,consisting of manual pull stations, smoke detectors, and horn and strobe indicating devices. The system is automatic and is monitored by a thirdparty. The system is not equipped with sufficient audible horns, strobe indicating devices, and smoke detectors. The system is not equipped withany flow switches,tamper switches, or heat sensors. The system thus will not support future fire suppression systems. The system is notadequately provided throughout, and does not have additional zone capabilities. The system is not fully compliant with Ohio Building Code,NFPA, and Ohio School Design Manual requirements.

Rating: 3 Needs Replacement

Recommendations: Provide complete replacement of fire alarm system to meet OBC, NFPA, and Ohio School Design Manual guidelines.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Fire Alarm System:$1.50sq.ft. Required Required $54,877.50(complete new system, including removal of existing) Sum: $54,877.50 $48,627.00 $6,250.50

Fire Alarm System Horn and Strobe Indication Device Fire Alarm System Smoke Detection Device

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 26

Page 27: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

O. Handicapped Access

Description: At the site, there is an accessible route provided from the public right-of-way, the accessible parking areas, and from the passenger unloadingzone to the main entrance of the school. There is an accessible route connecting all or most areas of the site. The exterior entrances are ADAaccessible. Access from the parking / drop-off area to the building entries is not compromised by steps or steep ramps. Adequate handicapparking is provided. Exterior doors are equipped with ADA hardware. The main entry is not equipped with an ADA power assist door. Playgroundlayout and equipment are mostly compliant. On the interior of the building, space allowances and reach ranges are not compliant. There is anaccessible route through the building which does include protruding objects. Ground and floor surfaces are compliant. Steps do not meet all ADArequirements, and are insufficient due to handrails and space allowances at entries to steps. Elevation changes within the overall facility arefacilitated by non-compliant steps at the stage in fair condition. Access to the Stage is not facilitated by a chair lift or ramp. Interior doors of theoverall facility are semi- recessed, are not provided adequate clearances, and are not provided with ADA-compliant hardware. 11 ADA-complianttoilets are required, and none are currently provided. 11 ADA-compliant lavatories are required, and none are currently provided. 3ADA-compliant urinals are required, and 2 are currently provided. No ADA-compliant showers are required for this grade level, and none arecurrently provided. Two ADA-compliant electric water coolers are required, and one is currently provided. Toilet partitions are metal, and do notprovide appropriate ADA clearances. ADA-compliant accessories are not adequately provided and mounted. Mirrors do meet ADA requirementsfor mounting heights. Sink base casework in the Classrooms do not meet ADA clearances. Health Clinic, Kitchen, Staff and KindergartenRestrooms are not compliant with ADA requirements due to lack of clearances and ADA accessories. A Special Education Restroom is notprovided. ADA signage is provided on both the interior and the exterior of the building.

Rating: 2 Needs Repair

Recommendations: Provide an ADA-compliant power assist door opener, 1 chair lift, 1 electric water cooler, 6 toilets, 6 sinks, 1 urinal, 6 toilet accessories, 27 doorsand frames in the overall facility to facilitate the school’s meeting of ADA requirements. Add new ADA compliant handrails at steps to the Stage.Provide funding for removal of existing glazed block screen walls in both Student Locker Restrooms. Enlarge and reconfigure 4 new single ADAToilet Rooms for the Kitchen, Health Clinic, Staff, and Kindergarten, including 4 toilets, 4 sinks and 4 sets of ADA accessories. Add 1 new singleADA Toilet Room for the Special Education Classroom, including 1 toilet, 1 sink, and 1 set of ADA accessories. Toilet partitions issues arecorrected in Item J. ADA compliant sink base casework in the Classrooms are corrected in Item J. For interior doors that are not being replacedunder this Item, door hardware to be replaced with funding provided in Item J. 10-02-14 Update: Change handicapped restroom conversionallowance from $10,000 for each restroom to $16,761.00 for each restroom. Add Allowance of $25,707.00 for converting space to handicappedaccessible Family Restroom.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

Lifts: $15,000.00unit 1 Required $15,000.00(complete) Electric Water Coolers: $1,800.00unit 1 Required $1,800.00(replacement double ADA) Toilet/Urinals/Sinks: $1,500.00unit 13 Required $19,500.00(replacement ADA) ADA Assist Door & Frame: $7,500.00unit 1 Required $7,500.00(openers, electrical, patching, etc) Replace Doors: $5,000.00leaf 23 Required 4 Required $135,000.00(rework opening and corridor wall to accommodate ADA

standards when door opening is set back from edge of corridorand cannot accommodate a wheelchair.)

Provide Toilet Accessories: $1,000.00per restroom

4 Required $4,000.00

Other: Add Accessible Family Restroom

$25,707.00each 1 Required $25,707.00Add Family Rest Room to meet ADA requirements (includesfixtures, walls, door and hardware, floor drain, and supply linesfrom nearby existing Restroom).

Other: Add Handrails $20.00ln.ft. 42 Required $840.00Add/Replace ADA Compliant handrails at the steps to theStage

Other: Enlarge existingRestroom to meet ADArequirements

$16,761.00each 4 Required $67,044.00Enlarge existing Restroom to meet ADA requirements

Sum: $276,391.00 $256,391.00 $20,000.00

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 27

Page 28: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Narrow Opening and Steps At the Stage Drinking Fountain and Staff Toilet

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 28

Page 29: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

P. Site Condition

Description: The 8.5 acre relatively flat site is located in a suburban residential setting with moderate tree, shrub, floral landscaping. There are no outbuildings.There are no apparent problems with erosion or ponding. The site is bordered by lightly traveled city streets. A single entrance onto the siteimpedes proper separation of bus and other vehicular traffic, and one way bus traffic is provided. A bus loop is provided for student loading andunloading, although it is not separate from the staff and visitor parking. Staff and visitor parking is facilitated by an asphalt parking lot in poorcondition, containing 44 parking places, which provides adequate parking for staff members, visitors, and the disabled. The site and parking lotdrainage design, consisting of sheet drainage and catch basins, provides adequate evacuation of storm water, and no problems with parking lotponding were observed. Concrete curbs are not located as required. Concrete sidewalks are properly sloped, are located to provide a logical flowof pedestrian traffic, and are in fair condition. Trash pick-up and service drive pavement is heavy duty and is in fair condition, and is not equippedwith a concrete pad area for dumpsters. There are no exterior steps or handrails associated with this facility. Site fencing is partially provide,however the Playground and athletic fields are not separated from vehicular traffic. The playground equipment is primarily constructed of coatedsteel and high density plastic, is in good to fair condition, with some in fair to poor condition, placed to provide compliant fall zones, and on acompliant mulch soft surface of insufficient depth, with a basketball court being provided on an asphalt surface. The playground area is equippedwith sufficient benches in fair condition. The athletic facilities are comprised of a baseball field and a small multi-purpose field, and are in goodcondition. Site features are suitable for outdoor instruction, which is enhanced through the District’s provision of benches. There is an area ofapproximately 20,000 SF to the east of the building where a small athletic field is located.

Rating: 2 Needs Repair

Recommendations: Provide a new concrete dumpster pad. Provide for the replacement of the asphalt pavement due to condition. Replace concrete sidewalks asrequired due to condition. Add concrete curbs as required to provide proper separation of pedestrian and vehicular traffic. Provide additionalPlayground mulch as the soft surface material to allow for a sufficient depth. Provide site contingency allowances for unforeseen conditions.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

Replace Existing Asphalt Paving (heavy duty): $30.60sq. yard 7,478 Required 924 Required $257,101.20(including drainage / tear out for heavy dutyasphalt)

Concrete Curb: $18.00ln.ft. 303 Required 37 Required $6,120.00(new) Concrete Sidewalk: $4.69sq.ft.

(Qty) 192 Required 24 Required $1,013.04(5 inch exterior slab)

Provide Soft Surface Playground Material: $30.00sq. yard 897 Required 111 Required $30,240.00Provide Concrete Dumpster Pad: $2,400.00each 1 Required $2,400.00(for two dumpsters) Base Sitework Allowance for Unforeseen Circumstances

$50,000.00allowance Required $50,000.00Include this and one of the next two. (Applies forwhole building, so only one addition should havethis item)

Sitework Allowance for UnforeseenCircumstances for buildings between 0 SFand 100,000 SF

$1.50sq.ft. Required Required $54,877.50Include this one or the next. (Each additionshould have this item)

Sum: $401,751.74 $363,118.28 $38,633.46

Playground Equipment Sitting Area

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 29

Page 30: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

Q. Sewage System

Description: The sanitary sewer system is tied in to the city system, and is in good to fair condition. No significant system deficiencies were reported by theschool district or noted during the physical assessment.

Rating: 1 Satisfactory

Recommendations: Existing conditions require no renovation or replacement at the present time.

Item CostUnitWhole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

SumComments

Sum: $0.00 $0.00 $0.00

Sanitary Waste Piping Kitchen Grease Trap Interceptor

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 30

Page 31: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

R. Water Supply

Description: The domestic water supply system is tied in to the city system, features 3" service and 1 1/2" water meter, and is in fair condition. The District wasnot able to provide water supply flow test data. The existing domestic water service appears to meet the facility’s current needs. The facility is notequipped with an automated fire suppression system, and the existing water supply will not provide adequate support for a future system. Thedomestic water service is not equipped with a water booster pump, and none is required. The system does not provide adequate pressure andcapacity for the future needs of the school.

Rating: 1 Satisfactory

Recommendations: Provide a new city water supply line of adequate capacity to support the existing needs of the facility, as well as a future automated firesuppression system. Funding provided in Item U.

Item CostUnitWhole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

SumComments

Sum: $0.00 $0.00 $0.00

Incoming Domestic Water Service Line Incoming Domestic Water Service Meter

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 31

Page 32: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

S. Exterior Doors

Description: Typical exterior doors in the overall facility are hollow metal type construction, installed on hollow metal frames, and in fair condition. Typicalexterior doors feature single glazed tempered glass or no vision panels. Entrance doors in the overall facility are aluminum FRP typeconstruction, installed on aluminum frames, and in good condition. Entrance doors feature single glazed tempered glass vision panels. There areno overhead doors in the facility.

Rating: 2 Needs Repair

Recommendations: Paint all exterior hollow metal doors and frames. Replacement of single glazed door vision panels is addressed in Item F.

Item Cost Unit Whole Building

Original Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Other: Prep and Paint Exterior Hollow Metal Doorsand Frames

$250.00each 5 Required $1,250.00Paint all exterior hollow metal doors andframes.

Sum: $1,250.00 $1,250.00 $0.00

Main Entry Doors to the 1953 Original Construction Exterior Hollow Metal Doors in the 1953 Original Construction

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 32

Page 33: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

T. Hazardous Material

Description: The School District did not provided an AHERA three year reinspection reports, or other documents regarding hazardous materials. An EnhancedEnvironmental Hazards Assessment (EEHA) will need to be conducted in order to establish abatement budgets. Vinyl asbestos floor tile andmastic and ceiling tile containing hazardous materials are located in the overall facility in fair condition. These materials were open to observationand found to be in non-friable condition with light damage. There are no underground storage tanks on the site. Due to the construction date,there is a potential for lead based paint. Fluorescent lighting will require special disposal.

Rating: 3 Needs Replacement

Recommendations: Remove all hazardous materials, inclusive of asbestos-containing materials in the overall facility, as noted in the attached Environmental HazardsAssessment. Provide for the testing of paint that has the potential of being lead-based. Provide for disposal of fluorescent lighting.

Item Cost Unit Whole Building

OriginalConstruction (1953)32,418 ft²

ClassroomAddition (1963)4,167 ft²

Sum Comments

Environmental Hazards Form EEHA Form EEHA Form —Breeching Insulation Removal $10.00sq.ft.

(Qty) 75 Required 0 Required $750.00

Estimated Cost For Abatement Contractor toPerform Lead Mock-Ups

$1.00per unit 5,000 Required 0 Required $5,000.00

Special Engineering Fees for LBP Mock-Ups $1.00per unit 5,000 Required 0 Required $5,000.00Fluorescent Lamps & Ballasts Recycling/Incineration

$0.10sq.ft. (Qty)

32,418 Required 4,167 Required $3,658.50

Pipe Insulation Removal $10.00ln.ft. 700 Required 0 Required $7,000.00Pipe Fitting Insulation Removal $20.00each 50 Required 0 Required $1,000.00Pipe Insulation Removal (Hidden in Walls/Ceilings)

$15.00ln.ft. 650 Required 100 Required $11,250.00

Dismantling of Boiler/Furnace/Incinerator $2,000.00each 2 Required 0 Required $4,000.00Fire Door Removal $100.00each 2 Required 0 Required $200.00See S Non-ACM Ceiling/Wall Removal (for access) $2.00sq.ft.

(Qty) 3,600 Required 400 Required $8,000.00See J

Resilient Flooring Removal, Including Mastic $3.00sq.ft. (Qty)

20,000 Required 3,100 Required $69,300.00See J

Carpet Removal (over RFC) $1.00sq.ft. (Qty)

350 Required 0 Required $350.00See J

Acoustical Tile Mastic Removal $3.00sq.ft. (Qty)

0 Required 3,100 Required $9,300.00

Sink Undercoating Removal $100.00each 0 Required 4 Required $400.00Other: EHA Other Hazard $1.00per unit 3,000 Required $3,000.00XRF testing for lead-based paint is recommended

for compliance with EPA’s RRP Program. Sum: $128,208.50 $106,491.80 $21,716.70

VAT Ceiling Tile

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 33

Page 34: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

U. Life Safety

Description: The overall facility is not equipped with an automated fire suppression system. Exit corridors are situated such that dead-end corridors are notpresent. Stair towers and guardrails are not present in this single story structure. The facility does not have any exterior stairways fromintermediate floors. The Mechanical Room and Stage handrails do not extend past the top and bottom stair risers as required by the OhioBuilding Code. Mechanical Room guardrails are constructed in a ladder effect and do not meet the 4’’ ball test. The Kitchen hood is in poorcondition, and is not equipped with the required UL 300 compliant wet chemical fire suppression system. The required 6’’ overhang of the cookingequipment is not provided by the hood. Kitchen hood exhaust ductwork is not of proper construction, material, insulation, and was not installed asrequired by the OSDM and OBCMC. The cooking equipment is not interlocked to shut down in the event of discharge of the fire suppressionsystem. Fire extinguishers are not provided in sufficient quantity. Existing fire extinguishers are inadequately spaced. The facility is not equippedwith an emergency generator. The existing water supply is provided by a tie-in to the city system, and is insufficient to meet the future firesuppression needs of the school. Rooms with a capacity greater than 50 occupants are equipped with adequate egress.

Rating: 3 Needs Replacement

Recommendations: Provide new automated fire suppression system to meet Ohio School Design Manual guidelines. Provide increased water service of a capacitysufficient to support the fire suppression system, with funding included in fire suppression funding. Provide new emergency generator, withfunding provided via complete replacement of electrical system in Item D. Provide new handrails to meet the requirements of the Ohio BuildingCode. Provide new guardrails to meet the requirements of the Ohio Building Code. Provide additional wall cabinets and fire extinguishers.Provide the new Kitchen hood with a UL 300 compliant wet chemical fire suppression system, with funding provided in Item J. Provide theinterlock to de-energize cooking equipment upon discharge of the Kitchen hood fire suppression system, with funding provided in Item J.10-02-14 Update: Existing 3" water service not sufficient to support sprinkler system. Provide new water service for fire protection. Water meter is1-12" and will need to be increased in size to meet fire protection flow requirements. Replace water meter.

Item Cost Unit Whole Building

Original Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

Sprinkler / Fire Suppression System:

$3.20sq.ft. (Qty)

32,418 Required 4,167 Required $117,072.00(includes increase of service piping, if required)

Water Main $40.00ln.ft. 200 Required $8,000.00(new) Handrails: $5,000.00level 1 Required $5,000.00Provide Fire Extinguisher andWall Cabinet:

$585.00each 1 Required $585.00(includes preparation of wall to receive recessedcabinet)

Other: Handrails / Guardrails $34.50ln.ft. 30 Required $1,035.00Provide new handrails to meet the requirements of theOhio Building Code.

Other: New Water Meter $21,000.00each 1 Required $21,000.00Replace water meter Sum: $152,692.00 $139,357.60 $13,334.40

Stage Non-compliant Handrails Wall Cabinet and Fire Extinguisher

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 34

Page 35: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

V. Loose Furnishings

Description: The typical Classroom furniture is mismatched, and in generally fair to poor condition, consisting of student desks & chairs, teacher desks &chairs, full height file cabinets, reading tables, bookcases, and wastebaskets. The facility’s furniture and loose equipment were evaluated in item6.17 in the CEFPI section of this report, and on a scale of 1 to 10 the overall facility received a rating of 3 due to observed conditions, and due tothe fact that it lacks some of the Design Manual required elements.

Rating: 3 Needs Replacement

Recommendations: Provide for replacement of outdated or inadequate furnishings.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

CEFPI Rating 0 to 3$5.00sq.ft. Required Required $182,925.00Sum: $182,925.00 $162,090.00 $20,835.00

Typical Teacher Desk Typical Student Desks

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 35

Page 36: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

W. Technology

Description: The typical Classroom is equipped with one of the required four technology data ports for student use, one data port for teacher use, one voiceport with a digitally based phone system / one cable port and monitor, and a 2-way PA system that can only be initiated by the Main Office tomeet Ohio School Design Manual requirements. The typical Classroom is not equipped with three of the required four technology data ports forstudent use and a 2-way PA system that can be initiated by either party to meet Ohio School Design Manual requirements. The facility isequipped with a centralized clock system that only operates three clocks and the school bell system. Specialized electrical / sound systemrequirements of Gymnasium, Stage, Student Dining, and Music spaces are inadequately provided, and in fair condition. OSDM-compliantcomputer network infrastructure is not provided. The facility does not contain a Media Distribution Center, and does not provide Computer Labsfor use by students.

Rating: 3 Needs Replacement

Recommendations: Provide complete replacement of technology systems to meet Ohio School Design Manual requirements.

Item Cost Unit Whole BuildingOriginal Construction (1953)32,418 ft²

Classroom Addition (1963)4,167 ft²

Sum Comments

ES portion of building with total SF < 50,000$13.18sq.ft. (Qty) 32,418 Required 4,167 Required $482,190.30Sum: $482,190.30 $427,269.24 $54,921.06

Music Space Sound System Non-Compliant OSFC Computer Network Infrastructure

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 36

Page 37: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Facility Assessment

X. Construction Contingency / Non-Construction Cost

Renovation Costs (A-W) $6,551,764.74

7.00% Construction Contingency $458,623.53

Subtotal $7,010,388.27

16.29% Non-Construction Costs $1,141,992.25

Total Project $8,152,380.52

Construction Contingency $458,623.53

Non-Construction Costs $1,141,992.25

Total for X. $1,600,615.78

Non-Construction Costs Breakdown

Land Survey 0.03% $2,103.12

Soil Borings / Phase I Envir. Report 0.10% $7,010.39

Agency Approval Fees (Bldg. Code) 0.25% $17,525.97

Construction Testing 0.40% $28,041.55

Printing - Bid Documents 0.15% $10,515.58

Advertising for Bids 0.02% $1,402.08

Builder’s Risk Insurance 0.12% $8,412.47

Design Professional’s Compensation 7.50% $525,779.12

CM Compensation 6.00% $420,623.30

Commissioning 0.60% $42,062.33

Non-Construction Contingency (includes partnering and mediation services) 1.12% $78,516.35

Total Non-Construction Costs 16.29% $1,141,992.25

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Facility Assessment Page 37

Page 38: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

School Facility Appraisal

Name of Appraiser Dave Gandee Date of Appraisal 2015-01-06

Building Name Elizabeth Price Elementary

Street Address 2610 Delmore Street

City/Town, State, Zip Code Cuyahoga Falls, OH 44221

Telephone Number(s) (330) 920-3635

School District Cuyahoga Falls City

Setting: Suburban

Site-Acreage 8.50 Building Square Footage 36,585

Grades Housed K-5 Student Capacity 293

Number of Teaching Stations 23 Number of Floors 1

Student Enrollment 386

Dates of Construction 1953,1963

Energy Sources: Fuel Oil Gas Electric Solar

Air Conditioning: Roof Top Windows Units Central Room Units

Heating: Central Roof Top Individual Unit Forced Air

Hot Water Steam

Type of Construction

Load bearing masonry

Steel frame

Concrete frame

Wood

Steel Joists

Exterior Surfacing

Brick

Stucco

Metal

Wood

Stone

Floor Construction

Wood Joists

Steel Joists

Slab on grade

Structural slab

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51School Facility Appraisal Page 38

Page 39: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

CEFPI Ratings Sheet

1.0 The School Site

School Facility Appraisal

Points Allocated Points

1.1 Site is large enough to meet educational needs as defined by state and local requirements 25 15

The site is 8.5 acres compared to 14 acres recommended by the OSDM.

1.2 Site is easily accessible and conveniently located for the present and future population 20 16

The School is centrally located within the School District, and is easily accessible.

1.3 Location is removed from undesirable business, industry, traffic, and natural hazards 10 8

The site is adjacent to residential uses, and there are no undesirable features adjacent to the School site.

1.4 Site is well landscaped and developed to meet educational needs 10 8

The site is moderately landscaped with mature shade trees, ornamental trees, and shrubs which define the property and emphasize the building entrance. Lawnareas where mowing is required do not exceed 3:1 slope.

1.5 ES Well equipped playgrounds are separated from streets and parking areas 10 6

MS Well equipped athletic and intermural areas are separated from streets and parking

HS Well equipped athletic areas are adequate with sufficient solid-surface parking

Playground areas consist of coated steel and high density plastic type play equipment, which is in good to fair condition, and is located on wood fiber mulch which isan approved soft surface material. Play equipment is ADA accessible, and includes an accessible route to equipment. Fencing is partially provided, but does notprovide proper separation of play areas from vehicular use areas.

1.6 Topography is varied enough to provide desirable appearance and without steep inclines 5 4

The site is gently sloped to provide positive drainage across the site. A flat area is provided to accommodate buildings, perimeter walks, vehicular circulation,parking areas, outdoor play areas, and physical education spaces, and is desirable.

1.7 Site has stable, well drained soil free of erosion 5 4

Soils appear to be stable and well drained, and no erosion was observed.

1.8 Site is suitable for special instructional needs , e.g., outdoor learning 5 4

The site has been developed to accommodate outdoor learning, including benches and picnic tables to facilitate instruction.

1.9 Pedestrian services include adequate sidewalk with designated crosswalks, curb cuts, andcorrect slopes

5 4

Sidewalks are adequately provided to accommodate safe pedestrian circulation including designated crosswalks, curb cuts, and correct slopes.

1.10 ES/MS Sufficient on-site, solid surface parking for faculty and staff is provided 5 3

HS Sufficient on-site, solid surface parking is provided for faculty, students, staff and community

Adequate parking is provided for faculty, staff, and community parking, and is located on asphalt pavement in poor condition.

TOTAL - The School Site 100 72

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 39

Page 40: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 40

Page 41: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

CEFPI Ratings Sheet

2.0 Structural and Mechanical Features

School Facility Appraisal

Structural Points Allocated Points

2.1 Structure meets all barrier-free requirements both externally and internally 15 9

Entire building is not ADA-compliant.

2.2 Roofs appear sound, have positive drainage, and are weather tight 15 8

The roofs over the entire building require replacement.

2.3 Foundations are strong and stable with no observable cracks 10 8

Foundations are in good condition with no observable cracks.

2.4 Exterior and interior walls have sufficient expansion joints and are free of deterioration 10 6

Exterior and interior walls are in fair condition. Some masonry repair work is required and all masonry surfaces require cleaning and sealing. Additional control jointsare required.

2.5 Entrances and exits are located so as to permit efficient student traffic flow 10 8

Exits are properly located to allow safe egress from the building.

2.6 Building ’’envelope’’ generally provides for energy conservation (see criteria) 10 6

Building envelope meets minimum energy conservation requirements.

2.7 Structure is free of friable asbestos and toxic materials 10 4

The building is assumed to contain asbestos and other hazardous materials.

2.8 Interior walls permit sufficient flexibility for a variety of class sizes 10 6

Interior walls throughout the facility are fixed walls and are not flexible.

Mechanical/Electrical Points Allocated Points

2.9 Adequate light sources are well maintained, and properly placed and are not subject to overheating 15 4

Light sources are improperly placed and provide inadequate lighting in some areas. Fixtures are poorly maintained in some areas. Light fixtures do not appear to besubject to overheating.

2.10 Internal water supply is adequate with sufficient pressure to meet health and safety requirements 15 6

Internal water supply will not support a future fire suppression system, but appears to be adequate for current requirements.

2.11 Each teaching/learning area has adequate convenient wall outlets , phone and computer cabling for technology applications

15 4

Classrooms have an inadequate number of outlets and data jacks for technology applications.

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 41

Page 42: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

2.12 Electrical controls are safely protected with disconnect switches easily accessible 10 2

Disconnect switches are not adequately provided to allow for safe servicing of equipment.

2.13 Drinking fountains are adequate in number and placement, and are properly maintained including provisions forthe disabled

10 2

Drinking fountains are not adequate in number and placement, and do not meet ADA requirements. Drinking fountains do not appear to be properly maintained.

2.14 Number and size of restrooms meet requirements 10 8

The number and size of Restrooms meet requirements.

2.15 Drainage systems are properly maintained and meet requirements 10 2

Drainage systems for the overall facility, consisting of sanitary waste piping, are cast iron, are original to each addition, exhibit some signs of leaking and are in fair condition.

2.16 Fire alarms, smoke detectors, and sprinkler systems are properly maintained and meet requirements 10 4

The fire alarm system does not meet requirements. Smoke detectors are not adequately provided. The facility is not sprinkled.

2.17 Intercommunication system consists of a central unit that allows dependable two-way communication betweenthe office and instructional areas

10 4

The central intercommunication system provides unreliable two-way communication between the Administration area and all teaching areas, can only be initiated bythe Main Office, and is outdated. Equipment such as speakers, are in fair condition. Telephone system is used as an alternate method of communication with the office.

2.18 Exterior water supply is sufficient and available for normal usage 5 4

Exterior wall hydrants are adequately provided around the exterior of the facility.

TOTAL - Structural and Mechanical Features 200 95

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 42

Page 43: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

CEFPI Ratings Sheet

3.0 Plant Maintainability

School Facility Appraisal

Points Allocated Points

3.1 Windows, doors, and walls are of material and finish requiring minimum maintenance 15 12

Exterior materials and finishes for doors, windows and walls are durable and require minimal maintenance.

3.2 Floor surfaces throughout the building require minimum care 15 12

Flooring throughout the facility consists of VCT, VAT, carpet, and terrazzo, which is well maintained throughout the facility.

3.3 Ceilings and walls throughout the building, including service areas, are easily cleaned and resistant to stain 10 6

Acoustical tile ceilings are not easily cleaned or resistant to stain. Glazed and painted block is easily cleaned and resistant to stain.

3.4 Built-in equipment is designed and constructed for ease of maintenance 10 4

Casework is wood type construction that is original to the building, and is in poor condition.

3.5 Finishes and hardware , with compatible keying system, are of durable quality 10 6

Door hardware varies throughout the facility, does not meet ADA requirements, and keying systems are worn.

3.6 Restroom fixtures are wall mounted and of quality finish 10 4

Fixtures are floor and wall mounted and are of fair to poor quality.

3.7 Adequate custodial storage space with water and drain is accessible throughout the building 10 8

Custodial storage space is adequately located throughout the facility, including provisions for water and drains.

3.8 Adequate electrical outlets and power , to permit routine cleaning, are available in every area 10 2

Electrical outlets are inadequately provided in Corridors and do not allow for convenient routine cleaning.

3.9 Outdoor light fixtures, electrical outlets , equipment, and other fixtures are accessible for repair and replacement 10 4

Outdoor light fixtures are inadequately provided, but are accessible for repair and replacement. Electrical outlets are inadequately provided around the exterior of the facility.

TOTAL - Plant Maintainability 100 58

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 43

Page 44: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

CEFPI Ratings Sheet

4.0 Building Safety and Security

School Facility Appraisal

Site Safety Points Allocated Points

4.1 Student loading areas are segregated from other vehicular traffic and pedestrian walkways 15 9

Student loading is not separated from other vehicular traffic.

4.2 Walkways , both on and offsite, are available for safety of pedestrians 10 8

Walkways are adequately provided both on and off-site for pedestrian safety.

4.3 Access streets have sufficient signals and signs to permit safe entrance to and exit from school area 5 4

School signs and signals are located as required on adjacent access streets.

4.4 Vehicular entrances and exits permit safe traffic flow 5 2

Buses and other vehicular traffic use the same entrance and exit points to the site, which does not provide safe vehicular traffic flow.

4.5 ES Playground equipment is free from hazard 5 3

MS Location and types of intramural equipment are free from hazard

HS Athletic field equipment is properly located and is free from hazard

Playground equipment consists of plastic coated steel and high density plastic type equipment in good yto fair condition, appears to be free from hazard, and islocated on an approved soft surface material to a insufficient depth.

Building Safety Points Allocated Points

4.6 The heating unit(s) is located away from student occupied areas 20 10

Heating boilers are located in rooms that are not accessible by students. Unit ventilators and fin tubes are located in the Classrooms and other learning areas.

4.7 Multi-story buildings have at least two stairways for student egress 15 15

The overall facility is one story without stairways.

4.8 Exterior doors open outward and are equipped with panic hardware 10 10

Exterior doors open in the direction of travel and are equipped with panic hardware.

4.9 Emergency lighting is provided throughout the entire building with exit signs on separate electrical circuits 10 2

Exit signs are not on separate circuits and are inadequately provided. The facility is inadequately equipped with emergency egress light fixtures. The facility is notequipped with an emergency generator.

4.10 Classroom doors are recessed and open outward 10 6

Classroom doors are semi-recessed from the Corridor and open outward without proper ADA clearances, but do not impede traffic flow in the Corridors.

4.11 Building security systems are provided to assure uninterrupted operation of the educational program 10 2

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 44

Page 45: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Security systems are inadequately provided and are in fair condition.

4.12 Flooring (including ramps and stairways) is maintained in a non-slip condition 5 4

VCT, Terrazzo, Carpet, and VAT flooring have been well maintained throughout the facility.

4.13 Stair risers (interior and exterior) do not exceed 6 1/2 inches and range in number from 3 - 16 5 4

The overall facility is one story without stairways. Stair treads and risers at the steps of the Stage are properly designed and meet requirements.

4.14 Glass is properly located and protected with wire or safety material to prevent accidental student injury 5 2

Glass at door vision panels are not tempered or provided with a wire mesh for safety.

4.15 Fixed Projections in the traffic areas do not extend more than eight inches from the corridor wall 5 3

Drinking fountains and electric water coolers have not been recessed and extend more than eight inches from the Corridor wall, which impede traffic flow in the Corridors.

4.16 Traffic areas terminate at an exit or a stairway leading to an egress 5 5

Exits are properly located to allow safe egress from the building.

Emergency Safety Points Allocated Points

4.17 Adequate fire safety equipment is properly located 15 2

The facility is not sprinkled. Fire alarm devices are not provided adequately. Fire extinguishers are inadequately provided.

4.18 There are at least two independent exits from any point in the building 15 8

There are no dead-end Corridors in the building.

4.19 Fire-resistant materials are used throughout the structure 15 12

The structure is a masonry load bearing system. Interior walls are masonry.

4.20 Automatic and manual emergency alarm system with a distinctive sound and flashing light is provided 15 2

The fire alarm is equipped with automatic actuation devices but is not adequately provided with visual indicating devices.

TOTAL - Building Safety and Security 200 113

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 45

Page 46: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

CEFPI Ratings Sheet

5.0 Educational Adequacy

School Facility Appraisal

Academic Learning Space Points Allocated Points

5.1 Size of academic learning areas meets desirable standards 25 15

The average Classroom in the 1953 Original Construction is 737 SF compared to 900 SF required by the OSDM. The average Classroom in the 1963 Addition is756 SF compared to 900 SF required by the OSDM.

5.2 Classroom space permits arrangements for small group activity 15 9

Undersized Classrooms do not allow sufficient space for effective small group activities.

5.3 Location of academic learning areas is near related educational activities and away from disruptive noise 10 6

The Gymnasium is properly isolated from the academic learning areas to reduce distractions. The Music Room is located adjacent to academic learning areas,which can be distracting.

5.4 Personal space in the classroom away from group instruction allows privacy time for individual students 10 4

Undersized Classrooms do not permit privacy time for individual students.

5.5 Storage for student materials is adequate 10 8

Lockers, located in the Corridor, are adequately provided for student storage. Storage cubbies, located in the Classroom, are adequately provided for student storage.

5.6 Storage for teacher materials is adequate 10 4

Casework is inadequately provided for storage of teacher materials.

Special Learning Space Points Allocated Points

5.7 Size of special learning area(s) meets standards 15 9

The Special Education Classroom is 737 SF compared to 900 SF recommended in the OSDM. Special Education Classrooms are undersized compared to standards.

5.8 Design of specialized learning area(s) is compatible with instructional need 10 4

Special Education spaces are not adequately provided to meet instructional needs.

5.9 Library/Resource/Media Center provides appropriate and attractive space 10 4

The Media Center is 735 SF compared to 1,351 SF recommended in the OSDM. The Library is not visually appealing and does not provide natural light.

5.10 Gymnasium (or covered P.E. area) adequately serves physical education instruction 5 4

The Gymnasium is 4,600 SF compared to 3,500-5,000 SF recommended in the OSDM.

5.11 ES Pre-kindergarten and kindergarten space is appropriate for age of students and nature of instruction 10 6

MS/HS Science program is provided sufficient space and equipment

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 46

Page 47: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Kindergarten spaces are undersized, and do not provide adequate instruction space.

5.12 Music Program is provided adequate sound treated space 5 2

The Music Room is 737 SF compared to 1,800-3,000 recommended in the OSDM. Music instruction is provided in a standard Classroom without any sound treatment.

5.13 Space for art is appropriate for special instruction, supplies, and equipment 5 2

The Art Room is 756 SF compared to 1,200 SF recommended in the OSDM. The Art Room is undersized and does not provide sufficient space for storage ofsupplies and equipment.

School Facility Appraisal Points Allocated Points

5.14 Space for technology education permits use of state-of-the-art equipment 5 0

The facility is not provided with Computer Labs for student use.

5.15 Space for small groups and remedial instruction is provided adjacent to classrooms 5 2

No spaces have been provided adjacent to Classrooms for small groups or remedial instruction.

5.16 Storage for student and teacher material is adequate 5 3

Lockers and storage cubbies have been adequately provided for storage of student materials. Casework is not adequately provided for storage of teacher materials.

Support Space Points Allocated Points

5.17 Teacher’s lounge and work areas reflect teachers as professionals 10 6

The Teacher’s Lounge is 334 SF compared to 450-900 SF, for 8-24 staff, recommended in the OSDM.

5.18 Cafeteria/Kitchen is attractive with sufficient space for seating/dining, delivery, storage, and food preparation

10 6

The Kitchen space is 780 SF compared to 1,351 SF recommended in the OSDM. Student Dining shares the Gymnasium space.

5.19 Administrative offices provided are consistent in appearance and function with the maturity of the students served

5 2

Administrative Offices are not adequately provided for Elementary School students.

5.20 Counselor’s office insures privacy and sufficient storage 5 2

The Counselor’s Office is 121 SF compared to 120 SF, plus 100 SF for Storage and 200 SF for Conference, recommended in the OSDM.

5.21 Clinic is near administrative offices and is equipped to meet requirements 5 2

The Clinic is 200 SF compared to 370 SF recommended in the OSDM.

5.22 Suitable reception space is available for students, teachers, and visitors 5 2

Reception space consists of approximately 167 SF compared to 200-400 SF recommended by the OSDM.

5.23 Administrative personnel are provided sufficient work space and privacy 5 1

The Administrative area consists of approximately 661 SF for the principal, assistant principal, secretary, Conference Room, Storage, Copy Room, and Restroom,compared to 2,600 SF recommended by the OSDM.

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 47

Page 48: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

TOTAL - Educational Adequacy 200 103

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 48

Page 49: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

CEFPI Ratings Sheet

6.0 Environment for Education

School Facility Appraisal

Exterior Environment Points Allocated Points

6.1 Overall design is aesthetically pleasing to age of students 15 12

The building is a conventional design with standard detailing, which is aesthetically acceptable.

6.2 Site and building are well landscaped 10 8

The site is moderately landscaped with mature shade trees, ornamental trees, and shrubs which define the property and emphasize the building entrance. Lawnareas where mowing is required do not exceed 3:1 slope.

6.3 Exterior noise and poor environment do not disrupt learning 10 8

The site is adjacent to residential uses, and there are no undesirable features adjacent to the school site.

6.4 Entrances and walkways are sheltered from sun and inclement weather 10 8

The main entrance to the School is partially sheltered.

6.5 Building materials provide attractive color and texture 5 4

Exterior building materials consist of brick and stone, which provide an attractive color and texture.

Interior Environment Points Allocated Points

6.6 Color schemes, building materials, and decor provide an impetus to learning 20 16

The color palette is comprised of neutral hues with accent color of more saturated hues. School colors are reflected in the athletic areas. The use of repeated colorsand materials give the building some unity and a sense of consistency, which enhances the learning environment.

6.7 Year around comfortable temperature and humidity are provided throughout the building 15 2

The facility is not air conditioned to provide year-round temperature and humidity control.

6.8 Ventilating system provides adequate quiet circulation of clean air and meets 15cfm VBC requirement 15 6

The ventilating systems do not provide an adequate quantity of ventilation air to the spaces. Ventilation systems introduce minimal noise into the teaching andlearning areas.

6.9 Lighting system provides proper intensity, diffusion, and distribution of illumination 15 4

The lighting system does not provide proper intensity in some areas. Location of lighting fixtures provides uneven distribution of illumination. Diffusion of illuminationis adequately provided by the light fixture lenses in some areas.

6.10 Drinking fountains and restroom facilities are conveniently located 15 12

Drinking fountains and Restroom facilities are conveniently located.

6.11 Communication among students is enhanced by commons area(s) for socialization 10 8

There are areas for students to gather in the Multi-Purpose Room, as well as a gathering area in the Entry Corridor.

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 49

Page 50: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

6.12 Traffic flow is aided by appropriate foyers and corridors 10 8

Corridors and Foyers are adequately designed for efficient traffic flow.

6.13 Areas for students to interact are suitable to the age group 10 8

There are areas for students to gather in the Multi-Purpose Room, as well as a gathering area in the Entry Corridor.

6.14 Large group areas are designed for effective management of students 10 8

The Multipurpose space is adequately designed to manage large groups of students.

6.15 Acoustical treatment of ceilings, walls, and floors provides effective sound control 10 4

Limited consideration has been given to acoustical treatment of Classrooms and Corridors.

6.16 Window design contributes to a pleasant environment 10 8

The windows are well designed and contribute to a pleasant environment.

6.17 Furniture and equipment provide a pleasing atmosphere 10 3

Classroom furniture is mismatched and in fair to poor condition.

TOTAL - Environment for Education 200 127

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51CEFPI Ratings Sheet Page 50

Page 51: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

LEED Observation NotesSchool District: Cuyahoga Falls City

County: Summit

School District IRN: 43836

Building: Elizabeth Price Elementary

Building IRN: 10215

Sustainable Sites

Construction process can have a harmful effect on local ecology, especially when buildings are build on productive agricultural, wildlife or open areas. Several measures can betake however to prevent the impact on undeveloped lands or to improve previously contaminated sites. Appropriate location reduces the need for private transportation and helpsto prevent an increase in air pollution. Developing buildings in urban areas and on brownfield sites instead of greenfield locations has economical and environmental benefits.Controlling stormwater runoff and erosion can prevent the worsening of water quality in receiving bodies of water and the impact on aquatic life. Once the building is constructed,it’s important to decrease heat island effects and reduce the light pollution on the site.

(source: LEED Reference Guide, 2001:9)

Water Efficiency

In the US ca. 340 billion gallons of fresh water are withdrawn daily from surface sources, 65% of which is discharged later after use. Water is also withdrawn from undergroundaquifers The excessive usage of water results in the current water deficit, estimated at 3,700 billion gallons. Water efficiency measures in commercial buildings can reduce waterusage by at least 30%. Low-flow fixtures, sensors or using non potable water for landscape irrigation, toilet flushing and building systems are just some of available strategies. Notonly do they result in environmental savings, but also bring about financial benefits, related to lower water use fees, lower sewage volumes to treat and energy use reductions.

(source: LEED Reference Guide, 2001:65)

Energy & Atmosphere

Buildings in the US account for more than 30% of the total energy use and for approximately 60% of electricity. 75% of energy is derived from the burning of fossil fuels, whichreleases CO2 into the Atmosphere and contributes to global warming. Moreover, coal fired electric utilities release nitrogen oxides and sulfur dioxide, where the former contributeto smog and the latter to acid rain. Other types of energy production are not less harmful. Burning of natural gas produces nitrogen oxides and greenhouse gases as well, nuclearpower creates nuclear wastes, while hydroelectric generating plants disrupt natural water flows. Luckily there are several practices that can reduce energy consumption and areenvironmentally and economically beneficial. Not only will they reduce the air pollution and mitigate global warming thanks to being less dependent on power plants, but also theywill reduce operational costs and will quickly pay back. In order to make the most of those practices, it’s important to adopt a holistic approach to the building’s energy load andintegrate different energy saving strategies.

(source: LEED Reference Guide, 2001:93)

Material & Resources

The steps related to process building materials, such as extraction, processing and transportation are not environmentally natural, as they pollute the air, water and use naturalresources. Construction and demolition wastes account for 40% of the solid waste stream in the US. Reusing existing documents is one of the best strategies to reduce solidwastes volumes and prevents then from ending up at landfills. It also reduces habitat disturbance and minimizes the need for the surrounding infrastructure. While using newmaterials one should take into account different material sources. Salvaged materials provide savings on material costs, recycled content material minimizes waste products andlocal materials reduce the environmental impact of transportation. Finally, using rapidly renewable materials and certified wood decreases the consumption of natural resources.Recycling and reusing construction waste is another strategy to be taken into consideration in sustainable design.

(source: LEED Reference Guide, 2001:167)

Indoor Environmental Quality

As we spend a big majority of our time indoors, the emphasis should be put on optimal indoor environmental quality strategies while (re)designing a building . Otherwise, a poorIEQ will have adverse effects on occupants’ health, productivity and quality of life. IEQ strategies such as ventilation effectiveness and control of contaminants or a buildingflush-out prior to occupancy can reduce potential liability, increase the market value of the building but can also result in a significantly higher productivity (16%). Other strategiesinvolve automatic sensors and controls, introducing fresh air to the building or providing lots of daylighting views.

(source: LEED Reference Guide, 2001:215)

Innovation & Design Process

This category is aimed at recognizing projects that implemented innovative building features and sustainable building knowledge, and whose strategy or measure resultsexceeded those which are required by the LEED Rating System. Expertise in sustainable design is the key element of the innovative design and construction process.

(source: LEED Reference Guide, 2001:271)

Report Generated at 21 Jul 2015 12:51<Untitled> Page 51

Page 52: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Justification for Allocation of Points

Building Name and Level: Elizabeth Price Elementary

K-5

Building features that clearly exceed criteria:

1.

2.

3.

4.

5.

6.

Building features that are non-existent or very inadequate:

1. The building does not meet ADA requirements.

2. The building does not contain a fire suppression system.

3. The building is reported to contain asbestos and other hazardous materials.

4. The Classrooms are undersized.

5. The Art Room and Music Room are undersized and lack storage space.

6.

Back to Assessment Summary

Report Generated at 21 Jul 2015 12:51Justification for Allocation of Points Page 52

Page 53: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Environmental Hazards Assessment Cost EstimatesOwner: Cuyahoga Falls City Facility: Elizabeth Price Elementary Date of Initial Assessment: Jan 6, 2015 Date of Assessment Update: Jan 22, 2015 Cost Set: 2015

District IRN: 43836 Building IRN: 10215 Firm: Gandee & Associates, Inc.

Scope remains unchanged after cost updates.

Building Addition Addition Area (sf)Total of Environmental Hazards Assessment Cost Estimates

Renovation Demolition 1953 Original Construction 32,418 $106,491.80 $93,491.80 1963 Classroom Addition 4,167 $21,716.70 $21,716.70 Total 36,585 $128,208.50 $115,208.50 Total with Regional Cost Factor (104.05%) — $133,400.94 $119,874.44 Regional Total with Soft Costs & Contingency — $165,991.20 $149,160.13

Report Generated at 21 Jul 2015 12:51<Untitled> Page 53

Page 54: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Environmental Hazards(Enhanced) - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) - Original Construction

Environmental Hazards(Enhanced) - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) - Original Construction

Owner: Cuyahoga Falls City Bldg. IRN: 10215

Facility: Elizabeth Price Elementary BuildingAdd: Original Construction

Date On-Site: 2015-01-06 Consultant Name: Gandee & Associates, Inc.

A. Asbestos Containing Material (ACM) AFM=Asbestos Free Material ACM Found Status Quantity Unit Cost Estimated Cost

1. Boiler/Furnace Insulation Removal Not Present 0 $10.00 $0.00 2. Breeching Insulation Removal Assumed Asbestos-Containing Material 75 $10.00 $750.00 3. Tank Insulation Removal Not Present 0 $8.00 $0.00 4. Duct Insulation Removal Not Present 0 $8.00 $0.00 5. Pipe Insulation Removal Assumed Asbestos-Containing Material 700 $10.00 $7,000.00 6. Pipe Fitting Insulation Removal Assumed Asbestos-Containing Material 50 $20.00 $1,000.00 7. Pipe Insulation Removal (Crawlspace/Tunnel) Not Present 0 $12.00 $0.00 8. Pipe Fitting Insulation Removal (Crawlspace/Tunnel) Not Present 0 $30.00 $0.00 9. Pipe Insulation Removal (Hidden in Walls/Ceilings) Assumed Asbestos-Containing Material 650 $15.00 $9,750.00 10. Dismantling of Boiler/Furnace/Incinerator Assumed Asbestos-Containing Material 2 $2,000.00 $4,000.00 11. Flexible Duct Connection Removal Not Present 0 $100.00 $0.00 12. Acoustical Plaster Removal Not Present 0 $7.00 $0.00 13. Fireproofing Removal Not Present 0 $25.00 $0.00 14. Hard Plaster Removal Reported / Assumed Asbestos-Free Material 0 $7.00 $0.00 15. Gypsum Board Removal Not Present 0 $6.00 $0.00 16. Acoustical Panel/Tile Ceiling Removal Reported / Assumed Asbestos-Free Material 0 $3.00 $0.00 17. Laboratory Table/Counter Top Removal Not Present 0 $100.00 $0.00 18. Cement Board Removal Not Present 0 $5.00 $0.00 19. Electric Cord Insulation Removal Not Present 0 $1.00 $0.00 20. Light (Reflector) Fixture Removal Not Present 0 $50.00 $0.00 21. Sheet Flooring with Friable Backer Removal Not Present 0 $4.00 $0.00 22. Fire Door Removal Assumed Asbestos-Containing Material 2 $100.00 $200.00 23. Door and Window Panel Removal Not Present 0 $100.00 $0.00 24. Decontamination of Crawlspace/Chase/Tunnel Not Present 0 $3.00 $0.00 25. Soil Removal Not Present 0 $150.00 $0.00 26. Non-ACM Ceiling/Wall Removal (for access) Assumed Asbestos-Containing Material 3600 $2.00 $7,200.00 27. Window Component (Compound, Tape, or Caulk) - Reno & Demo Reported / Assumed Asbestos-Free Material 0 $300.00 $0.00 28. Window Component (Compound, Tape, or Caulk) - Reno Only Reported / Assumed Asbestos-Free Material 0 $300.00 $0.00 29. Resilient Flooring Removal, Including Mastic Reported Asbestos-Containing Material 20000 $3.00 $60,000.00 30. Carpet Mastic Removal Not Present 0 $2.00 $0.00 31. Carpet Removal (over RFC) Assumed Asbestos-Containing Material 350 $1.00 $350.00 32. Acoustical Tile Mastic Removal Reported / Assumed Asbestos-Free Material 0 $3.00 $0.00 33. Sink Undercoating Removal Not Present 0 $100.00 $0.00 34. Roofing Removal Reported / Assumed Asbestos-Free Material 0 $2.00 $0.00 35. (Sum of Lines 1-34) Total Asb. Hazard Abatement Cost for Renovation Work $90,250.0036. (Sum of Lines 1-34) Total Asb. Hazard Abatement Cost for Demolition Work $90,250.00

B. Removal Of Underground Storage Tanks None Reported

Tank No. Location Age Product Stored Size Est.Rem.Cost1. (Sum of Lines 1-0) Total Cost For Removal Of Underground Storage Tanks $0.00

C. Lead-Based Paint (LBP) - Renovation Only Addition Constructed after 19801. Estimated Cost For Abatement Contractor to Perform Lead Mock-Ups $5,000.00 2. Special Engineering Fees for LBP Mock-Ups $5,000.00 3. (Sum of Lines 1-2) Total Cost for Lead-Based Paint Mock-Ups $10,000.00

D. Fluorescent Lamps & Ballasts Recycling/Incineration Not Applicable Area Of Building Addition Square Feet w/Fluorescent Lamps & Ballasts Unit Cost Total Cost

1. 32418 32418 $0.10 $3,241.80

E. Other Environmental Hazards/Remarks None ReportedDescription Cost Estimate

1. See Bulk Sample Record Nos. 1 through 6, & 8 for sampling results in this addition. $0.002. XRF testing for lead-based paint is recommended for compliance with EPA’s RRP Program. $3,000.003. (Sum of Lines 1-2) Total Cost for Other Environmental Hazards - Renovation $3,000.004. (Sum of Lines 1-2) Total Cost for Other Environmental Hazards - Demolition $0.00

F. Environmental Hazards Assessment Cost Estimate Summaries1. A35, B1, C3, D1, and E3 Total Cost for Env. Hazards Work - Renovation $106,491.802. A36, B1, D1, and E4 Total Cost for Env. Hazards Work - Demolition $93,491.80

* INSPECTION ASSUMPTIONS for Reported/Assumed Asbestos-Free Materials (Rep/Asm AFM):

a. Unless reported otherwise by the District, materials installed after 1980 are assumed to be asbestos-free.

b. Unless reported otherwise by the District, small quantities (less than 1,000 square feet) of the following materials are assumed to be asbestos free: hard plaster,acoustical plaster and gypsum board systems; acoustical panels and tiles; fireproofing; 12"×12" floor tile and mastic.

c. Unless reported otherwise by the District, all roofing materials are assumed to be asbestos-free.

THESE MATERIALS SHOULD BE PROPERLY SAMPLED AND ANALYZED FOR ASBESTOS PRIOR TO DISTURBING THEM.

Report Generated at 21 Jul 2015 12:51<Untitled> Page 54

Page 55: Building Information - Cuyahoga Falls City 43836 ...Renovation Cost Factor 104.05% Cost to Renovate (Cost Factor applied) $7,633,073.58 The Replacement Cost Per SF and the Renovate/Replace

Environmental Hazards(Enhanced) - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) - Classroom Addition

Environmental Hazards(Enhanced) - Cuyahoga Falls City (43836) - Elizabeth Price Elementary (10215) - Classroom Addition

Owner: Cuyahoga Falls City Bldg. IRN: 10215

Facility: Elizabeth Price Elementary BuildingAdd: Classroom Addition

Date On-Site: 2015-01-06 Consultant Name: Gandee & Associates, Inc.

A. Asbestos Containing Material (ACM) AFM=Asbestos Free Material ACM Found Status Quantity Unit Cost Estimated Cost

1. Boiler/Furnace Insulation Removal Not Present 0 $10.00 $0.00 2. Breeching Insulation Removal Not Present 0 $10.00 $0.00 3. Tank Insulation Removal Not Present 0 $8.00 $0.00 4. Duct Insulation Removal Not Present 0 $8.00 $0.00 5. Pipe Insulation Removal Not Present 0 $10.00 $0.00 6. Pipe Fitting Insulation Removal Not Present 0 $20.00 $0.00 7. Pipe Insulation Removal (Crawlspace/Tunnel) Not Present 0 $12.00 $0.00 8. Pipe Fitting Insulation Removal (Crawlspace/Tunnel) Not Present 0 $30.00 $0.00 9. Pipe Insulation Removal (Hidden in Walls/Ceilings) Assumed Asbestos-Containing Material 100 $15.00 $1,500.00 10. Dismantling of Boiler/Furnace/Incinerator Not Present 0 $2,000.00 $0.00 11. Flexible Duct Connection Removal Not Present 0 $100.00 $0.00 12. Acoustical Plaster Removal Not Present 0 $7.00 $0.00 13. Fireproofing Removal Not Present 0 $25.00 $0.00 14. Hard Plaster Removal Not Present 0 $7.00 $0.00 15. Gypsum Board Removal Reported / Assumed Asbestos-Free Material 0 $6.00 $0.00 16. Acoustical Panel/Tile Ceiling Removal Not Present 0 $3.00 $0.00 17. Laboratory Table/Counter Top Removal Not Present 0 $100.00 $0.00 18. Cement Board Removal Not Present 0 $5.00 $0.00 19. Electric Cord Insulation Removal Not Present 0 $1.00 $0.00 20. Light (Reflector) Fixture Removal Not Present 0 $50.00 $0.00 21. Sheet Flooring with Friable Backer Removal Not Present 0 $4.00 $0.00 22. Fire Door Removal Not Present 0 $100.00 $0.00 23. Door and Window Panel Removal Not Present 0 $100.00 $0.00 24. Decontamination of Crawlspace/Chase/Tunnel Not Present 0 $3.00 $0.00 25. Soil Removal Not Present 0 $150.00 $0.00 26. Non-ACM Ceiling/Wall Removal (for access) Assumed Asbestos-Containing Material 400 $2.00 $800.00 27. Window Component (Compound, Tape, or Caulk) - Reno & Demo Reported / Assumed Asbestos-Free Material 0 $300.00 $0.00 28. Window Component (Compound, Tape, or Caulk) - Reno Only Reported / Assumed Asbestos-Free Material 0 $300.00 $0.00 29. Resilient Flooring Removal, Including Mastic Reported Asbestos-Containing Material 3100 $3.00 $9,300.00 30. Carpet Mastic Removal Not Present 0 $2.00 $0.00 31. Carpet Removal (over RFC) Not Present 0 $1.00 $0.00 32. Acoustical Tile Mastic Removal Assumed Asbestos-Containing Material 3100 $3.00 $9,300.00 33. Sink Undercoating Removal Assumed Asbestos-Containing Material 4 $100.00 $400.00 34. Roofing Removal Reported / Assumed Asbestos-Free Material 0 $2.00 $0.00 35. (Sum of Lines 1-34) Total Asb. Hazard Abatement Cost for Renovation Work $21,300.0036. (Sum of Lines 1-34) Total Asb. Hazard Abatement Cost for Demolition Work $21,300.00

B. Removal Of Underground Storage Tanks None Reported

Tank No. Location Age Product Stored Size Est.Rem.Cost1. (Sum of Lines 1-0) Total Cost For Removal Of Underground Storage Tanks $0.00

C. Lead-Based Paint (LBP) - Renovation Only Addition Constructed after 19801. Estimated Cost For Abatement Contractor to Perform Lead Mock-Ups $0.00 2. Special Engineering Fees for LBP Mock-Ups $0.00 3. (Sum of Lines 1-2) Total Cost for Lead-Based Paint Mock-Ups $0.00

D. Fluorescent Lamps & Ballasts Recycling/Incineration Not Applicable Area Of Building Addition Square Feet w/Fluorescent Lamps & Ballasts Unit Cost Total Cost

1. 4167 4167 $0.10 $416.70

E. Other Environmental Hazards/Remarks None ReportedDescription Cost Estimate

1. Costs for lead-based paint mock-ups are included in assessment for 1953 (Original Construction). $0.002. See Bulk Sample Record Nos. 7 & 8 for sampling results in this addition. $0.003. (Sum of Lines 1-2) Total Cost for Other Environmental Hazards - Renovation $0.004. (Sum of Lines 1-2) Total Cost for Other Environmental Hazards - Demolition $0.00

F. Environmental Hazards Assessment Cost Estimate Summaries1. A35, B1, C3, D1, and E3 Total Cost for Env. Hazards Work - Renovation $21,716.702. A36, B1, D1, and E4 Total Cost for Env. Hazards Work - Demolition $21,716.70

* INSPECTION ASSUMPTIONS for Reported/Assumed Asbestos-Free Materials (Rep/Asm AFM):

a. Unless reported otherwise by the District, materials installed after 1980 are assumed to be asbestos-free.

b. Unless reported otherwise by the District, small quantities (less than 1,000 square feet) of the following materials are assumed to be asbestos free: hard plaster,acoustical plaster and gypsum board systems; acoustical panels and tiles; fireproofing; 12"×12" floor tile and mastic.

c. Unless reported otherwise by the District, all roofing materials are assumed to be asbestos-free.

THESE MATERIALS SHOULD BE PROPERLY SAMPLED AND ANALYZED FOR ASBESTOS PRIOR TO DISTURBING THEM.

Report Generated at 21 Jul 2015 12:51<Untitled> Page 55