ControlestaRCO-view

System architectureELESTA‘s innovative and interoperable building controls is ori-ented on the requirements of a sustainable energy effi ciency. Optimisation of the economy, the energy effi ciency and comfort of a building....throughout it´s life cycle. The free programmable, network-based, decentralised RCO-System is characterised by it´s high fl exibility and scalability. The open architecture, the future proofed communication abilities and with that the high degree on interoperability stands for a sustainable technology. Innovative Web- and network-technology enables the use of existing IT-Infrastructure, the access via a standard Web-Browser –and this on controller level as well as on building management level.

System Operation

RCO 700...

Network Controller with Expander Module

RCO 500D-M

1 ... 32RS485

Master Controller with integrated Display

Network Controller with text display

Master Controller with integrated Webserver

Text displayI / O Modules

Wi-FiRouter

Page 3: Building automation Controlesta RCO

Ethernet

RS232

RS485

L-Bus

WebClientPC/Intranet

WebClientPDA/Wireless

Your benefi t• BA effi ciency class A acc. EN15232 possible

• Future proofed: BACnet Building Controller ANSI/ASHRAE Standard 135-2004(ISO 16484-5)

• Variety of integration and communication abilities through inte-grated protocols (BACnet, Modbus, M-Bus, Wilo, Grundfos, ASCII, TCP/IP)

• Innovative integrated Web– and network-technology

• Integrated coloured graphical display for local operation

• High fl exibility and scalability through the modular use of the I/O-Modules

• High memory capacity for programs and data storage to SD-Memory Card

• Web-based Building Management Software

• Minimum space requirements through compact design

• Variant for DIN-rail and panel door mounting

L-Bus 2

L-Bus 2

Protokolle • BACnet-Ethernet• BACnet-IP• BACnet-MS/TP• BACnet-PTP• Modbus RTU Master• Modbus RTU Slave• M-Bus• WILO• Grundfos• ACSII• RCO C• TCP/IP

Interfaces

Room automation Integration

Single Room Controller

Fan-Coil Controller

Wireless

Technology convincesControlesta RCO offers a free programma-ble, scaleable and modular System. Highest interoperability through native BACnet and a variety of communication abilities.

Controlesta R CO2our contribution to CO2 reduction andeconomic optimisation of buildings.

It’s worth to invest!Our goal: Innovative building management for sustainable energy effi ciency.

Page 4: Building automation Controlesta RCO

Building Automation System Controlesta RCO

Master Controller RCO 7xxDThe Master-Controller is setting new dimensions in BMS.• Variety of integration and communication abilities• Extremely strong 32-Bit microprocessor• Integrated Web- and network-technology• Integrated coloured graphical LCD-Display on board• Trend-log indication at the display

Open CommunicationThe free programmable Controlesta RCO Master Controller of the D-Series with B-BC BACnet device profi le supports BACnet protocols Ethernet, IP, MSTP and PTP on request. Additional protocols such as Modbus, M-bus, Wilo, Grundfos, TCP/IP and ASCII are also supported. These various integration and communication abilities can be used simultaneously in dependence of the available interfaces.

BACnet RouterThe BACnet network option “Router” gives the opportunity for the system internal conversion of different BACnet network topologies, e.g. BACnet-Ethernet to BACnet-IP or BACnet-MS/TPto BACnet-IP. The BBMD functionality can be activated in the BACnet-IP operation mode if necessary.

Interfaces• 2 x Ethernet

(In/Out with Hub-Function)• 2 x RS485• 2 x RS232• 1 x L-Bus 1• 1 x L-Bus 2

SD-Memory CardNew dimensions for• Applications• Histories• Up-dates of

installations• Documentation

Trend-logOnline and historical data can be graphically indicated as trend-logs at the integrated display of the Master Controller.

Integrated Web-ServerThe Master Controllers are also available as variant with an integrated Web-Server.

Page 5: Building automation Controlesta RCO

Input/Output-ModulesThe fi ne modular Input/Output design with its individual modulesoffers an optimal coverage of the demanded Input and Outputconfi gurations. Up to 32 I/O-Modules can be connected to aMaster Controller. The integration of the manual override into theoutput modules leads to a reduction of the equipment variety andthe wiring efforts.

Signalisation through two coloured, programmable LED´sper input and output

Pluggable 45° terminals

Manual Override/Control levelThe output modules with integrated manual override, allows direct interventions on the connected fi eld devices. This is independentfrom the functionality of the bus or the master controller. The automatic feedback via the bus is of course integrated, both for thecontrol signals as well as for the manual override mode.

Panel door mounting DIN-rail mounting

Mounting• Power and communication

connection via mechanical plug connector

• Simple mounting through Plug-in philosophy

• Exchange of the modules during operation without interruption of the bus connection

Input-ModuleAnalogue-In (8 x universal inputs)• 0 ... 10 VDC / NTC10k / NTC30k /

NTC4,7k / NTCSAT / Ni1000 / Pt1000 / PTC / free selectable characteristics / digital

Digital-In (8 x digital inputs)• Inputs for potential free contacts

or marked contacts 24 VAC / DC• Counting input up to 20 Hz,

Pulse width > 1 ms

Output-ModulesAnalogue-Out (4 x analogue output)• 0 ... 10 VDC

Digital-Out (4 x relays)• 230 V / 4 A / change-over contacts

Tri-state-Out (2 x 2 relays)• 230 V / 4 A / change-over contacts

All output modules are available withor without manual override ability.

Page 6: Building automation Controlesta RCO

Building Automation System Controlesta RCO

Network Controller RCO 5xxDThe free programmable RCO-Network-Controller with B-BCBACnet device profi le supports BACnet protocols Ethernet, IP,MS/TP and PTP on request. Additional protocols such as Modbus,M-bus, Wilo, Grundfos, TCP/IP, ASCII are also supported. These various integration and communication abilities can be used simultaneously in dependence of the available interfaces. The local inputs and out-puts can be extended by Expander-Modules.

Compact ControllerThe free programmable RCO-Compact-Controller is designed for standalone operation. The input and output confi guration is identical with the Network Controller and can be extended with Expander-Modules. The RS232-interface enables the connection to PC, modem or messenger. The Controller can be connected via the interface with the Engineering-Software RCO-tool for programming and commissioning.

SD-Memory CardNew dimensions for• Applications• Histories• Up-dates of

installations• Documentation

InputsAnalogue-In (8 x universal inputs)• 0 ... 10 VDC / 0...20 mA /

NTC10k / NTC30k / NTC4,7k / NTCSAT / Ni1000 / Pt1000/ PTC / digital

Digital-In (6 x digital inputs)• Inputs for potential free or

marked contacts 24 VAC / DC• Counting input up to 20 Hz,

Pulse width > 1 ms

OutputsAnalogue-Out (4 x analogue output)• 0 ... 10 VDC / 0...20 mA

Digital-Out (4 x Relays)• 230 V / 4 A / closing contact

Interfaces• 1 x Ethernet• 1 x RS485• 1 x RS485 (operator panel)• 1 x RS232• 1 x Expander (up to 2 Expander)

Integrated Web-ServerThe Network Controllers are also available as variant with an integrated Web-Server.

Page 7: Building automation Controlesta RCO

Flexibility – when ever you needComplex building network or communica-tive single application – Elesta fi ts.

Expander I/O-ModuleThe Expander I/O-Module can be connected directly per quick connector with the Controller of the product series RCO 5XXD or to an Expander-Module. Up to two Expander modules can be connected to one Controller.

Pluggable terminals

Allround TalentThe product series RCO 5xxD with its highfl exibility is prepared for todays and futurerequirements of the modern building automation. The variable input and output design, the various integration abilities and the integrated Web technology makes the network controller usable for large sophisticated buildings as well as for multiple smaller building requiring remote communications.

Operator panelThe text oriented operator panelwith LCD-Display can be connected to the Network Controller as well as to the Compact Controller. The menus of all controllers in the network can be accessed by the operator panel. Up to four operator panels can be connected to one Controller.

InputsDigital-In (8 x digital inputs)• Inputs for potential free

or marked contacts 24 VAC / DC• Counting input up to 20 Hz,

Pulse width > 1 ms

OutputsDigital-Out (6 x Relays)• 230 V / 4 A / change-over-contacts

Signalisation through twocoloured, programmableLED´s per input and output

Page 8: Building automation Controlesta RCO

Building Automation System Embedded Web-Server

Innovative integrated Web– andNetwork TechnologyThe Master and Network-Controllers are available as variantswith integrated Web-Server. The innovative integrated Web–and Network-technology offers a high fl exibility and functionality.The Web-Server provides the visualisation and operation of plantdata and alarms with a standard Web-Browser. With the help ofthe Web-Browser every PC becomes an operator terminal. Theinstallation can be accessed at any time directly at the controlpanel or via Intranet or per remote control via the Internet.

Simple WEB-EngineeringThe web pages are generated time effi cient through the simpleconversion of the graphical operator menu of a web enabledController. In a network with several Controllers only one webenabled Controller is necessary to ensure the remote control ofall Controllers via the Web-Browser.

Trend-logController with an embedded Web-Server supports the indication of online– and historical data as graphical Trend-logs via a standard Web-Browser.

Page 9: Building automation Controlesta RCO

Engineering-SoftwareControlesta RCO-tool

TCP/IPMAC-Address

Effi cient EngineeringThe entire engineering process from the fi eld level across theautomation level up to the management level is based on thepowerful and established Microsoft.NET-Framework technology.The Controlesta RCO-tool serves the effi cient and economicprogramming of Controlesta RCO-D installations. It´s supportsthe engineering process starting from the confi guration via theprogramming until the commissioning and documentation.

Always OnlineThe RCO-tool offers the ability to access the Master and NetworkController in the Ethernet network via IP or MAC-Address.

Confi guration• Hardware confi guration• Alarms• Time schedules• Histories• Interactive menus• Embedded Web-Server• BACnet

Programming• Graphical and text programming can be done in parallel• Program and macro module library• Generation of individual program and macro modules• Online programming• Simple protocol implementation

Commissioning• Online Scanning of macro-modules• Scanning of the I/O-Modules• Alarm Info• Automatic generation of EDE-fi les

DocumentationPrint and export hardwareconfi guration, project tree,menu, etc.

Connect yourself. Take your benefi t from our network and competence.

Page 10: Building automation Controlesta RCO

Building Management Software Controlesta RCO-view

Controlesta RCO-view is a web-based Building Management Software designed on the modern Microsoft.Net-Framework Technology. The client server architecture enables the simultaneous access of different users (Multi-User) to one installation. The software offers a intuitive free confi gurable graphical user interface for the operation, monitoring and control of HVAC systems for the building automation system Controlesta RCO D.

The Web-Server of the Controlesta RCO-view enables the passwordprotected user access via Intranet, Internet or wireless network to aRCO-view installation from every PC in the network, respectivelyfrom any PC, notebook or PDA with Internet access. Multi-Site handling for the operation and monitoring of remote installations via all modern communication media like Ethernet, TCP/IP, modem (ISDN, GSM, GPRS and UMTS).

TCP/IP, Ethernet, Serial RS232, modem (ISDN, GSM, GPRS, UMTS)

WebClientPC/Internet

WebClientPC/Intranet

ControlestaRCO-view-Server

Internet Intranet

Wireless

Page 11: Building automation Controlesta RCO

Your benefi t• Licence free access as client

• Runs on Windows XP Professional or Windows 7

(XP Mode)

• Multi-User enabled

• Multi-Site-Handling

• Standard Browser (Firefox, IE) as GUI

• Effi cient Engineering

• Free confi gurable user interface

• Comprehensive widget library for dynamic animations in

2-D and 3-D

• Support of various graphic formats (GIF, JPEG, PNG)

On-line one, at each time,at each place.RCO-view creates transparency for all who needs access to their technology.Within seconds.

Access management for user and usergroups with username and password

Graphical indication of historical andon-line trends

Time and priority dependent dispatch ofemails, sms, printer, client

Intuitive Engineering,widget library, drag and drop positioning,online data binding

Time schedule management for weeklyand yearly schedules

Archiving of historical data

Priority and event controlled alarm andmessenger management

Event monitoring with Log-Files (alarms,user, values, commandos)

Implementation of IP cameras