BSR Inspection Case Study - Cyclone

download BSR Inspection Case Study - Cyclone

of 12

Transcript of BSR Inspection Case Study - Cyclone

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    1/12

    Case Study -2nd Regenerator Secondary Cyclones.

    Prepared By

    Mr. Tran Anh Vu

    Deputy Technical Manager

    1. Summary

    2. Drawing3. History

    4. Observation/ Findings

    5. Root Cause Analysis

    6. Recommendation

    7. Repair Method

    8. Lesson Learnt

    CONTENTS

    The RFCC unit was shut down for 2nd TA in 2014. During

    inspection secondary cyclone CY-1504 E~H in the 2nd

    regenerator D-1503 were found severe damaged. The carbon

    steel portion in the cyclone barrel were replaced with SS-304H

    material after detail analysis of root cause for damages by

    performing NDT methods like UTM, Hardness test, replica etc.

    Summary Drawing

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    2/12

    Drawing

    refractory crack

    refractory crack

    History

    In 1st TA, some crack were found in the refractory around the carbon steel

    portion of cyclone barrel

    BeforeHacking

    AfterHackingBracingBowing

    Observation/ Findings (TA 2014)

    Picture 2

    refractorycrack

    BeforeHacking

    refractorycrack

    Observation/ Findings

    Licenser Design Detail design & Actual

    LicensorDesign Detail design &Actual

    Dis-similar weld joint is slanting and near

    to 2nd regenerator shell

    Dis-similar weld joint is horizontal and

    far away from 2nd regenerator shell

    Have extrenal refractory to cover

    dis-similar weld

    125mm thick refractory outside the

    carbon steel material

    In cyclone barrel less carbon steel andmore SS material inside re-regenerator

    In cyclone more carbon steel and lessSS material inside re-generator

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    3/12

    Dis-similar

    weld joint

    Observation/ Findings

    Picture 4 shows degradation/metal flakes in cyclone barrel (Carbon

    Steel portion). For all 4 cyclones same condition

    Observation/ Findings

    CycloneF

    Dissimilar weld metal found crack in the heat affected zone of carbon steel

    portion in two cyclones E &F.

    CycloneE

    Observation/ Findings

    Picture 6b show horizontal Stiffener bracing found bend(Bowing) at

    middle of bracing & Picture 6a show crack in one of the dipleg weld

    metal

    Picture 6a Picture 6b

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    4/12

    UTM:38.8 H:115UTM:38.78H106

    H131

    Philosophy

    NDT inspection is carried out based on the API 579

    Fitness for service philosophy.For Assessment of fire damage chapter 11 fig: 11.7.

    NDT inspection are carried out step by step process

    First perform Hardness test to evaluate the hardness

    limit. If hardness limit is lower 240HB that means

    the metal is good

    If the hardness value is higher than 240 HB check the

    microstructure and follow subsequent test as per flowchart.

    UTM:38.8 H:115UTM:38.78H106

    H131

    Philosophy

    UTM:38.8 H:115UTM:38.78H106

    H131

    Observation/ Findings

    NDT- UTM ResultUTM result confirms there is no major thickness

    reduction. From the dis-similar weld zone to about 0.6

    meter in height towards Carbon Steel cannot measure the

    thickness due to high flaking of material and above 0.6

    meter For all four cyclones the similar condition.

    Picture 1 shows the thickness near the dis-similar weld

    seam is reduced about 3-4mm.

    Picture 1

    UTM:38.8 H:115UTM:38.78H106

    H131

    Observation/ Findings

    NDT- Hardness Result

    Hardness test result confirms that from the dis-

    similar weld zone to about 0.7-0.9 meter in heighttowards Carbon Steel the hardness value is very high

    around 600HB and many locations cannot measure

    hardness due to flaking. Above 0.9 meter the

    hardness value is with in the acceptable range. All

    four cyclones has the similar condition.

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    5/12

    UTM:38.8 H:115UTM:38.78H106

    UTM:39.8 H:488

    H131

    Observation/ Findings

    NDT- Replica Result

    Replica result says that Carbon steel material in the

    cyclone has undergone many damage mechanism like

    creep voids, degraded microstructure, no carbide have

    only ferrite, high temperature sulfidation, graphitation

    and microstructure degradation due to high temperature

    corrosion etc

    UTM:38.8 H:115UTM:38.78H106

    UTM:39.8 H:488

    H131

    Observation/ Findings

    NDT- Replica Result

    Cyclone H replica result says the Carbon steel material about 0.7 m above dis-similar

    weld joint has creep voids and degraded microstructure

    Report 3

    CY 1504-E

    Cyclone E replica result by PVI and Vietnam Material Institute says the Carbon steel

    material near the dis-similar weld zone is no carbide have only ferrite

    Report 4

    UTM:38.8 H:115UTM:38.78H106

    UTM:39.8

    H:

    488

    H131

    Observation/ Findings

    NDT- Replica Result

    Cyclone E replica result says the Carbon steel material about 0.5 m above

    dis-similar weld joint was damaged due to high temperature sulfidation, graphitation and

    microstructure degradation. Even after remove 5mm of degraded carbon steel material the

    replica result shows that the material microstructure structure is decomposed

    Report 5

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    6/12

    Cyclone G replica result says the Carbon steel material about 0.6 m above

    dis-similar weld joint was damaged due to high temperature sulfidation,

    Report 6 CY 1504-F

    Cyclone F replica result says the Carbon steel material about 0.3 m above

    dis-similar weld joint was partially degraded microstructure due to high

    temperature corrosion

    Report 7

    UTM:38.8 H:115UTM:38.78H106

    H131

    Observation/ Findings

    Metal Laboratory Analysis result

    The flaking metal portion was detailed analyzed in the laboratory, the

    results says that this is the corrosion product, which is iron oxide, a

    product of metal oxidation at high temperature.

    The laboratory report says the cause for corrosion at cyclone is due to the

    damage refractory. Oxygen has contacted with metal surface through the

    defect positions which led to chemical corrosion at high temperature.

    The corrosion products are iron oxides under the form of magnetite

    (Fe3O4) and hematite (-Fe2O3).

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    Replica result for CY-1504H microstructure @400X shows the

    isolated creep void.

    API 571, clause 4.2.8.3 point a says the rate of creep deformation is

    a function of the material, load, and temperature.

    API 571, clause 4.2.8 Table 4-2 says Threshold Temperatures for

    Creep for Carbon steel material is 370C

    API 571, clause 4.2.8.3 point b says If the metal temperature exceeds

    threshold temperature values, then creep damage and creep cracking

    can occur

    Creep Damage

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    7/12

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    8/12

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    9/12

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    10/12

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

    UTM:38.8 H:115UTM:38.78H106

    H131

    Root Cause Analysis

    JGC Heat Transfer Analysis

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    11/12

    UTM:38.8 H:115UTM:38.78H106

    H131

    RecommendationAPI 571 clause 4.2.8.6 point c says Creep damage is not reversible.

    Once damage or cracking is detected much of the life of the

    component has been used up and typically the options are to repair or

    replace the damaged component.

    ASM Volume 17 Table 2, creep classification table says for fewcavities of creep damage need to re-inspect after 20,000hrs (less than

    3 years estimated next Turn around)

    API 579 chapter 11 figure:11.7 says if hardness value high,

    microstructure is unacceptable, decarburized the material need to be

    replaced

    The laboratory sample test reports shows the Carbon steel metal was degraded due to high

    temperature oxidation. Referring to the above table (API-571) based on the current

    operation temperature of D-1503 the corrosion rate will be severe above 48 mils/year or

    1.21 mm/year. As per design the allowable corrosion allowance is 1.5 mm for CS and

    0.75mm for SS. This corrosion allowance is calculated for 25mm thickness of cyclone

    barrel CS material.

    Root Cause Analysis

    Key Factors Recommendation

    6. Project specification 8474L-000-JSS-6300-001 Rev-2 Clause 7.4.1 mention

    requirement for minimum weld distance is 100mm or 2T:

    Recommendation for Repair method

    Option 1: Replacement (Permanent repair) as licenser design

    The SS304H material can withstand the high temperature corrosion like

    sulfidation, graphitization, oxidation etc.

    Key factors recommendation should be considered in this option 1.

    Option 2: PatchingAPI 510 calls th is option 2 method as temporary method:Temporary repairs should be removed and replaced with suitable permanent repairs at

    the next available maintenance opportunity.

    Temporary repairs may remain in place for a longer period of time only if evaluated,

    approved, and documented by the engineer and inspector.

  • 8/11/2019 BSR Inspection Case Study - Cyclone

    12/12

    RecommendationOption 2: Patching

    Limitation for fillet welding patch

    Fillet-welded Patches

    Fillet-welded patches may be used to make temporary repairs to damaged, corroded,

    or eroded areas of pressure vessel components.

    This type of patch cannot control crack during opportunity maintenance

    As per ASME PCC-2 calls:

    i. Differential thermal expansion between the cyclone shell and the reinforcing

    lap band sleeve shall be considered in the design and application of sleeves.

    ii. Fillet welded patch repair is allowed up to 345C only. So the refractory

    work shall make sure the temperature of CS is not over 345C

    iii. ASME PCC2 clause 3.5 call The fillet weld patch thickness should be 1.4

    times the carrier steel

    7/31/2014

    Repair

    After Cyclone barrel cutting New Cyclone barrel

    7/31/2014

    Repair

    After new Cyclone barrel welding After completion of welding

    When Carbon steel material is operating under creep range

    for long period it undergoes multiple damage mechanisms.

    Replica shall be done to analysis the microstructure. Fitness

    for service should be followed to assess the damage.

    The dis-similar welding should be monitored closely at the

    every possible opportunity . When operating temperature is

    high Nickel chrome filler wire should be used rather than

    E-309 filler wire

    7/31/2014

    Lesson Learnt