IMPORTANT NOTE - TITLE BOUNDARY AND FENCE LINE LOCATIONS MAY DIFFER. OFFSETS SHOWN IN APPROXIMATE LOCATION & PLAN IS TO BE USED AS A GUIDE ONLY. IF DURING SETOUT STAGE IT IS FOUND THAT EXISTING FENCES AND APPROVED PLAN OF SUBDIVISION DO NOT MATCH BUILDER IS TO TAKE NECESSARY MEASURES AND NOT CONSTRUCT ANY WORKS IN CONTRAVENTION OF THE APPROVED DRAWINGS, A R E A A N A L Y S I S : SUBJECT SITE TOTAL AREA 920SQM (APPROX) GROUND FLOOR : 263SQM LOWER FLOOR: 131SQM ALFRESCO: 23SQM DECK: 15SQM FLOOR AREA TOTAL (INTERNAL): 394SQM / 42SQ SITE COVERAGE: 286SQM TOTAL - 31% DRIVEWAY: 88SQM PERMEABILITY: 374SQM APPROX. 60% (NOT COVERED BY HARD SURFACE) GENERAL NOTES (BCA VOL 2 - 2015) ALL MATERIALS AND WORK PRACTICES SHALL COMPLY WITH, BUT NOT LIMITED TO THE BUILDING REGULATIONS 2006, THE NATIONAL CONSTRUCTION CODE SERIES 201 5BUILDING CODE OF AUSTRALIA VOL 2 AND ALL RELEV ND CONSTRUCTION PRACTICE SHALL MEET THE PERFORMANCE REQUIREMENTS OF THE BCA. WHERE AN ALTERNATIVE SOLUTION IS PROPOSED THEN PRIOR TO IMPLEMENTATION OR INSTALLATION IT FIRST MUST BE ASSESSED AND APPROVED BY THE RELEVANT BUILDING SURVEYOR AS MEETING THE PERFORMANCE REQUIREMENTS OF THE BCA. FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS. ALL BRICKWORK SHALL COMPLY WITH AS3700 - MASONRY CODE (LATEST EDITION). BRICKWORK CONTROL JOINTS SPACED AT CENTRES AS PER ENGINEERS RECOMMENDATIONS IN CONJUNCTION WIT H BCA & NCC STANDARDS TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR. ALL SLABS & FOOTINGS TO BE CONSTRUCTED IN ACCORDANCE WITH WITH AS2870-2011 (OR LATEST EDITION). PROVIDE TREE ROOT BARRIERS IN AREAS AS REQUIRED TO ENGINEERS DESIGN & DETAILS ALL CONCRETE SHALL COMPLY WITH AS3600 SAA CONCRETE STRUCTURE CODE (LATEST EDITION) AND SHALL BE MINIMUM 20 MPA UNLESS OTHERWISE SPECIFIED. ALL FRAMING TIMBERS TO COMPLY WITH AS1684 (LATEST EDITION). ALL VENTILATION SHALL CONFORM TO THE REQUIREMENTS OF BCA SECTION F & IN THE INSTANCE OF SUB FLOOR CONSTRUCTION IE: STUMP/BEARERS/JOISTS MIN. RATE OF OF 6000M2/M RUN OF WALL TO BE ACHIEVED ALL GLAZING INCLUDING SAFETY GLAZING SHALL BE INSTALLED TO A SIZE, TYPE AND THICKNESS SO AS TO COMPLY WITH: -BCA PART 3.6 FOR CLASS 1 AND 10 BUILDINGS WITHIN A DESIGN WIND SPEED OF NOT MORE THAN N3, AND -NCC 2012 BCA VOL 1 PART B1.4 FOR CLASS 2 TO 9 BUILDINGS - AS1288-2006 & AS 2047 GLAZING PANELS WITHIN 500mm OF THE FINISHED FLOOR LEVEL AND LESS THAN 2m ARE TO BE GLAZED WITH AT LEAST 5mm ANNEALED GLASS. GLAZED PANELS NOT EXCEEDING 2mTO BE GLAZED WITH MIN. 3mm ANNEALED GLASS. GLAZING WITHIN 1.5m OF SHOWER OR BATH TO BE GLAZED WITH GRADE A SAFETY GLASS. GLAZING INCLUDING MIRRORS WITHIN 2m ABOVE FLOOR LEVEL IN BATHROOMS, ENSUITES, ROOMS AND/OR ENCLOSURES CONTAINING POOLS SPA'S SHALL BE A GRADE SAFETY GLASS. ANY DOORS OR SIDELIGHTS THAT COULD BE MISTAKEN FOR OPENINGS TO BE PROVIDED WITH SIGHT MOTIFS IN ACCORDANCE WITH AS1288 ALL POOL FENCING TO BE INSTALLED IN ACCORDANCE WITH AS1926 PARTS 1 & 2 (LATEST ADDITION) WINDOW SIZES NOMINATED ARE NOMINAL ONLY. ACTUAL SIZE MAY VARY ACCORDING TO MANUFACTURER. WINDOWS TO BE FLASHED ALL AROUND. WATERPROOFING OF WET AREAS, BEING BATHROOMS, SHOWERS, SHOWER ROOMS, LAUNDRIES, SANITARY COMPARTMENTS AND THE LIKE SHALL BE PROVIDED IN ACCORDANCE WITH AS 3740-2010: WATERPROOFING OF WET AREAS IN RESIDENTIAL BUILDINGS . ALL INTERNAL WET AREAS TO BE TO BE PROVIDED WITH AN IMPERVIOUS FLOOR & WALL COVERING. FOR WALLS 300mm ABOVE BASINS, TROUGH'S & BATHS & 1800mm ABOVE SHOWER BASES. BATHS & SHOWERS ARE NOT BE RECESSED IN AREAS WHEN SITUATED OVER LOAD BEARING WALLS WITH SUITABLE SUPPORT BEING SOUGHT AND SPECIFIED BY ENGINEER. DOORS TO WATER CLOSETS OR SIMILAR ARE TO BE FITTED WITH REMOVABLE HINGES, SLIDING OR DOORS THAT SWING AWAY FROM TOILET PAN IF WITHIN 1200mm. STEP SIZES (OTHER THAN FOR SPIRAL STAIRS) TO BE: RISERS (R) 190MM MAXIMUM AND 115MM MINIMUM GOING (G) 355MM MAXIMUM AND 240MM MINIMUM 2R + 1G = 700MM MAXIMUM AND 550MM MINIMUM WITH LESS THAN 125MM GAP BETWEEN OPEN TREADS ALL TREADS, LANDINGS AND THE LIKE TO HAVE NON SLIP FINISH OR SUITABLE NON-SKID STRIP NEAR EDGE OF NOSING. PROVIDE BALUSTRADES WHERE CHANGE IN LEVEL EXCEEDS 1000MM ABOVE THE SURFACE BENEATH LANDINGS, RAMPS AND/OR TREADS. BALUSTRADES (OTHER THAN TENSIONED WIRE BALUSTRADES) TO BE: 1000MM MIN. ABOVE FINISHED SURFACE LEVEL OF BALCONIES, LANDINGS OR THE LIKE, AND 865MM MIN. ABOVE FINISHED SURFACE LEVEL OF STAIR NOSING OR RAMP, AND VERTICAL WITH LESS THAN 125MM GAP BETWEEN, AND ANY HORIZONTAL ELEMENT WITHIN THE BALUSTRADE BETWEEN 150MM AND 760MM ABOVE THE FLOOR MUST NOT FACILITATE CLIMBING WHERE CHANGES IN LEVEL EXCEEDS 4000MM ABOVE THE SURFACE BENEATH LANDINGS, RAMPS AND/OR TREADS. WIRE BALUSTRADE CONSTRUCTION TO COMPLY WITH BCA PART 3.9.2.3 FOR CLASS 1 AND 10 BUILDINGS AND NCC 2015 BCA VOLUME 1 PART D2.16 FOR OTHER CLASSES OF BUILDINGS. SPECIFICATIONS CONCRETE STUMPS: UP TO 1400mm LONG TO BE 100mm x 100mm (1 No. H.D. WIRE) 1401mm TO 1800mm LONG TO BE 100mm X 100mm (2 No. H.D. WIRES) REFER TO ENGINEERS SPECIFICATION FOR FOOTING AND PAD DETAILS 100mm X 100mm STUMPS EXCEEDING 1200mm ABOVE GROUND LEVEL TO BE BRACED WHERE PERIMETER BASE BRICKWORK PROVIDED. PAD/STRIP FOOTINGS TO SPECIFIED DEPTH AS PER ENGINEERS DESIGN. SEE SOIL REPORT FOR SOIL CLASSIFICATION. NOTE: FOR ADDITIONS, EXTENSIONS & HOUSE RELOCATIONS & ADDITIONS SUB FLOOR CONSTRUCTION TO BE RESPONSIBILITY OF BUILDER/RELOCATION CONTRACTOR AND IN ACCORDANCE WITH BCA REQUIREMENTS AND RECOMMENDATIONS OF THE PREPARED SOIL REPORT. EXISTING SUB FLOOR STRUCTURE TO BE INSPECTED BY RELEVANT CONTRACTOR AND ANY DAMAGED MEMBERS TO BE REPAIRED OR REPLACED AS REQUIRED TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR. NO RESPONSIBILITY WILL BE TAKEN BY THIS OFFICE FOR NEW SUB FLOOR WORKS NOT DONE IN THE ACCORDANCE WITH THE ABOVE. WALLS: SEE ENGINEERS DOCUMENTATION FOR DETAILS OF WALL BRACING REQUIREMENTS 90X45X2 MGP10 TOP PLATE 90X45 MGP10 PINE BOTTOM PLATES. 90X45 MGP10 PINE STUDS AT 450 CTRS. 3.0m HEIGHT MAX. NOGGINGS 70x35 MGP10 AT 1350 CTRS JAMB STUDS. 0 - 900mm - 90x45 MGP10 901 - 1800mm - 2 x 90 x 45 MGP10 1801 - 2400mm - 2 x 90 x 45 MGP10 2401 - 3000 - 2 x 90 x 45 MGP10 70X35 MGP10 PINE NOGGINS @ 1350 CTRS PLINTH BOARDS INSTALLED UNDER WEATHERBOARD WALLS IN MATERIAL SUITABLE FOR OUTDOOR USE IF IN CONTACT WITH GROUND SURFACE AND GAPS FOR REQUIRED SUB FLOOR VENTILATION. 10MM PLASTERBOARD LINING TO INTERNAL WALLS. 13MM PLASTERBOARD LINING TO INTERNAL CEILINGS. BRACING GENERALLY IN ACCORDANCE WITH AS1684 AND/OR ENGINEERS DETAILS. BUILDER/INSTALLER OF PROPRIETARY WALL SYSTEMS AND LINING PRODUCTS IS TO ENSURE STRICT ADHERENCE WITH MANUFACTURERS SPECIFIC INSTALLATION REQUIREMENTS TO ENSURE MAXIMUM EFFICIENCY OF PRODUCT IS ACHIEVED. IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE UNDERSTANDING OF MATERIALS & PRODUCTS SPECIFIED PRIOR TO CONSTRUCTION. ROOF: SEE ENGINEERS DOCUMENTATION FOR SPECIFIED ROOF MEMBER AND CONSTRUCTION DETAILS LINTELS - SEE ENGINEERS DETAILS EXISTING ROOFS TO BE RE-COVERED AND OR EXTENDED. BUILDER/CONTRACTOR TO INSPECT ROOF STRUCTURE PRIOR TO INSTALLATION OF NEW COVER. ANY DAMAGED MEMBERS OR REPLACEMENT MEMBERS THAT ARE REQUIRED TO ENSURE STRUCTURAL INTEGRITY TO BE INSTALLED AS REQUIRED. SITE ENVIRONMENT DESIGN INFORMATION SITE BUSHFIRE ATTACK ASSESSMENT (SIMPLIFIED METHOD) BAL CLASSIFICATION 12.5 SEE REPORT PREPARED BY KEYSTONE ALLIANCE REF: 1691 FOR ALL CONSTRUCTION REQUIREMENTS SOIL CLASSIFICATION SITE CLASSIFICATION: P REFER TO SOIL REPORT: EMT040615 BY: BAYSIDE GEOTECHNICAL DESIGN GUST WIND SPEED / WIND CLASSIFICATION BUILDING TIE-DOWNS TO BE PROVIDED IN ACCORDANCE WITH AS1684-2010 FOR AN ASSUMED DESIGN GUST WIND SPEED / WIND CLASSIFICATION OF (N2) (SUBJECT TO CONFIRMATION ON SITE BY RELEVANT BUILDING SURVEYOR AT FIRST INSPECTION) REFER TO AS1684 FOR CONSTRUCTION REQUIREMENTS. CLIMATE ZONE CLIMATE ZONE FOR THERMAL DESIGN / THERMAL PERFORMANCE ASSESSMENT : ZONE 6 C ORROSION PROTECTION OF BUILT-IN STRUCTURAL MEMBERS PROVIDE CORROSION PROTECTION OF BUILT-IN STRUCTURAL STEEL MEMBERS SUCH AS STEEL LINTELS, SHELF ANGLES, CONNECTORS, ACCESSORIES (OTHER THAN WALL TIES) IN ACCORDANCE WITH TABLE 4.1 OF AS4773.1-2010 MASONRY IN SMALL BUILDINGS PART 1: DESIGN SUITABLE FOR AN ENVIRONMENT CLASSIFICATION OF 'MODERATE ENVIRONMENT' CORROSION PROTECTION FOR SHEET ROOFING PROVIDE CORROSION PROTECTION FOR SHEET ROOFING IN ACCORDANCE WITH BCA TABLE 3.5.1.1A SUITABLE FOR AN ENVIRONMENT CLASSIFICATION OF 'MODERATE ENVIRONMENT' AUTHORITIES / CONSULTANTS THESE PLANS HAVE BEEN PREPARED BY EMT PROJECTS - BEN EMMETT / DP-AD 28163 MUNICIPALITY: MOOROONDAH CITY COUNCIL SEWERAGE AUTHORITY: RELEVANT BUILDING SURVEYOR: CONTI GROUP / JEREMY CONTI CONSULTING STRUCTURAL ENGINEER: SHACKELFORD CONSUTING / CRAIG SHACKELFORD GEOTECHNICAL ENGINEER: BAYSIDE GEOTECHNICAL THERMAL PERFORMANCE ASSESSOR: KEYSTONE ALLINACE RESIDENTIAL SUSTAINABILITY MEASURES. FOR NEW CLASS 1: BUILDINGS MUST BE FITTED WITH (SEE OPTIONS BELOW) IN CONJUNCTION WITH SPECIFIED INSULATION SEEN IN THERMAL ASSESSORS REPORT PREPARED BY:KEYSTONE ALLIANCE REF: JOB NO: 10780 OPTION 1: ACHIEVE A HOUSE ENERGY RATING OF 6 STARS FOR THE BUILDING FABRIC PLUS A HOT WATER SYSTEM INSTALLED IN ACCORDANCE WITH PLUMBING REGULATION 2008 OR -OPTION 2: ACHIEVE A HOUSE ENERGY RATING OF 6 STARS FOR THE BUILDING FABRIC PLUS A 2000 LITRE RAINWATER TANK (HAVING A MIN. 50m2 ROOF CATCHMENT AREA SUPPLYING ALL SANITARY FLUSHING SYSTEMS: ARTIFICIAL LIGHTING LAMP POWER DENSITY OR ILLUMINATION POWER DENSITY OF ARTIFICIAL LIGHTING, EXCLUDING HEATERS THAT EMIT LIGHT, MUST NOT EXCEED (i) IN CLASS 1 BUILDING , 5W/M2, AND (ii) ON A VERANDAH OR BALCONY ATTACHED TO CLASS 1 BUILDING 4W/M2, AND (iii) IN CLASS 10 BUILDING, 3W/M2. WHERE ILLUMINATION POWER DENSITY IS USED, IT MAY BE INCREASED BY DIVIDING IT BY THE ILLUMINATION POWER DENSITY ADJUSTMENT FACTOR IN TABLE 3.12.5.3 AS PER PART 3.12.5.5 BCA LATEST EDITION NOTE: INSTALLATION OF LIGHTING AND RELATIVE SWITCHES TO BE IN AS PER REQUIREMENTS SET OUT IN PART 3.12.5.5 OF THE BCA - LATEST EDITION & INSTALLED TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR. IF THE SELECTION OF FITTING(S) OR PRESCRIBED WATTAGE DIFFERS OR IS GREATER THAN THAT SEEN IN SCHEDULE, INSTALLER IS TO ENSURE THAT THE ALTERED LAYOUT CONFORMS WITH THE STANDARD AND RATIOS INDICATED. ALL FINAL LIGHTING & FAN LOCATIONS AND SWITCHING TO BE CONFIRMED ON SITE BY CLIENT WITH INSTALLING CONTRACTOR PRIOR TO FINAL INSTALLATION. LIGHTS TO BE FITTED WITH DIMMER AS SPECIFIED BUILDER TO LIAISE WITH ELECTRICIAN TO ENSURE SUITABLE ACCESS FOR REPLACEMENT OF GLOBES / TRANSFORMERS ETC FOR DOWN LIGHTS PROVIDE 'ISOLITE' HEAT GUARD AND TRANSFORMER ISOLATOR TO EACH RECESSED DOWNLIGHT FITTING BY ARROWFORM PTY. LTD. OR SIMILAR APPROVED BY APPOINTED BUILDING SURVEYOR WHERE LIGHT FITTINGS REQUIRE SEPARATION FROM INSULATION MATERIAL. THIS WILL ENSURE THAT THERE IS NOT A REDUCTION OF THE REQUIRED CEILING INSULATION LEVELS. IN THE EVENT GUARDS ARE NOT FITTED BUILDER / INSTALLER IS TO UPGRADE INSULATION AS REQUIRED TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR. ALL OUTDOOR COMPONENTS TO BE WEATHER PROOF & SUITABLE FOR OUTDOOR USE. SWITCHES ADJACENT TO WET AREAS TO BE INSTALLED AS PER RELEVANT AUSTRALIAN STANDARD IN CONJUNCTION WITH BCA REQUIREMENTS, TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR TOP OF HAND RAILS TO BE MINIMUM 865MM ABOVE STAIR NOSING AND FLOOR SURFACE OF RAMPS. WHERE THE BUILDING (EXCLUDES A DETACHED CLASS 10) IS LOCATED IN A TERMITE PRONE AREA THE AREA TO UNDERSIDE OF BUILDING AND PERIMETER IS TO BE TREATED AGAINST TERMITE ATTACK. CONCRETE STUMPS: UP TO 1400MM LONG TO BE 100MM X 100MM (1 NO. H.D. WIRE) 1401MM TO 1800MM LONG TO BE 100MM X 100MM (2 NO. H.D. WIRES) 1801MM TO 3000MM LONG TO BE 125MM X 125MM (2 NO. H.D. WIRES) 100MM X 100MM STUMPS EXCEEDING 1200MM ABOVE GROUND LEVEL TO BE BRACED WHERE NO PERIMETER BASE BRICKWORK PROVIDED. FOR BUILDINGS IN MARINE OR OTHER EXPOSURE ENVIRONMENTS SHALL HAVE MASONRY UNITS, MORTAR AND ALL BUILT IN COMPONENTS AND THE LIKE COMPLYING WITH THE DURABILITY REQUIREMENTS OF TABLE 4.1 OF AS4773.1-2010 'MASONRY IN SMALL BUILDINGS' PART 1: DESIGN ALL STORMWATER TO BE TAKEN TO THE LEGAL POINT OF DISCHARGE TO THE RELEVANT AUTHORITIES APPROVAL. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL RELEVANT STRUCTURAL AND ALL OTHER CONSULTANTS DRAWINGS/DETAILS AND WITH ANY OTHER WRITTEN INSTRUCTIONS ISSUED IN THE COURSE OF THE CONTRACT. THE BUILDER SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE STABILITY AND GENERAL WATER TIGHTNESS OF ALL NEW AND/OR EXISTING STRUCTURES DURING ALL WORKS. THE BUILDER AND SUBCONTRACTORS SHALL CHECK AND VERIFY ALL DIMENSIONS, SETBACKS, LEVELS AND SPECIFICATIONS AND ALL OTHER RELEVANT DOCUMENTATION PRIOR TO THE COMMENCEMENT OF ANY WORKS. REPORT ALL DISCREPANCIES TO THIS OFFICE FOR CLARIFICATION. INSTALLATION OF ALL SERVICES SHALL COMPLY WITH THE RESPECTIVE SUPPLY AUTHORITY REQUIREMENTS. THE BUILDER AND SUBCONTRACTOR SHALL ENSURE THAT ALL STORMWATER DRAINS, SEWER PIPES AND THE LIKE ARE LOCATED AT A SUFFICIENT DISTANCE FROM ANY BUILDINGS FOOTING AND/OR SLAB EDGE BEAMS SO AS TO PREVENT GENERAL MOISTURE PENETRATION, DAMPNESS, WEAKENING AND UNDERMINING OF ANY BUILDING AND ITS FOOTING SYSTEM. THESE PLANS HAVE BEEN PREPARED FOR THE EXCLUSIVE USE BY THE CLIENT OF EMT PROJECTS FOR THE PURPOSE EXPRESSLY NOTIFIED TO THE DESIGNER. ANY OTHER PERSON WHO USES OR RELIES ON THESE PLANS WITHOUT THE DESIGNER'S WRITTEN CONSENT DOES SO AT THEIR OWN RISK AND NO RESPONSIBILITY IS ACCEPTED BY THE DESIGNER FOR SUCH USE AND/OR RELIANCE. THE APPROVAL BY THIS OFFICE OF A SUBSTITUTE MATERIAL, WORK PRACTICE, VARIATION OR THE LIKE IS NOT AN AUTHORISATION FOR ITS USE OR A CONTRACT VARIATION. ANY SAID VARIATIONS MUST BE ACCEPTED BY ALL PARTIES TO THE AGREEMENT AND WHERE APPLICABLE THE RELEVANT BUILDING SURVEYOR PRIOR TO IMPLEMENTING THE SAID VARIATION. STORMWATER 100 MM DIA. CLASS 6 UPVC STORMWATER LINE LAID TO A MINIMUM GRADE OF 1:100 AND CONNECTED TO THE LEGAL POINT OF STORMWATER DISCHARGE. PROVIDE INSPECTION OPENINGS AT 9000MM C/C AND AT EACH CHANGE OF DIRECTION. THE COVER TO UNDERGROUND STORMWATER DRAINS SHALL BE NOT LESS THAN 100MM UNDER SOIL 50MMUNDER PAVED OR CONCRETE AREAS 100MM UNDER UNREINFORCED CONCRETE OR PAVED DRIVEWAYS 75MM UNDER REINFORCED CONCRETE DRIVEWAYS THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ANY HOUSE ENERGY RATING (HERS) REPORT AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE STAMPED PLANS ENDORSED BY THE ACCREDITED THERMAL PERFORMANCE ASSESSOR WITHOUT ALTERATION IMPORTANT NOTE: LEVELS / TITLE BOUNDARY/ EASEMENT / TREE PROTECTION ZONES AND FENCE LINES REFERENCED DERIVE FROM LAND SURVEYORS DRAWINGS BY MILLAR | MERRIGAN (REF 1619P2_V4) ISSUED TO THIS OFFICE BEING RECORDED PRIOR TO EXCAVATION OF SUBJECT SITE. SEE RELEVANT DOCUMENTATION FOR DETAILS TO BE REFERENCED WITH APPROVED TOWN PLANNING PERMIT CONDITIONS AND REGISTERED PLAN OF SUBDIVISION. NO WORKS TO BE UNDERTAKEN WITHIN ANY BUILDING EXCLUSION ZONE OR EASEMENT WITHOUT APPROVAL FROM RELATIVE AUTHORITY. DIMENSIONS/LEVELS & LAYOUT OF PROPOSED NEW WORKS SHALL BE CHECKED ON SITE BY BUILDER/CONTRACTOR PRIOR TO COMMENCEMENT OF ANY WORKS. ANY DISCREPANCIES ARE TO BE REPORTED TO THE OWNER AND/OR DESIGNER IMMEDIATELY FOR RECTIFICATION. SITE CUT & FILL AREAS TO BE CHECKED AND ADJUSTED AS REQUIRED. / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / S S S S 148m 150m 153m 154m 152.87 BITUMEN DRAIN BANK / / / K A R D I N I A C R E S C E N T 187°06'40" 45.90M 99°40'40" 19.86 6 8 9 10 13 14 15 17 18 22 151m 7°06'40" 46.80 19.84 M 152m 153m 150m 149m JUNCTION PIT 152m 151m 149m - A - B - C - C - B - A BUILDER / CONTRACTOR TO REFER TO MARKERS ON SITE PROVIDED BY LAND SURVEYOR FOR CONFIRMATION OF EASEMENT & BUILDING EXCLUSION ZONE(S). DURING SETOUT IF IT IS FOUND THAT DIMENSIONS SHOWN ON PLANS ARE INCONSISTENT WITH LAND SURVEYORS MARKER(S). BUILDER TO ENSURE WORKS ARE CONTAINED WITHIN ALLOWABLE AREAS. IF DIMENSIONS ARE REQUIRED TO BE ADJUSTED THIS OFFICE IS TO BE CONTACTED. EMT PROJECTS WILL NOT BE RESPONSIBLE FOR ANY WORKS OUTSIDE ALLOWABLE ENVELOPE. A B C D 3 2 D A B C 1 D A B C PRIOR TO WORKS COMMENCING ALL LEVELS TO BE CHECKED & CONFIRMED BY RELEVANT CONTRACTOR(S) AFTER EXCAVATION TO ENSURE INSTALLATION OF ANY NEW CONSTRUCTION & SERVICES IS APPRORIATE AND IN CONJUNCTION WITH DOCUMENTS ISSUED. IF ANY FURTHER EARTHWORKS THAT ARE TO BE CONDUCTED AFTER ISSUING OF THIS DRAWING SET, DISCREPANCIES & REQUIRED ADJUSTMENTS ARE TO BE INDICATED TO SITE MANAGER/BUILDER FOR RECTIFICATION PLEASE REFER TO ENDORSED CIVIL PLAN BY APPOINTED ENGINEER FOR ALL DRAINAGE REQUIREMENTS PROPOSED DOUBLE STOREY RESIDENCE AT: 33 KARDINIA CRESCENT, WARRANWOOD VIC. FOR: DAVEY CONSTRUCTIONS SHEET 1: COVER / GENERAL NOTES / SPECIFICATION / SITE PLAN SHEET 2: GROUND FLOOR & LOWER FLOOR PLAN(S). SHEET 3: ELEVATIONS & WINDOW SCHEDULE SHEET 4: SECTION A-A & B-B SHEET 5: SECTION C-C 3 . 0 M W I D E E A S E M E N T 3 . 0 M W I D E B U I L D I N G E X C L U S I O N Z O N E 1 2 . 0 M W I D E B U I L D I N G E X C L U S I O N Z O N E 1 2 . 0 M W I D E B U I L D I N G E X C L U S I O N Z O N E RETAINING WALL (AT LOWER LEVEL OFFSET FROM WALL) TO ENGINEERS DETAILS. REFER TO RELEVANT DOCUMENTATION FOR CONSTRUCTION AND DRAINAGE REQUIREMENTS LANDSCAPING WORKS BY OTHERS. ANY BUILDING WORKS IN THIS AREA TO BE APPROVED BY RELEVANT AUTHORITY AND APPOINTED BUILDING SURVEYOR PRIOR TO COMMENCEMENT F A L L 3 ° R I D G E L I N E 4 0 0 ( W ) x 1 5 0 m m ( D ) B O X G U T T E R 4 0 0 ( W ) x 1 5 0 m m ( D ) B O X G U T T E R LINE O F ALFRESCO / MEALS WALL (BELOW) LINE O F FAMILY / DECK WALL (BELOW) LINE OF MPR WALL AT LOWEST LEVEL D E C K A L F R E S C O ( B E L O W ) F A L L 3 ° LINE OF ENTRY WALL AT LOWEST LEVEL LINE OF GARAGE WALL AT LOWEST LEVEL F A L L 3 ° F A L L 3 ° F A L L 3 ° F A L L 3 ° 4 0 0 ( W ) x 1 5 0 m m ( D ) B O X G U T T E R F F L - 1 5 3 . 4 8 G R O U N D F L O O R F F L - 1 5 0 . 2 5 G A R A G E SKY.L SKY.L BOXED FIN (UNDER) SKY.L 10430 3400 13840 12000 3020 LOWER 12000 3000 3000 13730 3000 3000 UPPER 3000 EASEMENT 12840 10640 S C A L E 1 : 1 0 0 @ A 1 N SITE PLAN V A C A N T L O T 14200 APPROX G A R A G E D R I V E W A Y APPROXIMATE LOCATION OF ADJACENT HOUSE 7350 APPROX NO: 33 NO: 35 NO: 31 NO: 29 S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S D R I V E W A Y W D 2 FOR CONSTRUCTION DATE ISSUED: 10.09.2015 THESE DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION UNLESS APPROVED / STAMPED BY APPOINTED BUILDING SURVEYOR REV B - 03.09.2015 THIS AREA HAS BEEN DESIGNATED AS LAND PRONE TO TERMITE ATTACK. BUILDER TO ENSURE BUILDING IS PROTECTED AS PER MEASURES SETOUT IN BCA / AS3660 F F L - 1 5 0 . 3 0 L O W E R F L O O R 1:100 1 5 B U I L D I N G D E S I G N C O N S U L T A N T S E M T - P R O J E C T S SHOP 3 - 20 BLACKBURN ROAD, BLACKBURN VIC 3130 p - 9878 8086 m - 0400 002 693 f - 9878 8087 [email protected] www.emtprojects.com.au REFERENCE NO: REVISION DATE: DRAWN: SHEET: OF COPYRIGHT - EMT PROJECTS RETAINS COPYRIGHT AND OWNERSHIP OF THESE PREPARED DOCUMENTS & MUST NOT BE REPRODUCED OR COPIED WITHOUT WRITTEN CONSENT FROM EMT PROJECTS. ALL RIGHTS RESERVED C SCALE: @ A1 BE A1 ORIGINAL SIZE PROPOSED DOUBLE STOREY RESIDENCE AT: 33 KARDNIA STREET, WARRANWOOD CLIENT: DAVEY CONSTRUCTIONS SEPT 2015 15-007 B CONTI GROUP BUILDING CONSULTANTS BUILDING PERMIT ISSUED 06/10/2015 NUMBER BS-U 26220-20150127/0 RELEVANT BUILDING SURVEYOR Jeremy Conti BS-U 26220 TERMITE PROTECTION REQUIRED BUSHFIRE PROTECTION REQUIRED

Transcript of BS-U 26220 99°40'40 19.86 S NO: 35 FOR:DAVEY ......OF AS4773.1-2010 MASONRY IN SMALL BUILDINGS PART...

  • IMPORTANT NOTE - TITLE BOUNDARY AND FENCE LINE LOCATIONSMAY DIFFER. OFFSETS SHOWN IN APPROXIMATE LOCATION & PLANIS TO BE USED AS A GUIDE ONLY. IF DURING SETOUT STAGE IT IS

    FOUND THAT EXISTING FENCES AND APPROVED PLAN OFSUBDIVISION DO NOT MATCH BUILDER IS TO TAKE NECESSARY

    MEASURES AND NOT CONSTRUCT ANY WORKS IN CONTRAVENTIONOF THE APPROVED DRAWINGS,

    A R E A A N A L Y S I S :

    SUBJECT SITE TOTAL AREA 920SQM (APPROX)GROUND FLOOR : 263SQMLOWER FLOOR: 131SQMALFRESCO: 23SQMDECK: 15SQMFLOOR AREA TOTAL (INTERNAL): 394SQM / 42SQ

    SITE COVERAGE: 286SQM TOTAL - 31%

    DRIVEWAY: 88SQMPERMEABILITY: 374SQM APPROX. 60%(NOT COVERED BY HARD SURFACE)

    GENERAL NOTES (BCA VOL 2 - 2015)

    ALL MATERIALS AND WORK PRACTICES SHALL COMPLY WITH, BUT NOT LIMITED TO THE BUILDINGREGULATIONS 2006, THE NATIONAL CONSTRUCTION CODE SERIES 201 5BUILDING CODE OF AUSTRALIA VOL2 AND ALL RELEV ND CONSTRUCTION PRACTICE SHALL MEET THE PERFORMANCE REQUIREMENTS OF THEBCA. WHERE AN ALTERNATIVE SOLUTION IS PROPOSED THEN PRIOR TO IMPLEMENTATION OR INSTALLATIONIT FIRST MUST BE ASSESSED AND APPROVED BY THE RELEVANT BUILDING SURVEYOR AS MEETING THEPERFORMANCE REQUIREMENTS OF THE BCA.

    FIGURED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALED DIMENSIONS.

    ALL BRICKWORK SHALL COMPLY WITH AS3700 - MASONRY CODE (LATEST EDITION). BRICKWORK CONTROL JOINTSSPACED AT CENTRES AS PER ENGINEERS RECOMMENDATIONS IN CONJUNCTION WIT H BCA & NCC STANDARDS TO THESATISFACTION OF THE APPOINTED BUILDING SURVEYOR.

    ALL SLABS & FOOTINGS TO BE CONSTRUCTED IN ACCORDANCE WITH WITH AS2870-2011 (OR LATESTEDITION). PROVIDE TREE ROOT BARRIERS IN AREAS AS REQUIRED TO ENGINEERS DESIGN & DETAILS

    ALL CONCRETE SHALL COMPLY WITH AS3600 SAA CONCRETE STRUCTURE CODE (LATEST EDITION) ANDSHALL BE MINIMUM 20 MPA UNLESS OTHERWISE SPECIFIED.

    ALL FRAMING TIMBERS TO COMPLY WITH AS1684 (LATEST EDITION).

    ALL VENTILATION SHALL CONFORM TO THE REQUIREMENTS OF BCA SECTION F & IN THE INSTANCE OF SUBFLOOR CONSTRUCTION IE: STUMP/BEARERS/JOISTS MIN. RATE OF OF 6000M2/M RUN OF WALL TO BEACHIEVED

    ALL GLAZING INCLUDING SAFETY GLAZING SHALL BE INSTALLED TO A SIZE, TYPE AND THICKNESS SO AS TOCOMPLY WITH:-BCA PART 3.6 FOR CLASS 1 AND 10 BUILDINGS WITHIN A DESIGN WIND SPEED OF NOT MORE THAN N3, AND-NCC 2012 BCA VOL 1 PART B1.4 FOR CLASS 2 TO 9 BUILDINGS- AS1288-2006 & AS 2047GLAZING PANELS WITHIN 500mm OF THE FINISHED FLOOR LEVEL AND LESS THAN 2m ARE TO BE GLAZED WITH AT

    LEAST5mm ANNEALED GLASS. GLAZED PANELS NOT EXCEEDING 2mTO BE GLAZED WITH MIN. 3mm ANNEALED GLASS.

    GLAZINGWITHIN 1.5m OF SHOWER OR BATH TO BE GLAZED WITH GRADE A SAFETY GLASS.GLAZING INCLUDING MIRRORS WITHIN 2m ABOVE FLOOR LEVEL IN BATHROOMS, ENSUITES, ROOMSAND/OR ENCLOSURES CONTAINING POOLS SPA'S SHALL BE A GRADE SAFETY GLASS.

    ANY DOORS OR SIDELIGHTS THAT COULD BE MISTAKEN FOR OPENINGS TO BE PROVIDED WITH SIGHT MOTIFS INACCORDANCE WITH AS1288

    ALL POOL FENCING TO BE INSTALLED IN ACCORDANCE WITH AS1926 PARTS 1 & 2 (LATEST ADDITION)

    WINDOW SIZES NOMINATED ARE NOMINAL ONLY. ACTUAL SIZE MAY VARY ACCORDING TO MANUFACTURER.WINDOWS TO BE FLASHED ALL AROUND.

    WATERPROOFING OF WET AREAS, BEING BATHROOMS, SHOWERS, SHOWER ROOMS, LAUNDRIES, SANITARYCOMPARTMENTS AND THE LIKE SHALL BE PROVIDED IN ACCORDANCE WITH AS 3740-2010:WATERPROOFING OF WET AREAS IN RESIDENTIAL BUILDINGS .ALL INTERNAL WET AREAS TO BE TO BE PROVIDED WITH AN IMPERVIOUS FLOOR & WALL COVERING. FORWALLS 300mm ABOVE BASINS, TROUGH'S & BATHS & 1800mm ABOVE SHOWER BASES.

    BATHS & SHOWERS ARE NOT BE RECESSED IN AREAS WHEN SITUATED OVER LOAD BEARING WALLS WITH SUITABLESUPPORT BEING SOUGHT AND SPECIFIED BY ENGINEER.

    DOORS TO WATER CLOSETS OR SIMILAR ARE TO BE FITTED WITH REMOVABLE HINGES, SLIDING OR DOORSTHAT SWING AWAY FROM TOILET PAN IF WITHIN 1200mm.

    STEP SIZES (OTHER THAN FOR SPIRAL STAIRS) TO BE:RISERS (R) 190MM MAXIMUM AND 115MM MINIMUMGOING (G) 355MM MAXIMUM AND 240MM MINIMUM2R + 1G = 700MM MAXIMUM AND 550MM MINIMUMWITH LESS THAN 125MM GAP BETWEEN OPEN TREADSALL TREADS, LANDINGS AND THE LIKE TO HAVE NON SLIP FINISH OR SUITABLE NON-SKID STRIP NEAR EDGEOF NOSING.

    PROVIDE BALUSTRADES WHERE CHANGE IN LEVEL EXCEEDS 1000MM ABOVE THE SURFACE BENEATHLANDINGS, RAMPS AND/OR TREADS. BALUSTRADES (OTHER THAN TENSIONED WIRE BALUSTRADES) TO BE:1000MM MIN. ABOVE FINISHED SURFACE LEVEL OF BALCONIES, LANDINGS OR THE LIKE, AND865MM MIN. ABOVE FINISHED SURFACE LEVEL OF STAIR NOSING OR RAMP, ANDVERTICAL WITH LESS THAN 125MM GAP BETWEEN, ANDANY HORIZONTAL ELEMENT WITHIN THE BALUSTRADE BETWEEN 150MM AND 760MM ABOVE THE FLOORMUST NOT FACILITATE CLIMBING WHERE CHANGES IN LEVEL EXCEEDS 4000MM ABOVE THE SURFACEBENEATH LANDINGS, RAMPS AND/OR TREADS.WIRE BALUSTRADE CONSTRUCTION TO COMPLY WITH BCA PART 3.9.2.3 FOR CLASS 1 AND 10 BUILDINGSAND NCC 2015 BCA VOLUME 1 PART D2.16 FOR OTHER CLASSES OF BUILDINGS.

    SPECIFICATIONS

    CONCRETE STUMPS:UP TO 1400mm LONG TO BE 100mm x 100mm (1 No. H.D. WIRE)1401mm TO 1800mm LONG TO BE 100mm X 100mm (2 No. H.D. WIRES)REFER TO ENGINEERS SPECIFICATION FOR FOOTING AND PAD DETAILS

    100mm X 100mm STUMPS EXCEEDING 1200mm ABOVE GROUND LEVEL TO BE BRACED WHERE PERIMETER BASEBRICKWORK PROVIDED.

    PAD/STRIP FOOTINGS TO SPECIFIED DEPTH AS PER ENGINEERS DESIGN. SEE SOIL REPORT FOR SOIL CLASSIFICATION.

    NOTE: FOR ADDITIONS, EXTENSIONS & HOUSE RELOCATIONS & ADDITIONS SUB FLOOR CONSTRUCTION TO BERESPONSIBILITY OF BUILDER/RELOCATION CONTRACTOR AND IN ACCORDANCE WITH BCA REQUIREMENTS ANDRECOMMENDATIONS OF THE PREPARED SOIL REPORT. EXISTING SUB FLOOR STRUCTURE TO BE INSPECTED BY RELEVANTCONTRACTOR AND ANY DAMAGED MEMBERS TO BE REPAIRED OR REPLACED AS REQUIRED TO THE SATISFACTION OF THEAPPOINTED BUILDING SURVEYOR. NO RESPONSIBILITY WILL BE TAKEN BY THIS OFFICE FOR NEW SUB FLOOR WORKS NOTDONE IN THE ACCORDANCE WITH THE ABOVE.

    WALLS:SEE ENGINEERS DOCUMENTATION FOR DETAILS OF WALL BRACING REQUIREMENTS90X45X2 MGP10 TOP PLATE90X45 MGP10 PINE BOTTOM PLATES.90X45 MGP10 PINE STUDS AT 450 CTRS. 3.0m HEIGHT MAX.NOGGINGS 70x35 MGP10 AT 1350 CTRSJAMB STUDS.0 - 900mm - 90x45 MGP10901 - 1800mm - 2 x 90 x 45 MGP101801 - 2400mm - 2 x 90 x 45 MGP102401 - 3000 - 2 x 90 x 45 MGP1070X35 MGP10 PINE NOGGINS @ 1350 CTRS

    PLINTH BOARDS INSTALLED UNDER WEATHERBOARD WALLS IN MATERIAL SUITABLE FOR OUTDOOR USE IF IN CONTACTWITH GROUND SURFACE AND GAPS FOR REQUIRED SUB FLOOR VENTILATION.

    10MM PLASTERBOARD LINING TO INTERNAL WALLS.13MM PLASTERBOARD LINING TO INTERNAL CEILINGS.

    BRACING GENERALLY IN ACCORDANCE WITH AS1684 AND/OR ENGINEERS DETAILS.BUILDER/INSTALLER OF PROPRIETARY WALL SYSTEMS AND LINING PRODUCTS IS TO ENSURE STRICT ADHERENCE WITHMANUFACTURERS SPECIFIC INSTALLATION REQUIREMENTS TO ENSURE MAXIMUM EFFICIENCY OF PRODUCT IS ACHIEVED.IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENSURE UNDERSTANDING OF MATERIALS & PRODUCTS SPECIFIEDPRIOR TO CONSTRUCTION.

    ROOF:SEE ENGINEERS DOCUMENTATION FOR SPECIFIED ROOF MEMBER AND CONSTRUCTION DETAILS

    LINTELS - SEE ENGINEERS DETAILS

    EXISTING ROOFS TO BE RE-COVERED AND OR EXTENDED.BUILDER/CONTRACTOR TO INSPECT ROOF STRUCTURE PRIOR TO INSTALLATION OF NEW COVER. ANY DAMAGEDMEMBERS OR REPLACEMENT MEMBERS THAT ARE REQUIRED TO ENSURE STRUCTURAL INTEGRITY TO BE INSTALLED ASREQUIRED.

    SITE ENVIRONMENT DESIGN INFORMATION

    SITE BUSHFIRE ATTACK ASSESSMENT (SIMPLIFIED METHOD)BAL CLASSIFICATION 12.5SEE REPORT PREPARED BY KEYSTONE ALLIANCE REF: 1691 FOR ALL CONSTRUCTION REQUIREMENTS

    SOIL CLASSIFICATIONSITE CLASSIFICATION: PREFER TO SOIL REPORT: EMT040615BY: BAYSIDE GEOTECHNICAL

    DESIGN GUST WIND SPEED / WIND CLASSIFICATIONBUILDING TIE-DOWNS TO BE PROVIDED IN ACCORDANCE WITH AS1684-2010 FOR AN ASSUMED DESIGNGUST WIND SPEED / WIND CLASSIFICATION OF (N2)(SUBJECT TO CONFIRMATION ON SITE BY RELEVANT BUILDING SURVEYOR AT FIRST INSPECTION) REFERTO AS1684 FOR CONSTRUCTION REQUIREMENTS.

    CLIMATE ZONECLIMATE ZONE FOR THERMAL DESIGN / THERMAL PERFORMANCE ASSESSMENT : ZONE 6

    CORROSION PROTECTION OF BUILT-IN STRUCTURAL MEMBERSPROVIDE CORROSION PROTECTION OF BUILT-IN STRUCTURAL STEEL MEMBERS SUCH AS STEEL LINTELS,SHELF ANGLES, CONNECTORS, ACCESSORIES (OTHER THAN WALL TIES) IN ACCORDANCE WITH TABLE 4.1OF AS4773.1-2010 MASONRY IN SMALL BUILDINGS PART 1: DESIGN SUITABLE FOR AN ENVIRONMENTCLASSIFICATION OF 'MODERATE ENVIRONMENT'CORROSION PROTECTION FOR SHEET ROOFINGPROVIDE CORROSION PROTECTION FOR SHEET ROOFING IN ACCORDANCE WITH BCA TABLE 3.5.1.1ASUITABLE FOR AN ENVIRONMENT CLASSIFICATION OF 'MODERATE ENVIRONMENT'

    AUTHORITIES / CONSULTANTSTHESE PLANS HAVE BEEN PREPARED BY EMT PROJECTS - BEN EMMETT / DP-AD 28163MUNICIPALITY: MOOROONDAH CITY COUNCILSEWERAGE AUTHORITY:RELEVANT BUILDING SURVEYOR: CONTI GROUP / JEREMY CONTICONSULTING STRUCTURAL ENGINEER: SHACKELFORD CONSUTING / CRAIG SHACKELFORDGEOTECHNICAL ENGINEER: BAYSIDE GEOTECHNICALTHERMAL PERFORMANCE ASSESSOR: KEYSTONE ALLINACE

    RESIDENTIAL SUSTAINABILITY MEASURES.

    FOR NEW CLASS 1:BUILDINGS MUST BE FITTED WITH (SEE OPTIONS BELOW) IN CONJUNCTION WITH SPECIFIED INSULATION SEEN INTHERMAL ASSESSORS REPORT PREPARED BY:KEYSTONE ALLIANCE REF: JOB NO: 10780

    OPTION 1: ACHIEVE A HOUSE ENERGY RATING OF 6 STARS FOR THE BUILDING FABRIC PLUS A HOT WATER SYSTEMINSTALLED IN ACCORDANCE WITH PLUMBING REGULATION 2008OR-OPTION 2: ACHIEVE A HOUSE ENERGY RATING OF 6 STARS FOR THE BUILDING FABRIC PLUS A2000 LITRE RAINWATER TANK (HAVING A MIN. 50m2 ROOF CATCHMENT AREA SUPPLYING ALL SANITARY FLUSHINGSYSTEMS:

    ARTIFICIAL LIGHTINGLAMP POWER DENSITY OR ILLUMINATION POWER DENSITY OF ARTIFICIAL LIGHTING, EXCLUDING HEATERSTHAT EMIT LIGHT, MUST NOT EXCEED(i) IN CLASS 1 BUILDING , 5W/M2, AND(ii) ON A VERANDAH OR BALCONY ATTACHED TO CLASS 1 BUILDING 4W/M2, AND(iii) IN CLASS 10 BUILDING, 3W/M2.WHERE ILLUMINATION POWER DENSITY IS USED, IT MAY BE INCREASED BY DIVIDING IT BY THEILLUMINATION POWER DENSITY ADJUSTMENT FACTOR IN TABLE 3.12.5.3 AS PER PART 3.12.5.5 BCA LATESTEDITION

    NOTE: INSTALLATION OF LIGHTING AND RELATIVE SWITCHES TO BE IN AS PER REQUIREMENTS SET OUT IN PART 3.12.5.5 OF THE BCA - LATESTEDITION & INSTALLED TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR. IF THE SELECTION OF FITTING(S) OR PRESCRIBED WATTAGEDIFFERS OR IS GREATER THAN THAT SEEN IN SCHEDULE, INSTALLER IS TO ENSURE THAT THE ALTERED LAYOUT CONFORMS WITH THE STANDARDAND RATIOS INDICATED.

    ALL FINAL LIGHTING & FAN LOCATIONS AND SWITCHING TO BE CONFIRMED ON SITE BY CLIENT WITH INSTALLING CONTRACTOR PRIOR TO FINALINSTALLATION. LIGHTS TO BE FITTED WITH DIMMER AS SPECIFIED

    BUILDER TO LIAISE WITH ELECTRICIAN TO ENSURE SUITABLE ACCESS FOR REPLACEMENT OF GLOBES / TRANSFORMERS ETC FOR DOWN LIGHTS

    PROVIDE 'ISOLITE' HEAT GUARD AND TRANSFORMER ISOLATOR TO EACH RECESSED DOWNLIGHT FITTING BY ARROWFORM PTY. LTD. OR SIMILARAPPROVED BY APPOINTED BUILDING SURVEYOR WHERE LIGHT FITTINGS REQUIRE SEPARATION FROM INSULATION MATERIAL. THIS WILL ENSURETHAT THERE IS NOT A REDUCTION OF THE REQUIRED CEILING INSULATION LEVELS. IN THE EVENT GUARDS ARE NOT FITTED BUILDER / INSTALLERIS TO UPGRADE INSULATION AS REQUIRED TO THE SATISFACTION OF THE APPOINTED BUILDING SURVEYOR.

    ALL OUTDOOR COMPONENTS TO BE WEATHER PROOF & SUITABLE FOR OUTDOOR USE. SWITCHES ADJACENT TO WET AREAS TO BE INSTALLED ASPER RELEVANT AUSTRALIAN STANDARD IN CONJUNCTION WITH BCA REQUIREMENTS, TO THE SATISFACTION OF THE APPOINTED BUILDINGSURVEYOR

    TOP OF HAND RAILS TO BE MINIMUM 865MM ABOVE STAIR NOSING AND FLOOR SURFACE OF RAMPS.

    WHERE THE BUILDING (EXCLUDES A DETACHED CLASS 10) IS LOCATED IN A TERMITE PRONE AREA THE AREATO UNDERSIDE OF BUILDING AND PERIMETER IS TO BE TREATED AGAINST TERMITE ATTACK.

    CONCRETE STUMPS:UP TO 1400MM LONG TO BE 100MM X 100MM (1 NO. H.D. WIRE)1401MM TO 1800MM LONG TO BE 100MM X 100MM (2 NO. H.D. WIRES)1801MM TO 3000MM LONG TO BE 125MM X 125MM (2 NO. H.D. WIRES)100MM X 100MM STUMPS EXCEEDING 1200MM ABOVE GROUND LEVEL TO BE BRACED WHERE NOPERIMETER BASE BRICKWORK PROVIDED.

    FOR BUILDINGS IN MARINE OR OTHER EXPOSURE ENVIRONMENTS SHALL HAVE MASONRY UNITS,MORTAR AND ALL BUILT IN COMPONENTS AND THE LIKE COMPLYING WITH THE DURABILITYREQUIREMENTS OF TABLE 4.1 OF AS4773.1-2010 'MASONRY IN SMALL BUILDINGS' PART 1: DESIGN

    ALL STORMWATER TO BE TAKEN TO THE LEGAL POINT OF DISCHARGE TO THE RELEVANTAUTHORITIES APPROVAL.

    THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL RELEVANT STRUCTURAL AND ALLOTHER CONSULTANTS DRAWINGS/DETAILS AND WITH ANY OTHER WRITTEN INSTRUCTIONS ISSUED INTHE COURSE OF THE CONTRACT.

    THE BUILDER SHALL TAKE ALL STEPS NECESSARY TO ENSURE THE STABILITY AND GENERAL WATERTIGHTNESS OF ALL NEW AND/OR EXISTING STRUCTURES DURING ALL WORKS.

    THE BUILDER AND SUBCONTRACTORS SHALL CHECK AND VERIFY ALL DIMENSIONS, SETBACKS, LEVELSAND SPECIFICATIONS AND ALL OTHER RELEVANT DOCUMENTATION PRIOR TO THE COMMENCEMENT OFANY WORKS. REPORT ALL DISCREPANCIES TO THIS OFFICE FOR CLARIFICATION.

    INSTALLATION OF ALL SERVICES SHALL COMPLY WITH THE RESPECTIVE SUPPLY AUTHORITYREQUIREMENTS.

    THE BUILDER AND SUBCONTRACTOR SHALL ENSURE THAT ALL STORMWATER DRAINS, SEWER PIPES ANDTHE LIKE ARE LOCATED AT A SUFFICIENT DISTANCE FROM ANY BUILDINGS FOOTING AND/OR SLAB EDGEBEAMS SO AS TO PREVENT GENERAL MOISTURE PENETRATION, DAMPNESS, WEAKENING ANDUNDERMINING OF ANY BUILDING AND ITS FOOTING SYSTEM.

    THESE PLANS HAVE BEEN PREPARED FOR THE EXCLUSIVE USE BY THE CLIENT OF EMT PROJECTS FORTHE PURPOSE EXPRESSLY NOTIFIED TO THE DESIGNER. ANY OTHER PERSON WHO USES OR RELIES ONTHESE PLANS WITHOUT THE DESIGNER'S WRITTEN CONSENT DOES SO AT THEIR OWN RISK AND NORESPONSIBILITY IS ACCEPTED BY THE DESIGNER FOR SUCH USE AND/OR RELIANCE.

    THE APPROVAL BY THIS OFFICE OF A SUBSTITUTE MATERIAL, WORK PRACTICE, VARIATION OR THE LIKEIS NOT AN AUTHORISATION FOR ITS USE OR A CONTRACT VARIATION. ANY SAID VARIATIONS MUST BEACCEPTED BY ALL PARTIES TO THE AGREEMENT AND WHERE APPLICABLE THE RELEVANT BUILDINGSURVEYOR PRIOR TO IMPLEMENTING THE SAID VARIATION.

    STORMWATER100 MM DIA. CLASS 6 UPVC STORMWATER LINE LAID TO A MINIMUM GRADE OF1:100 AND CONNECTED TO THE LEGAL POINT OF STORMWATER DISCHARGE. PROVIDE INSPECTIONOPENINGS AT 9000MM C/C AND AT EACH CHANGE OF DIRECTION.

    THE COVER TO UNDERGROUND STORMWATER DRAINS SHALL BE NOT LESS THAN100MMUNDER SOIL 50MMUNDER PAVED OR CONCRETE AREAS100MMUNDER UNREINFORCED CONCRETE OR PAVED DRIVEWAYS 75MM UNDER REINFORCED CONCRETE DRIVEWAYS

    THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ANY HOUSE ENERGY RATING (HERS) REPORTAND SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE STAMPED PLANS ENDORSED BY THEACCREDITED THERMAL PERFORMANCE ASSESSOR WITHOUT ALTERATION

    IMPORTANT NOTE: LEVELS / TITLE BOUNDARY/ EASEMENT / TREE PROTECTIONZONES AND FENCE LINES REFERENCED DERIVE FROM LAND SURVEYORS

    DRAWINGS BY MILLAR | MERRIGAN (REF 1619P2_V4) ISSUED TO THIS OFFICEBEING RECORDED PRIOR TO EXCAVATION OF SUBJECT SITE. SEE RELEVANTDOCUMENTATION FOR DETAILS TO BE REFERENCED WITH APPROVED TOWN

    PLANNING PERMIT CONDITIONS AND REGISTERED PLAN OF SUBDIVISION. NOWORKS TO BE UNDERTAKEN WITHIN ANY BUILDING EXCLUSION ZONE OR

    EASEMENT WITHOUT APPROVAL FROM RELATIVE AUTHORITY.

    DIMENSIONS/LEVELS & LAYOUT OF PROPOSED NEWWORKS SHALL BE CHECKED ON SITE BY

    BUILDER/CONTRACTOR PRIOR TO COMMENCEMENT OFANY WORKS. ANY DISCREPANCIES ARE TO BE REPORTED

    TO THE OWNER AND/OR DESIGNER IMMEDIATELY FORRECTIFICATION. SITE CUT & FILL AREAS TO BE CHECKED

    AND ADJUSTED AS REQUIRED.

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    //

    /

    ////////////////////

    S

    S

    S

    S

    148m

    150m

    153m

    154m

    152.87

    BITUMEN

    DRAIN

    BANK

    //

    /

    K A R D I N I A C R E S C E N T

    187°

    06'40

    "

    45.90

    M

    99°40'40" 19.866

    8

    9

    10

    13

    14

    15

    17

    18

    22

    151m

    7°06

    '40"

    46

    .80

    19.84 M

    152m

    153m

    150m

    149m

    JUNCTIONPIT

    152m

    151m

    149m

    -

    A

    -

    B

    -

    C

    -

    C

    -

    B

    -

    A

    BUILDER / CONTRACTOR TO REFER TO MARKERS ON SITE PROVIDED BY LANDSURVEYOR FOR CONFIRMATION OF EASEMENT & BUILDING EXCLUSION

    ZONE(S). DURING SETOUT IF IT IS FOUND THAT DIMENSIONS SHOWN ON PLANSARE INCONSISTENT WITH LAND SURVEYORS MARKER(S). BUILDER TO ENSURE

    WORKS ARE CONTAINED WITHIN ALLOWABLE AREAS. IF DIMENSIONS AREREQUIRED TO BE ADJUSTED THIS OFFICE IS TO BE CONTACTED. EMT PROJECTSWILL NOT BE RESPONSIBLE FOR ANY WORKS OUTSIDE ALLOWABLE ENVELOPE.A B C D

    3

    2

    DA B C

    1

    DA B C

    PRIOR TO WORKS COMMENCING ALL LEVELS TO BE CHECKED &CONFIRMED BY RELEVANT CONTRACTOR(S) AFTER EXCAVATION

    TO ENSURE INSTALLATION OF ANY NEW CONSTRUCTION &SERVICES IS APPRORIATE AND IN CONJUNCTION WITH

    DOCUMENTS ISSUED. IF ANY FURTHER EARTHWORKS THAT ARETO BE CONDUCTED AFTER ISSUING OF THIS DRAWING SET,DISCREPANCIES & REQUIRED ADJUSTMENTS ARE TO BE

    INDICATED TO SITE MANAGER/BUILDER FOR RECTIFICATION

    PLEASE REFER TO ENDORSED CIVIL PLAN BY APPOINTEDENGINEER FOR ALL DRAINAGE REQUIREMENTS

    PROPOSED DOUBLE STOREYRESIDENCE AT:33 KARDINIA CRESCENT,WARRANWOOD VIC.

    FOR: DAVEY CONSTRUCTIONS

    SHEET 1: COVER / GENERAL NOTES/ SPECIFICATION / SITE PLANSHEET 2: GROUND FLOOR &LOWER FLOOR PLAN(S).SHEET 3: ELEVATIONS &WINDOW SCHEDULESHEET 4: SECTION A-A & B-BSHEET 5: SECTION C-C

    3 . 0

    M

    W I D

    E

    E A S

    E M

    E N T

    3 . 0

    M

    W I D

    E

    B U

    I L D

    I N G

    E X

    C L

    U S

    I O N

    Z

    O N

    E

    1 2 . 0 M W I D E B U I L D I N G E X C L U S I O N Z O N E

    1 2 . 0 M W I D E B U I L D I N G E X C L U S I O N Z O N E

    RETAINING WALL (AT LOWER LEVEL OFFSET FROM WALL) TOENGINEERS DETAILS. REFER TO RELEVANT DOCUMENTATION FORCONSTRUCTION AND DRAINAGE REQUIREMENTS

    LANDSCAPING WORKS BY OTHERS. ANYBUILDING WORKS IN THIS AREA TO BE

    APPROVED BY RELEVANT AUTHORITY ANDAPPOINTED BUILDING SURVEYOR PRIOR TO

    COMMENCEMENT

    F A L L 3 °

    R I D

    G E

    L I N

    E

    4 0 0

    ( W

    ) x

    1 5

    0 m

    m (

    D )

    B O

    X G

    U T

    T E R

    4 0 0

    ( W

    ) x

    1 5

    0 m

    m (

    D )

    B O

    X G

    U T

    T E R

    LINE O

    F AL

    FRES

    CO /

    MEA

    LS W

    ALL (

    BELO

    W)

    LINE O

    F FA

    MILY

    / D

    ECK W

    ALL (

    BELO

    W)

    LINE O

    F MPR

    WAL

    L AT L

    OWES

    T LEV

    EL

    D E C K

    A L F R E S C O ( B E L O W )

    F A L L 3 °

    LINE OF ENTRY WALL AT LOWEST LEVEL

    LINE OF GARAGE WALL AT LOWEST LEVEL

    F A L L 3 °

    F A L L 3 °

    F A L L 3 °

    F A L L 3 °

    4 0 0

    ( W

    ) x

    1 5

    0 m

    m (

    D )

    B O

    X G

    U T

    T E R

    F F L - 1 5 3 . 4 8G R O U N D F L O O R

    F F L - 1 5 0 . 2 5G A R A G E

    SKY.L

    SKY.L

    BOXED FIN (UNDER)

    SKY.L

    1043

    0

    3400

    13840

    1200

    0

    3020 LOWER

    1200

    0

    3000 3000

    1373

    0

    3000

    3000 UPPER

    3000 EASEMENT

    1284

    010

    640

    S C A L E 1 : 1 0 0 @ A 1NSITE PLAN

    V A C A N T L O T

    14200 APPROX

    G A R A G ED R I V E W A Y

    APPROXIMATE LOCATION OFADJACENT HOUSE

    7350 APPROX

    NO: 33

    NO: 35

    NO: 31

    NO: 29

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    SS

    S

    S

    S

    S

    D R I V E W A Y

    W D 2FOR CONSTRUCTIONDATE ISSUED: 10.09.2015

    THESE DRAWINGS ARE NOT TO BE USED FORCONSTRUCTION UNLESS APPROVED / STAMPED

    BY APPOINTED BUILDING SURVEYOR

    REV B - 03.09.2015

    THIS AREA HAS BEEN DESIGNATED AS LAND PRONE TOTERMITE ATTACK. BUILDER TO ENSURE BUILDING IS

    PROTECTED AS PER MEASURES SETOUT IN BCA / AS3660

    F F L - 1 5 0 . 3 0 L O W E R F L O O R

    1:100

    1 5

    B U I L D I N G D E S I G N C O N S U L T A N T SE M T - P R O J E C T SSHOP 3 - 20 BLACKBURN ROAD, BLACKBURN VIC 3130

    p - 9878 8086 m - 0400 002 693 f - 9878 [email protected] www.emtprojects.com.au

    REFERENCE NO:

    REVISION

    DATE:

    DRAWN:

    SHEET:OF

    COPYRIGHT - EMT PROJECTS RETAINS COPYRIGHT AND OWNERSHIP OF THESE PREPARED DOCUMENTS & MUST NOT BEREPRODUCED OR COPIED WITHOUT WRITTEN CONSENT FROM EMT PROJECTS. ALL RIGHTS RESERVED

    C

    SCALE: @ A1

    BE

    A1 O

    RIGI

    NAL S

    IZE

    PROPOSED DOUBLE STOREY RESIDENCE AT:

    33 KARDNIA STREET,WARRANWOOD

    CLIENT: DAVEY CONSTRUCTIONS

    SEPT 2015 15-007

    B

    CONTI GROUPBUILDING

    CONSULTANTSBUILDING

    PERMIT

    ISSUED 06/10/2015NUMBER BS-U 26220-20150127/0

    RELEVANT BUILDING SURVEYORJeremy Conti

    BS-U 26220

    TERMITE PROTECTION REQUIREDBUSHFIRE PROTECTION REQUIRED

  • S C A L E 1 : 1 0 0 @ A 1

    1200

    0

    L I N E O F U P P E R F L O O R

    LOWERFLOOR PLAN

    L I N

    E N

    / S

    T O

    R A

    G ET WM

    GAS FIRE

    - DENOTES EXHAUST FAN DISCHARGING AT 10L/S TO MEETBCA REQUIREMENTS

    - DENOTES SMOKE ALARM. INSTALLED TO AUST. STANDARDSAND TO SATISFY BCA REQUIREMENTS PART 3.7.2 AND MUSTBE INTERCONNECTED IN THE EVENT THEY ARE ACTIVATED.

    EX

    SD

    SOIL CLASSIFICATION 'CLASS P 'REFER TO GEOTECHNICAL REPORT BY:

    BAYSIDE & SUBURBSSOIL REPORT NUMBER 040615 FOR FUTURE

    CONSTRUCTION RECOMMENDATIONSAND DETAILS.

    SPACE FLOOR AREA MAX ALLOWABLE WATTAGE

    GROUND FLOOR 263SQM 5WATTS = 1315 WATTS

    A R T I F I C I A L L I G H T I N G A L L O W A N C E

    X

    LOWER FLOOR X81SQM 5WATTS = 405 WATTS

    TOTAL ALLOWABLE INTERNAL AREAS 344 SQM X 5W = 1720 WATTS TOTAL COMBINED

    ALFRESCO 23SQM 4WATTS = 92 WATTSX

    PORCH 3SQM 4WATTS = 12 WATTSX

    TOTAL ALLOWABLE EXTERNAL AREAS 76SQM X 4W = 304WATTS TOTAL COMBINED

    GARAGE 50SQM X 3WATTS = 150 WATTS TOTAL

    BUILDER / ELECTRICIAN TO PROVIDE DOCUMENTATION ON REQUEST TO BUILDINGSURVEYOR CONFIRMING THE FITTING(S) INSTALLED DONT EXCEED ALLOWABLE RATESAS SEEN IN TABLE ABOVE.IN THE EVENT A LIGHTING PLAN IS REQUIRED BY THIS OFFICE NO WORKS TO COMMENCEUNTIL LIGHT FITTINGS ARE SELECTED AND WATTAGE CONFIRMED & ISSUED TO EMTPROJECTS FOR DOCUMENTING

    THESE DRAWINGS ARE NOT TO BE USED FORCONSTRUCTION UNLESS APPROVED / STAMPED

    BY APPOINTED BUILDING SURVEYOR

    240

    6350 OFFICE / GARAGE

    90

    3880 MPR

    90

    1100 WC

    240

    5070 MPR

    660

    90

    2280

    90

    660

    1200

    250 OH ABOVE

    230

    5510 GARAGE DOOR OPENING 240 2700 230 2140 240

    1200

    400

    11990 BUILDING OVERALL (LOWER)

    3000

    3250

    240

    2180

    90

    5490

    90

    2000

    240

    660

    660

    1423230

    8240

    240

    200

    1099

    0

    90

    2420

    2400 (ABOVE)

    1200 3400

    5750

    5120

    142054055165

    5520

    1064

    0

    2183

    0

    255

    1200

    0

    46003250

    10570

    825

    1200

    0

    240

    7140

    9027

    00

    240

    9837

    1370

    11780

    9837

    2161

    7

    C A R P E T

    SD

    EX

    DOORS CENTRED TO WALL UNLESSOTHERWISE SPECIFIED

    STAIRS SHALL BE PROVIDED WITH SUITABLE SLIP RESISTANTFINISH. TREAD SURFACE SHALL ACHIEVE A CLASSIFICATION OF P3OR R10 WHEN DRY OR P4 OR P11 WHEN TESTED IN ACCORDANCEWITH AS4586 SLIP RESISTANCE CLASSIFICATION OF NEWPEDESTRIAN MATERIALS

    BUILDER / PLUMBER TO ENSURENO SERVICES ARE INSTALLED IN

    WALL AREA FOR DOOR CAVITY

    WC DOORS TO TOILET PANS LOCATED WITHIN1.2m OF THE DOOR JAMB LIFT OFF HINGESMUST BE FITTED. OTHERWISE THE DOORSMUST SWING OUTWARDS

    1GF 2

    GF 3GF 4GF

    19GF

    18GF

    17GF

    16GF

    15GF

    14GF

    13GF

    12GF

    11GF

    10GF

    8GF

    9GF

    7GF

    6GF

    5GF

    LF25

    LF24

    LF23

    LF22

    LF21

    LF20

    240mm BRICK VENEER WALL90mm TIMBER STUD / 40mm CAVITY / 110mm BRICKW PLASTERBOARD TREATMENT AS SPECIFIED

    S C A L E 1 : 1 0 0 @ A 1

    GROUNDFLOOR PLAN

    WC DOORS TO TOILET PANS LOCATED WITHIN1.2m OF THE DOOR JAMB LIFT OFF HINGESMUST BE FITTED. OTHERWISE THE DOORS

    MUST SWING OUTWARDS

    ROBE DOORS AS SELECTED

    ROBE DOORS AS SELECTED

    ROBE

    DOO

    RS A

    S SE

    LECT

    ED

    EXEX

    EX

    EX

    EX

    C A R P E T

    C A R P E T

    C A R P E T

    C A R P E T

    T I L E S

    T I L E S

    T I L E S

    T I L E S

    T I L E S

    1880

    1270

    CPDSHELVES

    SHR

    BATH

    VBF L O O R B O A R D S

    F L O O R B O A R D S

    F L O O R B O A R D S

    F L O

    O R

    B O

    A R

    D S

    SD

    SD

    T I L E S

    SHR

    VBX2

    2050 WC 90 4600 1200 STAIR

    5030 LIVING

    90

    3555 L'DRY

    90

    1100

    90

    600

    90

    7535 DINING

    600 1300 950 1775

    3600

    11152050

    200

    1300

    1100

    1655

    1365

    3665 BATHROOM 90 2895 WIR 90 1200 90

    1555 90 915 90

    2560 ENSUITE 90 4000 BED 1 90 6320 LIVING

    13440

    1160 1570 1055 2170 1055 2170 1055 2170 1050

    13455 BUILDING OVERALL (ON ANGLE)

    100

    3555 BED 2

    90

    1100

    90

    4625 KITCHEN 4000 DECK

    3555 BED 390

    1100

    90

    190090 250

    2385

    1000

    190 464090

    5730 1400 1600

    960 1210 1055 1210 960 960 1210 1104 1210 960 3000

    13840

    400

    4180

    4360

    4180

    BED

    1

    90

    2000

    WIR

    1655

    2325

    LINE

    N13

    50 P

    'TRY

    1200

    3615

    FAMI

    LY80

    5

    9090

    9090

    90

    4050

    KITC

    HEN

    98015

    8012

    000

    1373

    0

    1315

    345

    1373

    0

    3000

    6930 5310 3400

    3000

    34003000

    445

    1284

    0

    1375

    9052

    50 S

    TAIR

    VOID

    90

    5480

    ALF

    RESC

    O10

    047

    80 FA

    MILY

    4450

    960

    2410

    2760

    2410

    2870

    240

    5000

    240

    960

    1210

    820

    1210

    960

    11410

    5480

    5160

    2205

    0

    2690

    ENSU

    ITE

    9090

    9090

    9090

    9090

    9010

    0

    900

    WC30

    00 B

    ATHR

    OOM

    1100

    PDR

    1807

    L'DR

    Y60

    033

    00 B

    ED 2

    600

    3300

    BED

    332

    00 B

    ED 4

    805

    3000

    1680

    1210

    2160

    1810

    590

    600

    480

    1570

    1560

    2170

    1920

    2170

    3930

    2185

    0

    W A

    L L

    L I N

    E

    O V E

    R A

    L L

    O V E

    R A

    L L

    W A

    L L

    L I N

    E

    O V E R A L L

    W A L L L I N E

    1200

    0

    1284

    0

    824

    O V E R A L L

    W A L L L I N E

    IF THIS PROPERTY IS LOCATED IN A DESIGNATEDTERMITE AREA (TBC).

    A SUITABLE TERMITE BARRIER IS TO BE INSTALLED INACCORDANCE WITH BCA PART 3.1.3 /OR AS 3660.1 TO

    THE SATISFACTION OF THE APPOINTED BUILDINGSURVEYOR

    IN AREAS AT JUNCTION OF DIFFERING MATERIAL FOR FLOORCOVERINGS - BUILDER CONTRACTOR TO ENSURE FINISHED

    SURFACE IS LEVEL WITH NO TRIP HAZARDS

    DIMENSIONS/LEVELS & LAYOUT OF PROPOSED NEW WORKS SHALLBE CHECKED ON SITE BY BUILDER/CONTRACTOR PRIOR TO

    COMMENCEMENT OF ANY WORKS. ANY DISCREPANCIES ARE TO BEREPORTED TO THE OWNER AND/OR DESIGNER IMMEDIATELY FOR

    RECTIFICATION. SITE CUT & FILL AREAS TO BE CHECKED ANDADJUSTED AS REQUIRED.

    MECHANICAL VENTILATION TO BE PROVIDED TO BE PROVIDED TOSANITARY COMPARTMENTS, LAUNDRY AND BATHROOM(S) DIRECTLY

    TO OUTSIDE OF BUILDING OR INTO ROOF SPACE IF ADEQUATELEYVENTILATED BY OPEN EAVES OR ROOF VENTS (OR) IS COVERED BY

    ROOF TILES WITHOUT SARKING OR SIMILAIR WHICH WOULD PREVENTVENTING THRU GAPS BETWEEN TILES

    REFER TO THERMAL ASSESSORS REPORT BY KEYSTONEALLIANCE FOR ALL INSULATION REQUIREMENTS

    REFER TO ENGINEERS DRAWINGS FOR LOCATION OF ARTICULATIONJOINTS. ARTICULATION JOINTS ARE REQUIRED EVERY 5 METRESAND ARE TO BE LOCATED AS FAR AWAY FROM A CORNER AS THE

    HEIGHT OF THE WALL, AT CHANGES IN WALL HEIGHTS ANDCHANGES IN FOUNDING MATERIALS.  THEY ARE REQUIRED TO BE

    10MM FOR MASONRY UP TO 3M AND 15MM FOR MASONRY UP TO 6M AND ARE TO BE FILLED WITH MASTIC. REFER TO RELEVANT

    DOCUMENTATION FOR CONSTRUCTION DETAILS

    230mm WIDE BRICK MASONRY WALL IN AREAS WHERESUB-FLOOR WALL HEIGHT EXCEEDS 1.6M IN HEIGHT

    110mm WIDE BRICK MASONRY SUB-FLOOR WALL230x120MM ENGAGED BRICK PIERS AT 960MM CTRS INAREAS WHERE WALL HEIGHTS ARE UNDER 1.6M

    3000

    RETAINING WALL TO ENGINEERS DETAILS. REFER TO RELEVANTDOCUMENTATION FOR CONSTRUCTION AND DRAINAGEREQUIREMENTS

    4110

    1210

    1179

    1210

    2400

    600

    480

    REFER

    TO ENG

    INEERS

    DOCU

    MENTA

    TION F

    OR SU

    BFLOO

    R

    LAYOU

    T / ME

    MBER

    SIZES

    AND C

    ONSTR

    UCTIO

    N

    REQUIR

    EMENT

    S

    RL.150.15

    5395 5445

    OUTLINE OF DECK AND STAIRS ABOVE

    6

    B

    1375

    2688

    WT2

    WT2

    WT2

    WT2

    WT2

    WT2

    WT3

    WT3

    WT3

    WT3

    WT3

    WT3

    WT3

    WT3

    6

    A

    6

    B

    7

    C

    WT1

    WT1

    WT1

    WT1

    WT1

    WT2

    WT2

    WT2

    WT2

    WT2

    WT4WT4

    WT5

    WT5

    WT5

    WT5

    GARAGE DOOR AS SELECTED INSTALLED TOINSTALLERS SPECIFICATION IN CONJUNCTIONWITH STRUCTURAL SUPPORT REQUIRED FOR

    OPENING. BUILDER TO LIAISE WITH INSTALLERTO ENSURE ALL SPATIAL REQUIREMENTS ARE

    KNOWN PRIOR TO WORKS COMMENCING

    STIFFENED RAFT SLAB TO ENGINEERS DESIGNSEE RELEVANT DOCUMENTATION FOR

    CONSTRUCTION DETAILS

    SUB SURFACE WATER TO BE DIVERTED AWAY FROMDWELLING TO COMPLY WITH BCA PART 3.1.2.3

    DEPENDANT ON SELECTED DRAINAGE TREATMENT ANDADJACENT LANDSCAPING / PAVING ETC TBC.

    SUB SURFACE WATER TO BE DIVERTED AWAY FROMDWELLING TO COMPLY WITH BCA PART 3.1.2.3

    DEPENDANT ON SELECTED DRAINAGE TREATMENT ANDADJACENT LANDSCAPING / PAVING ETC TBC.

    240mm BRICK VENEER WALL90mm TIMBER STUD / 40mm CAVITY / 110mm BRICKW PLASTERBOARD TREATMENT AS SPECIFIED

    W A L L T Y P E S C H E D U L E

    IF ALTERNATE SYSTEM OR COMBINATION IS TO BE USED FOR UPPERLIGHTWEIGHT WALL CLADDING. BUILDER / CONTRACTOR TO ISSUE RELEVANT

    MANUFACTURERS SPECIFICATION & CERTIFICATION DOCUMENTS TO APPOINTEDBUILDING SURVEYOR FOR APPROVAL PRIOR TO WORKS COMMENCING

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL SYSTEM INSTALLED TOMANUFACTURERS SPECIFICATION. WALL THICKNESS ADJUSTEDACCORDINGLY FOR ANY BRACING REQUIRED.

    INTERNAL WALLS 90mm W PLASTERBOARD TREATMENT ASSPECIFIED

    230mm WIDE BRICK MASONRY WALL IN AREAS WHERE SUB-FLOORWALL HEIGHT EXCEEDS 1.6M IN HEIGHT

    110mm WIDE BRICK MASONRY SUB-FLOOR WALL230x120MM ENGAGED BRICK PIERS AT 960MM MAX. CTRS INAREAS WHERE WALL HEIGHTS ARE UNDER 1.6M

    REFER TO ENGINEERS DRAWINGS FOR LOCATION OF ARTICULATION JOINTS.LEVELS ARE TO BE CONFIRMED AFTER EXCAVATION AND WALL TYPES FOR SUB

    FLOOR DETERMINED IN CONJUNCTION WITH ENGINEERS DESIGN.

    WT1

    WT2

    WT3

    WT4

    WT5

    SKY.L

    SKYLIGHT - VEULX OR SIMILAR INSTALLEDTO MANUFACTURERS SPECIFICATION.

    FINAL LOCATION TO BE CONFIRMED ONSITE BY OWNER PRIOR TO FRAMING OF

    SUBJECT AREA.

    SKY.L

    SKY.L

    ( R I D

    G E

    O V

    E R) LINE OF ROOF CHANGE (OVER)

    ( R I D

    G E

    O V

    E R)

    EXTENT OF ROOF OVER

    COLUMN / POST WITHINBOXED FIN. EXTERNALCLADDING AS SPECIFIED

    DOOR TO ALFRESCO AS SELECTED INSTALLED TOMANUFACTURERS SPECIFICATION IN CONJUNCTIONWITH STRUCTURAL SUPPORT REQUIRED FOROPENING. BUILDER TO LIAISE WITH INSTALLER TOENSURE ALL SPATIAL REQUIREMENTS ARE KNOWNPRIOR TO WORKS COMMENCING

    DECKING BOARDS AS SELECTED

    6

    A

    7

    C

    6

    A

    6

    B

    6

    B

    7

    C

    6

    A

    7

    C

    M P R

    E

    O F F I C E

    G A R A G E

    W D 2FOR CONSTRUCTIONDATE ISSUED: 10.09.2015

    N

    B E D 2

    B E D 4

    B E D 3

    B E D 1

    L I V I N G

    E

    D E C K

    K

    D I N I N G

    F A M I L Y

    P

    A L F R E S C O

    L

    B W I R4600

    F F L - 1 5 3 . 4 8

    F F L - 1 5 0 . 2 5

    3250

    N

    P A

    S S

    A G

    E

    O V E

    R A

    L L

    W A

    L L

    L I N

    E

    DN

    150m

    153m

    151m

    152m

    150m

    149m

    T I T L E B O U N D A R Y

    T I T L E B O U N D A R Y

    T I T

    L E

    B O

    U N

    D A

    R Y

    T I T

    L E

    B O

    U N

    D A

    R Y

    920720

    CSD

    720 CSD

    720 CSD

    820

    720

    820

    820

    820

    820

    620 CSD

    12345 6 7 8 9 1011121314 151617

    820

    820

    820

    A B C D

    3

    2

    DA B C

    1

    DA B C

    360

    1295

    1043

    010

    640

    1088

    1

    4450

    190

    DN

    12345 6

    UP

    150m

    153m

    151m

    152m

    150m

    149m

    T I T L E B O U N D A R Y

    T I T L E B O U N D A R Y

    T I T

    L E

    B O

    U N

    D A

    R Y

    T I T

    L E

    B O

    U N

    D A

    R Y

    820

    820

    820

    820820

    720

    820

    820

    12345 6 7 8 9 1011121314 151617

    A B C D

    3

    2

    DA B C

    1

    DA B C

    103515

    70

    1043

    010

    640

    20

    20805

    350350

    90 STUD

    100 90

    10090 STUD

    190100

    90 STUD

    20 LO

    WER

    OFFS

    ET

    90 S

    TUD

    100

    90 S

    TUD

    93°

    2385

    90 S

    TUD

    100

    90 S

    TUD

    100 90 STUD

    100 90

    100 90

    100 90

    100 90 10090

    10090

    10090

    3500

    3100

    71003100

    250 OH ABOVE

    3400 TO OS STUD

    4750 TO OS STUD

    3000

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL

    SYSTEM INSTALLED TO MANUFACTURERSSPECIFICATION. WALL THICKNESS

    ADJUSTED ACCORDINGLY FOR ANYBRACING REQUIRED.

    F F L - 1 5 0 . 3 0

    TENSIONED WIRE BALUSTRADE TO BE CONSTRUCTEDTO DECK PERIMETER IN ACCORDANCE WITH BCAPART 3.9.2 POST SPACED & FIXED INTO FRAME /STRUCTURE & AS REQUIRED MAX. 1.5M SPACING.MINIMUM HEIGHT OF 1.0M ABOVE UPPER FINISHEDDECK SURFACE AND SPACED SO A 80mm SPHERE ISUNABLE TO PASS THROUGH ANY OPENINGS

    TIMBER STUD WALL WITH POST WITHIN TO SUPPORT BEAMABOVE. FEATURE STONE CLADDING TO BE APPLIED TO OUTER FACE

    TO MANUFACTURERS INSTALLATION RECOMMENDATION WINDOWSIZES TO BE COS ADJUSTED AS REQUIRED

    BUILDER TO CONFIRM EXTENT OF STONE CLADDING ON SITE WITH INSTALLER ANDDIMENSIONS TO SUIT SELECTED SYSTEM. DIMENSIONS SHOWN ARE TO BRICK / STUD

    WALLS ONLY (SHOWN DASHED)

    SD

    WATERPROOFING OF ALL WET AREAS IS TO BE UNDERTAKEN INACCORDANCE WITH REFERENCED REQUIREMENTS LISTED IN

    GENERAL NOTES: CONTRACTOR / INSTALLER TO PROVIDE WRITTENCOMPLIANCE THAT WORKS HAVE BEEN UNDERTAKEN WITH AN

    APPROVED / CERTIFIED PRODUCT TO THE SATISFACTION OF THEAPPOINTED BUILDING SURVEYOR

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    THIS AREA HAS BEEN DESIGNATED AS LAND PRONE TOTERMITE ATTACK. BUILDER TO ENSURE BUILDING IS

    PROTECTED AS PER MEASURES SETOUT IN BCA / AS3660

    REV B - 03.09.2015

    500m

    m ST

    EP

    1:100

    2 5

    B U I L D I N G D E S I G N C O N S U L T A N T SE M T - P R O J E C T SSHOP 3 - 20 BLACKBURN ROAD, BLACKBURN VIC 3130

    p - 9878 8086 m - 0400 002 693 f - 9878 [email protected] www.emtprojects.com.au

    REFERENCE NO:

    REVISION

    DATE:

    DRAWN:

    SHEET:OF

    COPYRIGHT - EMT PROJECTS RETAINS COPYRIGHT AND OWNERSHIP OF THESE PREPARED DOCUMENTS & MUST NOT BEREPRODUCED OR COPIED WITHOUT WRITTEN CONSENT FROM EMT PROJECTS. ALL RIGHTS RESERVED

    C

    SCALE: @ A1

    BE

    A1 O

    RIGI

    NAL S

    IZE

    PROPOSED DOUBLE STOREY RESIDENCE AT:

    33 KARDNIA STREET,WARRANWOOD

    CLIENT: DAVEY CONSTRUCTIONS

    SEPT 2015 15-007

    B

    CONTI GROUPBUILDING

    CONSULTANTSBUILDING

    PERMIT

    ISSUED 06/10/2015NUMBER BS-U 26220-20150127/0

    RELEVANT BUILDING SURVEYORJeremy Conti

    BS-U 26220

    TERMITE PROTECTION REQUIREDBUSHFIRE PROTECTION REQUIRED

  • E A S T E L E V A T I O NS C A L E 1 : 1 0 0 @ A 1

    N O R T H E L E V A T I O NS C A L E 1 : 1 0 0 @ A 1

    2700

    2700

    2700

    W E S T E L E V A T I O NS C A L E 1 : 1 0 0 @ A 1

    S O U T H E L E V A T I O NS C A L E 1 : 1 0 0 @ A 1

    2750

    2700

    SECTIONAL GARAGE DOOR AS SELECTED INSTALLEDTO MANUFACTURERS SPECIFICATION

    LINE OF ROOF OVER ALFRESCO (INBACKGROUND)

    LINE OF BALCONY (IN BACKGROUND)

    ALUMINIUM WINDOWS IN COLOUR &CONFIGURATION AS SPECIFIED

    PARAPET WITH LOW PITCHED ROOFCONCEALED BEHIND

    ANGLED ROOF OVER ALFRESCO. SEESECTIONS FOR DETAILS

    REAR DOOR TO ALDRESC AS SELECTED

    ALUMINIUM WINDOWS IN COLOUR &CONFIGURATION AS SPECIFIED

    BRICK VENEER WALL TO LOWER FLOORRENDER FINISH IN COLOUR AS SELECTED

    TIMBER BASEBOARDS PAINTED INCOLOUR AS SELECTED

    ALUMINIUM WINDOWS IN COLOUR &CONFIGURATION AS SPECIFIED

    BRICK VENEER WALL TO LOWER FLOORRENDER FINISH IN COLOUR AS SELECTED

    RIDGE OF MAIN ROOF AT FRONT

    EXTENT OF ROOF OVER BED 4 /FAMILY ROOM

    EXTENT OF ROOF OVER KITCHEN /ALFRESCO

    TIMBER STAIRS TO REAR YARDTIMBER BASEBOARDS PAINTED INCOLOUR AS SELECTED

    F F L - 1 5 3 . 4 8

    F F L - 1 5 0 . 2 5

    F F L - 1 5 3 . 4 8

    7320

    DESCRIPTIONWIN No. SIZE (WXH)

    W I N D O W / G L A Z I N G S C H E D U L EHEAD HGT

    W15

    W16

    W17

    W18

    W19

    W20

    W21

    W22

    W01

    W02

    W04

    W03

    W06

    W05

    W08

    W07

    W10

    W09

    W11

    W12

    W13

    W141570mm x 2100mm 2400mm ALUMINIUM - AWNING

    ALL GLAZING TO COMPLY AND BE INSTALLED INACCORDANCE WITH AS1288-2006 - WINDOWS TO COMPLY WITH AS 2047ALL GLAZING IN BATHROOM OR ENSUITE WITHIN 2000mm OF FFL TO BE GRADE A SAFETY GLASS*WINDOWS TO BE IN MATERIAL FITTED WITH HARDWARE AND CONFIGURATION AS SELECTED BY OWNER**EXISTING OPENING SIZES TO BE CONFIRMED ON SITE (COS) BY SUPPLIER & BUILDER FOR WINDOWS THAT ARE BEINGREPLACED****REVEALS TO BE ADJUSTED TO SUIT TIMBER FRAME AND SELECTED CLADDING MATERIAL ACCORDINGLY.REFER TO THERMAL ASSESSORS, ENERGY RATING REPORT FOR GLAZING TYPES AND THICKNESSNOTE: WINDOW SIZES ARE SHOWN IN NOMINAL DIMENSIONS ONLY - DIMENSIONS MAY VARY DEPENDING ON MANUFACTURERSREQUIREMENTS AND EXISTING CONDITIONS. ALL SIZES TO BE CONFIRMED PRIOR TO ORDER OF MATERIALS. TIMBER WALLS ANDFRAMES TO BE BUILT IN CONJUNCTION WITH MANUFACTURERS REQUIREMENTS. IN AREAS OF MASONRY CONSTRUCTIONBUILDER IS LIAISE WITH RELATIVE TRADES TO ENSURE WINDOWS INDICATED ON DRAWINGS ARE IN CONJUNCTION WITHDIMENSIONS OF STANDARD METRIC BRICK.ALL WINDOWS ORDERED BY OWNER/BUILDER/PROJECT MANAGER ARE TO COMPLY WITH REQUIRENTS OF BCA & AS1288(LATEST EDITION).WINDOW OPENINGS ARE TO COMPLY WITH BCA 3.9.2.5 AND BE FITTED WITH DEVISE AND OR BE RESTRICTED TO OPENING SIZEAS SPECIFIED. ANY DEVICE OR SCREEN USED MUST BE ACCREDITED AND BE APPROVED BY THE APPOINTED BUILDINGSURVEYOR PRIOR TO INSTALLATION.

    W D 2FOR CONSTRUCTIONDATE ISSUED: 10.09.2015

    THESE DRAWINGS ARE NOT TO BE USED FORCONSTRUCTION UNLESS APPROVED / STAMPED

    BY APPOINTED BUILDING SURVEYOR

    4000

    PARAPET EXTENDED AT SAME LEVEL SFRONT FOR 4.0M TO SIDE WALL

    1GF

    2GF

    3GF

    4GF

    5GF

    6GF

    7GF

    8GF

    9GF

    13GF

    12GF

    11GF

    10GF

    19GF

    18GF

    17GF

    16GF

    15GF 14

    GF

    23GF

    24GF

    25GF

    LF20

    LF21

    LF22

    DESCRIPTIONWIN No. SIZE (WXH) HEAD HGT

    2170 1570

    2100

    300

    21702170

    2170mm x 2100mm 2400mm ALUMINIUM - AWNING

    2170mm x 2100mm 2400mm ALUMINIUM - AWNING

    2170mm x 2100mm 2400mm ALUMINIUM - AWNING

    2410 240

    0

    2410

    2100

    2410mm x 2100mm 2400mm ALUMINIUM - AWNING

    2400mm ALUMINIUM - AWNING

    4910

    2100

    300

    2400

    12101210

    ALUMINIUM - DOOR IN CONFIGURATION AS SELECTED

    2410mm x 2100mm

    2400mm

    ALUMINIUM - AWNING

    4910mm x 2400mm

    2400mm1210mm x 2100mm

    ALUMINIUM - AWNING2400mm1210mm x 2100mm

    2100

    300

    121012101210 1210

    2100

    300

    ALUMINIUM - AWNING2400mm1210mm x 2100mm

    ALUMINIUM - AWNING2400mm1210mm x 2100mm

    ALUMINIUM - AWNING2400mm1210mm x 2100mm

    ALUMINIUM - AWNING2400mm1210mm x 2100mm

    2170

    2100

    2170

    2170mm x 2100mm 2400mm ALUMINIUM - AWNING

    2170mm x 2100mm 2400mm ALUMINIUM - AWNING

    1210 1810 600 1570

    600

    1800 2

    400

    1570mm x 600mm 2400mm ALUMINIUM - AWNING

    2400mm ALUMINIUM - AWNING

    2400mm ALUMINIUM - AWNING

    2400mm ALUMINIUM - AWNING

    600mm x 600mm

    1810mm x 600mm

    1210mm x 600mm

    2140mm x 2400mm 2400mm ALUMINIUM - FIXED

    2400mm490mm x 2400mm

    ALUMINIUM - FIXED

    ALUMINIUM - FIXED

    2400mm490mm x 2400mmSPECIAL / DOOR COMBO

    W23

    W24

    W25

    2400

    1210

    600

    600

    2400

    1210

    2400mm ALUMINIUM - AWNING1210mm x 2400mm

    2400mm ALUMINIUM - AWNING1210mm x 2400mm

    2400mm ALUMINIUM - AWNING600mm x 600mm

    SUB SURFACE WATER TO BE DIVERTED AWAY FROMDWELLING TO COMPLY WITH BCA PART 3.1.2.3

    DEPENDANT ON SELECTED DRAINAGE TREATMENT ANDADJACENT LANDSCAPING / PAVING ETC TBC.

    WT1

    WT4

    WT5

    EXTENT OF SUBFLOOR PERIMTER WALL CONSTRUCTIONTO BE CONFIRMED ON SITE AFTER EXCAVATION WORKSAND DURING SETOUT

    240mm BRICK VENEER WALL90mm TIMBER STUD / 40mm CAVITY / 110mm BRICKW PLASTERBOARD TREATMENT AS SPECIFIED

    W A L L T Y P E S C H E D U L E

    IF ALTERNATE SYSTEM OR COMBINATION IS TO BE USED FOR UPPERLIGHTWEIGHT WALL CLADDING. BUILDER / CONTRACTOR TO ISSUE RELEVANT

    MANUFACTURERS SPECIFICATION & CERTIFICATION DOCUMENTS TO APPOINTEDBUILDING SURVEYOR FOR APPROVAL PRIOR TO WORKS COMMENCING

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL SYSTEM INSTALLED TOMANUFACTURERS SPECIFICATION. WALL THICKNESS ADJUSTEDACCORDINGLY FOR ANY BRACING REQUIRED.

    INTERNAL WALLS 90mm W PLASTERBOARD TREATMENT ASSPECIFIED

    230mm WIDE BRICK MASONRY WALL IN AREAS WHERE SUB-FLOORWALL HEIGHT EXCEEDS 1.6M IN HEIGHT

    110mm WIDE BRICK MASONRY SUB-FLOOR WALL230x120MM ENGAGED BRICK PIERS AT 960MM MAX. CTRS INAREAS WHERE WALL HEIGHTS ARE UNDER 1.6M

    REFER TO ENGINEERS DRAWINGS FOR LOCATION OF ARTICULATION JOINTS.LEVELS ARE TO BE CONFIRMED AFTER EXCAVATION AND WALL TYPES FOR SUB

    FLOOR DETERMINED IN CONJUNCTION WITH ENGINEERS DESIGN.

    WT1

    WT2

    WT3

    WT4

    WT5

    WT5

    WT3 WT3

    WT3

    WT3WT3

    4810

    WT1

    TENSIONED WIRE BALUSTRADE TO BE CONSTRUCTED TO DECK PERIMETER IN ACCORDANCEWITH BCA PART 3.9.2 POST SPACED & FIXED INTO FRAME / STRUCTURE & AS REQUIRED MAX.1.5M SPACING. MINIMUM HEIGHT OF 1.0M ABOVE UPPER FINISHED DECK SURFACE ANDSPACED SO A 80mm SPHERE IS UNABLE TO PASS THROUGH ANY OPENINGS

    WT3

    2400

    REV A - 11.08.2015

    REV A - 11.08.2015

    REV A - 11.08.2015

    RENDERED FINISH TO WALL CLADDING IN COLOUR ASSELECTED

    RENDERED FINISH TO WALL CLADDING IN COLOUR ASSELECTED

    F F L - 1 5 0 . 3 0

    F F L - 1 5 0 . 3 0F F L - 1 5 0 . 2 5F F L - 1 5 0 . 3 0

    BUILDER TO CONFIRM EXTENT OF STONECLADDING ON SITE WITH INSTALLER.

    ALL FIRST FLOOR WINDOWS WHICH ARE LESS THAN1.7M FROM FINISHED FLOOR LEVEL ARE TO BERESTRICTED TO A MAXIMUM 125mm OPENING.

    REV B - 03.09.2015

    REV B - 03.09.2015

    THIS AREA HAS BEEN DESIGNATED AS LAND PRONE TOTERMITE ATTACK. BUILDER TO ENSURE BUILDING IS

    PROTECTED AS PER MEASURES SETOUT IN BCA / AS3660

    F I N I S H E D C E I L I N G L E V E L

    F I N I S H E D C E I L I N G L E V E L

    F I N I S H E D C E I L I N G L E V E L

    F I N I S H E D F L O O R L E V E L

    F I N I S H E D F L O O R L E V E L

    F I N I S H E D F L O O R L E V E L

    1:100

    3 5

    B U I L D I N G D E S I G N C O N S U L T A N T SE M T - P R O J E C T SSHOP 3 - 20 BLACKBURN ROAD, BLACKBURN VIC 3130

    p - 9878 8086 m - 0400 002 693 f - 9878 [email protected] www.emtprojects.com.au

    REFERENCE NO:

    REVISION

    DATE:

    DRAWN:

    SHEET:OF

    COPYRIGHT - EMT PROJECTS RETAINS COPYRIGHT AND OWNERSHIP OF THESE PREPARED DOCUMENTS & MUST NOT BEREPRODUCED OR COPIED WITHOUT WRITTEN CONSENT FROM EMT PROJECTS. ALL RIGHTS RESERVED

    C

    SCALE: @ A1

    BE

    A1 O

    RIGI

    NAL S

    IZE

    PROPOSED DOUBLE STOREY RESIDENCE AT:

    33 KARDNIA STREET,WARRANWOOD

    CLIENT: DAVEY CONSTRUCTIONS

    SEPT 2015 15-007

    B

    CONTI GROUPBUILDING

    CONSULTANTSBUILDING

    PERMIT

    ISSUED 06/10/2015NUMBER BS-U 26220-20150127/0

    RELEVANT BUILDING SURVEYORJeremy Conti

    BS-U 26220

    TERMITE PROTECTION REQUIREDBUSHFIRE PROTECTION REQUIRED

  • 482

    2750

    FJ TO

    US

    TRUS

    S

    2750

    SLA

    D TO

    US

    FJ

    T I T

    L E

    B O

    U N

    D A

    R Y

    3250

    3400

    4590

    L I N

    E O

    F E

    A S

    E M

    E N T

    T I T

    L E

    B O

    U N

    D A

    R Y

    3000

    3000

    3400

    2400

    S E C T I O N A - AS C A L E 1 : 5 0 @ A 1

    S E C T I O N B - BS C A L E 1 : 5 0 @ A 1

    M A S T E R L I V I N G

    G A R A G EM P R

    STAIR

    B E D 3 A L F R E S C O K I T C H E N

    190

    41227

    00

    2700

    240

    3000

    190

    412

    230

    1100

    F F L - 1 5 3 . 4 8

    F F L - 1 5 0 . 3 0

    F F L - 1 5 3 . 4 8

    WINDOW SILLS AT OPENINGS TO BE FORMED ANDFLASHED AS REQUIRED IN CONJUNCTION WITH

    SELECTED WALL SYSTEM AND WINDOWS

    W D 2FOR CONSTRUCTIONDATE ISSUED: 10.09.2015

    THESE DRAWINGS ARE NOT TO BE USED FORCONSTRUCTION UNLESS APPROVED / STAMPED

    BY APPOINTED BUILDING SURVEYOR

    FB8

    CONTINUOUS HANDRAIL TO BE INSTALLED TO ONESIDE OF STAIRWELL AND IN CONJUNCTION WITHREQUIREMENTS OUTLINED IN BCA PART 3.9.2.4BASED ON SELECTION OF MATERIAL / SYSTEM

    DA B C

    B A T H R O O M

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL SYSTEM INSTALLED TO

    MANUFACTURERS SPECIFICATION. WALL THICKNESS ADJUSTEDACCORDINGLY FOR ANY BRACING REQUIRED.

    FLOOR JOIST SYSTEM AS SPECIFIED INSTALLED TOMANUFACTURERS INSTRUCTIONS TO BE READ IN

    CONJUNCTION WITH ENGINEERS STRUCTURAL DESIGN

    SUB SURFACE WATER TO BE DIVERTED AWAY FROMDWELLING TO COMPLY WITH BCA PART 3.1.2.3

    DEPENDANT ON SELECTED DRAINAGE TREATMENT ANDADJACENT LANDSCAPING / PAVING ETC TBC.

    WALL TYPE 1 - 240mm BRICK VENEER WALL90mm TIMBER STUD / 40mm CAVITY / 110mm BRICK

    W PLASTERBOARD TREATMENT AS SPECIFIED

    LANDSCAPING WORKS BY OTHERS. ANY WORKS IN THISAREA TO BE APPROVED BY RELEVANT AUTHORITY AND

    APPOINTED BUILDING SURVEYOR PRIOR TOCOMMENCEMENT

    FOOTING, SLAB & BEAM DESIGN TO ENGINEERS DESIGN ANDDOCUMENTATION. REFER TO RELEVANT DOCUMENTATIONFOR STRUCTURAL DETAILS AND CONSTRUCTIONREQUIREMENTS

    AREA DESIGNATED FOR SERVICES WITHIN ROOF TRUSS. SIZETO BE CONFIRMED WITH TRADES REQUIRING SPACE FOR

    SERVICES. PRIOR TO MANUFACTURERKLIPLOCK ROOF OR SIMILAR INSTALLED ON BATTENS - ROOFFRAMING @ MIN 3° PITCH. FIXING AS PER MANUFACTURERSSPECIFICATION

    FB3 (IN BACK GROUND)

    BARRIER TO BE CONSTRUCTED TO PERIMTER OF STAIR VOID INACCORDANCE WITH BCA PART 3.9.2. ASSUMED AS TIMBER STUD WALLFIXED INTO FRAME / STRUCTURE AS REQUIRED. LINED WITH PLASTER TOA MINIMUM HEIGHT OF 1.0M ABOVE UPPER FINISHED FLOOR SURFACE (TOBE CONFIRMED AND DIMENSIONS ADJUSTED ACCORDINGLY)

    LINE OF ROOF AT FRONT OF DWELLING BEHIND(SHOWN DASHED)

    JOINERY SHOWN INDICATIVE ONLY. BY OTHERS.REFER TO RELEVANT DOCUMENTATION FORDETAILS

    1100

    MIN

    TENSIONED WIRE BALUSTRADE TO BE CONSTRUCTED TO DECK PERIMETERIN ACCORDANCE WITH BCA PART 3.9.2 POST SPACED & FIXED INTOFRAME / STRUCTURE & AS REQUIRED. MINIMUM HEIGHT OF 1.0M ABOVEUPPER FINISHED DECK SURFACE AND SPACED SO A 125mm SPHERE ISUNABLE TO PASS THROUGH ANY OPENINGS

    DJ1

    WP1WP1

    FJ127

    50 FJ

    TO U

    S TR

    USS

    2700

    RB4

    P1 (IN WALL & BOXED FIN)

    TIMBER ROOF TRUSSES (SHOWN AT 3° PITCH) INSTALLEDTO MANUFACTURERS SPECIFICATION IN CONJUNCTION WITHENGINEERS DESIGN. DOCUMENTATION OF SYSTEM TO BEISSUED TO BUILDING SURVEYOR FOR APPROVAL

    TIMBER ROOF TRUSSES (SHOWN AT 3° PITCH) INSTALLEDTO MANUFACTURERS SPECIFICATION IN CONJUNCTION WITHENGINEERS DESIGN. DOCUMENTATION OF SYSTEM TO BEISSUED TO BUILDING SURVEYOR FOR APPROVAL.

    FOOTINGS & PIERS TO ENGINEERS DESIGN ANDDOCUMENTATION. REFER TO RELEVANT DOCUMENTATION

    FOR STRUCTURAL DETAILS AND CONSTRUCTIONREQUIREMENTS

    FLOOR JOIST SYSTEM AS SPECIFIED INSTALLED TOMANUFACTURERS INSTRUCTIONS TO BE READ IN

    CONJUNCTION WITH ENGINEERS STRUCTURAL DESIGN

    FB10

    RL1

    JOINERY SHOWN INDICATIVE ONLY. BY OTHERS.REFER TO RELEVANT DOCUMENTATION FORDETAILS

    DOOR TO ALFRESCO AS SELECTED INSTALLED TO MANUFACTURERSSPECIFICATION IN CONJUNCTION WITH STRUCTURAL SUPPORT REQUIREDFOR OPENING. BUILDER TO LIAISE WITH INSTALLER TO ENSURE ALLSPATIAL REQUIREMENTS ARE KNOWN PRIOR TO WORKS COMMENCING

    PARAPET WITH CAPPING FLASHED TO BOX GUTTER 400 X 150mmAND SEALED. BOX GUTTER INSTALLED WITH SUMP, CONNECTED TOEXTERNAL RAINWATER HEAD (SEE PLANS FOR LOCATIONS),DOWNPIPE AND DRAINAGE SYSTEM AS REQUIRED.

    SKYLIGHT

    NATURAL GROUND LINE SHOWN INAPPROXIMATE LOCATION

    PARAPET WITH CAPPING FLASHED TO BOX GUTTER 400 X 150mmAND SEALED. BOX GUTTER INSTALLED WITH SUMP, CONNECTED TO

    EXTERNAL RAINWATER HEAD (SEE PLANS FOR LOCATIONS),DOWNPIPE AND DRAINAGE SYSTEM AS REQUIRED.

    DOORS AS SELECTED

    ROOF EXTENSION TO BE FITTED BY BUILDER AFTERINSTALLATION OF TRUSSES. SEE ENGINEERS DETAILS FORTIMBER SIZES / FIXING DETAILS AND BRACINGREQUIREMENTS. NO WORKS ARE TO ENCROACH INTO LINE OFEASEMENT

    NATURAL GROUND LINE SHOWN INAPPROXIMATE LOCATION

    PERIMETER WALL SYSTEM TO BE DETERMINED AFTEREXCAVATION OF SUBJECT AREA AND HEIGHTS OF SUBJECT

    WALLS IS KNOWN

    SEWER IN APPROXIMATE LOCATION

    250

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL SYSTEM INSTALLED TO

    MANUFACTURERS SPECIFICATION. WALL THICKNESS ADJUSTEDACCORDINGLY FOR ANY BRACING REQUIRED.

    250

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    REV B - 03.09.2015

    ALL LEVELS SHOWN ON THIS ISSUE OF DRAWINGS ARE REFLECTIVE OF EXISTINGCONDITIONS PRIOR TO EXCAVATION WORKS & ARE TO BE USED FOR REFERENCE

    PURPOSES ONLY. FIGURED LEVELS ARE TO BE CONFIRMED BY BUILDER PRIOR TO WORKSCOMMENCING. IN THE EVENT THAT DIFFERENCES ARE RECORDED THAT CHANGE THEOVERALL HEIGHT AND REQUIRED SETBACKS THIS OFFICE IS TO BE CONTACTED FOR

    RECTIFICATION

    DIMENSIONS/LEVELS & LAYOUT OF PROPOSED NEW WORKS SHALL BE CHECKED ON SITEBY BUILDER/CONTRACTOR PRIOR TO COMMENCEMENT OF ANY WORKS. ANY

    DISCREPANCIES ARE TO BE REPORTED TO THE OWNER AND/OR DESIGNER IMMEDIATELYFOR RECTIFICATION. SITE CUT & FILL AREAS TO BE CHECKED AND ADJUSTED AS

    REQUIRED.

    REFER TO ENGINEERS DRAWINGS FOR LOCATION OF ARTICULATION JOINTS.ARTICULATION JOINTS ARE REQUIRED EVERY 5 METRES AND ARE TO BE LOCATED AS FARAWAY FROM A CORNER AS THE HEIGHT OF THE WALL, AT CHANGES IN WALL HEIGHTS ANDCHANGES IN FOUNDING MATERIALS.  THEY ARE REQUIRED TO BE 10MM FOR MASONRY UPTO 3M AND 15MM FOR MASONRY UP TO 6 M AND ARE TO BE FILLED WITH MASTIC. REFER

    TO RELEVANT DOCUMENTATION FOR CONSTRUCTION DETAILS

    SLABS / BEAMS / FOOTINGS SHOWN INDICATIVE ONLY. REFER TO ENGINEERSCOMPUTATIONS & STRUCTURAL DRAWINGS FOR ALL DETAILS

    SOIL CLASSIFICATION 'CLASS P 'REFER TO GEOTECHNICAL REPORT BY:

    BAYSIDE & SUBURBSSOIL REPORT NUMBER 040615 FOR FUTURE

    CONSTRUCTION RECOMMENDATIONSAND DETAILS.

    WINDOW SILLS AT OPENINGS TO BE FORMED ANDFLASHED AS REQUIRED IN CONJUNCTION WITH

    SELECTED WALL SYSTEM AND WINDOWS

    F F L - 1 5 0 . 2 5

    ALL FIRST FLOOR WINDOWS WHICH ARE LESS THAN1.7M FROM FINISHED FLOOR LEVEL ARE TO BERESTRICTED TO A MAXIMUM 125mm OPENING.

    REV B - 03.09.2015

    1:50

    4 5

    B U I L D I N G D E S I G N C O N S U L T A N T SE M T - P R O J E C T SSHOP 3 - 20 BLACKBURN ROAD, BLACKBURN VIC 3130

    p - 9878 8086 m - 0400 002 693 f - 9878 [email protected] www.emtprojects.com.au

    REFERENCE NO:

    REVISION

    DATE:

    DRAWN:

    SHEET:OF

    COPYRIGHT - EMT PROJECTS RETAINS COPYRIGHT AND OWNERSHIP OF THESE PREPARED DOCUMENTS & MUST NOT BEREPRODUCED OR COPIED WITHOUT WRITTEN CONSENT FROM EMT PROJECTS. ALL RIGHTS RESERVED

    C

    SCALE: @ A1

    BE

    A1 O

    RIGI

    NAL S

    IZE

    PROPOSED DOUBLE STOREY RESIDENCE AT:

    33 KARDNIA STREET,WARRANWOOD

    CLIENT: DAVEY CONSTRUCTIONS

    SEPT 2015 15-007

    B

    CONTI GROUPBUILDING

    CONSULTANTSBUILDING

    PERMIT

    ISSUED 06/10/2015NUMBER BS-U 26220-20150127/0

    RELEVANT BUILDING SURVEYORJeremy Conti

    BS-U 26220

    TERMITE PROTECTION REQUIREDBUSHFIRE PROTECTION REQUIRED

  • 150 (FR

    ONT E

    ASEME

    NT)

    151

    152

    152.60

    (REAR

    EASEM

    ENT)

    149

    153

    12000

    12000

    LINE O

    F GAR

    AGE /

    MPR

    (REA

    R)

    7000

    APP

    ROX.

    ROOF

    ZONE

    TBC

    F F L - 1 5 3 . 4 8

    F F L - 1 5 0 . 3 0

    S E C T I O N C - CS C A L E 1 : 5 0 @ A 1

    S T A I R V O I D

    F A M I L YK I T C H E N L I V I N G

    ( M A S T E R B E H I N D )

    ( S T O R E U N D E R )

    230

    2750

    FJ TO

    US

    TRUS

    S

    2750

    SLA

    D TO

    US

    FJ

    345

    412

    2700

    2700

    482

    4060

    190

    2700

    412 482

    3182

    3 2 1

    FOOTINGS & PIERS TO ENGINEERS DESIGN ANDDOCUMENTATION. REFER TO RELEVANT DOCUMENTATIONFOR STRUCTURAL DETAILS AND CONSTRUCTIONREQUIREMENTS

    BARRIER TO BE CONSTRUCTED TO PERIMTER OF STAIR VOID INACCORDANCE WITH BCA PART 3.9.2. ASSUMED AS TIMBER STUD WALLFIXED INTO FRAME / STRUCTURE AS REQUIRED. LINED WITH PLASTER TOA MINIMUM HEIGHT OF 1.0M ABOVE UPPER FINISHED FLOOR SURFACE (TOBE CONFIRMED AND DIMENSIONS ADJUSTED ACCORDINGLY)

    CONTINUOUS HANDRAIL TO BE INSTALLED TO ONE SIDE OFSTAIRWELL AND IN CONJUNCTION WITH REQUIREMENTSOUTLINED IN BCA PART 3.9.2.4 BASED ON SELECTION OFMATERIAL / SYSTEM

    FLOOR JOIST SYSTEM AS SPECIFIED INSTALLED TOMANUFACTURERS INSTRUCTIONS TO BE READ IN

    CONJUNCTION WITH ENGINEERS STRUCTURAL DESIGN

    TIMBER ROOF TRUSSES (SHOWN AT 3° PITCH) INSTALLEDTO MANUFACTURERS SPECIFICATION IN CONJUNCTION WITHENGINEERS DESIGN. DOCUMENTATION OF SYSTEM TO BEISSUED TO BUILDING SURVEYOR FOR APPROVAL

    WALL TYPE 1 - 240mm BRICK VENEER WALL90mm TIMBER STUD / 40mm CAVITY / 110mm BRICK

    W PLASTERBOARD TREATMENT AS SPECIFIEDSTAIRS CONSTRUCTED IN ACCORDANCE WITH BCA

    PART 3.9.1. ALLTREADS, LANDINGS AND THE LIKE TO HAVE NON SLIP

    FINISH OR SUITABLENON-SKID STRIP NEAR EDGE OF NOSING.

    DRAIN TO REAR OF LOWER REAR WALLCONNECTED TO STORMWATER SYSTEM TOCOUNCIL REQUIREMENTS

    JOINERY SHOWN INDICATIVE ONLY. BY OTHERS.REFER TO RELEVANT DOCUMENTATION FORDETAILS

    KLIPLOCK ROOF OR SIMILAR INSTALLED ONBATTENS - ROOF FRAMING @ MIN 3° PITCH. FIXING

    AS PER MANUFACTURERS SPECIFICATION

    ENTRY DOOR / WINDOWS TO GLAZIERS DETAILS

    HEATER / FIRE SYSTEM AS SELECTED INSTALLED TOMANUFACTURERS SPECIFICATION IN CONJUNCTION WITHREQUIREMENTS SETOUT IN BCA PART 3.7.3

    FOOTING, SLAB & BEAM DESIGN TO ENGINEERS DESIGN ANDDOCUMENTATION. REFER TO RELEVANT DOCUMENTATIONFOR STRUCTURAL DETAILS AND CONSTRUCTIONREQUIREMENTS

    NATURAL GROUND LINE SHOWN INAPPROXIMATE LOCATION

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL SYSTEM

    INSTALLED TO MANUFACTURERSSPECIFICATION. WALL THICKNESS ADJUSTEDACCORDINGLY FOR ANY BRACING REQUIRED.

    REV B - 03.09.2015

    WALL TYPE 3 - 190mm WIDE WALL.90MM STUD / 100MM MASTERWALL SYSTEMINSTALLED TO MANUFACTURERSSPECIFICATION. WALL THICKNESS ADJUSTEDACCORDINGLY FOR ANY BRACING REQUIRED.

    W D 2FOR CONSTRUCTIONDATE ISSUED: 10.09.2015

    THESE DRAWINGS ARE NOT TO BE USED FORCONSTRUCTION UNLESS APPROVED / STAMPED

    BY APPOINTED BUILDING SURVEYOR

    ALL LEVELS SHOWN ON THIS ISSUE OF DRAWINGS ARE REFLECTIVE OF EXISTINGCONDITIONS PRIOR TO EXCAVATION WORKS & ARE TO BE USED FOR REFERENCE

    PURPOSES ONLY. FIGURED LEVELS ARE TO BE CONFIRMED BY BUILDER PRIOR TO WORKSCOMMENCING. IN THE EVENT THAT DIFFERENCES ARE RECORDED THAT CHANGE THEOVERALL HEIGHT AND REQUIRED SETBACKS THIS OFFICE IS TO BE CONTACTED FOR

    RECTIFICATION

    DIMENSIONS/LEVELS & LAYOUT OF PROPOSED NEW WORKS SHALL BE CHECKED ON SITEBY BUILDER/CONTRACTOR PRIOR TO COMMENCEMENT OF ANY WORKS. ANY

    DISCREPANCIES ARE TO BE REPORTED TO THE OWNER AND/OR DESIGNER IMMEDIATELYFOR RECTIFICATION. SITE CUT & FILL AREAS TO BE CHECKED AND ADJUSTED AS

    REQUIRED.

    REFER TO ENGINEERS DRAWINGS FOR LOCATION OF ARTICULATION JOINTS.ARTICULATION JOINTS ARE REQUIRED EVERY 5 METRES AND ARE TO BE LOCATED AS FARAWAY FROM A CORNER AS THE HEIGHT OF THE WALL, AT CHANGES IN WALL HEIGHTS ANDCHANGES IN FOUNDING MATERIALS.  THEY ARE REQUIRED TO BE 10MM FOR MASONRY UPTO 3M AND 15MM FOR MASONRY UP TO 6 M AND ARE TO BE FILLED WITH MASTIC. REFER

    TO RELEVANT DOCUMENTATION FOR CONSTRUCTION DETAILS

    SLABS / BEAMS / FOOTINGS SHOWN INDICATIVE ONLY. REFER TO ENGINEERSCOMPUTATIONS & STRUCTURAL DRAWINGS FOR ALL DETAILS

    SOIL CLASSIFICATION 'CLASS P 'REFER TO GEOTECHNICAL REPORT BY:

    BAYSIDE & SUBURBSSOIL REPORT NUMBER 040615 FOR FUTURE

    CONSTRUCTION RECOMMENDATIONSAND DETAILS.

    REV B - 03.09.2015

    1:50

    5 5

    B U I L D I N G D E S I G N C O N S U L T A N T SE M T - P R O J E C T SSHOP 3 - 20 BLACKBURN ROAD, BLACKBURN VIC 3130

    p - 9878 8086 m - 0400 002 693 f - 9878 [email protected] www.emtprojects.com.au

    REFERENCE NO:

    REVISION

    DATE:

    DRAWN:

    SHEET:OF

    COPYRIGHT - EMT PROJECTS RETAINS COPYRIGHT AND OWNERSHIP OF THESE PREPARED DOCUMENTS & MUST NOT BEREPRODUCED OR COPIED WITHOUT WRITTEN CONSENT FROM EMT PROJECTS. ALL RIGHTS RESERVED

    C

    SCALE: @ A1

    BE

    A1 O

    RIGI

    NAL S

    IZE

    PROPOSED DOUBLE STOREY RESIDENCE AT:

    33 KARDNIA STREET,WARRANWOOD

    CLIENT: DAVEY CONSTRUCTIONS

    SEPT 2015 15-007

    B

    CONTI GROUPBUILDING

    CONSULTANTSBUILDING

    PERMIT

    ISSUED 06/10/2015NUMBER BS-U 26220-20150127/0

    RELEVANT BUILDING SURVEYORJeremy Conti

    BS-U 26220

    TERMITE PROTECTION REQUIREDBUSHFIRE PROTECTION REQUIRED

    Sheets and ViewsKARDINIA WD2A-1_SITEKARDINIA WD2A-2_FPSKARDINIA WD2A-3_ELEVSKARDINIA WD2A-4_SECTION_A-A_B-BKARDINIA WD2A-5_SECTION C-C