Oil coolersfor powertransformers
Axicooler
-
8/22/2019 Brochure Axicooler GB
2/10
2
The power of air
Flkt Solyvent-Ventec has been in the ventilation business since 1919.Te company specializes in the design, manufacture and sale of industrial fansand oil coolers for power transformers.
Ongoing innovation in its products and production facilities, and new fanand oil cooler technologies have made Flkt Solyvent-Ventec the Centre ofExcellence in the group worldwide for industrial centrifugal fans.
A global sales network ensures that Flkt Solyvent-Ventec customers will
enjoy a close collaboration.
ISO 9001 certification of its Environmental and Quality Managementsystems provides evidence of its commitment to a global quality policy.
-
8/22/2019 Brochure Axicooler GB
3/10
3
Design
Te oil coolers are designed andmanufactured in our Research &Production Centre based in Meyzieu
(near Lyon). Te facility housesthe most modern and advancedproduction processes:
Laser cuttingWelding robotsAutomated paint lines...
Te oil coolers are exclusively adaptedto cooling the oil used in powertransformers. Tey are designed to run
under the most stringent operatingconditions:emperatureCorrosive atmospheresDust, sand, rain and snow.
-
8/22/2019 Brochure Axicooler GB
4/10
4
Description
1 - Tube stacks
Our finned tubes, without inner
tubulators, are made of eitheraluminium or copper, depending onthe corrosion risk.
Pressure rating:+ 350,000 Pa absolute
Depression rating:+ 100 Pa absolute
Te tubes are roller expanded on athick steel tube plate (15 or 20 mm).
Internal cleanliness
After expansion the inside of each tubeis visually inspected. After the tightness
test (described below), the oil cooler isrinsed with filtered transformer oil at65C, circulating at high speed for20 minutes. Te input and outputpipes of the oil cooler are thenhermetically sealed.
Tightness testEach oil cooler undergoes a tightnesstest with hot transformer oil (65C)circulating for 3 hours at a pressure of300,000 Pa absolute.
2 - ManifoldsMade of steel, they can be bolted or
welded to the tube plate with a boltedcover. Sealing is provided with a nitrileseal.
3 - Hook-upTe inlet/outlet pipes are fastened withflanges.
4 - Air supply plenum
Te air supply plenum consists of twothick sheet side-members that connectthe tube plates, and a fan supportsheet. Spring washers on the plate/side-member attachments allow thestacks to expand.
5 - Axial fan
Tis fan, which is part of our Axipal
BZI line, ensures the lowest soundlevels and high effi ciency. Te casing,which forms a bell mouth for suctionand a diffuser for blowing, minimizespressure drops. Te blower wire guardis compliant with international safetystandards.
MotorsCompliant with internationalstandards:
foot mounted, aluminium frame,IP 55, class F, drain hole at low point.
Tey are electrically isolated from the
fan casing.
6 - Filter wire guard
7 - Electricalconnection box
Metal box compliant withinternational standards (IP 55sealing). It receives the cables fromthe fan motors (and in some casesfrom the pump). It is equipped withterminal strips and stuffi ng glands forconnection of the power cables.
Coatings
Surfaces in contact with oilAfter SA 2.5 sandblasting:
1 coat of paint resistant totransformer oil
Tickness: 20 microns.
Outer surfaces(standard version)
After SA 2.5 sandblasting:One coat of rust-proofing primerOne finishing coatotal thickness: 125 microns (other
coatings may be defined according tothe environment or specific requests).
Nuts and boltsSteel with 200h salt spray coating, zincbased.
Fan wire guardStainless steel.
BZI MA710 to 1250
Plenum top(depends on fan)
Tie rod (dependson dimensions
Side member (x2)
Plenum end-piece (x2)
Manifold (x2)
Finned tubes
-
8/22/2019 Brochure Axicooler GB
5/10
5
Accessories
Motor pump
exclusively adapted to the circulation of
transformer oilmotor integrated in pump, ensuring veryhigh reliabilityoperating safety
Filter wire guardprotection against plant fragmentseasily removable for cleaning operations
Oil circulation indicatorcontact normally closed or openalarm if oil flow stops or is too weakno maintenance required
Electrical cabinetdesigned and built as per specifications
-
8/22/2019 Brochure Axicooler GB
6/10
6
Selection charts
Selection chart for 1 oil passage
= 40k
ambient = +30C
Selection chart for 3 oil passage = 40k ambient = +30C
Dissipated
power
kW
Dissipated
power
kW
Oil flow m3/h
Figure 2
Figure 1
Oil flow m3/h
-
8/22/2019 Brochure Axicooler GB
7/10
7
Oil cooler
On the selection charts, dissipated power P40 (kW) is given as a function of the oil flow Q (m3/h) (figures 1 and 2).
Dissipated powerTe dissipated power is given for an ambientair temperature of 30C and an atmosphericpressure of 760 mm HG.
Te mean oil temperature rise () used in thecalculation is 40K.
If the mean oil temperature rise is different( = ), the new dissipated power P of the oilcooler is as follows:P = P40 + k ( - 40).k is a coeffi cient that is specific to each coolant.Its value is given in the table in figure 4.
Te selection charts allow you to select the oilcooler to perfectly suit your needs.
Motor-driven fans
Te oil coolers proposed are equipped with 2 or3 motor-driven fans whose rotational speed is720 rpm with a 50 Hz/8-pole motor or a60 Hz/10-pole motor. Te characteristics of eachmotor-driven fan are presented in the table infigure 4.
Oil inlet/outlet
Te oil coolers proposed are designed for 1 or 3oil passages inside the tube stacks. Te oil inletand outlet can then be positioned, on request, onthe respective manifolds.Note: for oil coolers with 3 oil passages, theymust be positioned symmetrically relative to axis1 (see figure 3).
Oil cooler fasteningTe oil cooler can be operated horizontally orvertically. Te supporting devices are definedaccording to demand.
Pump
o be selected on demand.
Mechanical characteristicsFor each oil cooler, the oil capacity, weight(without oil) and main dimensions are shown inthe table in figure 4.
Acoustics
Te sound power level Lwt is mentioned for eachoil cooler in the table in Figure 4. It is either 81dB(A) or 84 dB(A), depending on the number of
fans (2 or 3) in the oil cooler.
Acoustic pressure level as
per IEC 551
Acoustic pressure level at 2 meters, as perIEC 551, is defined as follows:Lp2m (dB(A)) = Lwt - 10 log SS = effective area calculated as per IEC 551.
Mobile power stationsOn request, a specific design is proposed to
withstand the shocks and vibrations due toinstallation on board of a wagon on a roadtrailer.
-
8/22/2019 Brochure Axicooler GB
8/10
8
Technical data and dimensions
Oil coolers with 1 and 3 oil passages
2 FANS (R2) 3 FANS (R3)
INLET
INLET
OUTLET OUTLET
Axis 1
Axis 1
TYPEof
oil-coolerA (mm)
Motor-driven fan (50Hz / 60 Hz 415V)Coefficient K Acoustic power
Lwt dB(A)Weight (kg)Oil capacity (l)
Per motor-driven fan
Line power (kW) Line current (A)Starting
current (A)1 passage 3 passages
R2-33-40-38xGy 2300 800 160 1.1 3 10 4.6 4.5 81
R2-33-50-38xGy 2300 850 170 1.1 3 10 - 5.2 81
R2-33-60-38xGy 2300 900 180 1.1 3 10 5.5 5.5 81
R2-33-40-38xCy 3300 1000 260 1.1 3 10 6.0 6.0 81
R2-33-50-38xCy 3300 1100 270 1.1 3 10 6.7 6.7 81
R2-33-60-38xCy 3300 1200 280 1.1 3 10 7.1 7.2 81
R3-37-40-38xCy 3300 1100 270 1.1 3 10 7.6 7.4 84
R3-37-50-38xCy 3300 1200 280 1.1 3 10 8.7 8.5 84
R3-37-60-38xCy 3300 1300 290 1.1 3 10 8.9 9.0 84
R3-37-40-38xAy 3800 1500 340 1.1 3 10 8.6 8.1 84
R3-37-50-38xAy 3800 1600 350 1.1 3 10 9.2 9.6 84
R3-37-60-38xAy 3800 1700 360 1.1 3 10 10.0 10.2 84x = C: copper tubes /A: aluminium tubes y = H: horizontal position /V: vertical position
Figure 4
Figure 3
-
8/22/2019 Brochure Axicooler GB
9/10
9
Some leading projects
NUCLEAR
SOUNDPROOFING
100 MVA
Germany ABB TransformatorenSchorch
Argentina FaradayAustria VA Tech ElinBelgium PauwelsIvory Coast CIECroatiaSpain ABB TrafosurFrance EDF - Transport/Distribution/Production
EDF - UTOEDF - HydrauliqueFrance TransfoAlstom T&DJeumont Schneider
Hungary Ganz AnsaldoIndia Bharat Heavy ElectricalsIsrael ElcoItaly ABB Distribuzione
ABB TrafoMorocco Alcatel
Lyonnaise des Eaux CasablancaNorway ABB National TransformerPoland ABB EltaPortugal EfacecUnited Kingdom ABB Power T&D
VA Tech Peebles ElectricSweden ABB TransformersSwitzerland ABB SecheronTurkey AEG - ETI
ABB Elektrik SanayiUSA Waukesha Electric SystemsYugoslavia Minel
-
8/22/2019 Brochure Axicooler GB
10/10
AXICOOLER/E-
05/2009-T
SJPG
-Pho
tos:
Pierre
Be
renger,
EDFan
dXp
ho
tolibrary
Flkt Solyvent-Ventec14 3 , r ue de la Rpublique - B.P. 6 769882 Meyzieu Cedex Francet + 33 4 72 4 5 13 00 f + 33 4 72 4 5 13 [email protected]
The Flkt Woods company reserves the right to
modify the characteristics of the apparatus describedin this document at any time. The information
contained in this document is therefore not legallybinding. For all information, please contact the
company that sells the equipment in your country.