Bradford Commercial Roofing Brochure BCA 2010

20
BRADFORD COMMERCIAL ROOFING design smart BCA 2010

description

Bradford Commercial Roofing Brochure BCA 2010

Transcript of Bradford Commercial Roofing Brochure BCA 2010

Page 1: Bradford Commercial Roofing Brochure BCA 2010

BRADFORD COMMERCIAL ROOFING

design

designsmart

BC

A 2

010

Page 2: Bradford Commercial Roofing Brochure BCA 2010
Page 3: Bradford Commercial Roofing Brochure BCA 2010

TABLE OF CONTENTS1. Overview 4

1.1.Introduction 4

1.2.TheDesignSmartProgram 4

1.3.UsingthisManual 4

2. DesigningandSpecifyingInsulation 5

2.1.TheBenefitsofUsingInsulation 5

2.2.DesigningforBCASectionJandGreenStar 5

2.3.DesigningforCondensationControl 5

2.4.DesigningforNoiseControl 5

2.5.DesigningforFireRisk 5

2.6.DesigningforSustainability 6

2.7.DesigningforInstalledCost 6

2.8.DesigningforIndoorAirQuality 6

2.9.DesigningforAgriculturalUse 6

2.10.DesigningforAesthetics 6

2.11.WhyUseBradfordProducts 6

3. RoofingDesign 7

3.1.MakingtheBCAasSimpleasABC 7

3.2.AnticonRoofSystemVeryLightRoofs 9

3.3.AnticonRoofSystemLightandDarkRoofs10

4. ApplicationsandProducts 11

4.1.Introduction 11

4.2.MaterialBaseBlanketandSystemR-Values 11

4.3.AvailableFacingsforRoofingBlanket 11

4.4.Ventilators 12

4.5.RoofingApplications 12

5. Installation-Insulation 13

5.1.General 13

5.2.InstallationofBulkInsulationBeneathMetalRoofs 13

5.3.InstallationBeneathConcreteSlabRoofs-Soffits 14

6. TechnicalInformation 15

6.1.DimensionsandWeights 15

6.2.PhysicalProperties 15

6.3.Acoustics 16

6.4.FireHazardProperties 16

6.5.ComplianceCertification 16

7. ProductsSoldbyBradford 17

8. ProductsSoldbyOthers 17

9. HealthandSafety 18

10. ProductWarranty 18

11. BradfordDesignSmart 18

Thisproductmanualcontainsalltheinformationyouneedto

design,specifyandinstallroofingsystemstomeetlocalbuilding

coderequirements.

Thismanualwasdevelopedtoserveasaguideforthosewhospecify,

useand/orinstallourproducts.BradfordInsulationmakesevery

efforttoensurethattheinformationinthismanualisuptodate.

However,asbuildingcodesaresubjecttochangeitisthe

responsibilityofthespecifierandinstallertoconfirmthatthe

productsselectedfortheirapplicationmeettherequirementsofall

aspectsoftherelevantlocalbuildingcodesandtheirproject.

Tokeepuptodatewithchangestobuildingcodes,energyefficiency

andproductinnovationourmanualsaresubjecttoperiodicchange.

Ensureyouhavethelatestrevisionofthismanualbyvisiting

www.bradfordinsulation.com.auorcontactinguson1300664653.

Pleasenotethatthisbrochurewasdevelopedinlinewiththe

requirementsoftheBuildingCodeofAustralia(2010).

Page 4: Bradford Commercial Roofing Brochure BCA 2010

1. OVERVIEW1.1. Introduction

Theroofofanycommercialprojectconstitutesamajorsurfacethatissubjecttotheeffectsofclimateandtemperature.Thiscanhaveamajoreffectonthecomfortandenergyefficiencyofthebuildingasawhole.

Theadditionofroofinsulationandventilationcanimprovetheoverallperformanceofabuilding,leadingtogreatercomfortforoccupants,costreductionsandevenimpactontheenvironment.

Bradfordhasalwaysbeenattheforefrontofinsulationdesignandouraimistohelpourcustomersmakesmarterchoiceswhendesigningandconstructingtheirbuildings.

BradfordwasthefirstAustralianinsulationcompanytocombinethebenefitsofreflectivefoilwithbuildingblankettocreateAnticon™,(anti-condensation)themosteffectiveinsulationforundermetalroofingandwallcladding.Forover30yearsAnticonhasprovidedcosteffectivethermalandacousticinsulationandcondensationcontroltohelpmakehomesandcommercialbuildingsenergyefficientandmorecomfortabletoliveandworkin.

Overtheyearswehavedevelopedourproductofferingtobeabletoprovideevenmoreeffectivesolutionsacrossawiderangeofapplications.NowwiththeinclusionofEdmondsroofventilation,Bradfordoffersthemostcomprehensivesystemstoassistyoutodevelopenergyefficientandcosteffectivebuildings.

Thismanualhelpstoclarifytheregulatoryrequirementsandsimplifytheproductselection.

Wearecommittedtocontinuousimprovementandwelcomeourcustomersfeedbackonourproductsandliterature.

1.2. TheDesignSmartProgram

Bradfordhasalwayshadaphilosophyofmakingourproductssimpleandquicktospecifyandrecognizethatthisisrequirednowmorethanever.

Werealisethatourcustomersareunderpressuretodesignnewandinnovativeprojects,whileensuringconformancetorelevantstandardsandcodesandalsomakingtheirdesignssimpletoinstall.

Nowwearewrappingthisphilosophyupinanewprogram:BradfordDesignSmart,wherewehelpyoumakeyourdesigneasier,smarterandmorereliable.

Ouraimistohelpyoufindtherightproductforyourapplicationquicklyandeasily,resultinginreduceddesigntimeandpeaceofmind.Wealsowanttoprovideyouwiththekeyinformationyouneedtoeasilycommunicatebenefitsandprojectrequirementstoowners,designers,builders,andcontractors.

1.3.UsingthisManual

Thismanualisdesignedtoprovidealltheinformationyouneedtodevelopaninformedspecificationforacommercialmetalroof.Ithasbeenstructuredinanumberofsectionstoleadyouthroughthespecificationprocess.

• Section2:Designing&SpecifyingInsulation:discussesthekeyconsiderationswhichneedtobetakenintoaccountwhendevelopingaspecification.

• Section3:RoofingDesign:helpsyouselecttheminimumrequiredinsulationnecessarytomeettheenergyefficiencyrequirementsoftheBCAforyourclassofbuilding.

• Section4:ApplicationsandProducts:allowsyoutorefineyourselectiontomeetyourspecificprojectneeds.

• Section5:Installation:ensuresyourspecifiedinsulationwillperformasintendedwhenyourprojectiscomplete.

• Section6:Technicalinformation:enablesyoutofindspecifictechnicalinformationonyourselectedproduct.

• Section7&8:Products:listsavailableproductsreferredtointhistechnicalmanual.

Thisissupportedbyadditionalinformationthatcanhelpsimplifyyourproject.

COMMERCIAL ROOFING | PAGE 4

Page 5: Bradford Commercial Roofing Brochure BCA 2010

2. DESIGNING AND SPECIFYING INSULATION2.1.TheBenefitsofUsingInsulation• HelpsmeetEnergyEfficiencyrequirements,by

providingthermalinsulation.Bymeetingtheserequirementsyoursmartdesignhelpsreducegreenhousegasemissions

• Amorecomfortableworkingenvironment,byreducingheatflowinandoutofthebuilding

• Abetterworkingenvironment,byreducingrainandotherexternalnoiseandbydampeninginternalnoise

• Asaferenvironment,asitreducesthepossibilityoffirespreadintheeventofaroof-spacefire

• Preventsdamagetoroofsheetingandinternalceilingliningsbystoppingcondensationformingundertheroof

• Reducedbuildingrunningcosts,byreducingloadrequiredtoheatandcoolthespaceand/orthesizeoftheplant

• Reduced“metalcreep”–creakingnoiseswhichoccurwhentherearesuddenexternaltemperaturechanges

2.2. DesigningforBCASectionJandGreenStar

TheBuildingCodeofAustralia(BCA)providestheminimumtotalthermalperformancerequiredforroofs.Insulationplaysamajorroleinachievingtheseminimumvalues.

InGreenStarbuildingsoneofthekeyfactorsthatcontributetoGreenStarpointsisenergyimprovement.Theupgradeofpassiveinsulationwithinabuildingcanresultinsignificantenergysavings.

RegardlessofthebuildingachievingaGreenStarratingormeetingdeemedtosatisfyprovisionsoftheBCAthereisastrongcasetoincreasespecifiedinsulationperformance,astheenergysavingscanquicklypayfortheincreaseinmarginalcosts.

AdditionallyBradfordiscommittedtoimprovingthesustainabilityofcommercialbuildingsbybecomingamemberoftheGreenBuildingCouncilofAustraliain2009.WebelieveBradfordInsulationcanaddsubstantialvaluetothelongtermsustainablefutureofcommercialpremises.

2.3. DesigningforCondensationControl

Condensationcanbecomeaproblemwhenwarm,moistaircomesincontactwithacoldermetalroof.Thiscanleadtodamageoftheroofsheetingandinternalliningsandpotentialadversehealtheffectsfrommouldandmildew.Correctspecificationofinsulationwillpreventcondensationoccurringunderneathmetalroofs.

Inmostcasestheinsulationthicknessrequiredtomeettheenergyefficiencyrequirementswillbesufficientforcondensationcontrolinmostclimatezones.AdditionalcareshouldbetakentoensuretheAnticon™thicknessselectedfortheclimatezoneissuitabletopreventcondensationoccurring,particularlyintropicalandalpineclimates,astheBCAdoesnotconsidercondensation.EvenwhenbuildingsarenotrequiredtomeettheBCAinsulationshouldstillbeconsideredtoreducethepotentialofcondensationoccurringinabuilding.

ForapplicationsintropicalclimatesAnticon™mustbeinstalledblanketfacedown,oralternativelylaytheAnticonblanketwithfoilfacingdownwardsandtheninstallanadditionallayeroffoiloverthetopoftheAnticonblanketagainsttheroofsheeting.

2.4. DesigningforNoiseControl

Anticoncanprovideconsiderableacousticbenefits.Whilereflectivefoillaminatesprovidelittleresistancetonoisetransfer,thebulkglasswoolinsulationcomponentofAnticonagainsttheroofmetalnotonlyreducesairbornenoise,itprovidesadampeningeffecttoreduceimpactnoise.Infact,Bradfordhavedevelopedaspecificproduct,Acousticon™,withscientificallyoptimisedacousticcharacteristics.Acousticon™reducesrainnoiseandeventropicalstormnoisebyupto18dB(A),whichisarounda75%reductioninloudness,comparedtoanuninsulatedmetalroof.

2.5.DesigningforFireRisk

BradfordInsulationoffersarangeofsarkingandbulkinsulationproductsthatcanmeetSpecificationC1.10andC1.10a.Refertosection6.4fordetailsonfireperformanceofproductsprovidedbyBradford.

Bradford Insulation is a member of the Green

Building Council of Australia

COMMERCIAL ROOFING | PAGE 5

Page 6: Bradford Commercial Roofing Brochure BCA 2010

2.6. DesigningforSustainability

BradfordInsulationglasswoolismanufacturedfromupto80%recycledglass.Muchofthisglassisnotsuitableforrecyclinginflatorcontainerglassmanufacture.Allwaterusedinthemanufactureofourglasswoolproductsisalsorecycled.

BradfordInsulationhasundertakenanauditofourglasswool,rockwoolandreflectivefoillaminateinsulationmanufacturingprocessesreferencingtheUSEPAListofOzoneDepletingSubstances(Class1andClass2).Thisauditfoundthatnoozonedepletingsubstancesareinvolvedineitherthemanufactureorcompositionoftheseproducts.

OurconclusionisthatBradfordInsulation’sglasswool,rockwoolandreflectivefoillaminateshaveanOzoneDepletingPotentialofzero.

Environmentalstudieshaveshownthatglasswoolandrockwoolproductshavelowembodiedenergy.Bradfordrecognisesthat,asaninsulationsupplier,wehaveasignificantroletoplayinthepassivereductionofenergyuseinourworld.

2.7.DesigningforInstalledCost

BradfordoffersaCuttoLengthservice,whereourroofblanketisdeliveredtositepre-cuttosize.Thisresultsinasignificantreductionintimeandwaste,leadingtolowerinstallationcosts.Bradfordoffersarangeofheavierdutyfoilswhichhelptoreducedamageandreworkduringinstallation.

2.8.DesigningforIndoorAirQuality

BradfordandEdmondsofferarangeofroofventsthatcanimprovetheoverallperformanceofabuilding.Edmondscancarryoutdesigncalculationstoshowhowtheadditionofventswillimprovethebuilding’sthermalperformanceandimprovetheairqualityforpersonnelwithinthebuilding.Bradford’sglasswoolandrockwoolinsulationhavebeentestedandfoundtohavelowVOC.FormoreinformationcontactBradfordInsulation.

2.9.DesigningforAgriculturalUse

Bradfordoffersarangeofproductsdesignedtoresisttheconditionsfoundinagriculturaluse.BradfordAgricon™isspeciallydesignedforareaswithacorrosiveenvironmentorwhichrequirewashdownsuchaspoultryandanimalhusbandryapplicationsandisavailableintwocolours:offwhiteandforestgreen.

2.10. DesigningforAesthetics

UseoftherightfoilfacingonyourAnticoncancontributetotheaestheticfinishofyourbuilding.Bradford’spremiumfoilrangecanensurethatyouachievetherightfinish.ContactBradfordforfurtherinformation.

2.11. WhyUseBradfordandEdmondsProducts

2.11.1. Bradford Insulation

Bradfordhasbeenattheforefrontofinsulationinnovation.IndevelopingtheAnticonrangeBradfordwasthefirstinsulationcompanytocombinethermalinsulationwithcondensationcontrol.

BradfordispartoftheCSRgroupthatprovidesspecialistbuildingproductstotheAustralasianmarket.BradfordisabletoleveragethecombinedresourcesoftheCSRBuildingProductsdivisiontodevelopnewandinnovativeproductsandsystemsthatarethoroughlytested.SoyoucanbesurewithCSR.

Bradfordalsohassignificantlocalknowledgeandacomprehensivesupportnetworkincludinganetworkofbranches,accountmanagersandtechnicalrepresentativesacrossAustraliathatcansupportitscustomersonsite.

BradfordistheonlylocallyownedglasswoolandrockwoolproducerinAustraliaandiscommittedtoexpandingitscapacitytomeettheneedsofthemarketwithplantslocatedalongtheeasternseaboard.

2.11.2. Edmonds Vents

Awelldesignedbuildingventilationsystemwillcontributetoimprovedproductivityandasaferworkenvironment.Itcanalsohelpreduceenergyusage,condensationforhumiditybuildupintheroofspaceandgreenhousegasemissions.

Edmondsofferawiderangeofnaturallywinddrivenandpoweredhybridventsolutions.Edmondsinvestssignificantresourceintoresearchanddevelopmenttoinvent,manufactureandmarketsignificantlybetterperformingproducts.

2.11.3. Bradford Foils

Bradfordmanufacturesandsuppliesanextensiverangeoffoilproductssuitableforsarkingandfacingapplications.Theseproductshavebeendevelopedusingthelatesttechnologyfromaroundtheworldtodeliversuperiorperformanceandgreatvalueformoney.Eachproducthasbeendesignedtoprovideyouwiththeoptimumperformanceforeachapplicationandtomakeiteasierforyoutogetthebestresult,everytime.

COMMERCIAL ROOFING | PAGE 6

Page 7: Bradford Commercial Roofing Brochure BCA 2010

3. ROOFING DESIGN TO MEET SECTION J OF THE BCA

3.1.MakingtheBCAassimpleasABC

ThefollowingtablesarebasedontheICANZThermalPerformanceTotalR-ValuecalculationsfortypicalbuildingcomponentsandtherequirementsoftheBCA.ForeachroofsystemtherearetablesforeachscenariobasedontheBuildingCodeofAustralia(2010)

Toselectthecorrectinsulationfortheapplicationcarryoutthefollowing3simplesteps;

A. SelecttheclimatezoneforyourprojectlocationfromtheBCAmap

B. Selectforroofcolour

C. Foryourroofingsystemreadoffminimumrequiredinsulationproduct

Pleasenotethatthetablesareonlydesignedforlight,mediumandheavydutyreflectivefoilfacings–forotherfacingscontactBradfordInsulationorrefertoBradfordwebsite:www.bradfordinsulation.com.au

COMMERCIAL ROOFING | PAGE 7

Page 8: Bradford Commercial Roofing Brochure BCA 2010

Climate Zones

Zone 1 Zone 5

Zone 2 Zone 6

Zone 3 Zone 7

Zone 4 Zone 8

STEPA.SelecttheClimateZone

TheBCAspecifiesminimumdeemedtosatisfyperformanceforroofsandisdependentontheclimatezoneyourbuildingisin.Locatetheclimatezoneyourbuildingisinfromthefollowingmap.

STEPB.SelecttheRoofColourTheenergyefficiencyprovisionsoftheBCArequireanincreaseofTotalR-Valueforroofswithsolarabsorbanceabove0.5inclimatezones1,2and3.Table3.3onpage10reflectsthisrequirement.Fordesignsinclimatezones1,2and3itiscriticaltoobtainsolarabsorbancevaluesfromroofmaterialmanufacturersinordertodeterminetherequiredminimuminsulation.TheBCAalsosetsoutarequirementforadjustmentofminimumR-Valuetocompensateforlossofceilinginsulation.PleasenotethefollowingtablesdonotaddresssolutionswherethelossofceilinginsulationexceedstheamountnominatedinBCA2010tableJI.3b(pleaserefertotheBCAforfurtherdetailsandcontactBradfordforsolutions).

ThetablebelowoutlinestheminimumTotalSystemR-Valuerequiredforroof/ceilingsystemsforeachclimatezone.

RoofColourClimateZones

1 2 3 4 5 6 7 8

DirectionofHeatflow Inwards Outwards

VeryLightRoofs(Absorbance≤0.5) 3.2 3.2 3.2 3.2 3.2 3.2 3.7 4.8

LightRoofs(0.5<Absorbance≤0.6) 3.7 3.7 3.7 3.2 3.2 3.2 3.7 4.8

DarkRoofs(Absorbance>0.6) 4.2 4.2 4.2 3.2 3.2 3.2 3.7 4.8

COMMERCIAL ROOFING | PAGE 8

Page 9: Bradford Commercial Roofing Brochure BCA 2010

3.2.AnticonRoofSystem-VeryLightColouredRoof(Absorbance≤0.5)Seetable3.3forLightandDarkroofcoloursinZones1,2and3

ThefollowingtablesallowyoutoselectBradfordinsulationproducttomeettheminimumBCArequirement.Simplyselecttheroofsystemandreadofftheinsulationproductfortheappropriateclimatezone.

Note:ThesetablesrelatetoAnticonfoilfacedproductsonly.ForAnticonwithalternatefacing,AcousticonorAgriconproductscontactBradfordforyourspecificdesign.

ROOFClimateZone 1 2 3 4 5 6 7 8

DirectionofHeatFlow Inwards Outwards

RequiredTotalR-Value 3.2 3.2 3.2 3.2 3.2 3.2 3.7 4.8

PitchedMetalRoofwithFlatCeiling(NonVentilated)R0200

AnticonFoilFacedBlanket 95 95 95 95 95 95 130 100HP

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil R1.5

PitchedMetalRoofwithCathedralCeilingBelowRafters(NonVentilated)R0400

AnticonFoilFacedBlanket 75 75 75 75 75 75 130 100HP

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil R1.5

FlatMetalRoofwithPlasterboardCeiling(NonVentilated)R0700

AnticonFoilFacedBlanket 55 55 55 55 55 55 130 100HP

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil R1.5

FlatMetalRoofwithnoCeilingR0900

AnticonFoilFacedBlanket 100HP 100HP 100HP 100HP 100HP 100HP 145 *

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil *

FlatMetalRoofwithSuspendedCeiling(NonVentilated)R1000

AnticonFoilFacedBlanket 55 55 55 55 55 55 130 100HP

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil R1.5

FlatMetalRoofSuspendedCeilingPlenumReturn(Ventilated)R1100

AnticonFoilFacedBlanket 140 140 140 140 140 140 145 *

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil *

Flat150mmConcreteRoofwithCeiling(NonVentilated)R1200

AnticonFoilFacedBlanket 55 55 55 55 55 55 130 100HP

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil R1.5

FlatConcreteRoofwithSuspendedCeilingPlenumReturn(ventilated)R1300

AnticonFoilFacedBlanket 140 140 140 140 140 140 140 *

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil Nil *

STEPC.Readofftheminimuminsulationrequiredforyourroofingsystem

minimumairgap100mm

minimumairgap100mm

airgap≥100mm<600mm

airgap≥100mm<600mm

*ContactBradford.FordetailedsystemdescriptionsrefertoICANZInsulationHandbook.Part1ThermalPerformanceorconsultyournearestBradfordrepresentative.InsomeclimatesconsiderationmustbegiventothepositioningofthevapourbarrierandthelevelofinsulationastheminimumBCAtargetsmaynotbeadequatetoprovidetherequiredcondensationcontrol.

COMMERCIAL ROOFING | PAGE 9

Page 10: Bradford Commercial Roofing Brochure BCA 2010

3.3.AnticonRoofSystem-LightandDarkColouredRoofs

ROOFSRoofColour Light(0.5<Absorbance≤0.6) Dark(Absorbance>0.6)

ClimateZone 1 2 3 1 2 3

DirectionofHeatFlow Inwards Inwards

RequiredTotalR-Value 3.7 3.7 3.7 4.2 4.2 4.2

PitchedMetalRoofwithFlatCeiling(NonVentilated)R0200

AnticonFoilFacedBlanket 100HP 100HP 100HP 130 130 130

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil

PitchedMetalRoofwithCathedralCeilingBelowRafters(NonVentilated)R0400

AnticonFoilFacedBlanket 95 95 95 130 130 130

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil

FlatMetalRoofwithPlasterboardCeilingR0700

AnticonFoilFacedBlanket 75 75 75 95 95 95

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil

FlatMetalRoofwithnoCeilingR0900

AnticonFoilFacedBlanket 130 130 130 145 145 145

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil

FlatMetalRoofwithSuspendedCeiling(NonVentilated)R1000

AnticonFoilFacedBlanket 75 75 75 95 95 95

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil

FlatMetalRoofSuspendedCeilingPlenumReturn(Ventilated)R1100

AnticonFoilFacedBlanket 145 145 145 * * *

AdditionalBradfordGoldInsulation

Nil Nil Nil * * *

Flat150mmConcreteRoofwithSuspendedCeiling(NonVentilated)R1200

AnticonFoilFacedBlanket 75 75 75 95 95 95

AdditionalBradfordGoldInsulation

Nil Nil Nil Nil Nil Nil

FlatConcreteRoofwithSuspendedCeilingPlenumReturn(Ventilated)R1300

AnticonFoilFacedBlanket 145 145 145 * * *

AdditionalBradfordGoldInsulation

Nil Nil Nil * * *

*ContactBradford.FordetailedsystemdescriptionsrefertoICANZInsulationHandbook.Part1ThermalPerformanceorconsultyournearestBradfordrepresentative.InsomeclimatesconsiderationmustbegiventothepositioningofthevapourbarrierandthelevelofinsulationastheminimumBCAtargetsmaynotbeadequatetoprovidetherequiredcondensationcontrol.

airgap≥100mm<600mm

minimumairgap100mm

minimumairgap100mm

airgap≥100mm<600mm

COMMERCIAL ROOFING | PAGE 10

Page 11: Bradford Commercial Roofing Brochure BCA 2010

FACING DESCRIPTION

Thermofoil™LightDuty

Aneconomicalgradereflectivefoil,BradfordThermofoil™LightDutyisalightweightradiantbarrierconsistingoftwolayersofaluminiumfoillaminatedtoacentralcoreofkraftpaperwithflameretardantadhesiveswithafibreglassreinforcingyarninatri-directionalpattern.

Thermofoil™MediumDuty

Atoughmediumdutyfacingforbulkinsulationconsistingoftwolayersofaluminiumfoillaminatedtoacentralcoreofheavykraftpaperwithflameretardantadhesiveswithatri-directionalfibreglassreinforcingyarn.Thisfoilisstrongerandhasmoreresistancetocrushingandcrinkling.

Thermofoil™HeavyDuty

BradfordThermofoil™HeavyDutyFoilispremiumstrength,heavy-dutyscrimreinforcedfoillaminatedesignedtoprovideapremiumfinishinareaswherefoilisexposed.

ThermoplastWhiteDecorativeFacing

Awhitefacing,idealwhereadecorativefinishandhighlevelofreflectivityisrequired.BradfordThermoplast™Whiteisamediumdutyreflectivelaminateconsistingofaluminiumfoilandkraftpaperbondedtoawhitepolymericfilmwithflameretardantadhesiveandisreinforcedwithfibreglassyarnintri-directionalpattern.

Thermofoilblack

Blackfacedblanketissuitableforunderslabinchilledbeamapplications,orforotheracousticrequirementswherelowlightreflectivityisrequired.Alsoavailableinperforatedfinish.

Perforatedfoil

AvailableinHeavyDuty(750P)andMediumDutyWhiteThermoplastforitsacousticperformance.Notsuitableforapplicationswherecondensationcontrolisrequired.

AcoustituffBradfordAcoustituffisatough,lightweightflexiblevapourbarrierconsistingofpolypropylenefilmbondedtoaluminiumfoilwithfireretardanthotmeltadhesive.TheflexiblenatureofAcoustituffprovideshighlevelsofsoundabsorptionandlightreflectivity.

UltraphonUltraphonisablackwovenfibreglassfacingdesignedtoprovideapremiumblackfinishwithalargeopenareaformaximumsoundabsorption.Pleasenotethisproductisnotsuitablewherecondensationcontrolisrequired.

4. APPLICATIONS AND PRODUCTS

4.1. IntroductionAsmostBradfordroofingproductscombineabaseblanketwithafacing,averywiderangeofproductsisavailable.Inordertoselecttherightproductsforyourapplicationwerecommendthatyoudeterminetheblanketthicknessrequiredtomeetthethermalandcondensationrequirementsoftheprojectandthenselectthefacingthatprovidesthebestlevelofperformanceforyourparticularapplication.

4.2. MaterialBaseBlanket(RMAT)andTotalSystemR-Values(RT)

AS/NZS4859.1:2002(amendment2006)allowsinsulationmanufacturerstopresenttheperformanceinanumberofways.

TwocommonmethodsofpresentingproductperformanceareRMAT(thebasematerialthermalperformance)orRT(thetotalperformanceoftheproductinstalledinasystem).Eg.Anticon100HPhasabaseblanketperformanceofR2.5(RMAT),however,wheninstalledinawarehouseroof,thetotalR-ValueoftheroofcanbecalculatedasR3.2(RT).BradfordpresentsitsproductperformanceasbaseblanketperformanceRMATtoallowdesignerstheflexibilitytodesignandspecifythemostcosteffectiveprojects.

Toensurevalueformoneyitisimportantthatproductsarecomparedbasedonthesamecriteria,eg.basematerialperformanceortotalperformance.

4.3. AvailableFacingsforroofingblanketAnticonproductsareavailablewitharangeoffacingsasfollows:

*BaseBlanketMaterialR-Value

COMMERCIAL ROOFING | PAGE 11

Page 12: Bradford Commercial Roofing Brochure BCA 2010

PRODUCT DESCRIPTION

Hurricane

TheAustralianleaderinindustrialventilation.TheHurricaneventhasaverticalvanedesign,whichconsiderablyincreasesitsexhaustcapacityovertraditionalsphericalvaneventdesignsofthesamethroatdiameter.Availableinthroatsizesfrom100mmto900mm,andcanalsobesuppliedtoworkincorrosiveenvironments.AlsoavailableinawiderangeofcolourstomatchColorbond®roofs.

EcoPower

Edmondsecopower®ventilatorsaretheworld'sfirsttruehybridventilatorsthatwillworkinallconditions,evenwhenthereisnowind.Theyprovidepeakperformance,usinglessenergythananaverageincandescentlightglobe.Availablein400mm,600mmand900mmthroats.AlsoavailableinawiderangeofcolourstomatchColorbond®roofs.

4.4.Ventilators

ForspecificapplicationscontactBradfordforfurtherinformationonproductsuitability.

APPLICATION PRODUCT

Roof where antiglare facing required ThermofoilRoofSarkinglaidseparatelyinconjunctionwithBradfordroofingblanket.ReferThermofoilRoofSarkingdatasheetformoreinformation

Cost effective roof insulation Anticon™withlightdutyfoil

Exposed roof insulation where aesthetics is a premium or a higher level of tear resistance is required.

Anticon™withmediumdutyfoil

Exposed roof insulation where aesthetics is critical or the highest level of tear resistance is required.

Anticon™withheavydutyfoil

Roofs with need to keep external noise out or internal noise in

Acousticon™

Roofs that require a white finish and improved light reflectance such as assembly halls and sports facilities.

Anticon™withThermoplastWhitefacing

Underslab applications – such as in use with chilled beams. Refer to Bradford Underslab brochure for more information.

Anticon™withblackUltraphonfacing

Farm sheds used for housing poultry and livestock Agricon™

Roofs where heat loads need to be ventilated HurricaneorEcopowerroofventilators

Roofs where noxious gases need to be ventilated Ecopowerroofventilators

Edmondsmanufacturesanextensiverangeofnaturalandhybridpoweredroofventsforcommercialapplications.

4.5.RoofingApplications

TheBradfordroofingrangecanbeusedforavarietyofapplications.Thefollowingtableprovidesguidanceastothemostappropriateproductforyourapplication:

COMMERCIAL ROOFING | PAGE 12

Page 13: Bradford Commercial Roofing Brochure BCA 2010

Spacer

PurlinSafety Mesh

Concealedx roong clip

Anticon Blanket

5.1.GeneralBradfordAnticon™shouldbeinstalledbyqualifiedprofessionals.Careshouldbetakenintheinstallationoftheinsulationthatsufficientroomisprovidedtoallowtheinsulationtorecovertoitsdesignthicknessbetweenpurlins.IftheinsulationiscompressedthetotalR-ValuewillbereducedandmaynotmeetrequireddesignR-Values.

5.2. InstallationofBulkInsulationBeneathMetalRoofs

5.2.1. Installation Details

Wheninsulationistobeinstalledundermetalroofsprovisionmustbemadeforinsulationtorecovertoitsnominalthickness.SpacerscanbeusedtolifttheroofsheetingabovethepurlinlineallowingtheinsulationtorecovertoitsdesignthicknessasshowninFigure1.

5.2.2. Installation of Insulation

Theinsulationissimplyrolledoutoverthesafetymesh.ThesubsequentrollsofAnticonmustbuttupagainsttheinstalledAnticonoverthefoillap.

Spacersandroofsheetingarefixedthroughtheinsulation.Fordetailsrefertofigure2.

*PleasecheckwithlocalGovernmentHealthandSafetybodyforsuitabilityofthismethod.

5.2.3. Spacers

ToensurecompliancewithsectionJoftheBCAtheinsulationmustbeallowedsufficientspacetorecovertonominalthicknessandathermalbreakofR0.2atpurlin

mustbeachieved.Arangeofspacersisavailableonthemarketthatwillachievethis.

BradfordofferstheThermodeckspacer,ahighperformancethermalspacerthatprovidesathermalbreakwellinexcessoftheR0.2requiredbytheBCA.BradfordalsoofferstheAshgridspacer,ametalpreassembledspacerdesignedforbothconcealedandpiercedfixedroofdecking.

SpacerheightrequirementsforAnticonproductsareasfollows;

Notes: Spacerswithsmallerfootprintsmaycompressinsulationmorethancontinuoussupportspacers.Toensuresufficientrecoveryspaceisprovidedincreaseminimumrecommendedspacerheightby5mm.

Bradfordrequiresspacerstoprovidesufficientspaceforinsulationtorecovertodesignthickness.Pleasecheckwithyourstructuralengineerandrollformerthatthespacerusediscompatiblewiththeirroofingsystem.

ANTICONPRODUCT

BLANKETTHICKNESS(mm)

MIN.SPACERHEIGHT(mm)

Anticon 55 60 35

Anticon 75 80 55

Anticon 95 100 75

Anticon 100HP 100 75

Anticon 110 110 85

Anticon 130 130 105

Anticon 140 140 115

Anticon 145 145 120

5. INSTALLATION - INSULATION

Figure2-Installinginsulationundermetalroofs

Figure1-Useofspacers

COMMERCIAL ROOFING | PAGE 13

Page 14: Bradford Commercial Roofing Brochure BCA 2010

50mm(min)

1200mm 150mm

150mm overlap

Foil tape to match facing

Plastic anchor

1100mm

1100mm50mm

(min)

When fixing insulation to underside of slab, insulation is pinned to slab using plastic anchors, such as Hilti X-IE6 or similar. Insulation lap is taped. Refer to Fixing option 1 for fixing recommendations.

5.3. InstallationBeneathConcreteSlabRoofs-Soffits

Fixing option 1

COMMERCIAL ROOFING | PAGE 14

Page 15: Bradford Commercial Roofing Brochure BCA 2010

6. TECHNICAL INFORMATIONThefollowingtablesoutlinethekeytechnicalinformationonAnticonproducts.FurtherinformationcanbefoundontheproductdatasheetsavailablefromtheBradfordwebsitewww.bradfordinsulation.com.au

6.1.DimensionsandWeights

Product

BaseBlanketMaterialR-ValueRMAT

Thickness(mm)

NominalLength(m)

NominalWidth(mm)

NominalCoverageper

roll(m2)

NominalDensity(kg/m3)

NominalPackWeight

(kg)

ANTICON

Anticon 55 R1.3 60 15 1200 18 9.8 18.63

Anticon 55 R1.3 60 15 1400 21 9.8 21.32

Anticon 75 R1.8 80 15 1200 18 10.8 23.49

Anticon 95 R2.3 100 10 1200 12 11.9 18.90

Anticon 110 R2.5 110 10 1200 12 11.0 19.86

Anticon 100HP R2.5 100 10 1200 12 14.0 22.14

Anticon 130 R3.0 130 10 1200 12 12.0 24.06

Anticon 140 R3.3 140 7.5 1200 9 13.5 21.02

Anticon 145 R3.6 145 7.5 1200 9 15.9 24.80

ACOUSTICON

Acousticon R1.5 75 15 1200 18 9.0 20.16

AGRICON

Agricon R1.5 75 15 1200 18 9.0 20.16

Property Product Test Result

Maximum Service Temperature

GlasswoolBaseblanket

Facings:Foil

Ultraphon

350ºC

70ºC

300ºC

Moisture Absorption Allproducts 4days@50Cand95%RH Lessthan0.2%byvolume

Compliance with Standards AllproductsAS/NZS4859.1"Materials

fortheThermalInsulationofBuildings"

Complies

6.2.PhysicalProperties

Note:NominalpackweightbasedonMediumDutyfoilfacing,contactBradfordforinformationonpackweightsforotherfacings.

COMMERCIAL ROOFING | PAGE 15

Page 16: Bradford Commercial Roofing Brochure BCA 2010

ProductThickness

(mm)

Frequency(Hz) NRC

125 250 500 1000 2000 4000 5000

ANTICON

Anticon 55 Thermofoil LD 60 0.34 0.86 1.04 0.41 0.20 0.07 0.04 0.65

Anticon 75 Thermofoil LD 80 0.60 1.21 1.21 0.41 0.28 0.10 0.12 0.70

Anticon 95 Thermofoil LD 100 0.72 1.43 1.43 0.43 0.26 0.14 0.08 0.75

ACOUSTICON

Acousticon 75 0.14 1.02 0.82 0.42 0.38 0.29 0.38 0.65

ProductThickness

(mm)

Frequency(Hz) NRC

125 250 500 1000 2000 4000 5000

ACOUSTICON

Acousticon 75 5 12 15 17 19 18 16 18

6.5.ComplianceCertificationForcompliancecertificateforyourprojectfilesrefertoDesignSmartatwww.bradfordinsulation.com.au

6.3.AcousticsSOUNDABSORPTIONinaccordancewithAS1045:1988

INSERTIONLOSS(dB)

6.4.FireHazardProperties

Product Facing1530.3 AS3837

Ignitability SpreadofFlame

HeatEvolved

SmokeDeveloped

GroupClassification

Building Blanket

Supertel

Ultratel

Foil 0 0 0 0-1 1

Thermofoil(Black/White) 14 0 0 4 1

Ultraphon 0 0 0 3 1

Acoustituff 12 0 1 5 1

PremiumUnderslabFacing 0 0 0 0-1 1

Where ceiling linings are to be designed for fire resistance the following table provides information on fire indices to AS1530.3 and group classifications to AS3837

COMMERCIAL ROOFING | PAGE 16

Page 17: Bradford Commercial Roofing Brochure BCA 2010

PRODUCT

AnticonBlanket

EdmondsEcoPower®

EdmondsHurricaneroofventilatorsandaccessories

Thermofoilfacings

PRODUCT

Safetymesh

AshgridSpacer80mm,110mm,120mm

Thermodeckspacers

Reinforcedfoiltape

7. PRODUCTS SOLD BY BRADFORDForacomprehensivelistofproductsandpricingrefertoBradfordpricelistorcontactyourlocalBradforddistributor.

8. PRODUCTS SOLD BY OTHERSForacomprehensivelistofproductsandpricingrefertoBradfordpricelistorcontactyourlocalBradforddistributor.

PRODUCT SUPPLIER

Roofingscrews-Forfixingtopurlins ITWBuildexorothers

NylonAnchorsX-IE6-Forfixingtoundersideofconcreteslabs

Pinlengthtomatchnearestroofinginsulationnominalthickness.

Hiltiorothers

AlternateSpacerProducts byothers

COMMERCIAL ROOFING | PAGE 17

Page 18: Bradford Commercial Roofing Brochure BCA 2010

9. HEALTH AND SAFETY

10. PRODUCT WARRANTY

Glasswoolandrockwoolinsulationproductsareexcellentinsulationmaterialsandarefullysafetouseunderallconditions.Bothinsulationmaterialshavebeeninworldwideuseforover70years,andduringthattimetheirmanufactureandusehavebeenextensivelymonitoredandresearched.

BradfordglasswoolandrockwoolproductsaremanufacturedusingthelatestFBS-1technologyandarenotclassifiedashazardousaccordingtothecriteriaoftheASCC(FormerlyNOHSC)guidelines.

Detailedinformationonhealth&safetyiscontainedintheMSDS&ICANZ(InsulationCouncilofAustralian&NewZealand)literatureavailablefromourwebsitewww.bradfordinsulation.com.au.

Forfurtherspecificationassistance,visittheDesignSmartsectionofourwebsitewhichincludesfulldetailsorregulations,specificationcalculators,productbrochures,datasheets,MSDSsandmuchmoretomakeyourjobeveneasier.

Visitwww.bradfordinsulation.com.auorcontactyourBradfordrepresentativeon1300664653.

CSRBuildingProductsLimitedwarrantsBradford™Insulationproductstobefreeofdefectsinmaterialsandmanufacture.

PleasenotethatfoilfacedAnticon™productsmustnotcomeincontactwithwater.IfAnticon™productisusedinanunusualapplicationoralkalineenvironmentcontactBradfordforfurtherdetails.

ForfullproductwarrantydetailspleaserefertoBradfordwebsite.

11. BRADFORD DESIGNSMART

COMMERCIAL ROOFING | PAGE 18

Page 19: Bradford Commercial Roofing Brochure BCA 2010
Page 20: Bradford Commercial Roofing Brochure BCA 2010

Publ

ish

date

: 05/1

0 D

oc r

ef: B

2010 R

OO

F E

Bradford Insulation 55 Stennett Rd Ingleburn NSW 2565 Australia Telephone (02) 9765 7000 Facsimile (02) 9765 7002 www.bradfordinsulation.com.au

Bradford Insulation is a business division of CSR Building Products Limited ABN 55 008 631 356The contents of this brochure are copyright protected and may not be reproduced in any form without prior written consent of Bradford Insulation. Recommendations and advice regarding the use of the products described in this brochure are to be taken as a guide only, and are given without liability on the part of the company or its employees. We reserve the right to change product specifications without prior notification, please refer to the Bradford website for the latest version of this document. The purchaser should independently determine the suitability of the product for the intended use and application.