Brackets Mounting plates - NIEDAX...In order to avoid the deformation of ceiling support during the...
Transcript of Brackets Mounting plates - NIEDAX...In order to avoid the deformation of ceiling support during the...
Support System
Ceiling bracket and wall bracket
Brackets
Profi les
Mounting plates
TKTKTKTK14
CABLE TRAY SYSTEM GFK
Compatible with our different ranges of cable trays, our supporting systems are available in
several fi nishes and different support structures. A range of support structures ranging from hot-dip
galvanized steel and epoxy, through the stainless steel, loaded polyester reinforced fi berglass.
Dimensions and perforations supports are suitable for EBO Systems cables trays.
The load capacities are variable according to the type of installation (ceiling, wall ...).
Profi les
Mounting plates
15
Overview brackets and hangers
Hangers and wall supports - average load KTAM 17
Hangers and wall supports, standard KTA 17
GRP brackets, pultruded FPAP 18
GRP brackets, pressed FPAM 18
GRP brackets, pultruded, Z Profi l FPCO 19
GRP support, pultruded FPPS 19
Hangers, U profi le HU 5050 20/21
Hangers-profi les HDS 21/22
Profi l U 5050 22/23
Anchor fi xing plate KU 5050 23
GRP hangers, U profi l FPES 24
GRP hangers, pultruded, Profi l C FPDS 24
STAINLESS STEEL Fixing system SS anchor bolt FPBGV 24
Track C-Profi l, opening of 15 mm, perforated FPAR 25
Protective cover KA 18
Protective cover K 5050 21
SYSTEM
ACCESSORIES
The classifi cation of brackets and hangers into categories like light, medium and heavy is only an indication for their typical usage. For engineering purposes exact calculations of overall loads considering the weight of the cable, the weight of the tray and the support span are mandatory. In the event that the support structures and loads of cables are uniformly distributed, the supporting capacity of the bracket must be calculated as follows: load F = (cables weight + weight of the various components of the support installation) x support distance
Load ratings shown in this catalog are valid only for proper anchorage to the building structure. Please refer to the general information section and consult site management or structural enginee-ring for details about the building structure and local regulations.
!16
SUPPORT SYSTEM
17
Hanger and wall bracketmiddle range
Warning: different properties for various lengths
for a wall mounting or a ceiling mounting
KTAM 100 E5
60 110 1,2 2 FLM 6x12 E5KTAM 200 E5 80 210 1,2 2 FLM 6x12 E5KTAM 300 E5 85 310 1,2 2 FLM 6x12 E5KTAM 400 E5 115 410 1,2 2 FLM 6x12 E5
E5
E5E5E5
Item ref. Height LengthL
adj. at L/2
Accessories/bolts
includedmm mm kN
Min. pack.
20 p.20 p.20 p.20 p.
EANcode
728305728404728503728602
Weight 100 units
pc.
16,5130,6144,3373,59
The load capacities are only valid if the main supporting part is sufficiently and correctly fixed,particularly the ceiling supports.
Ceiling support and wall bracketstandard range
for a wall mounting and for a ceiliing mounting
Mounting accessories required for cable ladder UL : ULKG, M10x30 V4A (to be ordered separatly )
KTA 100
45 40 110 2,5 2 FLM 6x12KTA 150 45 40 160 2,5 2 FLM 6x12KTA 200 55 40 210 2,5 2 FLM 6x12KTA 250 55 40 260 2,5 2 FLM 6x12KTA 300 65 50 310 2,5 2 FLM 6x12KTA 350 65 50 360 2,5 2 FLM 6x12KTA 400 75 50 410 2,5 2 FLM 6x12KTA 450 75 50 460 2,5 2 FLM 6x12KTA 500 90 50 510 2,5 2 FLM 6x12KTA 550 90 50 560 2,5 2 FLM 6x12KTA 600 90 50 610 2,5 2 FLM 6x12KTA 100 E5
45 40 110 2,5 2 FLM 6x12 E5KTA 200 E5 55 40 210 2,5 2 FLM 6x12 E5KTA 300 E5 65 50 310 2,5 2 FLM 6x12 E5KTA 400 E5 90 50 410 2,5 2 FLM 6x12 E5KTA 500 E5 110 50 510 2,5 2 FLM 6x12 E5KTA 600 E5 110 50 610 2,5 2 FLM 6x12 E5
F
FFFFFFFFFF
E5
E5E5E5E5E5
Item ref. Height WidthB
LengthL
adj. at L/2
Accessories/bolts
includedmm mm mm kN
Min. pack.
20 p.20 p.20 p.20 p.20 p.20 p.20 p.10 p.10 p.10 p.10 p.20 p.20 p.20 p.20 p.20 p.20 p.
EANcode
186907187003187102187201187300187409187508187607187706187805187904842605842629842643842667917402917426
Weight 100 units
pc. /
13,6016,9025,2029,8055,8062,7075,2083,80
106,70129,20122,8014,8025,9255,6980,00
120,00135,00
The load capacities are only valid if the main supporting part is sufficiently and correctly fixed,particularly the ceiling supports.
Oblong holes dimensions LL 7x40 mm in the KTA 100-600 seriesOblong holes dimensions LL 7x15 mm in the KTA 150-550 series (intermediate sizes) and in thealuminum finish KTA 100-600
Ceiling support and wall bracketepoxy, standard
for a wall mounting on supporting rail FPAR and on ceiling support FPES / FPDS
Mounting accessories required for cable ladder UL: ULKG, M6x30 V4A (to be ordered separatly )Mounting accessories required for cable ladder UL: ULKG, M10x30 V4A (to be ordered separatly )
KTA 100 C1KG
7032 45 40 110 2,5 2 FLM 6x12 E5KTA 150 C1KG 7032 45 40 160 2,5 2 FLM 6x12 E5KTA 200 C1KG 7032 55 40 210 2,5 2 FLM 6x12 E5KTA 250 C1KG 7032 55 40 260 2,5 2 FLM 6x12 E5KTA 300 C1KG 7032 65 50 310 2,5 2 FLM 6x12 E5KTA 350 C1KG 7032 65 50 360 2,5 2 FLM 6x12 E5KTA 400 C1KG 7032 75 50 410 2,5 2 FLM 6x12 E5KTA 450 C1KG 7032 75 50 460 2,5 2 FLM 6x12 E5KTA 500 C1KG 7032 90 50 510 2,5 2 FLM 6x12 E5KTA 550 C1KG 7032 90 50 560 2,5 2 FLM 6x12 E5KTA 600 C1KG 7032 90 50 610 2,5 2 FLM 6x12 E5
C1
C1C1C1C1C1C1C1C1C1C1
Item ref. RAL colour
Height WidthB
LengthL
adj. at L/2
Accessories/bolts
includedmm mm mm kN
Min. pack.
1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.
EANcode
967209967216967223967230967247967254967261967278967285967292967308
Weight 100 units
pc
13,116,424,428,853,960,772,881,1
103,3125,0118,8
The load capacities are only valid if the main supporting part is sufficiently and correctly fixed,particularly the ceiling supports.
Oblong holes dimensions LL 7x40 mm in the KTA 100-600 seriesOblong holes dimensions LL 7x15 mm in the KTA 150-550 series (intermediate sizes) and in thealuminum finish KTA 100-600
18
SUPPORT SYSTEM
Protective end cap
The end caps must prescripted in areas where the risk of hazard is important!
to protect the profile ends
KA 100-600
yellowK10
Item ref. Colour Min. pack.
10 p.
EANcode
347056
Weight 100 units
1,4
GRP bracketpultruded
for a wall mounting and for a ceiliing mounting
Used for: Hanger FPES… and FPDS…
Fixing accessories for cables trays ( to be ordered separately ) : for cables trays K² and KP : M6x20 V4A
FPAP 100/AC
7032 110 1,25FPAP 150/AC 7032 160 1,25FPAP 200/AC 7032 210 1,25FPAP 250/AC 7032 260 1,25FPAP 300/AC 7032 310 1,25
K23
K23K23K23K23
Item ref. RAL colour
LengthL
adj. at L/2
mm kN
Min. pack.
1 p.1 p.1 p.1 p.1 p.
EANcode
955725955732955749955756955763
Weight 100 units
pc. pc/
47,054,558,565,072,2
The load capacities are only valid if the main supporting part is sufficiently and correctly fixed,particularly the ceiling supports.
GRP bracketpultruded
for a wall mounting and for a ceiliing mounting
Used for: Hanger FPES… and FPDS…
FPAP 400/AC
7032 410 1,25FPAP 500/AC 7032 510 1,25FPAP 600/AC 7032 610 1,25
K23
K23K23
Item ref. RAL colour
LengthL
adj. at L/2
mm kN
Min. pack.
1 p.1 p.1 p.
EANcode
955770955787955794
Weight 100 units
pc
161,5174,5186,0
The load capacities are only valid if the main supporting part is sufficiently and correctly fixed,particularly the ceiling supports.
GRP bracketpressed
for a wall mounting and for a ceiliing mounting
Used for: Hanger FPES… and FPDS…
FPAM 100
7032 50 55 120 1,25FPAM 150 7032 60 55 170 1,25FPAM 200 7032 70 55 220 1,25FPAM 300 7032 90 55 320 1,25
K23
K23K23K23
Item ref. RAL colour
Height WidthB
LengthL
adj. at L/2
mm mm mm kN
Min. pack.
1 p.1 p.1 p.1 p.
EANcode
955848955855955862955879
Weight 100 units
pc.
17183650
The load capacities are only valid if the main supporting part is sufficiently and correctly fixed,particularly the ceiling supports.
19
GRP bracketpultruded, Z-profile
for the horizontal mounting of cable trays
Used for: Only for the cable trays KK… and KP…
Mounting accessories required for cable tray K2 and KP : M6x20 V4A ( to be ordered separatly )
FPCO 100/AC
7032 100FPCO 150/AC 7032 150FPCO 200/AC 7032 200FPCO 300/AC 7032 300
K23
K23K23K23
Item ref. RAL colour
WidthB
mm
Min. pack.
1 p.1 p.1 p.1 p.
EANcode
963102963119963126963133
Weight 100 units
pc
556877
100
GRP supportpultruded, Z-profile
The support is universal
for the horizontal mounting of cable trays
Used for: Only for the cable trays KK… and KP… and UL…
Mounting accessories required for cable tray K2 and KP : M6x20 V4A ( to be ordered separatly )
FPPS
7032K23
Item ref. RAL colour
Min. pack.
1 p.
EANcode
963140
Weight 100 units
pc
0
20
SUPPORT SYSTEM
Ceiling supportProfile U
Load F in kN
Def
lect
ion
f in
mm
In case of symetrical loads, the deflection is not significant.
Total length = U profile length, included fixing plate.HU 5050/200, has limited space for equipment in cable trays (bracket length & height)Used for: Rail FPAR and wall mounted bracket FPAP
Rail and wall mounted bracket KTA...
Load diagram : deflection of the hanger in case of one-sided charges
HU 5050/200
205HU 5050/250 255HU 5050/300 305HU 5050/400 405HU 5050/500 505HU 5050/600 605HU 5050/700 705HU 5050/800 805HU 5050/900 905HU 5050/1000 1005HU 5050/1100 1105HU 5050/1200 1205HU 5050/1500 1505HU 5050/2000 2005HU 5050/200 E5
205HU 5050/300 E5 305HU 5050/400 E5 405HU 5050/500 E5 505HU 5050/600 E5 605HU 5050/800 E5 805HU 5050/1000 E5 1005
F
FFFFFFFFFFFFF
E5
E5E5E5E5E5E5
Item ref. Total length L
mm
Min. pack.
1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.
EANcode
858705858729858743858767858781858804858828858842858866858880858903858927858941858965945757945702945764945771945788965953965960
Weight 100 units
pc. pc/
93,08105,23117,38141,68165,97190,27214,57238,87263,17287,46311,76336,06408,95530,4486,02
108,48130,92153,38175,83220,74265,65
The load data are only valid in case of a sufficiently strong fixing of the supporting part. The share ofloads in the building must be defined with the contractor. You must follow the guidelines anddefinitions in force.
In order to avoid the deformation of ceiling support during the mounting of brackets, it is necessaryfor mechanical reason, to take into account of the thickness of the ceiling support when screwing thehexagonal bolts. for static reasons and to facilitate the mounting of end caps, the bracket must be mounted at x=50 mmabove the ceiling support end.To prevent the deformation of the ceiling support profile when installing the brackets, it isrecommended to use hexagonal head bolts for mechanical reasons. Serie of oblong holes (13x40 mm) on 3 profile sides.
21
Hangerepoxy, U-profile
Load F in kN
Def
lect
ion
f in
mm
In case of symetrical loads, the deflection is not significant.
Total length = U profile length, included fixing plate.HU 5050/200, has limited space for equipment in cable trays (bracket length & height)Used for: Hangers FPES / FPDS and wall bracket FPAP
Rail FPAR and wall mounted bracket FPAP
Load diagram : deflection of the hanger in case of one-sided charges
HU 5050/200 C1KG
7032 205HU 5050/250 C1KG 7032 255HU 5050/300 C1KG 7032 305HU 5050/400 C1KG 7032 405HU 5050/500 C1KG 7032 505HU 5050/600 C1KG 7032 605HU 5050/700 C1KG 7032 705HU 5050/800 C1KG 7032 805HU 5050/900 C1KG 7032 905HU 5050/1000 C1KG 7032 1005HU 5050/1100 C1KG 7032 1105HU 5050/1200 C1KG 7032 1205HU 5050/1500 C1KG 7032 1505HU 5050/2000 C1KG 7032 2005
C1
C1C1C1C1C1C1C1C1C1C1C1C1C1
Item ref. RAL colour
Total length L
mm
Min. pack.
1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.
EANcode
967100967124967131967148967155967162967179967186967193967063967070967087967094967117
Weight 100 units
pc
88,099,5
111,0133,9156,9179,9202,9225,8248,8271,8294,8317,7386,6501,5
Protective end cap
The end caps must prescripted in areas where the risk of hazard is important!
to protect the profile ends
Used for: Profile U 5050/… and hanger HU 5050/…
K 5050
yellowK10
Item ref. Colour Min. pack.
10 p.
EANcode
347025
Weight 100 units
pc.
3
To facilitate the assembly of end caps, a minimum space of 50 mm is required between the bracketbottom and the ceiling support end.
Ceiling support profile
Used for: Profile U 5050/… and hanger HU 5050/…
HDS 50.50 F
1 SKM 10x80 F, 2 UGM 10HDS 50.50 E5
1 SKM 10x90 E4, 2 UGM 10F
E5
Item ref. Accessories/bolts
included
Min. pack.
50 p.50 p.
EANcode
931705962266
Weight 100 units
pc. pc/
7,56,8
In order to avoid the deformation of ceiling support during the mounting of brackets, it is necessaryfor mechanical reason, to take into account of the thickness of the ceiling support when screwing thehexagonal bolts. To prevent the deformation of the ceiling support profile when installing the brackets, it isrecommended to use hexagonal head bolts for mechanical reasons.
21
Pendardepoxy, Profil U
Charge F en KN
Déf
lexi
on f
en m
m
Dans le cas de charges à peu près symétriques, la déflexion est à peine mesurable.
Longueur totale = la longueur du profil U, plaque de fixation compriseHU 5050/200, dispose d'un espace restreint pour l'equipement en chemins de câbles (lalongueur des pendards - la hauteur des consoles)Utilisable pour : Pendard FPES / FPDS et console murale FPAP
Rail FPAR et console murale FPAP
Diagramme des charges : flexion du pendard dans le cas d'une charge unilatérale.
HU 5050/200 C1KG
7032 205HU 5050/250 C1KG 7032 255HU 5050/300 C1KG 7032 305HU 5050/400 C1KG 7032 405HU 5050/500 C1KG 7032 505HU 5050/600 C1KG 7032 605HU 5050/700 C1KG 7032 705HU 5050/800 C1KG 7032 805HU 5050/900 C1KG 7032 905HU 5050/1000 C1KG 7032 1005HU 5050/1100 C1KG 7032 1105HU 5050/1200 C1KG 7032 1205HU 5050/1500 C1KG 7032 1505HU 5050/2000 C1KG 7032 2005
C1
C1C1C1C1C1C1C1C1C1C1C1C1C1
Réf. Art. Cou-leurRAL
Longueur totale L
mm
Coli-sage mini.
1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.
CodeEAN
967100967124967131967148967155967162967179967186967193967063967070967087967094967117
Poids100uni.
pc
kg
88,099,5
111,0133,9156,9179,9202,9225,8248,8271,8294,8317,7386,6501,5
Embout de protection
Les embouts de protection sont à prescrire dans les zones où le risque d'accident estimportant !
pour la protection des extrémités de profils
Utilisable pour : Profil U 5050/... et pendard HU 5050/...
K 5050
jauneK10
Réf. Art. Couleur Coli-sage mini.
10 p.
CodeEAN
347025
Poids100uni.
pc.
kg
3
Pour faciliter le montage des embouts de protection, un écart d'au moins 50 mm est à respecter entrela partie inférieure de la console et le bout du pendard.
Profil du pendard
Utilisable pour : Profil U 5050/... et pendard HU 5050/...
HDS 50.50 F
1 SKM 10x80 F, 2 UGM 10HDS 50.50 E5
1 SKM 10x90 E4, 2 UGM 10F
E5
Réf. Art. Accessoires/Boulonnerie
incluse
Coli-sage mini.
50 p.50 p.
CodeEAN
931705962266
Poids100uni.
pc. pc/
kg
7,56,8
Dans le but d'éviter la déformation des pendards au moment du montage des consoles, il estnécessaire pour des raisons statiques, de tenir compte de l'épaisseur du profil du pendard au momentdu serrage avec les boulons à têtes hexagonales.Pour empêcher la déformation du profil du pendard lors du montage des consoles, il faut utiliser desboulons à tête hexagonale pour des raisons mécaniques.
22
SUPPORT SYSTEM
Ceiling support profileepoxy
Used for: Profile U 5050/... C1KG and hanger HU 5050/… C1KG
HDS 50.50 C1KG
7032 1 SKM 10x90 E4, 2 UGM 10C1
Item ref. RAL colour
Accessories/bolts
included
Min. pack.
10 p.
EANcode
967056
Weight 100 units
pc
7,5
To prevent the deformation of the ceiling support profile when installing the brackets, it isrecommended to use hexagonal head bolts for mechanical reasons.
Profile U 5050
for the manufacturing of ceiling supports and supporting systems made of different elements
U 5050/300 F
300U 5050/400 F 400U 5050/500 F 500U 5050/600 F 600U 5050/700 F 700U 5050/800 F 800U 5050/900 F 900U 5050/1000 F 1000U 5050/1100 F 1100U 5050/1200 F 1200U 5050/1500 F 1500U 5050/2000 F 2000U 5050/3000 F 3000U 5050/6000 F 6000U 5050/300 E5L
300U 5050/400 E5L 400U 5050/500 E5L 500U 5050/600 E5L 600U 5050/800 E5L 800U 5050/1000 E5L 1000U 5050/6000 E5L 6000
F
FFFFFFFFFFFFF
E5
E5E5E5E5E5E5
Item ref. LengthL
mm
Min. pack.
1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.2 m3 m6 m1 p.1 p.1 p.1 p.1 p.1 p.6 m
EANcode
918560918584918607918621918645918669918683918706918720918744918768918782859306859320965977965984965991966004966011966028966035
Weight 100 units
pc. pc/ m/
72,9097,20
121,50145,79170,09194,38218,68242,98267,28291,58364,47242,98242,98242,9867,3789,82
112,28134,73179,64224,55224,55
Serie of oblong holes (13x40 mm) on 3 profile sides
23
Profile U 5050epoxy
for the manufacturing of ceiling supports and supporting systems made of different elements
U 5050/300 C1KG
7032 300U 5050/400 C1KG 7032 400U 5050/500 C1KG 7032 500U 5050/600 C1KG 7032 600U 5050/700 C1KG 7032 700U 5050/800 C1KG 7032 800U 5050/900 C1KG 7032 900U 5050/1000 C1KG 7032 1000U 5050/1100 C1KG 7032 1100U 5050/1200 C1KG 7032 1200U 5050/1500 C1KG 7032 1500U 5050/2000 C1KG 7032 2000
C1
C1C1C1C1C1C1C1C1C1C1C1
Item ref. RAL colour
LengthL
mm
Min. pack.
1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 p.1 m
EANcode
967384967391967407967414967421967438967445967339967346967353967360967377
Weight 100 units
pc
72,0096,00
120,00144,00168,00192,00216,00128,33141,17154,00359,00229,73
Serie of oblong holes (13x40 mm) on 3 profile sides
Anchor fixing plate included bolts
for the mounting on straight ceilings
Used for: Profile U 5050/…
KU 5050
105 5 2 FLM 10x25 FKU 5050 E5
105 5 2 FLM 10x25 E5F
E5
Item ref. Total length L
thickness of top
plates (th)
Accessories/bolts
includedmm mm
Min. pack.
1 p.1 p.
EANcode
191956967322
Weight 100 units
pc. /
76,8578,75
Serie of oblong holes (13x40 mm) on 3 profile sides
Anchor fixing plate included boltsepoxy
for the mounting on straight ceilings
Used for: Profile U 5050/... C1KG
KU 5050 C1KG
7032 105 5 2 SKM 10x25 E5C1
Item ref. RAL colour
Total length L
thickness of top
plates (th)
Accessories/bolts
includedmm mm
Min. pack.
1 p.
EANcode
967315
Weight 100 units
pc
72,7
Serie of oblong holes (13x40 mm) on 3 profile sides
24
SUPPORT SYSTEM
Ceiling supportpultruded, C-profile
Total length = L + 53 millimetersThe ceiling support fixing to the ceiling with screws require the use of a large washer, to beordered separetly
for a mounting on 1 side of the support
Used for: Bracket FPAP…/AC and FPAM…/AC
Mounting accessories required : FPBGV10 V4A ( to be ordered separately )Other lengths are available on request
FPES 200/AC
7032 200 1,5FPES 300/AC 7032 300 1,5FPES 400/AC 7032 400 1,5FPES 500/AC 7032 500 1,5
K23
K23K23K23
Item ref. RAL colour
LengthL
Admissible load
F in tractionmm kN
Min. pack.
1 p.1 p.1 p.1 p.
EANcode
955923955930955947955954
Weight 100 units
pc
7592
110127
Ceiling supportpultruded, double C-profile
Total length = L + 53 millimetersThe ceiling support fixing to the ceiling with screws require the use of a large washer, to beordered separetly
to mount on the both support sides
Used for: Bracket FPAP…/AC and FPAM…/AC
Mounting accessories required : FPBGV10 V4A ( to be ordered separately )Other lengths are available on request
FPDS 200/AC
7032 200 2 x 1,5FPDS 300/AC 7032 300 2 x 1,5FPDS 400/AC 7032 400 2 x 1,5FPDS 500/AC 7032 500 2 x 1,5
K23
K23K23K23
Item ref. RAL colour
LengthL
Admissible load
F in tractionmm kN
Min. pack.
1 p.1 p.1 p.1 p.
EANcode
955886955893955909955916
Weight 100 units
pc
7696
175205
Anchor bolt
for fixing the cables on the C profile
Used for: Bracket FPAP/AC, FPAM/AC and FPAR/AC
FPBGV 10 E4
30E4
Item ref. LengthL
mm
Min. pack.
25 p.
EANcode
962662
Weight 100 units
pc
6,6
25
GRP fixing railpultruded, C-profile, slot width 15 mm, perforated
FPAR 500/AC
7032 500 1,5FPAR 750/AC 7032 750 1,5FPAR 1000/AC 7032 1000 1,5FPAR 2000/AC 7032 2000 1,5
K23
K23K23K23
Item ref. RAL colour
LengthL
Admissible load
F in tractionmm kN
Min. pack.
1 p.1 p.1 p.1 p.
EANcode
955961955978955985955992
Weight 100 units
pc
5276
168244