    Ferraz Shawmut iS now

    Fuse-links according toIEC 60282-1 and VDE 0670 T4

    High Voltage

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    2/282

    High Voltage use-links

    t Lg vlg fs-lks ln by Msn s sn, manfa an s as a Qaly

    Management System certied to the ISO 9001:2000 International standard.

    t ms g vlg fs-lks are made of pure materials. Some parts of them and some manufacturing

    processes are patented.t Lg vlg fs-lks line by Mersen encompasses 6 different product ranges as per the following table:

    Productran Nam

    SanagnalPurposecategory

    Bak-category

    Sk

    AdditionalThermalskfunction

    AdditionalControlledPowerDissipationfunction

    Switch-fusecombinationdedication

    Limitor-gIEC 60282-1

    VDE 0670 T4

    Limitor-pIEC 60282-1

    VDE 0670 T4

    Limitor-ptIEC 60282-1

    VDE 0670 T4

    Limitor-pdIEC 60282-1

    VDE 0670 T402

    Limitor-ptdIEC 60282-1

    VDE 0670 T402

    Limitor-ptSIEC 60282-1

    VDE 0670 T402

    4 5 D B 1 2 0 V 5 0 P t S

    Catalog Numbering for Limitor high voltage fuse-links

    D fordiN

    45 mm diameterof contact caps

    B forBak-

    G forgnalpurpose

    P forsk

    p. 7

    p. 8

    p. 11

    p. 14

    p. 16

    p. 20

    t forThermalStriker or

    Controlled PowerDissipation

    D forVDE 0670 T402

    S forVDE 0670 T402an a

    switch-fusecombination

    D forVDE 0670 T402

    Vlg g V/100 C g a

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    3/283

    General inormation

    hV fs-lks v b sd f lbl pc g vlg scg d clg

    d syss f dcds.

    ty pc pps d qp gs l d dyc ffcs f s-ccs.

    t sdg fs f LhV fs-lks by ms :

    High breaking capacity

    High current limitation

    Low switching voltage

    Qk bakn

    Non-ageing

    LhV fs-lks cf fllg sdds:

    IEC 60282-1: High voltage fuses - Part 1: current-limiting fuses.

    This international standard is identical to the German standard VDE 0670 T4.

    VDE 0670 T402: Selection of curent-limiting fuse-links for transformer circuits.

    IEC 60787: Application guide for the selection of high voltage fuse-links for transformer circuit applications.

    VDE 0671 T105/IEC 62271-105: High voltage switchgear and controlgear - Part 105: Alternating switch-fuse combinations. DIN 43 625: DIN 43625: High voltage fuses; rated voltages 3,6 to 36kV (fuse-links dimensions).

    DIN 43 624: High voltage fuse-links, rated voltages 3/3,6 to 30/36kV (single-pole fuse-bases).

    The quality management system of Mersen is certied to the international standard DIN EN ISO 9001.

    Mersen operates a certied environment management system. Mersen manufactures HV fuse-links with dimensions conforming

    to DIN 43 625 with striker for indoor and outdoor use, where the striker serves for actuating a trip-free mechanism as well

    as an indicator due to its red colour.

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    4/28

    HV

    fslnks

    4

    Terms and defnitions

    Sk

    The striker of HV fuse-links in this product list has an effective length of 30 mm and is a medium type.

    This classication results from the energy released by the striker between the points A and B (within the rst 20 mm

    of the operating distance). The initial force is about 80N, the force at the end of free movement is about 15N.

    The striker serves for actuation of the trip-free mechanism of the switch (gure 1).

    ln

    l3

    l1

    cnan

    Mnmm abakn n

    Maxmm abakn n

    Bck-p fs-lks gsBack-up fuse-links have a rated minimum breaking current from which the fuse-links are able to interrupt current.

    Back-up fuse-links are not supposed to operate below their minimum breaking current (below l3). Their operating

    range is from l3

    to the maximum rated breaking current (l1). For the assignment of back-up fuse-links, it is important

    to note that the lowest short-circuit current is higher at the site of the HV back-up fuse-link than l3

    (IKmn

    > i3).

    If the short-circuit current is lower than the minimum breaking current, additional protection must be provided.

    Gl pps fs-lks gMersen General purpose fuse-links have an extended operating range for low currents. The fuse-links are capable

    of interrupting all currents from a current that causes the fuse-link to melt within a time not less than 1 hour

    up to the maximum rated breaking current (l1). These fuse-links are therefore also able to reliably interrupt

    low fault currents.

    Bck-p fs-lks gs CPD

    (Clld P Dssp)The CPD designed by Mersen controls the power dissipation of the fuse-link according to Ohms

    law and ts both Limitor-PD and -PTD ranges.

    The striker of all the Limitor high voltage fuse-links published here are of medium type

    (80N class) as per the IEC 60282-1 standard (strikers are ranked as per the energy they release

    between two specied points during their trip). As the back-up fuse-link is combined with a switch

    the CPD operates the switch before a too high power level is dissipated by the fuse-link.

    Bck-p fs-lks gs l skThe thermal striker patented by Mersen ts the Limitor-PTS range. The Limitor-ptS an

    is dedicated to switch-fuse combination.

    ln

    l3

    l1

    cnan

    Mln nwith melting

    time 1h

    Maxmm abakn n

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    5/28

    HVfuse-links

    5

    Terms and defnitions

    Bkg cpcy i1

    The breaking capacity is also referred to as the rated maximum breaking

    current. This clearly indicates that this is the maximum current which

    can be interrupted by the fuse-link. I1

    of the fuse-link must be greater

    than the maximum short-circuit current at the site of the fuse-link (I1

    > iKmax

    ).

    m bkg c i3

    The minimum breaking current is referred to as the rated minimum breaking current. This value must be

    specied for back-up fuse-links. From this current, back-up fuse-links are capable to breaking fault currents.

    The fuse-links must be assigned to the system so that no fault current below I3

    can occur at the site

    of the fuse-link (due to the system parameters or other protective devices).

    P dssp f fs-lk P

    The power dissipation of a HV fuse-link is specied at the rated current of the fuse-link. For protectionwith HV fuse-links, it should be noted that the operating current is normally half the rated current.

    Because of the physical relationships, the actual power dissipation is less than a quarter of the value

    pwarm

    for HV fuse-links shown in the technical data table.

    t-c ccsc (i/ ccsc)The time-current characteristic shows the correlation between current and time up to the melting

    of a fuse-element. The virtual time (tvs

    ) is specied to enable a comparison of the l/t characteristics

    of fuse-links below 100ms. For co-ordination with other protective devices, e.g. load interrupter switches

    or circuit breakers, the melting integral I2t must be referred to for melting times below 100ms.

    C lAt high short-circuit currents, HV fuse-links interrupt current within several milliseconds that means,

    the sinusoidal current does not reach its peak value and that HV fuse-links are current limiting devices.

    This is a signicant advantage compared to mechanical switches whose contacts take longer to open

    and interrupt currents at natural zero. During this time, the peak short-circuit current is able to freely develop

    its dynamic force. By using HV fuse-links, this surge current is limited within several ms to a fraction

    of its peak value and the design of the subsequent system can be reduced in terms of dynamic forces.

    Scg vlgSo that HV fuse-links perform a current-limiting action, the short-circuit current must be limited

    and reduced as it increases.

    This requires a switching voltage that exceeds the driving system voltage and forces the current to zero.This switching voltage must not exceed the specied permissible value of 2,2 times the peak value

    of the maximum rated voltage. Limitor HV fuse-links are within this limit.

    rd vlg gIt is important for HV fuse-links that they must be operated at the voltage

    for which they have been rated. Accordingly, the operating voltage

    corresponds to the maximum rated voltage of the fuse-link.

    Owing to the switching voltage occurring during arcing, the fuse-link cannot

    be used at lower voltages without limitation. A lower operating voltage at which

    the fuse-link can still be used without exceeding the system insulation level

    during extinction must therefore be taken into account.

    From these two values results the permissible voltage range of the fuse-link,

    which is shown on the fuse-link or in the technical data, e.g. 10/24kV.

    Fig. 1

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    6/28

    HV

    fslnks

    6

    Terms and defnitions

    DssHV fuse-links in this product list conform to DIN 43 625. The contact cap dimensions dened in this standard are shown in Fig. 2.

    The dimension e varies depending on the rated voltage of HV fuse-links, which is shown as a dimension for fuse-links

    in the technical data tables. The diameter d also varies with the rated current, whereby this dimension is also shownin the tables.

    Pc f sfsThe following should be observed for HV fuse-link selection:

    a) Transformer ratings

    Service voltage (U)

    Rated output (S)

    Relative short-circuit voltage (Uk

    %)

    Inrush current (factor 8...12 In)

    b) Time-current characteristic of HV fuse-linksc) Secondary devices/selectivity

    Pcd bsd xpl:A 630kVA transformer has a transformer rated current of 18,2A at a service voltage of 20kV. The relative short-circuit voltage

    is 4% and the inrush current is 12 x In. The short-circuit current on secondary terminal short-circuit is given from the relative

    short-circuit voltage. The transformer must be designed to withstand this current for 2 seconds. This condition results in point b)

    in Fig. 3. HV fuse-links must interrupt this current within 2 seconds. In Fig. 3, the fuse-link F4 must not be used

    for this transformer, as the fuse-link will require longer than 2 seconds to melt at this short-circuit current.

    The inrush current is plotted for a duration of 0,1 seconds,

    resulting in point a). This inrush current must not melt the fuse-link,

    for which reason the fuse-link F1 cannot be used for this

    transformer. The fuse-links F2 and F3 can be used for this

    transformer, since their time-current characteristics are

    between the points a) and b). A transformer can thus be

    assigned several HV fuse-links for various rated currents.

    Decisive for selection of the correct fuse-link is the time-current

    characteristic and not the rated current of the HV fuse-link.

    Dimensions acc. to DIN 43 625 in mm.

    d= 88 max

    Fig. 2

    Fig. 3

    F1 F4) Time-current characteristics of HV fuse-links

    a) Inrush current

    b) lowest short-circuit current of transformer

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    7/28

    HVfuse-links

    7

    Slc bl

    Limitor-G General Purpose use-linksaccording to IEC 60282-1

    t-c ccccs

    Fig. 13

    6/12 kV

    Fig.14

    10/24 kV

    Clgnb

    rfcnb

    rg u(kV)

    i(a)

    L()

    D()

    i1

    (ka)r(m)

    P(w)

    i(kas)

    wg(kg)

    45DG120V6,3P W1000151A General Purpose, striker 6/12 6,3 292 65 40 128 6 2 2,3

    45DG120V10P X1000152A General Purpose, striker 6/12 10 292 65 40 70 8 3,8 2,3

    45DG120V16P Y1000153A General Purpose, striker 6/12 16 292 65 40 35 10 14 2,3

    45DG120V25P Z1000154A General Purpose, striker 6/12 25 292 65 40 20,5 15 36 2,3

    45DG120V40P A1000155A General Purpose, striker 6/12 40 292 78 40 12,2 24 110 3,1

    45DG120V50P B1000156A General Purpose, striker 6/12 50 292 88 40 9,9 31 150 3,7

    45DG240V4P C1000157A General Purpose, striker 10/24 4 442 78 40 280 5 1,8 4,1

    45DG240V6,3P D1000158A General Purpose, striker 10/24 6,3 442 78 40 256,5 11 2 4,1

    45DG240V10P E1000159A General Purpose, striker 10/24 10 442 78 40 135 15 3,6 4,1

    45DG240V16P F1000160A General Purpose, striker 10/24 16 442 78 40 70,3 21 14 4,1

    45DG240V25P G1000161A General Purpose, striker 10/24 25 442 88 40 41,2 31 39 4,5

    Rated voltage range

    of fuse-link [kV]Service voltage oftransformer [kV]

    Mode of protectionRated current of fuse-link [A]

    Transformer output [kVA]

    rel. short-circuit voltage UK = 4% uK = 5%

    50 100 125 160 200 250 315 400 500 630 800 1000

    6/12 Transformer rated current [A] 4,8 9,6 12 15,4 19,2 24,1 30,3 38,5 48,1 60,6 77,1 96,3

    6 Rated current of fuse-link [A 6,3 16 16 16-25 25 25-40 40 40-50 50 50 - -

    6/12Transformer rated current [A] 2,9 5,8 7,2 9,2 11,5 14,4 18,2 23,1 28,9 36,4 46,2 57,7

    Rated current of fuse-link [A] 6,3 6,3-10 10 16 16 16-25 25 25-40 40 40-50 50 5010

    10/24Transformer rated current [A] 1,5 2,9 3,6 4,6 5,8 7,2 9,1 11,5 14,4 18,2 23,1 28,9

    Rated current of fuse-link [A] - 4 4-6,3 6,3 6,3-10 10 16 16 16 25 25 2520

    Table 5

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    8/28

    HV

    fslnks

    8

    Bck-p fs-lksIn order to increase the utilization range of a switch, it is combined with current limiting HV fuse-links.

    This combination unit offers short-circuit protection in addition to load switching capacity. HV fuse-links

    provide short-circuit protection, while the switch interrupts the currents below the take-over current of the

    combination unit. In addition to the inrush current, short-circuit current on secondary terminal

    short-circuits and low voltage selectivity, the following switch characteristics should be taken into account:

    Rated transfer current (lansf

    )

    Fuse-initiated opening time of the switch (t0)

    Fig. 9 shows the rated transfer current (lansf

    ) as a vertical line.

    The fuse-initiated opening time (t0) must be multiplied by 0,9 (procedure according to IEC 62271-105

    and VDE 0671 T105) and a horizontal line be drawn. This results in an intersection that is characteristicto the switch and must be established for each switch individually.

    This switch intersection divides the sheet into four quadrants (see Fig. 9).Suitable for the switch-fuse combination are HV fuse-links only with a time-current characteristic

    that does not pass through quadrant IV (forbidden area).

    Generally suitable for use in switch-fuse combinations according to IEC 62271-105

    and VDE 0671 T105 are all HV fuse-links with striker which meet this criterion.

    Mersen has assigned HV fuse-links to the switch-fuse combination and the transformers of all

    major manufactures. These documents are available on request.

    Fig. 9: Selection of HV fuse-links acc. to IEC62 271-105 and VDE 0671 T105

    High voltage alternating current switch-use

    according to IEC 62271-105and VDE 0671 T105

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    9/28

    HVfuse-links

    9

    Clgnb

    rfcnb

    rg u(kV)

    i(a)

    L()

    D()

    i1

    (ka)i3

    (a)r(m)

    P(w)

    i(kas)

    wg(kg)

    45DB72V2P N1000098A Back-up with striker 3/7,2 2 192 56 63 15 256 1,8 0,6 1,1

    45DB72V4P P1000099A Back-up with striker 3/7,2 4 192 56 63 20 256 5 0,8 1,1

    45DB72V6,3PD S209293A Back-up with striker 3/7,2 6,3 192 56 63 20 256 11 0,8 1,1

    45DB72V10PD T209294A Back-up with striker 3/7,2 10 192 56 63 35 144 19 3 1,1

    45DB72V16PD V209295A Back-up with striker 3/7,2 16 192 56 63 64 41 13 2,34 1,1

    45DB72V20PD W209296A Back-up with striker 3/7,2 20 192 56 63 80 32 14,5 3,9 1,1

    45DB72V25PD X209297A Back-up with striker 3/7,2 25 192 56 63 95 25 20 4,9 1,1

    45DB72V32PD Y209298A Back-up with striker 3/7,2 31,5 192 56 63 110 19 23 7 1,1

    45DB72V40PD Z209299A Back-up with striker 3/7,2 40 192 56 63 134 12,5 30 14 1,1

    45DB72V50PD A209300A Back-up with striker 3/7,2 50 192 56 63 190 9,25 35 25,3 1,1

    45DB72V63P B209301A Back-up with striker 3/7,2 63 192 65 63 220 8,75 60 41,2 1,4

    45DB72V80P C209302A Back-up with striker 3/7,2 80 192 65 63 300 6,25 85 84 1,4

    45DB72V100P D209303A Back-up with striker 3/7,2 100 192 65 63 350 5 96 93,6 1,4

    45DB72V125PD Q1000100A Back-up with striker 3/7,2 125 192 88 63 435 3 75 440 2,4

    45DB72V160P R1000101A Back-up with striker 3/7,2 160 192 88 63 500 2,9 120 500 2,4

    45DB72V200P S1000102A Back-up with striker 3/7,2 200 192 88 63 610 2,5 200 654 2,4

    Limitor-P back-up use-linkswithout controlled power dissipation CPD

    rd vlg gf fs-lk [kV]

    3/7,2 6/12 10/24 20/36

    Svc vlgf sf [kV]

    6 10 20 30

    rel.sho-cicui

    volge

    tnsfome

    oupu

    [kVa]

    tnsfomeed

    cuen[a]

    redcuenof

    fuse-link[a]

    tnsfomeed

    cuen[a]

    redcuenof

    fuse-link[a]

    tnsfomeed

    cuen[a]

    redcuenof

    fuse-link[a]

    tnsfomeed

    cuen[a]

    redcuenof

    fuse-link[a]

    uK

    = 4%

    50 4,8 1620 2,9 10 1,5 4 0,96 26,3

    100 9,6 2031,5 5,8 1620 2,9 10 1,9 6,310

    125 12 2540 7,2 2025 3,6 1016 2,4 10

    160 15,4 31,550 9,2 2031,5 4,6 1620 3,1 10

    200 19,2 4063 11,5 2540 5,8 1620 3,8 1016

    250 24,1 4080 14,4 31,550 7,2 2025 4,8 1620

    315 30,3 50100 18,2 4063 9,1 2031,5 6,1 1625

    400 38,5 63125 23,1 4080 11,5 2540 7,7 2025

    500 48,1 80160 28,9 50100 14,4 31,550 9,6 2031,5

    630 60,6 100200 36,4 63100 18,2 4063 12,1 2540

    800 77,1 125200 46,2 80125 23,1 4063 15,4 31,540

    uK

    = 5%1000 96,3 125160 57,7 100160 28,9 5080 19,2 4050

    1250 120,3 160200 72,2 125200 36,1 63100 24,1 4050

    uK = 6% 1600 154 200 92,4 125200 46,2 80100 30,8 5063

    Table 1

    Bold typed gures are preferred values

    Slc bl

    Limitor-P&-PT back-up use-linkswith and without controlled power dissipation CPD

    according to IEC 60282-1

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    10/28

    HV

    fslnks

    10

    Clg

    nb

    rfc

    nb

    rg u

    (kV)

    i

    (a)

    L

    ()

    D

    ()

    i1

    (ka)

    i3

    (a)

    r

    (m)

    P

    (w)

    i

    (kas)

    wg

    (kg)45DB120V1P T1000103A Back-up with striker 6/12 1 292 56 63 14 1400 1,6 0,2 1,7

    45DB120V2P V1000104A Back-up with striker 6/12 2 292 56 63 16 500 2,2 0,4 1,7

    45DB120V4P W1000105A Back-up with striker 6/12 4 292 56 63 22 340 6 0,7 1,7

    45DB120V6,3P F209305A Back-up with striker 6/12 6,3 292 56 63 30 185 9 1 1,7

    45DB120V10P G209306A Back-up with striker 6/12 10 292 56 63 42 138 17 1,5 1,7

    45DB120V16P H209307A Back-up with striker 6/12 16 292 56 63 54 107 38 2 1,7

    45DB120V20P J209308A Back-up with striker 6/12 20 292 56 63 73 71 38 4 1,7

    45DB120V25P K209309A Back-up with striker 6/12 25 292 56 63 93 52 46 6 1,7

    45DB120V32P L209310A Back-up with striker 6/12 31,5 292 56 63 105 42 65 10 1,7

    45DB120V40P M209311A Back-up with striker 6/12 40 292 56 63 125 22,5 54 30 1,7

    45DB120V50P N209312A Back-up with striker 6/12 50 292 56 63 160 18 70 50 1,7

    45DB120V63P P209313A Back-up with striker 6/12 63 292 56 63 230 12,8 85 100 1,7

    45DB120V80P Q209314A Back-up with striker 6/12 80 292 65 63 350 10,6 115 150 2,1

    45DB120V100P R209315A Back-up with striker 6/12 100 292 65 63 500 8,5 156 200 3,1

    45DB120V125P X1000106A Back-up with striker 6/12 125 292 88 63 480 4,75 117 440 3,7

    45DB120V160P Y1000107A Back-up with striker 6/12 160 292 88 63 560 4,25 217 500 3,7

    45DB120V200P Z1000108A Back-up with striker 6/12 200 292 88 63 610 3,75 333 654 3,7

    45DB175V6,3P V1000564A Back-up with striker 10/17,5 6,3 367 56 63 30 245 11 1 2,1

    45DB175V10P W1000565A Back-up with striker 10/17,5 10 367 56 63 43 180 22 1,5 2,1

    45DB175V16P X1000566A Back-up with striker 10/17,5 16 367 56 63 54 150 53 2 2,1

    45DB175V20P Y1000567A Back-up with striker 10/17,5 20 367 56 63 73 102 56 4 2,1

    45DB175V25P Z1000568A Back-up with striker 10/17,5 25 367 56 63 93 78 73 6 2,1

    45DB175V32P A1000569A Back-up with striker 10/17,5 31,5 367 56 63 105 59 95 10 2,1

    45DB175V40P B1000570A Back-up with striker 10/17,5 40 367 56 63 125 33,8 79 30 2,1

    45DB175V50P C1000571A Back-up with striker 10/17,5 50 367 56 63 205 26 106 50 2,145DB175V63P D1000572A Back-up with striker 10/17,5 63 367 56 63 280 18,4 130 100 2,1

    45DB175V80P E1000573A Back-up with striker 10/17,5 80 367 65 63 350 15 180 150 2,6

    45DB175V100P F1000574A Back-up with striker 10/17,5 100 367 88 63 500 13 280 200 3,5

    45DB240V1P A1000109A Back-up with striker 10/24 1 442 56 63 14 2170 2,2 0,2 2,5

    45DB240V2P B1000110A Back-up with striker 10/24 2 442 56 63 16 800 3,4 0,4 2,5

    45DB240V4P C1000111A Back-up with striker 10/24 4 442 56 63 23 545 10 0,7 2,5

    45DB240V6,3P S209339A Back-up with striker 10/24 6,3 442 56 63 30 297 13 1 2,5

    45DB240V10P T209340A Back-up with striker 10/24 10 442 56 63 43 220 26 1,5 2,5

    45DB240V16P V209341A Back-up with striker 10/24 16 442 56 63 54 197 73 2 2,5

    45DB240V20P W209342A Back-up with striker 10/24 20 442 56 63 73 132 76 4 2,5

    45DB240V25P X209343A Back-up with striker 10/24 25 442 56 63 93 96 89 6 2,5

    45DB240V32P Y209344A Back-up with striker 10/24 31,5 442 56 63 105 78 127 10 2,5

    45DB240V40P Z209345A Back-up with striker 10/24 40 442 56 63 125 45 114 30 2,5

    45DB240V50P A209346A Back-up with striker 10/24 50 442 56 63 205 35 147 50 2,5

    45DB240V63P B209347A Back-up with striker 10/24 63 442 56 63 280 24 170 100 2,5

    45DB240V80P C209348A Back-up with striker 10/24 80 442 65 63 310 20 233 150 3,1

    45DB240V100P D209349A Back-up with striker 10/24 100 442 78 63 430 18 400 200 4,2

    45DB240V125P D1000112A Back-up with striker 10/24 125 442 88 40 760 11,7 117 350 5,9

    45DB240V160P E1000113A Back-up with striker 10/24 160 442 88 31,5 900 9,45 217 500 5,9

    45DB240V200P F1000114A Back-up with striker 10/24 200 442 88 31,5 1050 7 333 730 5,9

    45DB360V2P G1000115A Back-up with striker 20/36 2 537 56 31,5 15 755 9 0,6 2,7

    45DB360V4P H1000116A Back-up with striker 20/36 4 537 56 31,5 20 755 32 0,8 2,7

    45DB360V6,3PD S209362A Back-up with striker 20/36 6,3 537 56 31,5 20 827 39 0,6 2,7

    45DB360V10PD T209363A Back-up with striker 20/36 10 537 56 31,5 33 463 65 2 2,7

    45DB360V16PD V209364A Back-up with striker 20/36 16 537 56 31,5 66 210 67 2,34 2,745DB360V20PD W209365A Back-up with striker 20/36 20 537 56 31,5 95 147 84 3,9 2,7

    45DB360V25PD X209366A Back-up with striker 20/36 25 537 56 31,5 110 125 100 6,5 2,7

    45DB360V32PD Y209367A Back-up with striker 20/36 31,5 537 65 31,5 135 85 119 7 3,7

    45DB360V40PD Z209368A Back-up with striker 20/36 40 537 65 20 200 65 176 14,2 3,7

    45DB360V50PD J1000117A Back-up with striker 20/36 50 537 88 20 220 42 183 40 6,5

    45DB360V63PD K1000118A Back-up with striker 20/36 63 537 88 20 280 35 271 61,7 6,5

    Limitor-P back-up use-linkswithout controlled power dissipation CPD

    according to IEC 60282-1

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    11/28

    HVfuse-links

    11

    applcLimitor HV fuse-links type CPD meet the requirements of IEC 60282-1 and were specically developed to be installed in

    compact sized enclosed SF6

    insulated substations. In these substations HV fuse-links are enclosed in narrow fuse compartments

    which on the one hand prevent efcient cooling of the fuse-links and on the other hand have a limited thermal power acceptance

    themselves. Overheating of fuse compartments in such enclosures is, however, not to be expected, if the fuse-links have been

    properly selected by their rated current according to the transformer to be protected (see table 3) and if the melting elements of

    the fuse-links are in faultless condition (Fig. 8).

    One or more of the melting elements connected in parallel may, however, be interrupted by transient currents caused by

    transformer inrush or lightning strikes. Fuse-links having one or more of the paralleled melting elements interrupted, dissipate

    signicantly more heat than faultless fuse-links. There is a certain risk that the limited power acceptance of fuse compartments

    may be exceeded at or even below rated transformer current. HV back-up fuse-links type CPD prevent such potential

    overheating when installed in conjunction with a transformer switch having trip-free mechanism

    Fc dThe CPD striker system controls the power dissipation

    of the fuse-link according to Ohms law (CPD means

    controlled power dissipation). The striker pin is released

    depending on the voltage drop across the fuse-link

    and, therefore depending on the power dissipation.

    The release voltage of the CPD striker system has been

    selected so that the fuse carrying the operating current

    iB does not exceed the limiting value. The CPD striker

    system controls the power dissipation of the fuse-link

    and releases the transformer switch before the permissible

    power acceptance of the fuse compartment will be

    exceeded (Fig. 8).

    Limitor-PT back-up use-linksmeet the requirements oIEC 60282-1with controlled power dissipation CPD

    Fig. 8

    Controlled power dissipation

    Power

    dissipationacc.to

    perm.v

    alueoftheswitchgear

    Voltagedropacc.tothe

    releaseoftheHV

    Fuse-link

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    12/28

    HV

    fslnks

    12

    Clgnb

    rfcnb

    rg u(kV)

    i(a)

    L()

    D()

    i1

    (ka)i3

    (a)r(m)

    P(w)

    i(kas)

    wg(kg)

    45DB120V1PT L1000119A Bak-, sk, cpd 6/12 1 292 56 63 14 1500 1,6 0,09 1,6

    45DB120V2PT M1000120A Bak-, sk, cpd 6/12 2 292 56 63 16 510 2 0,28 1,6

    45DB120V4PT N1000121A Bak-, sk, cpd 6/12 4 292 56 63 22 338 6 0,5 1,6

    45DB120V6,3PT P1000122A Bak-, sk, cpd 6/12 6,3 292 56 63 30 190 8 0,6 1,6

    45DB120V10PT Q1000123A Bak-, sk, cpd 6/12 10 292 56 63 42 139 16 1,15 1,6

    45DB120V16PT R1000124A Bak-, sk, cpd 6/12 16 292 56 63 54 107 38 1,29 1,6

    45DB120V20PT S1000125A Bak-, sk, cpd 6/12 20 292 56 63 73 71 38 3,2 1,6

    45DB120V25PT T1000126A Bak-, sk, cpd 6/12 25 292 56 63 93 52 46 5,2 1,6

    45DB120V32PT V1000127A Bak-, sk, cpd 6/12 31,5 292 56 63 105 43 65 7,2 1,6

    45DB120V40PT W1000128A Bak-, sk, cpd 6/12 40 292 56 63 125 23 54 23,3 1,6

    45DB120V50PT X1000129A Bak-, sk, cpd 6/12 50 292 56 63 160 18 70 34,9 1,6

    45DB120V63PT Y1000130A Bak-, sk, cpd 6/12 63 292 56 63 230 12 85 58,3 1,6

    45DB120V80PT Z1000131A Bak-, sk, cpd 6/12 80 292 65 63 350 10,6 114 90 2,1

    45DB120V100PT A1000132A Bak-, sk, cpd 6/12 100 292 65 63 500 8,5 156 140 2,1

    45DB120V125PT B1000133A Bak-, sk, cpd 6/12 125 292 88 63 480 4 117 440 3,7

    45DB120V160PT C1000134A Bak-, sk, cpd 6/12 160 292 88 63 560 4,3 217 500 3,7

    45DB120V200PT D1000135A Bak-, sk, cpd 6/12 200 292 88 63 610 3,8 333 654 3,7

    45DB240V1PT E1000136A Bak-, sk, cpd 10/24 1 442 56 63 14 2100 2 0,09 2,3

    45DB240V2PT F1000137A Bak-, sk, cpd 10/24 2 442 56 63 16 800 3 0,34 2,3

    45DB240V4PT G1000138A Bak-, sk, cpd 10/24 4 442 56 63 23 550 10 0,45 2,3

    45DB240V6,3PT H1000139A Bak-, sk, cpd 10/24 6,3 442 56 63 30 300 13 0,53 2,3

    45DB240V10PT J1000140A Bak-, sk, cpd 10/24 10 442 56 63 43 220 26 0,94 2,3

    45DB240V16PT K1000141A Bak-, sk, cpd 10/24 16 442 56 63 54 197 73 1,4 2,3

    45DB240V20PT L1000142A Bak-, sk, cpd 10/24 20 442 56 63 73 134 76 3,1 2,3

    45DB240V25PT M1000143A Bak-, sk, cpd 10/24 25 442 56 63 93 96 89 4,5 2,3

    45DB240V32PT N1000144A Bak-, sk, cpd 10/24 31,5 442 56 63 105 79 127 5,9 2,3

    45DB240V40PT P1000145A Bak-, sk, cpd 10/24 40 442 56 63 125 45 114 18,8 2,3

    45DB240V50PT Q1000146A Bak-, sk, cpd 10/24 50 442 56 63 205 35 147 33,5 2,3

    45DB240V63PT R1000147A Bak-, sk, cpd 10/24 63 442 56 63 280 24 170 59,6 2,3

    45DB240V80PT S1000148A Bak-, sk, cpd 10/24 80 442 65 63 310 20,5 233 84 3,1

    45DB240V100PT T1000149A Bak-, sk, cpd 10/24 100 442 78 63 430 18 400 93,6 4,1

    45DB240V125PT V1000150A Bak-, sk, cpd 10/24 125 442 88 40 760 11,7 117 350 5,9

    Limitor-PT back-up use-linkswith controlled power dissipation CPD

    according to IEC 60282-1

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    13/28

    HVfuse-links

    13

    Limitor-P&-PT back-up use-linkswith and without controlled power dissipation CPD

    according to IEC 60282-1

    Fig.4

    3/7,2 kV

    Fig.6

    10/24 kV

    Fig.5

    6/12 kV

    Fig.7

    20/36 kV

    t-c ccccs

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    14/28

    HV

    fslnks

    14

    Limitor-PD back-up use-linkswithout controlled power dissipation CPD

    according to VDE 0670 T402

    Rated voltage rangeof fuse-link [kV]

    Service voltage oftransformer [kV]

    Mode of protectionra nof fuse-link [A]

    Transformer output [kVA]

    rel. short-circuit voltage UK

    = 4% uK

    = 5%

    50 100 125 160 200 250 315 400 500 630 800 1000

    3/7,2

    Transformer ratedcurrent [A]

    4,8 9,6 12 15,4 19,2 24,1 30,3 38,5 48,1 60,6 77,1 96,3

    with NH gG 16 20-25 25-31,5 31,5-40 40-50 50-63 63-80 80-100 100-125 125-160 160 160

    6

    with NH gTr - 20-25 25-31,5 31,5-40 40-50 50-63 63-80 80-100 100-125 125-160 160 160

    6/12

    Transformer ratedcurrent [A]

    2,9 5,8 7,2 9,2 11,5 14,4 18,2 23,1 28,9 36,4 46,2 57,7

    with NH gG 10 16 16 20-25 25-31,5 31,5-40 40-50 50-63 63-80 80-100 100-125 100-125

    10with NH gTr - 16 16 20-25 25-31,5 31,5-40 40-50 50-63 63-80 80-100 100-125 125-160

    10/24

    Transformer ratedcurrent [A]

    1,5 2,9 3,6 4,6 5,8 7,2 9,1 11,5 14,4 18,2 23,1 28,9

    with NH gG 6,3 10 10 16 16 16-25 25 25-31,5 31,5-40 40-50 63 63

    20with NH gTr - 10 10 16 16 16-25 25 25-31,5 31,5-40 40-50 63 63-80

    20/36

    Transformer ratedcurrent [A]

    1 1,9 2,4 3,1 3,8 4,8 6,1 7,7 9,6 12,1 15,4 19,2

    with NH gG - 6,3 10 10 16 16-20 20-25 25 25-31,5 31,5-40 40-50 40-50

    30 with NH gTr - 6,3 10 10 16 16-20 20-25 25 25-31,5 31,5-40 40-50 40-50

    Table 1

    Bold typed gures are preferred values

    Slc bl

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    15/28

    HVfuse-links

    15

    Limitor-PD back-up use-linkswithout controlled power dissipation CPD

    according to VDE 0670 T402

    Clgnb

    rfcnb

    rg u(kV)

    i(a)

    L()

    D()

    i1

    (ka)i3

    (a)r(m)

    P(w)

    i(kas)

    wg(kg)

    45DB72V6,3PD S209293A Outdoor with striker 3/7,2 6,3 192 56 63 21 256 11 0,8 1,1

    45DB72V10PD T209294A Outdoor with striker 3/7,2 10 192 56 63 38 144 19 3 1,1

    45DB72V16PD V209295A Outdoor with striker 3/7,2 16 192 56 63 65 41 13 2,34 1,1

    45DB72V20PD W209296A Outdoor with striker 3/7,2 20 192 56 63 92 32 14,5 3,9 1,1

    45DB72V25PD X209297A Outdoor with striker 3/7,2 25 192 56 63 110 25 20 4,9 1,1

    45DB72V32PD Y209298A Outdoor with striker 3/7,2 31,5 192 56 63 123 19 23 7 1,1

    45DB72V40PD Z209299A Outdoor with striker 3/7,2 40 192 56 63 140 12,5 30 14 1,1

    45DB72V50PD A209300A Outdoor with striker 3/7,2 50 192 56 63 194 9,25 35 25,3 1,1

    45DB72V63PD M1000235A Outdoor with striker 3/7,2 63 192 65 63 220 7 60 61,7 1,4

    45DB72V80PD N1000236A Outdoor with striker 3/7,2 80 192 65 63 300 5,2 85 87,4 1,4

    45DB72V100PD P1000237A Outdoor with striker 3/7,2 100 192 78 63 440 4 96 180 2

    45DB72V125PD Q1000100A Outdoor with striker 3/7,2 125 192 88 63 440 3 75 440 2,4

    45DB72V160PD Q1000238A Outdoor with striker 3/7,2 160 192 88 63 610 2,3 120 654 2,4

    45DB120V6,3PD R1000239A Outdoor with striker 6/12 6,3 292 56 63 23 409 19 0,8 1,6

    45DB120V10PD S1000240A Outdoor with striker 6/12 10 292 56 63 35 231 29 3 1,6

    45DB120V16PD T1000241A Outdoor with striker 6/12 16 292 56 63 64 69 21 3,7 1,6

    45DB120V20PD V1000242A Outdoor with striker 6/12 20 292 56 63 90 53 25 4,7 1,6

    45DB120V25PD W1000243A Outdoor with striker 6/12 25 292 56 63 95 41 31 4,92 1,6

    45DB120V32PD X1000244A Outdoor with striker 6/12 31,5 292 56 63 110 31 39 7 1,6

    45DB120V40PD Y1000245A Outdoor with striker 6/12 40 292 56 63 134 20 46 14 1,6

    45DB120V50PD Z1000246A Outdoor with striker 6/12 50 292 56 63 190 16,7 62 25,3 1,6

    45DB120V63PD A1000247A Outdoor with striker 6/12 63 292 65 63 220 11,7 60 63 2,1

    45DB120V80PD B1000248A Outdoor with striker 6/12 80 292 65 63 345 8,7 82 87 2,1

    45DB120V100PD C1000249A Outdoor with striker 6/12 100 292 78 63 400 6,7 96 180 3,1

    45DB120V125PD D1000250A Outdoor with striker 6/12 125 292 88 63 480 4,9 117 440 3,7

    45DB120V160PD E1000251A Outdoor with striker 6/12 160 292 88 63 610 3,8 175 654 3,7

    45DB240V6,3PD F1000252A Outdoor with striker 10/24 6,3 442 56 63 23 640 32 0,8 2,3

    45DB240V10PD G1000253A Outdoor with striker 10/24 10 442 56 63 36 386 48 2 2,3

    45DB240V16PD H1000254A Outdoor with striker 10/24 16 442 56 63 73 127 43 2,34 2,3

    45DB240V20PD J1000255A Outdoor with striker 10/24 20 442 56 63 91 97 53 3,9 2,3

    45DB240V25PD K1000256A Outdoor with striker 10/24 25 442 56 63 116 74 64 6,5 2,3

    45DB240V32PD L1000257A Outdoor with striker 10/24 31,5 442 56 63 125 61 85 7 2,3

    45DB240V40PD M1000258A Outdoor with striker 10/24 40 442 56 63 161 43 103 14,2 2,3

    45DB240V50PD N1000259A Outdoor with striker 10/24 50 442 65 63 230 35 116 24,2 3,1

    45DB240V63PD P1000260A Outdoor with striker 10/24 63 442 65 63 350 25 163 46,4 3,1

    45DB240V80PD Q1000261A Outdoor with striker 10/24 80 442 65 63 460 19 196 104 3,1

    45DB240V100PD R1000262A Outdoor with striker 10/24 100 442 88 63 420 14 279 140 4,1

    45DB360V6,3PD S209362A Outdoor with striker 20/36 6,3 537 56 31,5 23 827 39 0,6 2,7

    45DB360V10PD T209363A Outdoor with striker 20/36 10 537 56 31,5 34 463 65 2 2,7

    45DB360V16PD V209364A Outdoor with striker 20/36 16 537 56 31,5 70 210 67 2,34 2,7

    45DB360V20PD W209365A Outdoor with striker 20/36 20 537 56 31,5 100 147 84 3,9 2,7

    45DB360V25PD X209366A Outdoor with striker 20/36 25 537 56 31,5 110 125 100 6,5 2,7

    45DB360V32PD Y209367A Outdoor with striker 20/36 31,5 537 65 31,5 135 85 119 7 3,7

    45DB360V40PD Z209368A Outdoor with striker 20/36 40 537 65 20 200 65 176 14,2 3,7

    45DB360V50PD J1000117A Outdoor with striker 20/36 50 537 88 20 220 42 183 40 6,5

    45DB360V63PD K1000118A Outdoor with striker 20/36 63 537 88 20 280 35 271 61,7 6,5

    Table 2

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    16/28

    HV

    fslnks

    16

    applcLimitor HV fuse-links type CPD meet the requirements of VDE 0670 T402 and were specically developed to be installed

    in compact sized enclosed SF6

    insulated sub-stations. In these substations HV fuse-links are enclosed in narrow fuse

    compartments which on the one hand prevent efcient cooling of the fuse-links and on the other hand have a limited thermal

    power acceptance themselves(as a rule about 75 W).

    Overheating of fuse compartments in such enclosures is, however, not to be expected, if the fuse-links have been properly

    selected by their rated current according to the transformer to be protected (see table 3) and if the melting elements of the

    fuse-links are in faultless condition (Fig. 9).

    One or more of the melting elements connected in parallel may,

    however, be interrupted by transient currents caused by

    transformer inrush or lightning strikes. Fuse-links having one ormore of the paralleled melting elements interrupted, dissipate

    signicantly more heat than faultless fuse-links.

    There is a certain risk that the limited power acceptance of fuse

    compartments may be exceeded at or even below rated

    transformer current. HV back-up fuse-links type CPD prevent

    such potential overheating when installed in conjunction with a

    transformer switch having trip-free mechanism.

    Fc dAs a rule, the power acceptance of fuse compartments in SF

    6insulated switchgear is limited,

    to e.g. 75 W. In order to prevent thermal overheating, the power dissipation Pa

    of the fuse-link

    must not exceed this value: Pa

    75 W.

    The CPD striker system controls the power dissipation of the fuse-link according to Ohms law

    (CPD means controlled power dissipation).

    The striker pin is released depending on the voltage drop across the fuse-link and,therefore depending on the power dissipation:

    ua

    = r iB

    ua

    iB

    = pa

    75 W

    The release voltage Ua

    of the CPD striker system has been

    selected so that the fuse carrying the operating current

    iB

    does not exceed the limiting value, e.g. 75 W,

    when the resistance R of the fuse-link increases because of

    interrupted melting elements. In this case the CPD striker

    system controls the power dissipation of the fuse-link

    and releases the transformer switch before the permissible

    power acceptance of the fuse compartment will be exceeded

    (Fig. 10). Voltagedropacc.tothe

    re

    leaseoftheHVFuse-link

    Fig. 10

    Controlled power dissipation at 1.3 times transformer rated current

    Powerdissipationacc.to

    perm.valueoftheswitchgear

    630 kVA-Transformer; 40 A fuse-link

    Fig. 9

    Power dissipation of HV fuse-links 40 A and 50 A

    for a 20 kV, 630 kVA transformer

    PowerdissipationPaofHV

    fuse-link[W]

    Transformer operating current to rating current IB/I

    N

    Limitor-PTD back-up use-linkswith controlled power dissipation CPD

    according to VDE 0670 T402

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    17/28

    HVfuse-links

    17

    Rated voltage rangeof fuse-link [kV]

    Service voltage oftransformer [kV]

    Mode of protectionra nof fuse-link [A]

    Transformer output [kVA]

    rel. short-circuit voltage UK

    = 4% uK

    = 5%

    100 125 160 200 250 315 400 500 630 800 1000

    6/12

    Transformer ratedcurrent [A]

    5,8 7,2 9,2 11,4 14,4 18,2 23,1 28,9 36,4 46,2 57,7

    ra nof fuse-link [A]

    16 16 20 25 31,5 40 50 63 80 100 125

    10Power dissipation of HV

    fs-lnks a a nof transformer [W]

    2,4 3,6 4,5 5,3 6,7 8,6 10,7 10,4 13,1 20,8 18,3

    10/24Transformer rated

    current [A]2,9 3,6 4,6 5,8 7,2 9,1 11,6 14,4 18,2 23,1 28,9

    ra nof fuse-link [A]

    10 10 16 161625

    252531

    31,5 40 63 63

    20 Power dissipationof HV fuse-links at rated

    current of transformer [W]3,3 5 2,9 4,6

    7,23,8

    6,210,28,3

    13 15,2 14 22,7

    20/36

    Transformer ratedcurrent [A]

    1,9 2,4 3,1 3,8 4,8 6,1 7,7 9,6 12,1 15,4 19,2

    ra nof fuse-link [A]

    6,3 10 10 16 16 20 25 25 31,5 404050

    30 Power dissipation of HVfs-lnks a a nof transformer [W]

    2,8 3 4,7 3 4,5 5,6 6,5 10 12,3 16,9 27,617,3

    Table 3

    Limitor-PTD back-up use-linkswith controlled power dissipation CPD

    according to VDE 0670 T402

    Benets of thermal protection of the fuse

    cp by CPD:

    CPD controls the power dissipation of the fuse-links

    CPD is based on Ohms law

    CPD works independent on the mounting position of the fuse-links

    CPD releases the striker, before an overheating is reached

    CPD mechanism is non-ageing

    Slc bl

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    18/28

    HV

    fslnks

    18

    Clgnb

    rfcnb

    rg u(kV)

    i(a)

    L()

    D()

    i1

    (ka)i3

    (a)r(m)

    P(w)

    i(kas)

    wg(kg)

    45DB120V10PTD S1000263A Bak-, sk, cpd 6/12 10 292 56 63 35 227 29 3 1,6

    45DB120V16PTD T1000264A Bak-, sk, cpd 6/12 16 292 56 63 64 66 21 3,7 1,6

    45DB120V20PTD V1000265A Bak-, sk, cpd 6/12 20 292 56 63 90 51 25 4,7 1,6

    45DB120V25PTD W1000266A Bak-, sk, cpd 6/12 25 292 56 63 95 40 29 4,9 1,6

    45DB120V32PTD X1000267A Bak-, sk, cpd 6/12 31,5 292 56 63 110 30 39 7 1,6

    45DB120V40PTD Y1000268A Bak-, sk, cpd 6/12 40 292 56 63 134 20 46 14 1,6

    45DB120V50PTD Z1000269A Bak-, sk, cpd 6/12 50 292 56 63 190 15 62 25 1,6

    45DB120V63PTD A1000270A Bak-, sk, cpd 6/12 63 292 65 63 220 12 62 63 2,1

    45DB120V80PTD B1000271A Bak-, sk, cpd 6/12 80 292 65 63 345 8,7 85 87 2,1

    45DB120V100PTD C1000272A Bak-, sk, cpd 6/12 100 292 65 63 500 8,1 152 140 2,1

    45DB120V125PTD D1000273A Bak-, sk, cpd 6/12 125 292 88 63 480 4,5 117 430 3,7

    45DB120V160PTD E1000274A Bak-, sk, cpd 6/12 160 292 88 63 610 4 175 670 3,7

    45DB240V6,3PTD F1000275A Bak-, sk, cpd 10/24 6,3 442 56 63 23 640 31 0,8 2,3

    45DB240V10PTD G1000276A Bak-, sk, cpd 10/24 10 442 56 63 36 386 48 2 2,3

    45DB240V16PTD H1000277A Bak-, sk, cpd 10/24 16 442 56 63 73 127 42 2,3 2,3

    45DB240V20PTD J1000278A Bak-, sk, cpd 10/24 20 442 56 63 91 97 53 3,9 2,3

    45DB240V25PTD K1000279A Bak-, sk, cpd 10/24 25 442 56 63 116 73 60 6,5 2,3

    45DB240V32PTD L1000280A Bak-, sk, cpd 10/24 31,5 442 56 63 125 57 84 7 2,3

    45DB240V40PTD M1000281A Bak-, sk, cpd 10/24 40 442 56 63 161 41 96 14,2 2,3

    45DB240V50PTD N1000282A Bak-, sk, cpd 10/24 50 442 65 63 230 35 146 24,2 3,1

    45DB240V63PTD P1000283A Bak-, sk, cpd 10/24 63 442 65 63 350 24 163 46,4 3,1

    45DB240V80PTD Q1000284A Bak-, sk, cpd 10/24 80 442 65 63 460 19 196 104 3,1

    45DB240V100PTD R1000285A Bak-, sk, cpd 10/24 100 442 78 63 420 14 279 140 4,1

    45DB360V6,3PTD S1000286A Bak-, sk, cpd 20/36 6,3 537 56 31.5 23 889 39 0,6 2,7

    45DB360V10PTD T1000287A Bak-, sk, cpd 20/36 10 537 56 31.5 34 529 66 2 2,7

    45DB360V16PTD V1000288A Bak-, sk, cpd 20/36 16 537 56 31.5 70 190 67 2,35 2,7

    45DB360V20PTD W1000289A Bak-, sk, cpd 20/36 20 537 56 31.5 100 153 84 3,9 2,7

    45DB360V25PTD X1000290A Bak-, sk, cpd 20/36 25 537 56 31.5 110 118 100 6,5 2,7

    45DB360V32PTD Y1000291A Bak-, sk, cpd 20/36 31,5 537 65 31.5 135 82 119 7 3,7

    45DB360V40PTD Z1000292A Bak-, sk, cpd 20/36 40 537 65 20 205 63 176 14,2 3,7

    45DB360V50PTD A1000293A Bak-, sk, cpd 20/36 50 537 88 20 220 41 183 40 6,5

    Table 2

    Limitor-PTD back-up use-linkswith controlled power dissipation CPD

    according to VDE 0670 T402

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    19/28

    HVfuse-links

    19

    Limitor-PD&-PTD back-up use-linkswith and without controlled power dissipation CPD

    according to VDE 0670 T402

    Fig.4

    3/7,2 kV

    Fig.6

    10/24 kV 6,3 A-40 A

    Fig.8

    20/36 kV

    Fig.5

    6/12 kV

    Fig.7

    10/24 kV 50 A-100 A

    t-c ccccs

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    20/28

    HV

    fslnks

    20

    Limitor-PTS is a series of DIN high voltage fuse-links designed

    with low power losses meeting high voltage switch-fuse combination.

    Limitor-PTS is designed for protecting transformers in conjunction

    with air and gas-insulated switchgear up to 3 MVA transformer power.

    This series is a good solution for high ratings. They are designed

    with monobloc fuse-elements and with a built-in thermal striker.

    Because of the new thermal striker patented by Mersen, the Limitor-ptS

    prevent overheating in the fuse compartment when installed with switch-

    fuse combination. The new thermal striker releases before the permissible

    power acceptance is exceeded.

    Fs Monobloc fuse-elements structure

    Built-in thermal striker (30mm release) patented by Mersen

    Extension adaptor

    New caps design for easier maintenance

    Bfs No overheating

    Compact switchgear

    Energy efciency

    n cps

    rgs

    Up to 160A for 12kV

    Up to 125A for 24kV

    Up to 80A for 36kV

    Sdds

    IEC 60282-1

    IEC 62271-105

    VDE 0670 T402

    Limitor-PTS back-up use-linksor switch-use combination

    according to VDE 0670 T402

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    21/28

    HVfuse-links

    21

    Limitor-PTS back-up use-linksor switch-use combination

    according to VDE 0670 T402

    Rated voltage rangeof fuse-link [kV]

    Service voltage oftransformer [kV]

    Mode of protectionra nof fuse-link [A]

    Transformer output [kVA]

    rel. short-circuit voltage UK

    = 4% uK

    = 5%

    100 125 160 200 250 315 400 500 630 800 1000

    6/12

    Transformer ratedcurrent [A]

    5,8 7,2 9,2 11,4 14,4 18,2 23,1 28,9 36,4 46,2 57,7

    ra nof fuse-link [A]

    16 16 20 25 31,5 40 50 63 80 100 125

    10 Power dissipation of HVfs-lnks a a n

    of transformer [W]2,4 3,6 4,5 5,3 6,7 8,6 10,7 10,4 13,1 20,8 18,3

    10/24Transformer rated

    current [A]2,9 3,6 4,6 5,8 7,2 9,1 11,6 14,4 18,2 23,1 28,9

    ra nof fuse-link [A]

    10 10 16 161625

    252531

    31,5 40 63 63

    20 Power dissipationof HV fuse-links at rated

    current of transformer [W]3,3 5 2,9 4,6

    7,23,8

    6,210,28,3

    13 15,2 14 22,7

    20/36

    Transformer ratedcurrent [A]

    1,9 2,4 3,1 3,8 4,8 6,1 7,7 9,6 12,1 15,4 19,2

    ra n

    of fuse-link [A]

    6,3 10 10 16 16 20 25 25 31,5 4040

    50

    30 Power dissipation of HVfs-lnks a a n

    of transformer [W]2,8 3 4,7 3 4,5 5,6 6,5 10 12,3 16,9

    27,617,3

    Table 3

    Slc bl

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    22/28

    HV

    fslnks

    22

    Clgnb

    rfcnb

    rg u(kV)

    i(a)

    L()

    D()

    i1

    (ka)i3

    (a)r(m)

    P(w)

    tl i(Kas)

    wg(kg)

    45DB120V10PTS2 R1032945A Back-up, th. striker, CPD, S 6/12 10 292 56 65 35 227 29 3 1,6

    45DB120V16PTS2 S1032946A Back-up, th. striker, CPD, S 6/12 16 292 56 65 64 66 21 3,7 1,6

    45DB120V20PTS2 T1032947A Back-up, th. striker, CPD, S 6/12 20 292 56 65 90 51 25 4,7 1,6

    45DB120V25PTS2 V1032948A Back-up, th. striker, CPD, S 6/12 25 292 56 65 95 40 29 4,92 1,6

    45DB120V32PTS2 W1032949A Back-up, th. striker, CPD, S 6/12 31,5 292 56 65 110 30 39 7 1,6

    45DB120V40PTS2 X1032950A Back-up, th. striker, CPD, S 6/12 40 292 56 65 134 20 46 14 1,6

    45DB120V50PTS2 Y1032951A Back-up, th. striker, CPD, S 6/12 50 292 56 65 190 15 62 25,3 1,6

    45DB120V63PTS2 M1018313A Back-up, th. striker, CPD, S 6/12 63 292 65 80 260 11,9 58 57 2,1

    45DB120V80PTS2 N1018314A Back-up, th. striker, CPD, S 6/12 80 292 65 80 280 9,6 82 90 2,1

    45DB120V100PTS2 P1018315A Back-up, th. striker, CPD, S 6/12 100 292 78 80 350 7,5 105 145 2,3

    45DB120V125PTS2 Q1018316A Back-up, th. striker, CPD, S 6/12 125 292 88 80 440 5,3 110 296 2,5

    45DB120V100PTS3 R1018317A Back-up, th. striker, CPD, S 6/12 100 442 78 80 350 7,5 95 150 3,3

    45DB120V125PTS3 S1018318A Back-up, th. striker, CPD, S 6/12 125 442 78 80 440 5,4 105 300 3,3

    45DB120V160PTS3 V1018320A Back-up, th. striker, CPD, S 6/12 160 442 78 80 600 4,1 145 500 3,3

    45DB240V10PTS Z1032952A Back-up, th. striker, CPD, S 10/24 10 442 56 65 36 386 48 0,8 2,3

    45DB240V16PTS A1032953A Back-up, th. striker, CPD, S 10/24 16 442 56 65 73 127 42 2 2,3

    45DB240V20PTS B1032954A Back-up, th. striker, CPD, S 10/24 20 442 56 65 91 97 53 2,34 2,3

    45DB240V25PTS C1032955A Back-up, th. striker, CPD, S 10/24 25 442 56 65 113 73 60 3,9 2,3

    45DB240V32PTS D1032956A Back-up, th. striker, CPD, S 10/24 31,5 442 56 65 125 57 84 6,5 2,3

    45DB240V40PTS E1032957A Back-up, th. striker, CPD, S 10/24 40 442 56 65 161 41 96 7 2,3

    45DB240V50PTS X1018322A Back-up, th. striker, CPD, S 10/24 50 442 65 65 230 27,4 82 39 3,1

    45DB240V63PTS Y1018323A Back-up, th. striker, CPD, S 10/24 63 442 78 65 250 21,6 102 63 3,3

    45DB240V80PTS Z1018324A Back-up, th. striker, CPD, S 10/24 80 442 78 65 280 17,3 153 99 3,3

    45DB240V100PTS A1018325A Back-up, th. striker, CPD, S 10/24 100 442 88 65 350 13,6 200 159 4,1

    45DB240V125PTS B1018326A Back-up, th. striker, CPD, S 10/24 125 442 88 65 440 10,1 254 290 4,1

    45DB360V10PTS F1032958A Back-up, th. striker, CPD, S 20/36 10 537 56 31,5 34 529 66 2 2,7

    45DB360V16PTS G1032959A Back-up, th. striker, CPD, S 20/36 16 537 56 31,5 66 190 67 2,34 2,7

    45DB360V20PTS H1032960A Back-up, th. striker, CPD, S 20/36 20 537 56 31,5 95 153 84 3,9 2,7

    45DB360V25PTS J1032961A Back-up, th. striker, CPD, S 20/36 25 537 56 31,5 110 118 100 6,5 2,7

    45DB360V32PTS K1032962A Back-up, th. striker, CPD, S 20/36 31,5 537 65 20 135 82 119 7 3,7

    45DB360V40PTS L1032963A Back-up, th. striker, CPD, S 20/36 40 537 65 20 200 63 176 14,2 3,7

    45DB360V50PTS M1032964A Back-up, th. striker, CPD, S 20/36 50 537 88 20 220 40 183 40 6,5

    45DB360V63PTS C1018327A Back-up, th. striker, CPD, S 20/36 63 537 88 36 260 31,9 165 65 6,5

    45DB360V80PTS F1018330A Back-up, th. striker, CPD, S 20/36 80 537 88 36 350 24,2 230 11,2 6,5

    Limitor-PTS back-up use-linksor switch-use combination

    according to VDE 0670 T402

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    23/28

    HVfuse-links

    23

    t-c ccccs

    Actualprearcingtime

    (s)

    rms value of prearc current (A) +/- 10%

    12 kV - 292mm 12 kV - 442mm

    rms value of prearc current (A) +/- 10%

    Actualprearcingtime

    (s)

    Actualprearcingtime(s)

    Actualprearcingtime(s)

    rms value of prearc current (A) +/- 10% rms value of prearc current (A) +/- 10%

    24 kV 36 kV

    Limitor-PTS back-up use-linksor switch-use combination

    according to VDE 0670 T402

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    24/28

    HV

    fslnks

    24

    Dss

    Limitoruse-links dimensions

    Un (kV)

    3 / 7,2 192

    6 / 12 292

    10 / 17,5 367

    10 / 24 442

    20 / 36 537

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    25/28

    HVfuse-links

    25

    Clips

    Bases

    Dss

    Sz rfn Nmb Catalog Number pakan

    MR 45 + spring L096472A MR45R 1

    MR 45 without connection lug S210236B MR55R 2

    Voltage (kV) Sz us rfn Nmb Catalog Number pakan

    7,2 SI 7,2/192 Indoor G209421A SI72V192 1

    12 SI 12/292 Indoor H209422A SI120V292 1

    17,5 SI 17,5/292 Indoor J209423A SI175V292 1

    24 SI 24/442 Indoor K209424A SI240V442 1

    36 SI 36/537 Indoor M209426A SI360V537 1

    12 SE 12/292 Outdoor S210328A SE120V292 1

    17,5 SE 17,5/292 Outdoor T210329A SE175V292 1

    24 SE 24/442 Outdoor V210330A SE240V442 1

    36 SE 36/537 Outdoor W210331A SE360V537 1

    Voltage(kV)

    Length of fuseL (mm)

    Sz

    Dielectric withstand (phase to ground) Dimensions (mm)Weight(kg)50Hz-1mn

    Kv Rms1,2/50s peakvoltage A B c d e F

    7,2 192 SI 7,2/192 20 60 400 226 322 347 175 270 3,8

    12 292 SI 12/292 28 75 424 324 200 445 175 270 4,1

    17,5 292 SI 17,5/292 38 95 424 324 200 445 220 315 5,1

    24 442 SI 24/442 50 125 576 476 270 597 270 365 5,5

    36 537 SI 36/537 70 170 670 570 350 691 354 449 7,7

    12 292 SE 12/292 28 75 424 324 200 445 261 356 7,5

    17,5 292 SE 17,5/292 38 95 424 324 200 445 261 356 7,5

    24 442 SE 24/442 50 125 576 476 270 597 309 404 8,8

    36 537 SE 36/537 70 170 670 570 350 691 381 476 13,2

    Limitoruse-links accessories

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    26/28

    HV

    fslnks

    26

    External adaptor

    292/442mm

    Indicating devices

    Neutral conductors

    Dss

    Dss

    Voltage (kV) Nmbof contacts

    Length of exiblepart (mm)

    L (mm) rfn Nmb Catalog Number pakan

    12/36 1 NO/NF 550 710 E092855A MC1-5NFLEXQS500 1

    12/36 2 NO/NF 550 710 F092856A MC1-9NFLEXQS500 1

    Lenght (mm) rfn Nmb Catalog Number pakan

    292 J1006419A 45DB292NEUTRAL 1

    442 L1006421A 45DB442NEUTRAL 1

    rfn Nmb Catalog Number pakan

    H1026244A ADAPTOR292/442 1

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    27/2827

    Notes

  • 7/27/2019 BR High Voltage Fuse Links IEC 60282 1 Product Guide En

    28/28

    Mersen Fac sB

    s.A.s.Rue Jacques de VaucansonF-69720 Saint-Bonnet-de-Mure

    Mersen shaghai Co.

    Ltd.No.55-A6. Shu Shan Road,Songjiang 201611 Shanghai

    Mersen UsA

    nwbuypot-MA L.L.C.374 Merrimac StreetNewburyport, MA 01950

    -7418

    -02-2012

    Main production sites

    Industrial or commercial branch

    A WORLD LEADER

    sfy & lbly

    f lccl p

    a GLoBaL PLaYer

    Mersen designs innovative solutions to address

    its clients specifc needs to enable them to optimize

    their manuacturing process in sectors such as Energy,

    Transportation, Electronics, Chemical, Pharmaceutical

    and Process Industries.

    Global expert in materials and equipment

    or extreme environments and in the saety

    and reliability o electrical equipment.

    BR-HVIEC-02-0612