Retail futurescape - changing technologies for improving retail operations
Boilers: Basic Operations and New Technologies
Transcript of Boilers: Basic Operations and New Technologies
Boilers: Basic Operations and New Technologies
DOUG RITCHIE, SELLERS MANUFACTURING COMPANY, ON BEHALF OFTHE AMERICAN BOILER MANUFACTURERS ASSOCIATION OC T. 27 , 2016
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Do I really have to use a boiler formy steam and hot water?
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Can a guy representing theABMAreally tell me the real story?
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Yes. Like the performance advances of the very practical and efficient internal combustion engine, today’s boilers provide thepractical, reliable and cost-effective steamand hot water to meet your operational needs.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Your source of steam and hot water is reliable and safe if properly maintained, inspected and operated, as with the automobile.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Your boiler or water heater is a pressure vessel with combustion equipment. It is designed with a variety of controls that will shut the unit down for your safety.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Independent Testing is YourAssurance
Underwriters Laboratories (UL) , Edison Testing Laboratories (ETL) and other testing agencyapprovals are examples of independent verification for acceptable products offered by boiler manufacturers.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Many Boiler Types
Boilers are manufactured in many different sizes and configurations depending on the characteristics of the fuel, the specified heat output and the required emissions. Some boilers are designed to produce hot water, while others are designed to produce steam.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Many Boiler Types
The basic pressure vessel with burner
works very well, while we pursue multiple
methods of creating and transferring heat
to the contents of the vessel.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Many Fuel Types
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Boilers run on electricity, natural gas, propane, bio-gas from multiple sources, refuse materials, oil, coal, wood, hydrogen, solar and nuclear energy.
Many Fuel Types
Natural gas is emerging as an ideal packageof cost-effective, reliable, widely-availableand reduced-emissions fuel.
It is also significant that the USA has become the largest natural gas producer in the world.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Basic Classes of Boilers by Design Concept
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Most boilers are classified as either“firetube” or “watertube”.
Firetube Design Class
The “fire” is in the tube(s) and the water is outside the tube(s).
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Watertube Design Class
The water is in the tube(s) and the “fire” is outside the tube(s).
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Other Designs and Basic Principle
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Designs such as cast-iron, coil-type andtubeless shell-type boilers are also available.
The intent is the same. Transfer as much heat content as possible from the fuel to the water for hot water or steam production.
Typical Boiler Metrics
Boilers are generally measured in BTU/hr. and Bhp output. (1 Bhp = 33,479 BTU or about 9.81KW/hr.)
Boiler efficiency can be measured by “stack” temperature, ultimately reflecting the amount of heat transfer from the fuel to the steam or hot water.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Typical Boiler Metrics
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Boiler efficiency is also measured by fuel-to-steam efficiency, basically BTU input versus BTU output, also ultimatelyreflecting the amount of heat transfer from the fuel to the steam or hot water.
(But itdoesn’t consider cycling and purge losses, along with other operating
variables by application that will reduce actualefficiency.)
2 Major Types of Boilers byApplication
“Heating Boilers” and “Power Boilers” as determined by the American Society of Mechanical Engineers (ASME)
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Heating Boilers
ASME states these are for “Steam heating, hot water heating, hot water supply boilers, and potable water heaters intended for low pressure service that are directly fired by oil, gas, electricity, coal or other solid or liquid fuels.”
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Heating Boilers
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Heating boilers that produce hot water are allowed to operate to 160psi or 250 deg F at or near the boiler outlet. If they produce steam, only to 15psi.
This type is identified with an “H Stamp”. (More on this marking shortly.)
Power Boilers
ASME states “Power, electric, and miniature boilers; high temperature water boilers, heat recovery steam generators, and certain fired pressure vessels.”
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Power Boilers
Power boilers operate above 15psi for steam and above 160psi or 250 deg F for hot water.
This type is identified with an “S Stamp”.(More on this marking shortly.)
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
All pressure vessels fall under your “jurisdiction having authority”. Such authorities typically use the AmericanSociety of Mechanical Engineers Boilerand Pressure Vessel Code.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Another key player is the NationalBoard, made up of representativemembers from all US states. Thisorganization provides training and certification for inspectors working in state or municipal agencies, as well as insurance companies.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Per ASME, every pressure vessel manufactured must display a permanent stamp with 1) unique vessel identifiernumber and 2) unique Manufacturer’svessel number.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Each vessel manufactured is electronically and permanently recorded with the National Board, with details includingdestination location, prior to completion and shipment . The vessel is completely traceable from raw materials, through its manufacturing, to the client.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
After shipment, it is up to the owner to conform to the requirements of the jurisdiction having authority where the boiler will be used.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Typical Boiler Permanent Stamps
Large Industrial Steam Boiler Small Commercial Water Heater
ASME H
Stamp
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Inspection, Prevention, Good Operation
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Your jurisdiction having authority typically follows ASME Section VII, for inspection of power boilers and SectionVI for heating boilers:
General Requirements for In-Service Inspection of Pressure-Retaining Items
Inspection is Mandatory
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
In general, if your unit is high pressure steam above15 psi, inspection is typically required annually.
In general, if your unit is hot water, inspectionis typically required every 3 years.
Your jurisdiction having authority will determinethe frequency of inspection.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Inspection is Mandatory – Frequency Inspection is Mandatory
The “pre-inspection activities” and “preparation for internal inspection” are usually carried out bycertified boiler mechanical contractors.
Larger operations have in-housecapability.
The inspector inspects, the owner does everythingelse.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
The actual inspection activity is performed by yourlocal authority having jurisdiction or your insurancecompany.
Inspection is Mandatory
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
There is no substitute for visual inspection both internally and externally, even though there mightbe good preventative maintenance.
Inspection is Mandatory
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Remember, your “jurisdiction having authority” has the final say on your overall boiler inspection, includingthe scope of the inspection, when it will be performed, code(s) compliance, inspection approval or denial with corrective action(s) and frequency of inspection.
Inspection is Mandatory
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Contact your local jurisdiction for yourarea’sspecific requirements.
You can get a state-by-state synopsisatwww.nationalboard.org
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Inspection is Mandatory
http://www.nationalboard.org/PrintAllSynopsis.aspx?Jurisdiction=Select
Is your operation on a Periodic Inspection and
Preventative Maintenance program?
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
1. Overpressure
2. Weakening of the structure
3. Errors in operation of the combustionequipment
Per ASME, there are 3 general areas of
boiler/heater failure
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Prevention - Overpressure
1. Steam pressure gages – readings, calibration
2. Pressure relief valves and fusible plugs,the last resort- leakage, damage
3. Water sight glasses – visual, level fluctuation
4. High and Low water level alarms, trips - indications
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Prevention – Weakening of Structure
1. Boiler start-up - follow procedure to prevent stresson multiple-pass types, less an issue with single-pass and coil tube types (thermalgradients)
2. Control of water level – consistentsupply
3. Internal corrosion – maintain water quality (O2pitting)
4. External corrosion – maintain your room or shelter
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Prevention – Weakening of Structure
5. Boiler shutdown – follow procedure to preventstress, again on the common multi-pass types
6. Boiler out of service – extended periodsprocedure
7. Failure of supports – joints, piping, foundation
8. Mechanical damage – blowdown, scale removal
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Prevention – Operation of Combustion Equipment
1. Follow Manufacturer’s operating instructions in accordance withASME CSD-1 and NFPA85 standards
2. Only properly trained operators, familiar withfuel-burning equipment, should be in charge of theunits
3. Only qualified personnel should solve what appearsto be a malfunction, but is typically a proper safety shutdown. (It shutdown for a reason.)
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
1. Water leaks can be from loose connections, wornor defective components external to theboiler/heater
2. Unusual noises can be from air infiltration inthesystem, low water pressure or scaledeposits
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Prevention – Symptoms “Hints and Tips” Prevention – Symptoms “Hints and Tips”
3. Pressure loss may indicate system steam leakage, defective pressure limit controls, return system check valve, steam trap, feedpump
4. Frequent cycling or shutdown can be result of room or air handler air intake restriction, stack/flue draft change, gas pressure drop, water level fluctuation,a change in demand during the day or from pastusage
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
TheASME has recommended rules for the care andoperation of boilers and related pressure vesseldevices
Good Operation
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
1. Water chemical and deaeration treatment for steam equipment, to maintain efficiency, reduce energy consumption, minimize maintenance, extend equipment life considerably (pH >8.5 and no oxygen greatly reduces corrosion)
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Good Operation – “Some tips from the trenches”
2. Frequent blowdown water removal for steam equipment to remove accumulation of solids released from the water when turned to steam, that can otherwise lead to excessive scaledeposits and poor performance (manual or automatic)
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Good Operation – “Some tips from the trenches” Good Operation – “Some tips from the trenches”
3. Good housekeeping –please keep the boiler room clean and clear of debris and “temporary” storage. Where does the air come into the room? Is it filtered? Is the room dry?
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
4. Hire a reputable mechanical contractor with aboilerspecialty or equivalent experience.
5. Consult with manufacturer’s representative to help train your personnel to properly maintain your equipment.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Good Operation – “Some tips from the trenches”
6. Please follow the manufacturer’s maintenance schedule, with alternative of schedules fromthe ASME, UL and in some cases your jurisdiction having authority.
Good Operation – “Some tips from the trenches”
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
New Technologies
1. Digital Modulating Immersion-Fired Single-Pass Steam or
Hot Water Firetube Boiler - provides volume rapid-
response cold water to steam in <20 minutes and
digitally modulates to your load demands
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
The TYPICAL MULTI-PASSFIRETUBE BOILER IS ALWAYS UNDER STRESS
Large
Temperature
Differentials
One Large
Diffusion
Burner Flame
into Large
Furnace Tube
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
The Immersion-Fired Single-Pass BoilerHeats Evenly and is Not Stressed
Individual
Pre-Mixed
High Velocity
Flames
Directly
into One
Tube Row
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
New Technologies
Digital Modulating Immersion-Fired Single-Pass Boiler<20 minute steam from cold. No hours-long warm-up or cool-down periods cuts energy usage.
Modulates to demand to further cut energy usage. Thermally stable design without
refractories, eliminates most repairs and maintenance costs up to 90%. Very long life, upwards
of 50 years, due to this unique design. From 40Bhp (1,700,000 BTU/hr.) up to 800Bhp
(27,000,000 BTU/hr.)
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
The Immersion-Fired Single-Pass Boiler Significantly Reduces Floorspace/Footprint and Volume for Easier Retrofit and More Compact New Installations
Up to 46% less space taken in your facility
Typical 300bhp Boiler 1,435 ft3,
very large volume and footprint
300bhp Immersion-Fired Boiler
769 ft3, drastically reduced
volume and footprint
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
160 ft2
103 ft2
New Technologies
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
2. Non-Ferrous Immersion-Fired Single-Pass Steam or Hot
Water Firetube Boiler
Good for up to 15psi applications trying to reduce
chemical additives costs.
Good for up to 15 psi applications needing untreated
water passed through from the water source.
New Technologies
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
3. “Parallel Positioning” or “Linkageless” Controls
Newer burners and burner/boiler packages provide this
technology.
New TechnologiesEssentially “fly by wire” as in modern aircraft. Instead of
mechanical cable/rod linkage, individual servos are
electrically-driven for better fuel and air flow adjustment.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
New Technologies
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
4. Variable Frequency Drive (VFD) Motors and Pumps
Modulate to load and reduce electricity consumption
Motors run cooler, last longer
Many utilities provide rebates for the purchase and use
of VFD’s.
New Technologies
Variable Frequency Drive Motors and Pumps
A practical upgrade/retrofit in many cases.
Integral VFD
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
External VFD
New Technologies
5. Economizers – essentially stack/flue-mounted heat
exchangers that extract the last bit of heat and return
warm feedwater to the boiler for improved efficiency
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
New Technologies
6. Condensing Boilers
Started in Europe, and became mandated in the UK.
There is pushback
now due to the short
boiler life (5-10
years) and unrealized
efficiency or savings.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
New Technologies
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
In a non-condensing boiler, about 15-20% of the heat vents out of the
stack/flue in the form of hot steam/water vapor and gases.
In a condensing boiler, a condenser recovers much of the lost heat. As
steam condenses into water, it puts heat back into the system.
In theory, this can increase overall efficiency from the 80-85% range to
as much as 96%.
New Technologies
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
In practice, for a condensing boiler to actually work and achieve this
efficiency, the water returning from your equipment and system back
to the boiler has to be below about 110 deg F. This allows the steam
in the boiler to condense into water.
For many applications the returning water is not cool enough, thus no
condensing occurs and the efficiencies are lost.
Real world lesson: Be sure you actually achieve above 110 deg F return
temperature if you wish to change to a condensing boiler.
Do I really have to use a boiler formy steam and hot water?
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Boilers provide the practical, reliable and cost-effective steam and hot water to meet your operational needs.
@2016 TRSA - 1800 DIAGONAL ROAD, SUITE 200, ALEXANDRIA, VA 22314 – 877.770.9274 - TRSA.ORG
Thank you.
Boilers: Basic Operations and NewTechnologies
DOUG RITCHIE, SELLERS MANUFACTURING CO. WWW.SELLERSMFG.COM
DRITCHIE@ SELLERSMFG. COM 859 -236 -3181 X222