    BOILER TRIP PROTECTION

    MASTER FUEL TRIP PROTECTIONS:

    SLNO

    PARAMTR TRIPCONDN ALARMTRIP TIME

    DELAY REMARKS

    1 Both ID Fans OFF -- -- -- 3 hardwired contacts foreach ID fan (2/3) (HTSwitchgear)

    2 Both FD Fans OFF -- -- -- 3 hardwired contacts foreach FD fan (2/3) (HTSwitchgear)

    4 UCP: EMG PB MFT1and MFT 2

    Pressedtogether

    -- -- --

    5 Any OWS: EMG trip

    command

    Initiated &

    Confirmed

    -- -- --

    6 Furnace Pressure V LO -100 -175 -- 2/3 Pressure Switches

    7 Furnace Pressure V HI +75 +150 -- 2/3 Pressure Switches

    8 Drum Level V LO -125 -225 5 sec 2/3 Transmitter

    9 Drum Level V HI +125 +225 10 sec 2/3 Transmitter

    10 Total Air Flow V LO -- 540rpm) < -0.7 kg/cm

    04. Lub Oil pressure very low 2/3. < 1.2 kg/cm

    05. HP exhaust steam temp. Very high 2/3. > 450oC

    06.Axial shift Very high 2/3.

    >

    .5 mm

    07. Cold gas temp. after H2 cooler high AB 2/3. > 55oC

    08. Cold gas temp. after H2 cooler CD 2/3. > 55oC

    09. Seal oil temp. after cooler high 2/3. > 55oC

    10. Liquid level in main leads high 2/3. > 90 mm

    11. Hot air temp. exciter high 2/3. > 85oC

    12. Turbine / Generator brg Temp >90 deg / > 130 deg

    13. ATRS Trip

    14. Over Speed Trip >3210 rpm

    15. Boiler trip to Turbine trip. -

    16. Generator trip to Turbine trip. -

    17. MOT level very low (2/3) (Through Fire Protectionlogic)

    < 1050 mm