BOILER TRIP PROTECTION
MASTER FUEL TRIP PROTECTIONS:
SLNO
PARAMTR TRIPCONDN ALARMTRIP TIME
DELAY REMARKS
1 Both ID Fans OFF -- -- -- 3 hardwired contacts foreach ID fan (2/3) (HTSwitchgear)
2 Both FD Fans OFF -- -- -- 3 hardwired contacts foreach FD fan (2/3) (HTSwitchgear)
4 UCP: EMG PB MFT1and MFT 2
Pressedtogether
-- -- --
5 Any OWS: EMG trip
command
Initiated &
Confirmed
-- -- --
6 Furnace Pressure V LO -100 -175 -- 2/3 Pressure Switches
7 Furnace Pressure V HI +75 +150 -- 2/3 Pressure Switches
8 Drum Level V LO -125 -225 5 sec 2/3 Transmitter
9 Drum Level V HI +125 +225 10 sec 2/3 Transmitter
10 Total Air Flow V LO -- 540rpm) < -0.7 kg/cm
04. Lub Oil pressure very low 2/3. < 1.2 kg/cm
05. HP exhaust steam temp. Very high 2/3. > 450oC
06.Axial shift Very high 2/3.
>
.5 mm
07. Cold gas temp. after H2 cooler high AB 2/3. > 55oC
08. Cold gas temp. after H2 cooler CD 2/3. > 55oC
09. Seal oil temp. after cooler high 2/3. > 55oC
10. Liquid level in main leads high 2/3. > 90 mm
11. Hot air temp. exciter high 2/3. > 85oC
12. Turbine / Generator brg Temp >90 deg / > 130 deg
13. ATRS Trip
14. Over Speed Trip >3210 rpm
15. Boiler trip to Turbine trip. -
16. Generator trip to Turbine trip. -
17. MOT level very low (2/3) (Through Fire Protectionlogic)
< 1050 mm