BOILER INSTRUMENTATION AND CONTROL
SAYYID AHAMMED SAHAL.P.S S7-DOI
![Page 2: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/2.jpg)
2
How does a boiler works?
A boiler is a water containing vessel which transfers heat from a fuel
source (oil, gas or coal) into steam which is piped to a point where
it can be used to run production equipment, to sterilize, to provide
heat, to steam-clean, etc.
The energy given up by the steam is sufficient to convert it back
into the form of water. When 100% of the steam produced is
returned to be reused, the system is called a closed system.
Since some processes can contaminate the steam, so it is not
always desirable to feed the condensate back into the boiler. A
system that does not return the condensate is called an open
system.
Introduction
![Page 3: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/3.jpg)
3
Open system
![Page 4: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/4.jpg)
4
Closed system
![Page 5: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/5.jpg)
5
Basic type of boilers
The two main types of boilers are:1. Firetube2. Watertube
![Page 6: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/6.jpg)
6
1. Firetube boilers
Fire or hot gases are directed through the inside of tubes within the boiler shell which are surrounded by water. The tubes are arranged in banks so that the gases can be passed through the boiler up to 4 times before passing out the stack. This system exposes the maximum heat transfer surface to the water. Firetube boilers are also known as shell boilers and can produce up to approximately 750 hp or 25,000 lbs of steam per hour. 80% of boilers in use are of this configuration.
![Page 7: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/7.jpg)
7
Firetube Boiler
![Page 8: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/8.jpg)
8
Image of FTB
![Page 9: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/9.jpg)
9
2. Watertube boiler
Fire or hot gases are directed to and around the outside of tubes containing water, arranged in a vertical position. Watertube boilers are usually rectangular in shape and have two or more drums. The separation of steam and water takes place in the top drum, while the bottom drum serves as a collection point for sludge. This system is usually used when more than 750 hp or several hundred thousand lbs of steam per hour, are needed.
There are other designs with special configurations, adapting them to particular applications
![Page 10: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/10.jpg)
10
Watertube Boiler
![Page 11: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/11.jpg)
11
Image of WTB
![Page 12: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/12.jpg)
12
Block diagram of boiler drum
BOILER DRUM
TRANSMITTER
CONTROLLER
CONVERTER
VALVE
FIG. 1. GENERAL BLCOK DIAGRAM OF BOILER DRUM
![Page 13: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/13.jpg)
13
1. Increase uptime and availability
2. Reduce flue gas emissions
3. Maintain boiler safety
4. Control operating costs
Why need boiler controls?
![Page 14: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/14.jpg)
14
Boiler efficiency relates the boilers energy output to
the boilers energy input and can be expressed as:-
Boiler efficiency (%) = Heat exported by fluid/Heat provided by fuel
An accurate control of the amount of air is essential to the boiler
efficiency. Too much air will cool the furnace and carried away
useful heat. And too little air and the combustion will be incomplete. Unburned fuel will be carried over and smoke
may be produced.
Boiler efficiency
![Page 15: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/15.jpg)
15
1. Increase uptime and availability
The primary objective of most boilers operation is maintaining the uptime and availability. It is essential to maintain and upgrade the boiler control systems to assure steam availability.
Modern controls are more reliable and can be readily adjusts to load swings caused by varying plant operations.
![Page 16: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/16.jpg)
16
2. Reduce flue gas emissionsFailure to comply with the current emissions regulations can be as costly as loss of utilities. Government mandates are enforced by fines, threat of closure, or imprisonment will provide sufficient incentives for plants to comply with the regulations; thus, modernize controls are necessary.
Improved in combustion efficiency means reduction in waste disposal problems. And by accurately controlling the oxygen, fuel flow and stack temperature, you will see reductions in plant emissions.
![Page 17: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/17.jpg)
17
3. Maintain boiler safety
Modernize control system will have tight integration with flame safety or burner management system to improve safety.
Accessing field data, diagnostics functions and alarms can be achieved by coupling modern electronic controls. Password security of the configuration software also assures no unintended changes can be done which can endanger your personnel and equipment.
![Page 18: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/18.jpg)
18
4. Control operating costs Reduction in fuel consumption
Reduction in engineering, installation and startup costs
Reduction maintenance costs associated with older
equipment
Reduction manpower with automatic responds
Provide a flexible control strategy to reduce process upsets
Readily data available for remote monitoring to determine process optimization, boiler efficiency and load allocations
![Page 19: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/19.jpg)
19
CONTROL LOOPS
Boiler control systems contain several variable with interaction occurring among the control loops for fuel, combustion air, & feedwater . The overall system generally can be treated as a series of basic control loops connected together. for safety purposes, fuel addition should be limited by the amount of combustion air and it may need minimum limiting for flame stability.
Combustion controls
Amounts of fuel and air must be carefully regulated to keep excess air within close tolerances-especially over the loads. This is critical to efficient boiler operation no matter what the unit size, type of fuel fired or control system used.
Feedwater control Industrial boilers are subject to wide load variations and require quick responding control to maintain constant drum level. Multiple element feed water control can help faster and more accurate control response
![Page 20: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/20.jpg)
20
A combustion control system is broken down into
(a) fuel control and (b) combustion air control subsystems. The interrelationship between these two subsystems necessitate the use of fuel air ration controls.
The primary boiler fuels are coal, oil and gas. The control of gas and oil fuels requires simplest controls- ie, a control valve in the fuel line.
The steam drum pressure is an indication of balance between the inflow and outflow of heat. Therefore by controlling the steam supply one can establish balance between the demand for steam (process load ) and supply of water.
Cumbustion control
![Page 21: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/21.jpg)
21
There are three general types of combustion control schemes used today: (a) Series(b) Parallel(c) Series-parallel
Types of combustion control
![Page 22: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/22.jpg)
22
STEAM PRESSURE
AIR FLOW
FUEL FLOW
(a) Series
In series control, variations in steam header pressure(the master control signal) cause a change in combustion air flow which in turn results in a sequential change in fuel flow. This type of control is limited to small boilers having relatively constant steam load & burning fuel.
![Page 23: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/23.jpg)
23
(b)Parallel
STEAM PRESSURE
AIR FLOW
FUEL FLOW
In parallel control, variation in steam pressure simultaneously adjusts both fuel & air flows. This method is common to any size boilers
![Page 24: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/24.jpg)
24
(c)series-parallel
FUEL FLOW
STEAM FLOW
AIR FLOW
In series-parallel, variation in steam pressure set points are used to adjust the fuel. Flow to the above boiler since steam flow is directly related to heat release of the fuel and hence the air flow, the steam flow can be used as an index of the required combustion air.
![Page 25: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/25.jpg)
25
The control hardware used to carryout the above schemes include
(1) ON-OFF control system(2) Positioning control system(3) Metering controll system
Hardwares used in combustion controll
![Page 26: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/26.jpg)
26
(1) On/off controls Are still used in many industries but are
generally used in small water tube boilers. When the pressure drops to a present value, fuel & air are automatically fed into the boiler at predetermined rate until pressure has risen to its upper limit.
![Page 27: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/27.jpg)
27
On-off control operation
![Page 28: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/28.jpg)
28
(2) Positioning systems
Respond to changes in header pressure by simultaneously positioning the forced draft damper and fuel valve to a predetermined alignment. This is not used in liquid , gaseous fuel – fired boilers
There are two types of positioning systems(a) Single point positioning(b) parallel positioning
![Page 29: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/29.jpg)
29
(a) single point positioning
position system respond to changes in header pressure by simultaneously positioning the forced draft damper and fuel valve to a predetermined alignment either through a common jackshaft and cam valve arrangement called single point positioning.
In single point positioning,the air-fuel ratio adjustment are set up through a manipulation of cam valve and linkage angles,which is performed before the boiler goes into operation
![Page 30: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/30.jpg)
30
(b) Parallel positioning
Parallel positioning with with fuel air ratio is widely used on sigle and multiple burner boilers.It permits the operator to adjust the fuel air ratio over the entire load range’through either a manual or an automatic bias. In bias adjustment,a constant is added or subtracted from the signal to the fuel valve.
![Page 31: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/31.jpg)
31
Parallel positioning with fuel air ratio control
![Page 32: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/32.jpg)
32
(c) Metering control system
In this system control is regulated in accordance with the measured fuel and air flows. This maintains combustion efficiency over a wide load ranges & over long period of time.
In metering controll,the combustion is regulated in
accodance with measured airflow and fuelflows.Metered flow serves as the feedback signal to the controllers to ensure that flow corresponds to demand.
This method helps compensate for the effects of boiler slagging,barometric conditions and changes in fuel quality on boiler perfomance.It also maintains combustion efficiency over wide load ranges and over long periods.
![Page 33: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/33.jpg)
33
Metering control system
![Page 34: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/34.jpg)
34
Feedwater control is the regulation of water to the boiler drum. It provide a mass accounting system for steam leading and feedwater entering the boiler. The water is admitted to the steam drum and after absorbing the heat from furnace generates the steam produced by the boiler.
Feedwater conrol
![Page 35: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/35.jpg)
35
Proper boiler operation requires that the level of water in the steam drum should be maintained within certain band. A decrease in this level may uncover boiler tubes, allowing them to become overheated. An increase in the level of water may interfere with the internal operation of internal devices in the boiler drum. It is important to made that the water level in the boiler drum must be above 50% all the time.
The water level in the boiler drum is related to, but is not a direct indicator of , the quantity of water in the drum. At each boiler load, there is different volume in the water that is occupied by steam bubbles. So if load is increased there are more steam bubbles and this cause water to ‘swell’ or rise, rather than fall because of added water usage.
![Page 36: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/36.jpg)
36
Partial vaporisation in evaporating tubes
![Page 37: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/37.jpg)
37
For small boilers having relatively high storage volumes and slow changing loads ,single element control system is used. It controls feed water flow based on drum level. Response is very slow because a change in feedwater flow takes a long time to show up the level change. As a result the steam drum causes water to increase and decrease in volume, resulting in false measurements.
(1) Single element control system
![Page 38: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/38.jpg)
38
Single element control
![Page 39: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/39.jpg)
39
The two element system overcome these inadequacies by using steam flow changes as a feed forward signal. This control is used in intermediate boilers as well as large boilers. Here the flow and level transmitters are summed by a computing relay and will be the set point for feedwater. Here the response is faster
(2) Two element control system
![Page 40: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/40.jpg)
40
Two element control
![Page 41: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/41.jpg)
41
Boilers that experiences wide and rapid load changes require three element control. Three element control is similar to two element system except that the water flow loop is closed rather than open.
Control action, the third element based on feedwater flow. The level and steam flow signals are summed and used as an index or set point to the feedwater flow. The feedwater flow measurement provides corrective action for variation in feedwater pressure.
(3) Three element control
![Page 42: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/42.jpg)
42
THREE ELEMENT CONTROL
DRUM Computing
Relay
Level
Controller
FC
X
X
X
Flow Controller
FV
Feedwater
FT 1
LT3
STEAM
Feedwater
FT 2
Three element control
![Page 43: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/43.jpg)
43
![Page 44: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/44.jpg)
44
Additional elements can be added to a feedwater control system to improve response accuracy. A five element feedwater control system is essentially a three element configuration in which the steam flow measurement is temperature compensated and drum level measurement is pressure compensated.
(4) Five element control
![Page 45: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/45.jpg)
45
DRUM Computing
Relay
Level
Controller
f(x)
X
FC
X TT
PT
X
5 FT 2
Temperature compensated steam flow
Pressure Compensated Drum Level
Flow Controller
FV
Feedwater
FT 1
4
STEAM
Five element control
![Page 46: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/46.jpg)
46
Transmitters for blow down flow and sootblower flow could be added to five element control to make up seven element feedwater control.
(5) Seven element control
![Page 47: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/47.jpg)
47
DRUM Computing
Relay
Level
Controller
f(x)
X
FC
X TT
PT
X
FT
X
X
f(x)
f(x)
FT
5 FT 2
Temperature compensated steam flow
Pressure Compensated Drum Level
Flow Controller
Drum Blowdown
Tubes Blowdown
Economiser
FV
Feedwater
FT 1
4
LT3
6
7
Bo
iler T
ub
e
STEAM
Seven element controll
![Page 48: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/48.jpg)
48
Advantages
1.Multiple element feedwater control can help: Faster response of systems. More accurate control. Maximum system stability.
2.Metering control system maintains combustion efficiency over wide. load changes and over long period of time.
3.Parallel combustion control can be used in any size of boilers
![Page 49: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/49.jpg)
49
Disadvantages
1. Boilers require quick responding controls.2. Level of the water in the boiler must be kept above 50% of height
![Page 50: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/50.jpg)
50
Future Directions
Microcontrollers & PLC are used as controllers.
![Page 51: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/51.jpg)
51
Conclusion
The various goals of boiler control includes:
To minimize excess air To minimize blowdown To minimize steam pressure To measure efficiency To find when to perform maintenance
![Page 52: boiler instrumentation and control](https://reader036.fdocuments.us/reader036/viewer/2022081414/5532ae4b5503464f7d8b46f2/html5/thumbnails/52.jpg)
52
BIBLIOGRAPHY
Instrumentation Controls Journal -July 2001 Boiler Instrumentation, R. Ramamoorthy Instrument Engineers’ Hand Book Process Control – Bela G. Liptak Process Control Instrmentation
- C.D. Johnson www.control.com www.ask.com