BNI EIP-502-105-Z015 IP67 Modules 4 IO Link/In-/Outputs,12 In-/Outputs User’s Guide

Transcript of BNI EIP-502-105-Z015 E - Balluffusa.balluff.com/manuals/BNI Network Blocks/EtherNet... ·  ·...

BNI EIP-502-105-Z015 IP67 Modules

4 IO Link/In-/Outputs,12 In-/Outputs

User’s Guide

www.balluff.com 1

Content

1 Notes 3 1.1. About this guide 3 1.2. Structure of the guide 3 1.3. Typographical Conventions 3

Enumerations 3 Actions 3 Syntax 3 Cross-references 3

1.4. Symbols 3 1.5. Abbreviations 3

2 Safety 4 2.1. Intended use 4 2.2. General safety notes 4 2.3. Meaning of the warnings 4

3 Getting Started 5 3.1. Modul overview 5 3.2. Mechanical connection 6 3.3. Electrical connection 6

Power Supply 6 Grounding 6 Ethernet IP Interface 6 I/O-Port 7 IO Link-Port 7

4 Technical data 8 4.1. Dimensions 8 4.2. Mechanical data 8 4.3. Operating conditions 8 4.4. Electrical data 8 4.5. Ethernet 9 4.6. Function indicators 9

Modul status 9 Port 9

5 Integration 10 5.1. Data Configuration 10 5.2. Config Data 10

Module Configuration 10 IO Link Port Configuration 10

6 Process Data 11 6.1. Process Data Inputs 11

Standard Input Data 11 IO Link Input Data 11

6.2. Process Data Outputs 12 Standard Output Data 12 IO Link Output Data 12

7 Display 13 7.1. General 13 7.2. Adress Defaults 13 7.3. Controls and visualization 13 7.4. Display information 13 7.5. Design and Symbols 14 7.6. Startup 14

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 2

7.7. Main Menue 14 7.8. IP Setup 15 7.9. IP Config 15 7.10. Module information 16 7.11. General Informations 16

8 Webserver 17 8.1. General 17 8.2. Home 17 8.3. Diagnostic Process 17 8.4. Device Properties 17 8.5. Diagnostic Module 17 8.6. Configurations 17

9 Appendix 18 9.1. Included material 18 9.2. Ordercode 18 9.3. Order Information 18

www.balluff.com 3

1 Notes

1.1. About this guide The BNI EIP-… serves as a decentralized IO Link, input and output module for connecting to an EtherNet/IP™ network.

1.2. Structure of the

guide The guide is organized so that the chapters build on one another.

Chapter 2: Basic safety information. Chapter 3: The main steps for installing the device. Chapter 4: Technical data for the device Chapter 5: Integration Chapter 6: Process data Chapter 7: Display Chapter 8: Webserver Chapter 9:Appendix

1.3. Typographical

Conventions The following typographical conventions are used in this Guide.

Enumerations Enumerations are shown in list form with bullet points.

• Entry 1, • Entry 2.

Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated

by an arrow. � Action instruction 1. � Action result.

� Action instruction 2. Procedures can also be shown as numbers in brackets.

(1) Step no. 1 (2) Step no. 2

Syntax Numbers:

Decimal numbers are shown without additional indicators (e.g. 123), Hexadecimal numbers are shown with the additional indicator hex (e.g. 00hex) or with the prefix “0x” (e.g. 0x00)

Cross-references Cross references indicate where additional information on the topic can be found (see

chapter 4 ”Technical Data”).

1.4. Symbols Note tip This symbol indicates general notes.

Note This symbol indicates a security notice which most be observed.

1.5. Abbreviations BNI Balluff Network Interface

I Standard input port EIP EtherNet/IP™ EMC Electromagnetic Compatibility FE Function ground O Standard output port

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 4

2 Safety

2.1. Intended use

This guide describes The BNI EIP-… serves as a decentralized IO Link, input and output module for connecting to an EtherNet/IP™ network.

2.2. General safety

notes Installation and startup are to be performed only by trained specialists. Any damage

resulting from unauthorized manipulation or improper use voids the manufacturer’s guarantee and warranty. The device is in accordance with EMC Class A. Such equipment may generate RF noise. The operator must take precautionary measures accordingly. The device must be powered only using an approved power supply (see chapter 4 “Technical data”). Only approved cable may be used. Operating and testing The operator is responsible for observing local prevailing safety regulations. When defects and non-clearable faults in the device occur, take it out of service and secure against unauthorized use. Approved use in ensured only when the housing is fully installed.

2.3. Meaning of the warnings

Note! The pictogram used with word ”Caution“ warns of a possible hazardous situation affecting the health of persons or equipment damage. Ignoring these warnings can result in injury or equipment damage. Always observe the described measures for preventing this danger.

www.balluff.com 5

3 Getting Started

3.1. Modul overview

Figure 0.1 – Overview BNI EIP-502-100-Z016 1 Mounting hole

2 EtherNet/IP™ port 2 3 Display 4 Status LED: Communication / Module 5 Port 5 (Standard I/O) 6 Pin/Port LED : Signal status 7 Port 6 (Standard I/O) 8 Port 7 (IO Link, Standard I/O) 9 Port 8 (IO Link, Standard I/O)

10 Port 4 (IO Link, Standard I/O) 11 Port 3 (IO Link, Standard I/O) 12 Port 2 (Standard I/O) 13 Port 1 (Standard I/O) 14 Power Supply Port 15 Label 16 EtherNet/IP™ port 1 17 Grounding connection

1

5

2

3

11

10

12

13

14

17

7

9

6

8

16

15

4

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 6

3 Getting Started

3.2. Mechanical connection

The module is attached using 2 M6 screws and 2 washers. Isolation pad as accessory available

3.3. Electrical

connection

Power Supply Pin Function Description

1 +24 V Output Power

2 +24 V Input Power

3 0 V Input Power Common GND 4 0 V Output Power Common GND

Note Provide sensor/bus power and actuator power from separate power sources if possible. Total current <9A. The total current of all modules may not exceed 9A even when daisy chaining the actuator supply.

Grounding

Note! The FE connection from the housing to the machine must be low-impedance and kept as short as possible.

Ethernet IP Interface

M12, D-coded, female

Pin Function

1 Tx+

2 Rx+

3 Tx-

4 Rx-

www.balluff.com 7

3 Getting Started

I/O-Port M12, A-coded, female

Pin Function

1 +24V, 200mA

2 Input / Output

3 GND

4 Input / Output 5 FE

Note! For the digital sensor inputs follow the input guideline per EN61131-2, type 2.

Note! Each output serves a maximum current of 1,6 amperes. Total current of the module has to be lower than 9 amperes.

Note! Unused I/O port socket must be fitted with cover caps to ensure IP67 protection rating.

IO Link-Port M12, A-coded, female

Pin Function 1 +24V, 1,6 A

2 Input / Output

3 GND

4 IO Link / Input / Output 5 n.c.

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 8

4 Technical data

4.1. Dimensions

4.2. Mechanical data Housing material Die case zinc, matt nickel plated

Enclosure rating per IEC 60529 IP 67 (only when plugged-in and threaded-in)

Supply voltage 7/8” 4-pin male

Input ports / Output ports M12, A-coded (8 x female)

Dimensions (W x H x D in mm) 68 x 224 x 30.9

Mounting type 2-hole screw mount

Ground strap attachment M4

Weight Approx. 670 gr.

4.3. Operating conditions

Operating temperature Ta

Storage temperature -5 °C ... 70 °C -25 C ... 70 °C

EMC - EN 61000-4-2/3/4/5/6 - EN 55011

- Severity level 2B/3A/4B/2B/3A - Gr.1, CL. B

Shock/vibration EN 60068-2-6, EN 60068-2-27 EN 60068-2-29, EN 60068-2-64

4.4. Electrical data Supply voltage 18...30.2 V DC, per EN 61131-2

Ripple <1%

Input current at 24 V 130 mA

www.balluff.com 9

4 Technical data

4.5. Ethernet Ethernet IP port 1 x 10Base-/100Base-Tx

Connection for Ethernet IP port M12, D-coded

Cable types per IEEE 802.3 Shielded twisted pair min. STP CAT 5/ STP CAT 5e

Data transmission rate 10/100 Mbit/s

Max. cable length 100 m

Flow control Half Duplex/Full Duplex (IEEE 802.33x-Pause)

4.6. Function

indicators

Modul status LED Anzeige Funktion

green Output power OK UA

red Low Output power (< 18V)

green Input power OK US

red Low Input power (<18V)

green flashing Wrong or no configuration on module

green Modul operating red flashing Fixed busclock is not possible

Mod

red-green flashing Initial sequence off Module got no IP address

green flashing Module got IP, but no connection could be established

green Connection established

red flashing Connection timeout

Net

red-green flashing Initial sequence off Bus clock: 10 Mbit/s

100 yellow Bus clock: 100 Mbit/s

LNK green Data transfer

Port Each Port has two two-colour LEDs to indidcate the I/O-States. Anzeige Funktion Bemerkung

off I/O-State State of the Input or Output Pin is 0

yellow I/O-State State of the Input or Output Pin is 1

single LED: Short-circuit on dedicated Pin (only if this pin is used as an output)

I/O

Port

red Short-circuit

both LEDs: Short-circuit between Pin 1 and 3 or Short-circuit on both output pins

green IO Link IO Link communication running

Green flashing

IO Link No IO Link communication

red Short-circuit single LED: Short-circuit on Pin 4 both LEDs: Short-circuit between Pin 1 and 3

IO-L

ink P

ort

red flashing

IO Link IO Link Device has wrong configuration

Status –LEDs: Modul status

Port/Pin LEDs: Status of the IO Link and I/O ports

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 10

5 Integration

5.1. Data Configuration

Please enter the following values to your Control System. They describe the datasizes for input, output and config data.

Instance ID Data length

INPUT 100 200

OUTPUT 101 134

CONFIG 102 98 5.2. Config Data In the following tables you can see the mapping of the configuration data string. The default

values which are stated below describe a configuration with IO Link function on Pin 4 and standard input function (normally open) on Pin 2 of each IO Link port. The other Ports does not get configured by config data string, the function of standard I/O ports is set by process data (see 6.1 - Process Data Inputs)

Byte Slot Modul part Description

0…1 1 Module General configuration for the whole module (see 0 - Module Configuration)

2…25 2 IO-Link Port 1 Configuration for the IO-Link Port 1 (see 0 - IO Link Port Configuration)

26…49 3 IO-Link Port 2 Configuration for the IO-Link Port 2 (see 0 - IO Link Port Configuration)

50…73 4 IO-Link Port 3 Configuration for the IO-Link Port 3 (see 0 - IO Link Port Configuration)

74…97 5 IO-Link Port 4 Configuration for the IO-Link Port 4 (see 0 - IO Link Port Configuration)

Module Configuration

Bit

Byte

7 6 5 4 3 2 1 0 Description

0 P3 P2 0 0

1 P7 P6 0 0

Port function 0x00: Standard I/O 0x01: IO-Link

IO Link Port Configuration (optional)

Bit

Byte

7 6 5 4 3 2 1 0 Description

2 Base Time Cycle Time

3 Validation type

Validation type 0 no validation 1 compatible (VID + DID) 2 identical (VID + DID + SerNum)

4 Vendor ID 1

5 Vendor ID 2 Vendor ID

6 Device ID 1

7 Device ID 2

8 Device ID 3

Device ID

9 Serial number 1

… …

24 Serial number 16

Serial number

25 Parameter server

Parameter server 0x8X Enable 0xX1 Upload enable 0xX2 Download enable

… The data of the other IO Link ports has the same structure and follows here

www.balluff.com 11

6 Process Data

6.1. Process Data Inputs

There are 200 bytes of Input data. Have a look at the tables below to see the mapping of the process data inputs.

Byte Modul part Description

0…7 Standard I/O ports Process data inputs on standard Inputs 8…55 IO-Link Port 1 Process data inputs on IO Link Port 1

56…103 IO-Link Port 2 Process data inputs on IO Link Port 2 104…151 IO-Link Port 3 Process data inputs on IO Link Port 3

152…199 IO-Link Port 4 Process data inputs on IO Link Port 4

Standard Input Data

Bit

Byte

7 6 5 4 3 2 1 0 Description

0 I32 I34 I22 I24 I12 I14 I02 I04

1 I72 I74 I62 I64 I52 I54 I42 I44

Input data I04 � Input on port 0 pin 4 If a port is configured as an IO Link port, result is 0.

2 S3 S2 S1 S0

3 S7 S6 S5 S4

Short circuit status Short circuit between Pin 1 and 3 on stated port

4 O22 O34 O22 O24 O12 O14 O02 O04

5 O72 O74 O62 O64 O52 O54 O42 O44

Overload status O04 � Overload on port 0 pin 4 Only if port is configured as output

6 0 0 0 0 0 0 PS PA Power status PS: Sensor power PA: actor power

7 0 0 0 0 0 0 0 0 Reserved

IO Link Input Data

Bit

Byte

7 6 5 4 3 2 1 0 Description

8…39

IO Link Port 1 Input data

40 0 0 0 0 0 0 DC IOL

IO-Link status IOL: Port in IO Link Mode DC: Device connected 0: reserved

41 0 0 0 0 0 0 0 VF IO-Link Error VF: Validation failed 0: reserved

42 Vendor ID 1 43 Vendor ID 2

Vendor ID

44 Device ID 1

45 Device ID 2

46 Device ID 3

Device ID

47 Error Code

48 Additional Code

49 Additional Code

Event 1

50 Error Code

51 Additional Code

52 Additional Code

Event 2

53 Error Code

54 Additional Code

55 Additional Code

Event 3

… The data of the other IO Link ports has the same structure and follows here

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 12

6 Process Data

6.2. Process Data Outputs

There are 134 bytes of output data. Have a look at the tables below to see the mapping of the process data outputs.

Byte Modul part Description

0…5 Standard I/O ports Process data outputs on standard Inputs 6…37 IO-Link Port 1 Process data outputs on IO Link Port 1

38…69 IO-Link Port 2 Process data outputs on IO Link Port 2 70…101 IO-Link Port 3 Process data outputs on IO Link Port 3

102…133 IO-Link Port 4 Process data outputs on IO Link Port 4

Standard Output Data

Bit

Byte

7 6 5 4 3 2 1 0

Description

0 O32 O34 O22 O24 O12 O14 O02 O04

1 O72 O74 O62 O64 O52 O54 O42 O44

Output data O04 � Output on port 0 pin 4 To use this function on a IO Link port the port must be configured as an output (see 0- Module Configuration)

2 R32 R34 R22 R24 R12 R14 R02 R04

3 R72 R74 R62 R64 R52 R54 R42 R44

Restart Restart output here after a detected short-circuit

4 0 0 0 0 0 0 0 0 Reserved

5 0 0 0 0 0 DL GO RO

Display Control DL: Display lock / PLC lock GO: Green LED on Display on RO: Red LED on Display on

IO Link Output Data

Bit

Byte

7 6 5 4 3 2 1 0

Description

6…37

IO Link Port 1 Output data

… The data of the other IO Link ports has the same structure and follows here

www.balluff.com 13

7 Display

7.1. General With the implemented display, the address is set directly on the BNI EIP… devices. The following address types are implemented:

• IP address • Subnet mask • Gateway address.

Each address type consists of 4 octets. Additional the display shows information about the hard- and firmwarerevision. There is a lock function fort he display which can be activated out of the control system. If the lock is set editing isn’t possible anymore (see Bit layout, chapter 8 „Appendix“).

7.2. Adress Defaults IP Address: 169.254.1.1

Subnetmask: 255.255.255.0 Gatewayaddress: 0.0.0.0

7.3. Controls and

visualization

1 Display 2 Arrow-Key 3 Octett-Cursor

4 Address type cursor 5 „Set“-Key 6 LED

7.4. Display

information

IP: IP address SN: Subnet address GW: Gateway address

3: fourth octet 2: third octet 1: second octet 0: first octet

S ↑ IP

SN GW

3 2 1 0

1

2

3 4

5

6

2 3 1 0

Cursor for selecting address type Cursor zur Auswahl der Adressausprägung

Cursor for selecting octet

IP

SNIP

GW

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 14

7 Display

7.5. Design and Symbols

There are some symbols used in the following flow-charts to describe the display-functionality:

7.6. Startup

7.7. Main Menue

• Scolling in main meue with short-time keypress on set-key • Step in menue with short-time keypress on arrow-key

IP 192 . 168 .

015 . 005

VERSION H W : 1 . 0 S W : 1 . 0

Subnet 255 . 255 .

255 . 000

Gateway 000 . 000 .

000 . 000

hard- und firmware-revision

Current IP

Current subnetmask e

Current gatewayaddress

BNI EIP-502- 105-Z015

Module name

B A L L U F F BALLUFF

actual state

change-over

S condition: short-time keypress on set key

S condition: long-time keypress on setkey (min. 3 seconds)

condition: short-time keypress on arrow key

IP CONFIG

Default-view 4. octet of IP address

Menue: IP Config

Menue: IP Setup

Menue: Module Information

007

S

S

S

S

� …

IP SETUP

MODULE INFO

www.balluff.com 15

7 Display

7.8. IP Setup

• Long-time keyoress on set key starts editing mode. • Configuration of the favored value by short-time keypress on arrow-key

7.9. IP Config

• Long-time keyoress on set key starts editing mode. • Configuration of the favored value by short-time keypress on arrow-key • Long-time keypress on arrow key uses fast program mode • Shorttime keypress on set key saves entered value and scrolls to the next octet.

The 4.octet is the start of editing • The whole entered address gets saved by short keypress on set value when

editing first octet. The entered value can immediately seen on the ip overview screen.

• Manual changes of ip, subnet or gateway results in automatic change to “static” in IP Setup.

Hinweis: To work with the new configuration the module needs a power-down reset.

STATIC DHCP X FACTORY

STATIC X DHCP FACTORY

x STATIC DHCP FACTORY

S �

S S

S

editing mode

X STATIC DHCP FACTORY

IP editing mode

IP 192.168. 015.005

Subnet 255.255. 255.000

Gateway 000.000.

000.000

IP Config �

editin

g m

ode

Pro

gra

mm

ierm

odus

005

015

168

192

S

S

S

S

S

editin

g m

ode

Pro

gra

mm

ierm

odus

000

255

255

255

S

S

S

S

S

editin

g m

ode

Pro

gra

mm

ierm

odus

000

000

000

000

S

S

S

S

S

Balluff Network Interface EtherNet/IP™, BNI EIP-502-105-Z015

www.balluff.com 16

7 Display

7.10. Module information

• By short-time keypress on arrow key you can scroll through module information

menu. • Informations are the product name, the module revisions and the MacID.

7.11. General

Informations • Longtime keypress for „fast scrolling“ in editing mode

• 10 secondes without keypress results in leaving actual screen and entering the default screen mode (4

th octet of ip address). Unsaved changes gets lost

• Differences between new configuration and the configuration the module is working with are shown by a unequal-symbol. In this case the time to default screen is only 5 seconds.

• In editing mode the screen flashes. In fast scroll mode the screen is flickering • If the module receives a single ping, the word “ping” is shown in the display screen

for a few seconds. Afterwards the screen is reset to the screen which had been shown before. By short-time key press on set key the ping-mode can be left preterm.

• If the module receives a double ping, the word “ping” is shown in the display. This screen can be left only by short-time key press on set key. The screen shown before ping gets viewed again.

• The Led function at the display leds can be defined user specific ba setting some bits in the process data inputs. (see Bitlayout, chapter 8 „Annex“)

• The function plc-lock can also be used by setting a bit in the process data inputs. (see Bitlayout, chapter 8 „Annex“)

Hinweis: Editing mode can not be chosen in display if the plc lock bit in process data inputs is (see Bitlayout, chapter 8 „Annex“)

BNI EIP-502-

100-Z016

Version SW: x.x

HW: x.x

MAC-ID XX : XX : XX :

XX : XX : XX

… �

www.balluff.com 17

8 Webserver

8.1. General The BNI EIP-502 module includes an internal webserver to get detailed information about the current state. Also you can use it to configurate the module and the connected IO Link devices. First make sure that a correct integration into your network has been done. To get a connection to the webserver enter the IP address of the module to your browser address bar. A welcome page with a list of all Balluff Ethernet Network-interfaces is shown. Please use Internet Explorer 7 or 8. Other Browsers might not function correctly at the current development state.

8.2. Home By click on “play”-button “Home” active.

You can get some information about the configuration and network-activity of the module. At the top of the window you can see the navigation bar which allows you to switch between the different webpages, just click on the corresponding text.

8.3. Diagnostic

Process On this page you can get some information about the module’s current process data by

having a look at the leds. If a IO Link Device is connected to on of the IO Link ports some device data is shown besides the modul. You can use this text or the port on the module as a link to “Device properties”.

8.4. Device Properties On this page you can get information about the IO Link device that is connected on the

selected port. Also it is possible to configure the device by using the read/write functions. The indices and subindices which can be written or read are defined by the connected device. So for this reason have a look at the IO Link device manual.

8.5. Diagnostic

Module On this page you can see the current module and network status like you can see it on the

module itself. 8.6. Configurations The configuration page allows you to configure the module. You can change network-

parameters and also assign own module information texts like a module description. This can only be used by entering a username and a password: Username: Balluff Password: BNIEIP

8.7.

www.balluff.com 18

9 Appendix

9.1. Included material The BNI EIP consists of the following components: • IO-Link block • 4 blind plugs M12 • Ground strap • Screw M4x6 • 20 labels

9.2. Ordercode BNI EIP-502-105-Z015

Balluff Network Interface Ethernet IP Functions 502 = IP 67 IO Link Master-Modul Variants 105 = Display version, 2-port switch Mechanical version Z015 = Die-cast zinc housing Material: 1. Balluff housing version Uplink: 2 x M12x1 internal thread Power: 7/8“ external thread Sensor Ports: 8 x M12x1 internal thread

9.3. Order Information Product ordering code Order code

BNI EIP-502-105-Z015 BNI004A

www.balluff.com

www.balluff.com

Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a.d.F. Germany Tel. +49 7158 173-0 Fax +49 7158 5010 [email protected]

Nr.

880