Comparison of the American and Canadian Methods of Wind Load Calculations for Low-Rise and High-Rise (Tall) Buildings Wind Engineering and Building Aerodynamics By: Mohamad Meneeim ID#: 6175163 Sherif Hafez ID#: 9787143 Professor: Dr. T. Stathopoulos BLDG 6071 - PROJECT - SUMMER 2011

Transcript of Bldg 6071 Project Presentation Final

Page 1: Bldg 6071 Project Presentation   Final

BLDG 6071 - PROJECT - SUMMER 2011

Comparison of the American and Canadian Methods of Wind Load

Calculations for Low-Rise and High-Rise (Tall) BuildingsWind Engineering and Building Aerodynamics

By: Mohamad Meneeim ID#: 6175163Sherif Hafez ID#: 9787143

Professor: Dr. T. Stathopoulos

Page 2: Bldg 6071 Project Presentation   Final

The purpose of this project is to determine the similarities and differences in the American and Canadian methods of wind load calculations using the appropriate guidelines and the available procedures for each case.

Purpose

Page 3: Bldg 6071 Project Presentation   Final

Location of the Low Rise Buildings

Page 4: Bldg 6071 Project Presentation   Final

Location of the High Rise Buildings

Page 5: Bldg 6071 Project Presentation   Final

Low RiseElevation Views

Page 6: Bldg 6071 Project Presentation   Final

High RiseElevation Views

Page 7: Bldg 6071 Project Presentation   Final

Directional Procedure:◦ Part 1: All Heights◦ Part 2: Simplified h<160 ft

Envelope Procedure Wind Tunnel Procedure

ASCE 7-10 Methods

Page 8: Bldg 6071 Project Presentation   Final

Low Rise Wind Pressure Distribution

Page 9: Bldg 6071 Project Presentation   Final

High Rise Wind Pressure Distribution

Page 10: Bldg 6071 Project Presentation   Final

Without converting 3-sec gust to 1-hour mean speed:

◦ VAmerican Code = 2.00 VCanadian code ◦ V2

American Code= 4.00 V2Canadian Code

Converting 3-sec gust to 1-hour mean:◦ VAmerican Code = 1.38 VCanadian code ◦ V2

American Code= 1.69 V2Canadian Code

Comparison

Page 11: Bldg 6071 Project Presentation   Final

Static Procedure Dynamic procedure Experimental procedure

Canadian Code Wind Calculation Procedure

Page 12: Bldg 6071 Project Presentation   Final

Building Basic Characteristics:• H/W < 4.• No susceptible vibrations.• H ≤ 20m.

Low Rise Wind Load Calculation

Page 13: Bldg 6071 Project Presentation   Final

Determination of the importance factor Iw Calculating Reference Velocity Pressure q Calculating the Exposure Factor Ce Verified H ≤ 20 – low rise Calculating CpCg on different structural

components and cladding. Calculating Cgi Calculating Cpi

Low Rise Static Procedure – Wind Pressures Structural Components and Cladding

Page 14: Bldg 6071 Project Presentation   Final

Determination of external wind pressure Pe = IwqCeCgCp

Determination of internal wind pressure Pi = IwqCeCiCi

Low Rise Static Procedure – Wind Pressures Structural Components and Cladding

Page 15: Bldg 6071 Project Presentation   Final

Verified H ≤ 120, H/W ≤ 4, and no susceptible to vibrations.

Calculating the Exposure Factor Ce Verified H ≤ 20 m, and H/Ds < 1 Calculating CpCg in different wind directions. Determination of wind external pressure Pe

Low Rise Static Procedure – Wind Pressures on Building Structure

Page 16: Bldg 6071 Project Presentation   Final

Determination of external wind pressure Pe = IwqCeCgCp

Low Rise Static Procedure – Wind Pressures on Building Structure

Page 17: Bldg 6071 Project Presentation   Final

Low Rise Wind Load Distribution

Page 18: Bldg 6071 Project Presentation   Final

Building Basic Characteristics• High rise H > 20m.• No susceptible vibrations.• H/W < 4.

High Rise Wind Load Calculation

Page 19: Bldg 6071 Project Presentation   Final

Determination of the importance factor Iw Calculating Reference Velocity Pressure q Calculating the Exposure Factor Ce Verified H > 20 – High rise Calculating CpCg on different structural

components and cladding. Calculating Cgi Calculating Cpi

High Rise Static Procedure – Wind Pressures Structural Components and Cladding

Page 20: Bldg 6071 Project Presentation   Final

Determination of external wind pressure Pe = IwqCeCgCp

Determination of internal wind pressure Pi = IwqCeCiCi

High Rise Static Procedure – Wind Pressures Structural Components and Cladding

Page 21: Bldg 6071 Project Presentation   Final

Verified H ≤ 120, H/W ≤ 4, and no susceptible to vibrations.

Calculating the Exposure Factor Ce Verified H > 20 m, and H/Ds > 1 Determining Cg . it is 2.0 in our case

because it is a flat terrain. Determining Cp. Determination of wind external pressure Pe

High Rise Static Procedure – Wind Pressures on Building Structure

Page 22: Bldg 6071 Project Presentation   Final

Determination of external wind pressure Pe = IwqCeCgCp

High Rise Static Procedure – Wind Pressures on Building Structure

Page 23: Bldg 6071 Project Presentation   Final

High Rise Wind Load Distribution