Binder1 - CITELIIimpimp 1515 kA kA L/N MI t° Ft L/N C 14 11 12 36 90 10.6 67 DS150E-300 10108 USA...

2
Iimp Iimp 15 kA 15 kA L/N MI Ft L/N C 14 11 12 36 90 10.6 67 DS150E-300 10108 USA Today Way, Miramar, FL 33025 TF 800.248.3548 P 954.430.6310 F 954.430.7785 citel.us [email protected] Enhanced Multi-MOV Design Individual Fault Indicator Windows Iimp : 15kA at 10/350µs Imax : 165kA at 8/20µs In : 50-70kA at 8/20µs UL 1449 4th Edition Characteristics Note 1: Rating in compliance with NF C15-100 art. 534.1.3.5. In order to increase service continuity, higher rating can be used (up to 250 A). For further information, please consult product instructions. V : High energy varistor network t° : Thermal disconnection system Ft : Thermal fuse MI : Disconnection indicator C : Remote signaling contact CITEL Part Number DS150E-480 DS150E-300 DS150E-120 AC network voltage 347V-480V 220-277V 120V-127V SPD configuration 1-pole 1-pole 1-pole AC system All All All Maximum operating voltage Uc 550 Vac 330 Vac 150 Vac TOV withstand UT 770 Vac 440 Vac 230 Vac Operating current Ic < 2 mA < 2 mA < 2 mA Follow current If none none none Nominal discharge current (IEC/UL) 15 x 8/20 µs impulses In 50 kA / 20 kA 70 kA / 20 kA 70 kA / 20 kA Maximum discharge current 8/20 µs withstand Imax 165 kA 165 kA 165 kA Maximum discharge current 10/350 µs withstand Iimp 15 kA 15 kA 15 kA Voltage protection rating Vpr 1500 V 1000 V 600 V Short-circuit current rating Sccr 100 kA 100 kA 100 kA Associated Disconnection Devices l a n r e t n I r o t c e n n o c s i d l a m r e h T . x a m A 5 2 1 - G g e p y t s e s u F s e s u F (see Note 1) Installation ground fault breaker Type «S» or delayed Mechanical Characteristics m a r g a i d e e S s n o i s n e m i D s u b y b / ² m m 5 3 - 6 : s l a n i m r e t w e r c s y B n o i t c e n n o C s r o t a c i d n i l a c i n a h c e m 3 r o t a c i d n i n o i t c e n n o c s i D Remote signaling of disconnection Output on changeover contact m m 5 3 l i a r l a c i r t e m m y S g n i t n u o M C ° 5 8 + / 0 4 - e r u t a r e p m e t g n i t a r e p O 0 2 P I s s a l c n o i t c e t o r P 0 V - 4 9 L U c i t s a l p o m r e h T l a i r e t a m g n i s u o H Standards Compliance IEC 61643-11: International Low Voltage SPD - Test Class I and II I I d n a I s s a l C t s e T - D P S e g a t l o V w o L e p o r u E : 1 1 - 3 4 6 1 6 N E I I t e I e s s a l C s i a s s E - n o i s n e T e s s a B e r d u o f a r a P e c n a r F : 1 1 - 3 4 6 1 6 N E F N e 4CA p y T A S U : n o i t i d E 4th 9 4 4 1 L U Part Number 2 2 3 2 0 8 4 - E 0 5 1 S D 7 9 6 1 0 0 3 - E 0 5 1 S D 0 4 8 1 0 2 1 - E 0 5 1 S D Dimensions and Electrical Diagram (in mm) AC Surge Protectors DS150E Series U061602A

Transcript of Binder1 - CITELIIimpimp 1515 kA kA L/N MI t° Ft L/N C 14 11 12 36 90 10.6 67 DS150E-300 10108 USA...

IimpIimp15 kA15 kA

L/N

MI

Ft

L/N

C

141112

36

90

10.6

67

DS150E-300

10108 USA Today Way, Miramar, FL 33025 TF 800.248.3548 P 954.430.6310 F 954.430.7785 citel.us [email protected]

Enhanced Multi-MOV Design

Individual Fault Indicator Windows

Iimp : 15kA at 10/350µs

Imax : 165kA at 8/20µs

In : 50-70kA at 8/20µs

UL 1449 4th Edition

Characteristics

Note 1: Rating in compliance with NF C15-100 art. 534.1.3.5. In order to increase service continuity, higher rating can be used (up to 250 A). For further information, please consult product instructions.

V : High energy varistor networkt° : Thermal disconnection systemFt : Thermal fuseMI : Disconnection indicatorC : Remote signaling contact

CITEL Part Number DS150E-480 DS150E-300 DS150E-120AC network voltage 347V-480V 220-277V 120V-127VSPD configuration 1-pole 1-pole 1-poleAC system All All All Maximum operating voltage Uc 550 Vac 330 Vac 150 VacTOV withstand UT 770 Vac 440 Vac 230 VacOperating current

Ic < 2 mA < 2 mA < 2 mA

Follow current If none none noneNominal discharge current (IEC/UL) 15 x 8/20 µs impulses

In 50 kA / 20 kA 70 kA / 20 kA 70 kA / 20 kA

Maximum discharge current 8/20 µs withstand

Imax 165 kA 165 kA 165 kA

Maximum discharge current 10/350 µs withstand

Iimp 15 kA 15 kA 15 kA

Voltage protection rating Vpr 1500 V 1000 V 600 VShort-circuit current rating Sccr 100 kA 100 kA 100 kAAssociated Disconnection Devices

lanretnIrotcennocsid lamrehT .xam A 521 - Gg epyt sesuFsesuF (see Note 1)

Installation ground fault breaker Type «S» or delayedMechanical Characteristics

margaid eeSsnoisnemiDsub yb / ²mm 53-6 : slanimret wercs yBnoitcennoC

srotacidni lacinahcem 3rotacidni noitcennocsiDRemote signaling of disconnection Output on changeover contact

mm 53 liar lacirtemmySgnitnuoMC° 58+/04-erutarepmet gnitarepO

02PIssalc noitcetorP0V-49LU citsalpomrehTlairetam gnisuoH

Standards ComplianceIEC 61643-11: International Low Voltage SPD - Test Class I and II

II dna I ssalC tseT - DPS egatloV woLeporuE :11-34616 NEII te I essalC siassE - noisneT essaB erduofaraPecnarF :11-34616 NE FN

e 4CApyT ASU :noitidE 4th 9441LUPart Number

2232084-E051SD7961003-E051SD0481021-E051SD

Dimensions and Electrical Diagram(in mm)

AC Surge ProtectorsDS150E Series

U061602A

DS253E-400

DS15x E-xxx/G

144144

7272 1081 2 3

4 5

GSG

Ft

MI

C

L (L) N

Ft

MI

C

Ft

MI

C

L/N (L/N) L/N (L/N)

Ft

MI

C

Ft

MI

C

Ft

MI

C

L1 (L1) L2 (L2) L3 (L3)

Ft

MI

C

Ft

MI

C

Ft

MI

C

Ft

MI

C

L1 (L1) L2 (L2) L3 (L3) N (N)

GSG

Ft

MI

C

Ft

MI

C

Ft

MI

C

L1 (L1) L2 (L2) L3 (L3) N

1 2 3

4 5

DS25DDS25DS25DSDDSDDSDSDS2DS2DS2DSDSDS2DSDDS2DDSS2SSSSSSDS25DS25DSDS25SS2222222555DS25DS25DS25DS25S25DSS2252522522DS2555DS25S25S222S2S2S2S2555DS252S2522S22S22S255DS255555S25DS25S25SS2S2S252555552S2S2S22555DS25SDS25SSSS22255DS25DDSSS25SS2255SS 555SS222252525522225255555555SS2225252252555522D 22D 2DDS253333333333333333333333333333333333333333333333333333333EEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEEE-400-40-40-40444444440444444444444444444004044044400-440-40-4-4000-4-400-40-40-4000004000000

DS154E-300/G

10108 USA Today Way, Miramar, FL 33025 TF 800.248.3548 P 954.430.6310 F 954.430.7785 citel.us [email protected] U061602A

Dimensions and Electrical Diagrams

« » = Configuration CT1 (common mode)«G» = Configuration CT2 (common and differential mode)Operating voltage (120, 300, 480)«E» = Enhanced «Varistor» technologyNumber of protected poles (2, 3, 4)

Multi-Pole AC Surge ProtectorsDS152E, DS153E, DS154E

Reference Part Number Network ACSystem

Protection Mode Iimp

TotalUp

L/PEUpL/N Diagram

Com

mon

Diffe

rent

ial

DS154E-300/G 2758 277/480 V 3-phase+N Wye 100 kA 2.5 kV 2.5 kV5

DS154E-120/G 2759 120/208 V 3-phase+N Wye 100 kA 1.5 kV 1 kV

DS154E-480 3943 347/600 V 3-phase+N Wye 100 kA 2.5 kV -

4DS154E-300 3329 277/480 V 3-phase+N Wye 100 kA 2.5 kV -

DS154E-120 - 120/208 V 3-phase+N Wye 100 kA 1 kV -

DS153E-480 3481 480 V 3-phase Delta 75 kA 2.5 kV -

3DS153E-300 3791 240 V 3-phase Delta 75 kA 2.5 kV -

DS153E-120 3408 240 V 2-phase+N Split phase 75 kA 1 kV -

DS152E-300/G 3406 277 V 1-phase+N Single phase 50 kA 2.5 kV 2.5 kV2

DS152E-120/G - 120 V 1-phase+N Single phase 50 kA 1.5 kV 1 kV

DS152E-480 - 277 V 1-phase+N, 2-phase Single/Split phase 50 kA 2.5 kV -

1DS152E-300 3723 277 V 1-phase+N, 2-phase Single/Split phase 50 kA 2.5 kV -

DS152E-120 3790 120 V 1-phase+N, 2-phase Single/Split phase 50 kA 1 kV -