Bill and Helen Norrie Library - Winnipeg€¦ · a2.1 main floor plan a2.2 roof plan a3.1 main...

1
SET #. ______ Project No.: 2017-082 Tender No.: 542-2019 Address: LM COMM. NO. 1847 - Bill and Helen Norrie Library - 15 Poseidon Bay, Winnipeg, MB. Issued for Construction 07.08.19 Bill and Helen Norrie Library 15 Poseidon Bay, Winnipeg, MB. PROJECT TEAM: LM ARCHITECTURAL GROUP ARCHITECT / PRIME CONSULTANT TOWER ENGINEERING GROUP STRUCTURAL / MECHANICAL / AND ELECTRICAL ENGINEERING HTFC PLANNING & DESIGN LANDSCAPE ARCHITECT SISON BLACKBURN CONSULTING INC. CIVIL ENGINEER MORR TRANSPORTATION CONSULTING LTD. TRANSPORTATION ENGINEERING FOOTPRINT S + A SUSTAINABILITY SUSTAINABLE DESIGN GWH CMS LTD. QUANTITY SURVEYOR DRAWING LIST: COVER SHEET TOPOGRAPHICAL SURVEY PROPOSED SUBDIVISION PLAN CIVIL C1.1 SITE SERVICING PLAN LANDSCAPE L-100 SITE DEMOLITION PLAN L-200 SITE MATERIALS PLAN L-300 SITE LAYOUT PLAN L-400 SITE GRADING PLAN L-500 SITE PLANTING & SIGNAGE PLAN L-600 WOOD DECK DETAILS L-601 CONCRETE & TIMBER BENCH DETAILS L-602 GARBAGE ENCLOSURE & SITE FURNITURE DETAILS L-603 HARDSCAPE DETAILS ARCHITECTURAL A0.1 BUILDING KEY PLAN A2.0 CRAW LSPACE PLAN A2.1 MAIN FLOOR PLAN A2.2 ROOF PLAN A3.1 MAIN FLOOR REFLECTED CEILING PLAN A4.1 EXTERIOR ELEVATIONS A4.2 ALUMINUM WINDOW TYPES A4.3 BUILDING SECTIONS A5.1 WALL SECTIONS A5.2 WALL SECTIONS A5.3 MISCELLANEOUS SECTIONS A5.4 PLAN DETAILS A5.5 PLAN DETAILS A7.1 ENLARGED FLOOR PLAN & INTERIOR ELEVATIONS A8.1 INTERIOR ELEVATIONS A8.2 INTERIOR ELEVATIONS A9.1 FURNITURE, EQUIPMENT & FLOOR FINISHES PLAN STRUCTURAL S1.1 GENERAL NOTES S1.2 TYPICAL DETAILS & SECTIONS S2.1 FOUNDATION PLAN S2.2 MAIN FLOOR FRAMING PLAN S2.3 ROOF FRAMING PLAN S3.1 PLAN DETAILS & SECTIONS S3.2 SECTIONS & DETAILS A3.3 SECTIONS & DETAILS A4.1 FRAMING ELEVATIONS MECHANICAL M0.1 LEGENDS, CALCULATIONS & DRAWING LISTS M0.2 ASHRAE 62.1 CALCULATIONS M0.3 SITE PLAN M1.0 CRAWLSPACE - PLUMBING LAYOUT M1.1 MAIN FLOOR - PLUMBING LAYOUT M1.2 PLUMBING DETAILS M1.3 PLUMBING DETAILS M2.0 CRAWLSPACE - HVAC LAYOUT M2.1 MAIN FLOOR - HVAC LAYOUT M2.2 HVAC DETAILS M2.3 HVAC SECTIONS M3.1 MAIN FLOOR - HYDRONIC LAYOUT M3.2 HYDRONIC DETAILS & SCHEMATIC M3.3 HYDRONIC DETAILS & SCHEMATIC M4.1 MAIN FLOOR - FIRE PROTECTION LAYOUT M5.1 MECHANICAL EQUIPMENT SCHEDULES M5.2 MECHANICAL EQUIPMENT SCHEDULES ELECTRICAL E1.1 SITE PLAN E2.0 LIGHTING LAYOUT - CRAWLSPACE E2.1 LIGHTING LAYOUT - MAIN FLOOR E3.0 POWER & SYSTEM LAYOUT - CRAWLSPACE E3.1 POWER & SYSTEM LAYOUT - MAIN FLOOR E4.0 LIFE SAFETY LAYOUT - CRAWLSPACE E4.1 LIFE SAFETY LAYOUT - MAIN FLOOR E5.1 ELECTRICAL SCHEDULES E5.2 ELECTRICAL SCHEDULES E6.1 SINGLE LINE DIAGRAM, RISER DIAGRAM & DETAILS PROJECT DESCRIPTION: THE PROJECT CONSISTS OF A NEW STAND ALONE 14,000 SF (1,300 SQ.M) ONE STOREY LIBRARY BUILDING ON UNDEVELOPED LAND ON THE NORTHWEST CORNER OF THE GRANT PARK RECREATION CAMPUS. THE NEW LIBRARY BUILDING PROGRAM INCLUDES STAFF LOUNGE AND WORK AREAS, SERVICES COUNTER, PUBLIC WASHROOM FACILITIES, AND AN OPEN LIBRARY W ITH TUTORIAL SPACES AND MULTI-PURPOSE ROOM. THE SITE WILL BE DEVELOPED TO INCORPORATE A NEW PRIVATE APPROACH AND 40 NEW DEDICATED LIBRARY PARKING STALLS NORTHWEST OF THE EXISTING PAN-AM POOL. BUILDING CODE ANALYSIS: BUILDING CODE ASSESSMENT THIS ASSESSMENT, REVIEWED UNDER THE NATIONAL BUILDING CODE OF CANADA 2010, INCLUDING MANITOBA AMENDMENTS CONSIDERS ONLY THE PRELIMINARY DESIGN PROVIDED FOR THE PROPOSED NEW STANDALONE BILL AND HELEN NORRIE LIBRARY AND IS LIMITED TO THE DETAIL AND MATERIAL AS APPLICABLE AND APPROPRIATE TO THE DESIGN CURRENTLY IN DEVELOPMENT. MAJOR OCCUPANCIES: BUILDING AREA: 1,300 sm (14,000 sf). 3.2.2.25, Group A, Division 2 Up to 2 Storeys Not more than two storeys Building area is not more than 1,600 sm if one storey facing 1 street The building can be combustible or non-combustible construction Floor assemblies if of combustible construction shall be 45 min. fire rated separations. Mezzanines if of combustible construction shall be 45 min. fire rated separations. Roof assemblies if of combustible construction shall be shall be 45 min. fire rated separations Loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall have a 45 min. fire-resistance rating or be of non-combustible construction. OCCUPANT LOAD: Per Table 3.1.17, the Occupant Load is calculated as a function of its area: TOTAL OCCUPANT LOAD: 215 persons total (to be confirmed with library design development.) STAFF: = 15 persons TUTORIAL ROOMS: 6 each * (2) total = 12 persons MPR: = 59 persons OPEN LIBRARY: = 129 persons LIFE SAFETY: Separation of Suites Section 3.3.1.5 mandates that 2 egress doorways be provided from a room or suite that is intended for an occupant load more than 60, and in a floor area that is sprinklered with a travel distance to an egress doorway is more than 25m or an area of the room or suite that is more than the value below from table 3.3.1.5.B. Section 3.3.1.5.2) Where 2 egress doorways are provided they shall be placed at a distance from one another equal to or greater than one third of the maximum overall diagonal dimension. Section 3.3.1.21 requires that a non-rated fire separation be provided for a janitor room (in a sprinklered building) Exits Exits shall be located, per Section 3.4.2.5, such that the travel distance to at least one exit be no more than 30 meters in a non-sprinklered A2 Occupancy Exit Width Refer to Section 3.4.3.2. The aggregate exit width required is 6.1mm per person (for doorways) for Assembly Occupancies (215 persons at 6.1mm each) = 1.312 meters required HEALTH REQUIREMENTS: Plumbing Facilities Table 3.7.2.2.A. Water Closets for an Assembly Occupancy: The following Occupant Loads and corresponding min. number of water closets for each sex were calculated. Occupant Load: 215 persons total (subtract by 10 as per 3.7.2.2.2) Staff served by (1) UNIVERSAL TOILET ROOM 98 Male = 2 Water Closets (4 PROVIDED) 98 Female = 4 Water Closets (4 PROVIDED) As per 3.7.2.3.1) the following amount of Lavatories shall be provided. Male = 2 Lavatories (2 PROVIDED) Female = 2 Lavatories (2 PROVIDED) BARRIER-FREE ACCESSIBILITY: Section 3.8.1.2 mandates that all pedestrian entrances shall be barrier-free accessible. Section 3.8.2.1.1) requires that a barrier-free path of travel shall be provided throughout the whole building and to every exit from the barrier-free entrances. As per 3.8.1.3.1) the barrier-free path of travel shall not be less than 1100mm unobstructed width. CITY OF WINNIPEG CLIENT Conceptual Artist Rendering - Subject to Change - Approach from Grant Avenue and Cambridge Street SITE CONTEXT PLAN

Transcript of Bill and Helen Norrie Library - Winnipeg€¦ · a2.1 main floor plan a2.2 roof plan a3.1 main...

Page 1: Bill and Helen Norrie Library - Winnipeg€¦ · a2.1 main floor plan a2.2 roof plan a3.1 main floor reflected ceiling plan a4.1 exterior elevations a4.2 aluminum window types a4.3

SE

T #

. ______

Project No.: 2017-082

Tender No.: 542-2019

Address:

LM

CO

MM

. N

O.

1847

-

Bill

and H

ele

n N

orr

ie L

ibra

ry

-15 P

oseid

on B

ay,

Win

nip

eg,

MB

.

Issued f

or

Constr

uction

07.0

8.1

9

Bill and Helen Norrie Library

15 Poseidon Bay, Winnipeg, MB.

PROJECT TEAM:

LM ARCHITECTURAL GROUPARCHITECT / PRIME CONSULTANT

TOWER ENGINEERING GROUPSTRUCTURAL / MECHANICAL / AND ELECTRICAL ENGINEERING

HTFC PLANNING & DESIGNLANDSCAPE ARCHITECT

SISON BLACKBURN CONSULTING INC.CIVIL ENGINEER

MORR TRANSPORTATION CONSULTING LTD.TRANSPORTATION ENGINEERING

FOOTPRINT S + A SUSTAINABILITYSUSTAINABLE DESIGN

GWH CMS LTD.QUANTITY SURVEYOR

DRAWING LIST:

COVER SHEETTOPOGRAPHICAL SURVEYPROPOSED SUBDIVISION PLAN

CIVIL

C1.1 SITE SERVICING PLAN

LANDSCAPE

L-100 SITE DEMOLITION PLANL-200 SITE MATERIALS PLANL-300 SITE LAYOUT PLANL-400 SITE GRADING PLANL-500 SITE PLANTING & SIGNAGE PLANL-600 WOOD DECK DETAILSL-601 CONCRETE & TIMBER BENCH DETAILSL-602 GARBAGE ENCLOSURE & SITE FURNITURE DETAILSL-603 HARDSCAPE DETAILS

ARCHITECTURAL

A0.1 BUILDING KEY PLANA2.0 CRAWLSPACE PLANA2.1 MAIN FLOOR PLANA2.2 ROOF PLANA3.1 MAIN FLOOR REFLECTED CEILING PLANA4.1 EXTERIOR ELEVATIONSA4.2 ALUMINUM WINDOW TYPESA4.3 BUILDING SECTIONSA5.1 WALL SECTIONSA5.2 WALL SECTIONSA5.3 MISCELLANEOUS SECTIONSA5.4 PLAN DETAILSA5.5 PLAN DETAILSA7.1 ENLARGED FLOOR PLAN & INTERIOR ELEVATIONSA8.1 INTERIOR ELEVATIONSA8.2 INTERIOR ELEVATIONSA9.1 FURNITURE, EQUIPMENT & FLOOR FINISHES PLAN

STRUCTURAL

S1.1 GENERAL NOTESS1.2 TYPICAL DETAILS & SECTIONSS2.1 FOUNDATION PLANS2.2 MAIN FLOOR FRAMING PLANS2.3 ROOF FRAMING PLANS3.1 PLAN DETAILS & SECTIONSS3.2 SECTIONS & DETAILSA3.3 SECTIONS & DETAILSA4.1 FRAMING ELEVATIONS

MECHANICAL

M0.1 LEGENDS, CALCULATIONS & DRAWING LISTSM0.2 ASHRAE 62.1 CALCULATIONSM0.3 SITE PLANM1.0 CRAWLSPACE - PLUMBING LAYOUT M1.1 MAIN FLOOR - PLUMBING LAYOUTM1.2 PLUMBING DETAILSM1.3 PLUMBING DETAILSM2.0 CRAWLSPACE - HVAC LAYOUTM2.1 MAIN FLOOR - HVAC LAYOUTM2.2 HVAC DETAILSM2.3 HVAC SECTIONSM3.1 MAIN FLOOR - HYDRONIC LAYOUTM3.2 HYDRONIC DETAILS & SCHEMATICM3.3 HYDRONIC DETAILS & SCHEMATICM4.1 MAIN FLOOR - FIRE PROTECTION LAYOUTM5.1 MECHANICAL EQUIPMENT SCHEDULESM5.2 MECHANICAL EQUIPMENT SCHEDULES

ELECTRICAL

E1.1 SITE PLANE2.0 LIGHTING LAYOUT - CRAWLSPACEE2.1 LIGHTING LAYOUT - MAIN FLOORE3.0 POWER & SYSTEM LAYOUT - CRAWLSPACEE3.1 POWER & SYSTEM LAYOUT - MAIN FLOORE4.0 LIFE SAFETY LAYOUT - CRAWLSPACEE4.1 LIFE SAFETY LAYOUT - MAIN FLOORE5.1 ELECTRICAL SCHEDULESE5.2 ELECTRICAL SCHEDULESE6.1 SINGLE LINE DIAGRAM, RISER DIAGRAM & DETAILS

PROJECT DESCRIPTION:

THE PROJECT CONSISTS OF A NEW STAND ALONE 14,000 SF (1,300 SQ.M) ONE STOREY LIBRARY BUILDING ON UNDEVELOPED LAND ON THE NORTHWEST CORNER OF THE GRANT PARK RECREATION CAMPUS. THE NEW LIBRARY BUILDING PROGRAM INCLUDES STAFF LOUNGE AND WORK AREAS, SERVICES COUNTER, PUBLIC WASHROOM FACILITIES, AND AN OPEN LIBRARY WITH TUTORIAL SPACES AND MULTI-PURPOSE ROOM. THE SITE WILL BE DEVELOPED TO INCORPORATE A NEW PRIVATE APPROACH AND 40 NEW DEDICATED LIBRARY PARKING STALLS NORTHWEST OF THE EXISTING PAN-AM POOL.

BUILDING CODE ANALYSIS:

BUILDING CODE ASSESSMENTTHIS ASSESSMENT, REVIEWED UNDER THE NATIONAL BUILDING CODE OF CANADA 2010, INCLUDING MANITOBA AMENDMENTS CONSIDERS ONLY THE PRELIMINARY DESIGN PROVIDED FOR THE PROPOSED NEW STANDALONE BILL AND HELEN NORRIE LIBRARY AND IS LIMITED TO THE DETAIL AND MATERIAL AS APPLICABLE AND APPROPRIATE TO THE DESIGN CURRENTLY IN DEVELOPMENT.

MAJOR OCCUPANCIES:BUILDING AREA: 1,300 sm (14,000 sf).

3.2.2.25, Group A, Division 2 Up to 2 Storeys• Not more than two storeys• Building area is not more than 1,600 sm if one storey facing 1 street• The building can be combustible or non-combustible construction• Floor assemblies if of combustible construction shall be 45 min. fire rated separations.• Mezzanines if of combustible construction shall be 45 min. fire rated separations.• Roof assemblies if of combustible construction shall be shall be 45 min. fire rated separations• Loadbearing walls, columns and arches supporting an assembly required to have a fire-resistance rating shall have a 45 min. fire-resistance

rating or be of non-combustible construction.

OCCUPANT LOAD:Per Table 3.1.17, the Occupant Load is calculated as a function of its area:

TOTAL OCCUPANT LOAD: 215 persons total (to be confirmed with library design development.)

• STAFF: = 15 persons• TUTORIAL ROOMS: 6 each * (2) total = 12 persons• MPR: = 59 persons• OPEN LIBRARY: = 129 persons

LIFE SAFETY:

Separation of SuitesSection 3.3.1.5 mandates that 2 egress doorways be provided from a room or suite that is intended for an occupant load more than 60, and in a floor area that is sprinklered with a travel distance to an egress doorway is more than 25m or an area of the room or suite that is more than the value below from table 3.3.1.5.B.Section 3.3.1.5.2) Where 2 egress doorways are provided they shall be placed at a distance from one another equal to or greater than one third of the maximum overall diagonal dimension.Section 3.3.1.21 requires that a non-rated fire separation be provided for a janitor room (in a sprinklered building)

ExitsExits shall be located, per Section 3.4.2.5, such that the travel distance to at least one exit be no more than

• 30 meters in a non-sprinklered A2 Occupancy

Exit WidthRefer to Section 3.4.3.2. The aggregate exit width required is 6.1mm per person (for doorways) for Assembly Occupancies (215 persons at 6.1mm each) = 1.312 meters required

HEALTH REQUIREMENTS:

Plumbing FacilitiesTable 3.7.2.2.A. Water Closets for an Assembly Occupancy:The following Occupant Loads and corresponding min. number of water closets for each sex were calculated.

• Occupant Load: 215 persons total (subtract by 10 as per 3.7.2.2.2)

• Staff served by (1) UNIVERSAL TOILET ROOM • 98 Male = 2 Water Closets (4 PROVIDED)• 98 Female = 4 Water Closets (4 PROVIDED)

As per 3.7.2.3.1) the following amount of Lavatories shall be provided.• Male = 2 Lavatories (2 PROVIDED)• Female = 2 Lavatories (2 PROVIDED)

BARRIER-FREE ACCESSIBILITY:Section 3.8.1.2 mandates that all pedestrian entrances shall be barrier-free accessible.Section 3.8.2.1.1) requires that a barrier-free path of travel shall be provided throughout the whole building and to every exit from the barrier-free entrances. As per 3.8.1.3.1) the barrier-free path of travel shall not be less than 1100mm unobstructed width.

CITY OF WINNIPEGCLIENT

Conceptual Artist Rendering - Subject to Change - Approach from Grant Avenue and Cambridge Street

SITE CONTEXT PLAN