Beyond Commissioning: Optimizing Electrical Systems files/Chapters/San Francisc… · electrical...
Transcript of Beyond Commissioning: Optimizing Electrical Systems files/Chapters/San Francisc… · electrical...
© 2012 Eaton Corporation. All rights reserved.
Beyond Commissioning: Optimizing Electrical Systems“Testing, Start-up, Maintenance, NFPA, Life Extension”
Presented By
Jill Jackson, Tom Santrach, Scott Manske & David RudolphEaton Corporation
2© 2012 Eaton Corporation. All rights reserved.
Introductions
• Jill Jackson – Healthcare Industry Specialist• Tom Santrach – Director of West Zone Operations• Scott Manske – District Manager• David Rudolph – Service Sales Specialist Healthcare
Systems
Thank You to CPMC for hosting this evening!
3© 2012 Eaton Corporation. All rights reserved.
Agenda
• Overview• Equipment Testing & Maintenance• NFPA 70E• Equipment Life Extension Methods (ELEM) • Q&A
4© 2012 Eaton Corporation. All rights reserved.
Power & Energy in Healthcare Facility The objectives of today’s healthcare providers are therefore twofold; provide the bestand safest level of patient care, while ensuring reliable infrastructure performance atthe best possible cost.
• Critical Infrastructure• Regulation / Codes / Standards• Data Management & Information• Investment• Safety Systems
As a planned and precautionary measure, healthcare facilities should design orretrofit integrated power solutions to achieve superior patient care by protecting theirpower distribution, building management, IT, and security.
In addition to improved safety, robust critical power supplies can also haveadvantageous financial repercussions, as well as long-term gains in productivity.
5© 2012 Eaton Corporation. All rights reserved.
Power & Energy in Healthcare Facility
• Critical Infrastructure: Maintaining power to critical loads when loss of power occurs. Facilities rely on
their IT and medical equipment for patient care, and equipment relies on the constant availability of
electrical power.
• Regulation / Codes / Standards: Hospitals must meet strict regulatory requirements related to keeping
the power infrastructure compliant – NFPA, OSHPD, Fed/State/Local
• Data Management & Information: The modern day hospital/care center handles huge amounts of
patient data every day, IE test results, patient records, prognosis/prescriptions, registrations, billing and
collaboration with insurance companies -- hospital data relies heavily on the facility’s IT and data center
solutions.
• Investment: Energy Management, Maintenance, Training, Repairs, Unplanned Downtime, Backup
systems.
• Safety Systems: Fire, Air, Water, Lighting, Evaluations, Security, Disaster Events all lean on reliable
and well managed power distribution systems.
6© 2012 Eaton Corporation. All rights reserved.
Testing and Maintenance…Definitions
1. New-Installation Equipment Testing (Acceptance Testing)2. Start-up/Commissioning
• Systematic Planned Approach to Energize• Bring Loads in an Organized Manner• Optimization• System is placed into Operation.
3. Service-Aged Equipment Testing (Maintenance Testing)• Preventative – Time/Scheduled Based• Conditional – Predictive (Developing Technologies)
7© 2012 Eaton Corporation. All rights reserved.
New Equipment Acceptance Testing
Focal Point – Design, Documentation, Studies, Manufacturing, Installation, Energize• Meet Design Specification & Requirements• Installed Properly per OEM, Local Regulatory Codes, Engineers Design• Functional & Ready for Intended Use – Ready to Energize• Performance Criteria • Safe to Operate• Warranty• Documentation• Safety• At Site, not a Factory Test• Baseline Data for Future Analysis/Trends
8© 2012 Eaton Corporation. All rights reserved.
Commissioning & Start-up of Equipment
Systematic Approach to Energization• Plan developed to bring power distribution equipment to operation• Systematic approach, with additional checks/tests staged• Ensure voltages, rotations, connections, flow and protection are correct• Conduct performance tests• Ensure applications are working• Brings loads under a planned approach• Safe and secure approach• System applications started and tested• Plant wide final commissioning and tuning
9© 2012 Eaton Corporation. All rights reserved.
Service-Aged Equipment Testing (Maintenance Testing)
Routine, Annual and Long Term 3/5 Year Maintenance• Determination if the Electrical Equipment is Suitable for Continued
Service• Equipment that falls out of Specification or Standards• Safe/Unsafe - Danger to Equipment and Personnel – Public Safety• Conduct Requirement Maintenance
o Cleaning, Mechanical, Electrical, Tolerances • Repair or Replacement – Now or Near Term• Life Cycle Investment
o Reliability of the Equipment – MTTF, MTTRo Availability of Power – 100%o Maintainability
10© 2012 Eaton Corporation. All rights reserved.
Why do Maintenance of PD/PQ Equipment
1. Complexity of Technology2. Criticalness of Applications3. Investment4. Safety5. Documentation
11© 2012 Eaton Corporation. All rights reserved.
Complexity of Technology
• Microprocessor – Protection, Control & Monitoring• Complex Transfer Schemes – MTM, UPS & Batteries, Generators• Multiple Levels of Redundancy• Communication Networks• Fault Tolerant Demand• Integration w/ Alternative Energy – Wind, Solar, FC, Geo, Battery• Integration w/ Foreign Systems• - Energy & Demand Management, BMS, Manufacturing Systems, CMMS, SCADA• Energy Efficiency, Demand Management & Load Shedding• Regulatory Agencies & Utility Companies
12© 2012 Eaton Corporation. All rights reserved.
Criticalness of Applications
• Hospitals/Medical Centers• Data Centers (Power, UPS and Cooling)• Financial• Internet/Retail• High-WIP Manufacturing (Semi, Pharmaceutical, Food)• Transportation• Public Infrastructure• Energy• Entertainment
13© 2012 Eaton Corporation. All rights reserved.
Investment
• SAT & PM can approximately Cost 4-8% of the Overall Project• Design, Equipment, Installation, Commissioning, Fees
• Much Higher Percentage in Data Centers (15% excluding the Computers)
• Distribution Gear• Power Monitoring• Power Quality - UPS/Generator Systems
• Energization is Critical Path in the Project Schedule• Minimum 20 Year Life Cycle• 2/3 of all Electrical System Failures…..
……are do the “Lack of Maintenance”
14© 2012 Eaton Corporation. All rights reserved.
Safety & Protection
- Protection of Utility Feed/Grid- Prevent Loss of Equipment- Arc Flash/Aux Equipment- Personnel Safety- Downtime Cost
- Average Downtime Impact- $ 4,800 Labor/hr- $12,800 Revenue/hr- $30,000 - $40,000/hr Liability- x100 for repair cost
15© 2012 Eaton Corporation. All rights reserved.
Documentation
- Baseline Comparison – Trending Issues- Develop Accurate Records – Troubleshooting, Recalibration,
Replacement, Repair- Testing Labels – Who, Want, When- Capture Corrections and Updated – Redlines- Settings As Found/As Left/As Entered- Update O&Ms- One Lines, Schematics, Wiring Diagrams, BOM, SCCS, VFD & SS Parameters- Coverage of Training
16© 2012 Eaton Corporation. All rights reserved.
Why Do Testing – On What Equipment…
• Power Distribution Equipment• Cables• Bus• Bus Duct• Circuit Breakers• Controllers & PLC & HMI• CTs/PTs• Generator• Grounding Equipment• Low voltage assembled equipment• Low voltage discrete equipment• Medium voltage assembled equipment• Motors and generators• Network Protectors• Power Supplies/CPTs• Relays, Trip Units• Surge Assistors/Snubbers• Switches• Transformers• VFDs and Starters
Power Monitoring Equipment– Power & Energy Meters– Gateways & Networks– Monitoring Software– Enterprise Software– Historical/Reporting– Demand Management– Load Shed
Power Quality Equipment– Power Factor Correction– Power Conditioning– UPS – ATS & Paralleling Systems– Stand-by & Emergency Power Software– Batteries/Fly Wheel– Generators
17© 2012 Eaton Corporation. All rights reserved.
Approach…Maintenance Testing Frequency
• Battery Visual Inspection Monthly• Battery Specific Gravity Annual• Battery Capacity Test 3 year• MV Cables 3 - 5 Years• Breakers Exercise/Inspection Annual• Breakers Full PM 3 - 5 years• Breakers Exercise 6 - 12 Months• Relays/Meter Observation Weekly or Network• Relay/Trip Unit Full Test 2 - 4 years• Oil Sampling 1 year• Generators/ATS Monthly Tests/Transfer• Generator Load Test 2 years• LV and MV Switches PM 3 years• LV and MV Switches Exercise 6 - 12 Months• Grounding 3 - 6 years
• Most OEMs, Standards Agencies will have recommendations…
18© 2012 Eaton Corporation. All rights reserved.
• Surface TRACKING is Common - Bushings, PTs, Bus, Isolators• High Electric Field at End-points• Contamination & Moisture – One Builds on the Other• Evaporation into “Tiny Islands” due to heat, starting at end-
points • Small Arcs between these “Tiny Islands”• Permanent Carbon Tracking• Short Circuit
4160 Volt breaker bushing with surface tracking -detected with only 5/8” remaining before fault
(PD occurs in the non-tracked area)
Voltage Isolation Build-up
19© 2012 Eaton Corporation. All rights reserved.
Predictive Maintenance
IR Scans & Ultrasonic (Partial Discharge)NFPA 70B indicates that routine IR scanning should be conducted annually for all critical process equipment.
20.17.5 Inspection Frequency and Procedures. Routine infrared inspections of energized electrical systems should be performed annually prior to shutdown.
20.17.5.1 All critical electrical equipment or hazard related equipment…
20.17.5.2 Infrared surveys should be performed during periods of maximum possible loading but not less than 40 percent of rated load.
Top Percentage of IR Issues – Connections
Do Not Over Tighten!
20© 2012 Eaton Corporation. All rights reserved.
Approach…Preventative Maintenance
• IR Scans• Best Solution to Safety - IR Scan Ports
21© 2012 Eaton Corporation. All rights reserved.
NFPA 70E – Moving from 2015 to 2018
22© 2012 Eaton Corporation. All rights reserved.
NFPA 70E – 2015 Changes110.1 Electrical Safety Program
(B) Maintenance.The electrical safety program shall include elements that consider condition of maintenance of electrical equipment and systems.
23© 2012 Eaton Corporation. All rights reserved.
NFPA 70E – 2015 Changes130.2(A) Energized Work - Permitted
(4) Normal Operation Permitted if equipment is:
• properly installed• properly maintained• doors are closed and secured• covers are in place and secured• no evidence of impending failure
24© 2012 Eaton Corporation. All rights reserved.
Properly Maintained?
25© 2012 Eaton Corporation. All rights reserved.
Properly Maintained?
26© 2012 Eaton Corporation. All rights reserved.
No Evidence of Impending Failure?
27© 2012 Eaton Corporation. All rights reserved.
Implications of 2015 NFPA 70E
130.5 Arc Flash Risk AssessmentAn arc flash risk assessment shall be performed and shall:
(3) Take into consideration the design of the overcurrent protective device and its opening time, including its condition of maintenance.
If the equipment condition is unknown or the setting are not properly implemented, the electrical worker may be exposed to a higher incident energy level than anticipated
28© 2012 Eaton Corporation. All rights reserved.
How to Determine the Condition of Maintenance
• Test Forms• Service Labels• Documentation
29© 2012 Eaton Corporation. All rights reserved.
205.3 General Maintenance Requirements.
• The equipment owner or the owner’s designated representative shall be responsible for maintenance of the electrical equipment and documentation.• Common practice is to apply test or calibration decals to
equipment to indicate the test or calibration date and overall condition of equipment that has been tested and maintained.
• Decals provide employees immediate indication of1. Last maintenance date2. If the tested device or system was found acceptable
Information can assist the employee with electrical equipment maintenance status.
30© 2012 Eaton Corporation. All rights reserved.
205.4 Overcurrent Protective Devices
Overcurrent protective devices shall be maintained in accordance with the manufacturers’ instructions or industry consensus standards. Maintenance, tests, and inspections shall be documented.
31© 2012 Eaton Corporation. All rights reserved.
Implications of 2015 NFPA 70E
• NFPA 70B states a maximum of 3 years between maintenance intervals for most equipment.
• NFPA 70B is a guideline to be used if the manufacturer does NOT have specific recommendations.
32© 2012 Eaton Corporation. All rights reserved.
22.6 kA SymmetricalAvailable Fault Current
@ 480 V, 3 Phase
Arc Flash Risk Analysis for this PanelIncident Energy: 5.8 cal/cm2 @ 18”AFB: 47 inches
Panel
800 A OCPD6-cycle opening for arcing current
Electrical Safety Work Practices Equipment Condition
33© 2012 Eaton Corporation. All rights reserved.
22.6 kA SymmetricalAvailable Fault Current
@ 480 V, 3 Phase
What happens if…Lack of maintenance causes the OCPD to clear in 30 cycles rather than 6 cycles?
Panel
800 A OCPD30-cycle opening for arcing current 29 cal/cm2125”
Arc Flash Risk Analysis for this PanelIncident Energy: 5.8 cal/cm2 @ 18”AFB: 47 inches
Electrical Safety Work Practices Equipment Condition
34© 2012 Eaton Corporation. All rights reserved.
1Arc flash risk assessment
PPE Level for OCPD 1 Then, PPE Level for
OCPD 2“Protecting” overcurrent protective
deviceX If does not
operate
2
Next higher upstream
OCPD used for analysis
Electrical Safety Work Practices Equipment Condition
35© 2012 Eaton Corporation. All rights reserved.
Electrical Safety Work Practices Equipment Condition
• What am I required to do?• Explicit
• NFPA 70E 110.1 - …electrical safety program shall include elements that consider condition of maintenance…
• NFPA 70E 130.2(A)(4) – …normal operation of electric equipment shall be permitted where all of the following conditions are satisfied:
(2) The equipment is properly maintained.• NFPA 70E Chapter 2 (highlights below)
• Maintenance is defined as the act of preserving or restoring the condition of electrical for the safety of employees who may be exposed to electrical hazards
• Must maintain an up to date single-line diagram• The equipment owner shall be responsible for the maintenance
of the electrical equipment• Overcurrent protective devices shall be maintained in
accordance with the manufacturers’ instructions or industry consensus standards.
36© 2012 Eaton Corporation. All rights reserved.
Electrical Safety Work Practices Equipment Condition
• What am I required to do?• Explicit
• NFPA 70 700.3(C) – Systems shall be tested periodically…to ensure systems are maintained in proper operating condition
• NFPA 70 708.6(C) - The AHJ shall require a documented preventive maintenance program for critical operating systems
• NFPA 99 6.4.4 Administration (Type 1 EES)6.4.4.1.1 Maintenance and Testing of Alternate Power Source and Transfer Switches
6.4.4.1.1.3 • Required to do maintenance per NFPA 110
6.4.4.1.2 Maintenance and Testing of Circuitry.6.4.4.1.2.1* Circuit Breakers.
• Requires service and feeder circuit breakers to be inspected yearly and exercised
A.6.4.4.1.2.1* • Main and feeder circuit breakers to be overload tested
periodically
37© 2012 Eaton Corporation. All rights reserved.
Electrical Safety Work Practices Equipment Condition
• What am I required to do?• Implicit
• NFPA 70 90.1(B) - This Code contains provisions that are considered necessary for safety. Compliance therewith and proper maintenance results in an installation that is essentially free from hazard…
• OSHA Subpart R & S – …n
38© 2012 Eaton Corporation. All rights reserved.
Electrical Safety Work Practices Equipment Condition
• What can I do to guarantee the condition of the equipment I’m responsible for?• Insulation integrity – catastrophic failure
• Cables• Transformers• Switchgear/Switchboards/MCCs
• Protective devices & controls – risk management• Circuit breakers• Relays• Fuses• Transfer Switches
39© 2012 Eaton Corporation. All rights reserved.
Electrical Safety Work Practices Equipment Condition
• What can I do to guarantee the condition of the equipment I’m responsible for?• New systems
• Perform Site Acceptance Testing (SAT) – baseline data • Perform periodic maintenance done in accordance with
manufacturer instructions and industry standards (NFPA 70B)• Existing systems
• Perform periodic maintenance done in accordance with manufacturer instructions and industry standards (NFPA 70B)
• Recondition to improve performance• Modernize equipment where any of the following exists:
• Equipment has reached the end of serviceable life• Ex: Serviceable replacement parts are difficult to find or expensive
• Service or operation of equipment increases personnel risk• Newer generation solutions offer better performance and/or
decreased risk
40© 2012 Eaton Corporation. All rights reserved.
Electrical Safety Work Practices Equipment Condition
• NFPA 70 National Electrical Code • Installation Requirements • Some maintenance requirements• Adopted as law• National consensus standard
• NFPA 70E Standard for Electrical Safety in the Work Place• Safe Work Practices• Includes maintenance requirements (not prescriptive)• National consensus standard
• NFPA 70B Recommended Practice for Electrical Equipment Maintenance• Best practices• Preventative Maintenance• Guide (easy to understand language)• Not intended to duplicate or supersede manufacturers’ instruction
41© 2012 Eaton Corporation. All rights reserved.
Equipment Life Extension & Modernization
• Switchgear modernization and upgrade solutions offers cost-effective renovation to existing equipment, with minimal power interruptions and without total replacement.
• Solutions extend the useful life of aging electrical power systems by providing safe and reliable reconditioning of existing equipment, as well as new replacement circuit breakers and other components that improve reliability and safety in existing power systems.
• Extension programs on average cost 40% less than capitol replacement.
• Modernization projects are usually 1/4 the time of replacement projects.
42© 2012 Eaton Corporation. All rights reserved.
Power System Modernization Breaker Solutions
Technology Upgrades• Protective relaying & metering• Switchgear & Bus• Retrofits (New Trip Systems)-• AR & MVVR• Grounding Schemes• Power Factor Correction• Remote switching• Transfer schemes• Communications/Automation
Expanding or Improving the regulatory compliance, life, capacity, and/or
functionality of existing infrastructure
43© 2012 Eaton Corporation. All rights reserved.
After
• Direct replacement of Siemens-Allis LA1600B Air Circuit Breaker• Customer required power on at all times (no outage for bus work) • Replaced for reliability reasons and high repair expenses • ANSI tested design
Before
Power System ModernizationLow Voltage Replacement Breaker
44© 2012 Eaton Corporation. All rights reserved.
ELEM Examples
Arc Flash ReductionArc Flash LimitersArc Quenching
Relay & Project UpgradesSnubber
Bus Duct Systems
Safety Systems
Rating UpgradesUL CertsSeismic Retrofits
© 2012 Eaton Corporation. All rights reserved.
QUESTIONS