BERMUDA PANEL INSTALLATION DETAILS
Transcript of BERMUDA PANEL INSTALLATION DETAILS
BERMUDA PANELINSTALLATION DETAILS
BERRIDGEMANUFACTURINGCOMPANY
800-669-0009 • www.Berridge.com
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
INDEX
BP-1
DATE: 8-15-06
PAGE\FILE
BP-1BERMUDA PANEL SYSTEM
INDEX
INSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONS
INTRODUCTION TO TYPICAL DETAILSOVERVIEW BP PANEL
EAVE DETAIL; EAVE DETAIL;
RIDGE DETAIL; (SOLID SHEATHING)RIDGE DETAIL; (OPEN FRAMING)
GABLE DETAIL; (SOLID SUBSTRATE)GABLE DETAIL; (OPEN FRAMING)
HEAD WALL; HEAD WALL; (OPEN FRAMING)
RAKE WALL; (SOLID SUBSTRATE)
RAKE WALL; (OPEN FRAMING)
SLOPE TRANSITION WITH FLASHING
BP-1
BPI-1BPI-2BPI-3
BP-4BP-5
BP-10BP-11
BP-20BP-21
BP-30BP-31
BP-40BP-41
BP-50
BP-52
BP-60
INDEX
INSTALLATION INSTRUCTIONS BPI-4
RIDGE DETAIL; (SOLID SUBRATE) BP-22SHED RIDGE DETAIL BP-23
HEAD WALL; (SOLID SUBSTRATE) BP-42
RAKE WALL; (SOLID SUBSTRATE) BP-51
INDEX BP-2
SPLICE PLATE DETAIL (SOLID SHEATHING) BP-6SPLICE PLATE DETAIL (OPEN FRAMING) BP-7
RIDGE TERMINATION AT DORMER VALLEY BP-26
NOMINAL LINEAR EXPANSION BPI-5
RIDGE DETAIL; (SOLID SHEATHING)RIDGE DETAIL; (OPEN FRAMING)
BP-24BP-25
HEAD WALL; WITH PARAPET BP-43
RAKE WALL; STEP FLASHING (SOLID SHEATHING) BP-53
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
INDEX
BP-2
DATE: 8-15-06
PAGE\FILE
BP-2 BERMUDA PANEL SYSTEM
U.L. 90 CONST. NO. 405 (SOLID WOOD SHEATHING) BP-90
INDEX
BP-84
BP-82BP-83
BP-81
ROOF PENETRATION; OPEN FRAMING
ROOF PENETRATION; SECTION AROOF PENETRATION; SECTION B
ROOF PENETRATION; SQUARE (PLAN VIEW)ROOF PENETRATION; PIPE PENETRATION BP-80
VALLEY; VALLEY BP-70
BP-71
VALLEY; ISOMETRICVALLEY BP-72
BP-73VALLEY; OPEN FRAMING BP-74
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
INSTALLATION INSTRUCTIONS
BPI-1
BE USED AS AN UNDERLAYMENT FOR ALL CORRUGATED DECKS.BERRIDGE MANUFACTURING RECOMMENDS GRACE ICE AND WATERSHIELD OR EQUAL TODUE TO # 30 FELTS TENDENCY TO TEAR WHEN USED OVER CORRUGATED DECKING,
IN "OIL-CANNING" IN PANELS. SUBSTRATE SHOULD BE LEVEL TO 1/4" IN 20'-0".4. USE SHIMS TO KEEP ENTIRE SUBSTRATE EVEN. UNEVEN SUBSTRATE WILL RESULT
REMAIN FLAT UNDER THE WEIGHT OF WORKMEN.3. BLOCKING OR "H" CLIPS SHOULD BE USED ON PLYWOOD IF JOINTS DO NOT
2. ALL END JOINTS SHOULD MEET AT EITHER A JOIST OR RAFTER.
1. SHEATHING END JOINTS SHOULD BE STAGGERED.
ENGINEERING DEPARTMENT FOR USE OF ANY OTHER TYPE OF SOLID SHEATHING.SUFFICIENT HOLDING POWER FOR FASTENERS. CONTACT BERRIDGE MANUFACTURING'Sx 11/16" DEPTH) OR A MINIMUM OF 1/2" PLYWOOD SHEATHING TO PROVIDETHE USES OF EITHER BERRIDGE 24 GA. CORRUGATED METAL (NOMINAL 2-1/2" PITCH
BERRIDGE MANUFACTURING COMPANY RECOMMENDS
PROTECTS THE FINISH DURING FABRICATION AND TRANSIT. THIS FILM MUST BEBERRIDGE PREFINISHED PRODUCTS, PANELS, FLASHINGS, COILS AND FLAT SHEETS
THE STRIPPABLE PLASTIC FILM WHICH IS APPLIED OVER MOST
STRIPPABLE PLASTIC FILM TO ADHERE TO THE METAL PERMANENTLY AND DISCOLOREXPOSURE TO DIRECT SUNLIGHT AND/OR MOISTURE MAY CAUSE THE FACTORY APPLIED
WITH ADEQUATE VENTILATION AND OUT OF DIRECT SUNLIGHT.TO INSTALLATION. KEEP ALL BERRIDGE PREFINISHED MATERIAL IN A DRY LOCATION
CAUTION MUST BE EXERCISED IN STORAGE OF MATERIALS PRIOR
FOR 3 IN 12 SLOPES.GREATER. A DOUBLE LAYER OF 30# FELT UNDERLAYMENT IS RECOMMENDED
PANELS ARE RECOMMENED FOR ROOF SLOPES OF 3 IN 12 OR
PANEL DEPTH OF 1".ROLL FORMER. PANELS ARE FORMED TO A CONSTANT EXPOSURE WIDTH OF 11" AND A
CAN BE FACTORY OR FIELD FABRICATED USING A PORTABLE
REMOVED PRIOR TO INSTALLATION.
THE FINISH.
INSTALLATIONINSTRUCTIONS
B. MINIMUM SLOPE:
C. MATERIAL STORAGE:
A. BERMUDA PANEL SYSTEM:
D. STRIPPABLE FILM:
E. SOLID SHEATHING REQUIREMENTS:
F. SHEATHING INSPECTION:
NOTE: FOR PROJECTS REQUIRING UL 90 ASSEMBLY, REFER TO UL 90 DETAILS.
(30 # FELT UNDERLAYMENT OR EQUAL MUST BE USED OVER ANY SOLID SHEATHING).
5. ALL CUTS AT PENETRATIONS SHOLUD BE TIGHT, WITHOUT GAPS.
6. USE WOOD FRAMED CRICKETS AT LARGE PENETRATIONS.
7. MAKE SURE SUBSTRATE JOINTS ARE TIGHT AT ALL HIPS, VALLEYS AND RIDGES.
REMOVED PRIOR TO INSTALLATION.THIS FILM MUST BE
DIAPHRAGM CAPABILITIES AND PURLIN STABILITY ARE MINIMAL AS PROVIDED BY THEBERMUDA PANEL SYSTEM, THEREFORE OTHER BRACING MAY BE REQUIRED TO CONFORM
G. INSTALLATION OVER OPEN FRAMING;
TO A.I.S.C. OR A.I.S.I. SPECIFICATIONS.
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BPI-1
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BPI-2
INSTALLATION INSTRUCTIONS
TOLERANCE OF 1/4" IN 20'-0". UNEVENNESS IN THE TOP PLANE OF THE PURLINS1. PURLINS SHOULD BE ALIGNED WITH TOP FLANGES IN THE SAME PLANE TO A
INSTALLATIONINSTRUCTIONS
H. OPEN FRAMING INSPECTION:
ADEQUATELY BRACED.WILL RESULT IN ABNORMAL "OIL CANNING" OF PANELS. PURLINS SHALL BE
AROUND ROOF PENETRATIONS. DO NOT APPLY PANELS ON OPEN FRAMING AT VALLEYSOR ROOF PENETRATIONS WITHOUT REFERRING TO DETAILS
2. BERRIDGE MANUFACTURING COMPANY REQUIRES SOLID SHEATHING IN VALLEY AND
EXTREME CARE IS NOT USED.ARE DESIGNED FOR AESTHETICS AND CAN BE EASILY DAMAGED OR DEFORMED IF
3. FOOT TRAFFIC ON THE PANELS MUST BE KEPT TO A MINIMUM. ARCHITECTURAL PANELS
A SINGLE LAYER OF NUMBER THIRTY FELT UNDERLAYMENT (OREQUAL) MUST BE APPLIED OVER SOLID SHEATHING AS SHOWN IN THE BERRIDGEMANUFACTURING COMPANY TYPICAL UNDERLAYMENT DETAILS. THE USE OF ADDITIONAL LAYERS OF NUMBER THIRTY FELT IS RECOMMENDED ON LOW-SLOPED ROOFS, AT ALL VALLEY CONDITIONS, AT ROOF PENETRATIONS, AND CERTAIN OTHER FLASHING CONDITIONS AS DEPICTED IN THE BERRIDGE TYPICAL UNDERLAYMENT DETAILS. GRACE ICE AND WATER SHIELD MAY BE
1. DO NOT USE RED ROSIN PAPER UNDER METAL ROOFING PANELS.
3. USE FLAT HEAD GALVANIZED ROOFING NAILS x 1-1/4" LONG WITH BERRIDGE
5. INSTALL FELT PARALLEL TO EAVE (2 LAYERS REQUIRED AT EAVE), STARTING ATEAVE AND USING MINIMUM 6" LAPS. USE TWO LAYERS OF FELT ON ENTIRE ROOFDECK IF ROOF SLOPE IS 3:12 OR LESS. 2 LAYERS REQUIRED AT EAVE REGARDLESS
6. INSULATE BETWEEN WOOD BLOCKING AND METAL WITH FELT OR ICE AND WATER SHIELD.
OF SLOPE.
J. FELT UNDERLAYMENT:
K. FELTING INSTALLATION:
2. SWEEP ROOF AREA CLEAN.
GALVANIZED FELT CAPS.
4. INSTALL VALLEY FELT FIRST.
1. STRIKE A LINE THE FULL LENGTH OF THE FASCIA OR RAKE. IF NOT STRAIGHT,CORRECT WITH SHIMS.
2. MAKE SURE FASCIA/RAKE IS FLUSH WITH SHEATHING.
I. FASCIA/RAKE INSPECTION:
REQUIRED ON LOW SLOPED ROOFS OR AT CERTAIN FLASHING CONDITIONS.
7. REFER TO UNDERLAYMENT DETAILS. WHEN VALLEYS OR ROOFPENETRATIONS ARE INVOLVED ON OPEN FRAMING CONDITIONS.
1. PANELS OVER 30'-0" LONG REQUIRE EXPANSION JOINTS SEE DETAIL BP-6 AND BP-7.
PANELS TO DISENGAGE FROM THE FLASHING, ALLOW OIL-CANNING IN PANEL AND/ORTHERMAL MOVEMENT OF THE PANELS. IMPROPERLY DESIGNED FLASHING CAN ALLOWAND PANELS. PLEASE REFER TO THE CHART ON PAGE BPI-5 TO DETERMINE ANTICIPATEDFEET IN LENGTH CAN BE A FACTOR IN THE DESIGN AND INSTALLATION OF FLASHING
EXPANSION AND CONTRACTION OF PANELS WHICH EXCEED THIRTYL. THERMAL MOVEMENT:
CAUSE FLASHING TO WORK LOOSE FROM ITS ANCHORAGE.
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BPI-2
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
INSTALLATION INSTRUCTIONS
BPI-3
INSTALLATIONINSTRUCTIONS
AVOID ALLOWING FLASHING AND PANELS TO COME INTO CONTACT WITHEITHER LEAD OR COPPER, AND PREVENT EXPOSURE TO WATER RUNDOWN FROM
IF BERRIDGE MANUFACTURING COMPANY IS TO SUPPLY FLASHING, ALLFLASHINGS WILL BE FABRICATED IN 10'-0" LENGTHS WITH SQUARE END CUTS ONLY.THE PURCHASER MUST PROVIDE ALL DIMENSIONS AND DEGREE OF ANGLES.
M. ELECTROLYSIS:
COPPER AND/OR LEAD.
N. FLASHING:
1. REMOVE STRIPPABLE PLASTIC FILM FROM ALL FLASHINGS PRIOR TO INSTALLATION.
2. ALWAYS STAGGER JOINTS WHEN ONE FLASHING IS INSTALLED OVER OTHER FLASHINGS.
3. INSTALL ALL FLASHINGS AS PER BERRIDGE TYPICAL DETAILS.
4. ALL FLASHINGS ARE TO BE DESIGNED AND INSTALLED TO NOT TRAP WATER.
BERRIDGE MANUFACTURING COMPANY WILL PROVIDE SQUARE END CUTS ONLYON ALL BERMUDA PANELS. COMPUTATION OF ALL QUANTITIES AND DIMENSIONS ARE THE
2. REMOVE STRIPPABLE PLASTIC FILM FROM EACH PANEL PRIOR TO INSTALLATION.
3. START AT EAVE WITH PANEL AND WORK TOWARD THE RIDGE. PANEL END CUTS NEED
4. KEEP PANELS ALIGNED SO THAT PANELS MATCH AT HIPS AND VALLEYS. DO NOTINSTALL LONG CONTINUOUS RUNS OF PANELS ALL AT ONE TIME WHERE PANEL LINESMUST MATCH. INSTALL TEN TO TWELVE PANELS IN ONE ELEVATION AND THEN FOLLOWWITH A LIKE NUMBER OF PANELS ON THE OTHER ELEVATION. WHEN YOU INSTALL
5. INSTALL CLIPS AS PER CLIP INSTALLATION NOTES.
6. EACH PANEL IS TO BE KEPT TIGHT AGAINST THE ADJOINING PANEL. NEVER PERMITA GAP BETWEEN THE MALE/FEMALE JOINT ANY CRIMPS IN MALE LEG MUST BESTRAIGHTENED (TOTALLY STRAIGHT WITH OUT ANY BENDS, CRIMPS, CREASES, ETC.)PRIOR TO PANEL INSTALLATION.
P. PANELS:
RESPONSIBILITY OF THE PURCHASER.
Q. PANEL INSTALLATION:
TO BE ACCURATE WHEN USING THE VINYLWEATHERSEAL.
TREMCO, INC. "SPECTREM 1" SILICONE SEALANT.O. SEALENT RECOMMENDATIONS:
1. INSTALL STARTER STRIP CONTINUOUS AT EAVE.
PANELS IN THIS MANNER, YOU WILL BE ABLE TO MAKE ANY ADJUSTMENTS REQUIRED TO INSURE PANEL MATCHING.
DO NOTDO NOT
MUST MUST
FINISHES. DO NOT MIX LOTS.EFFECT OF THE PIGMENTS IN THE FINISH.WILL APPEAR, FROM A DISTANCE, A DIFFERENT SHADE DUE TO THE GRANULARPANEL IS REVERSED (ARROWS POINTING OPPOSITE OF THOSE ON OTHER PANELS) ITTHE ARROWS ON EVERY PANEL ARE ALL POINTING IN THE SAME DIRECTION. IF APANEL. ALL PANELS MUST BE INSTALLED IN A CONSISTENT MANNER, MEANING THATINSTALLATION: NOTE THE SERIES OF ARROWS PAINTED ON THE UNDERSIDE OF THE
7. COPPER-COTE, CHAMPAGNE, LEAD-COTE, AND PREWEATHERED GALVALUME PANELTM
METALLIC FINISHES ARE MATCH - LOT
TM R
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BPI-3
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BPI-4
INSTALLATION INSTRUCTIONS
INSTALLATIONINSTRUCTIONS
MAKE SURE ALL FASTENERS ARE DRIVEN STRAIGHT AND SET FLAT. DO NOT OVERDRIVE
INSTALL FASTENERS AS PER TYPICAL DETAILS. USE 11 GAUGE 1-1/4"GALVANIZED ROOFING NAILS FOR INSTALLATION OVER WOOD SHEATHING AND USE #10PANCAKE HEAD TEKS FASTENERS (ZINC-PLATED SCREW WITH PHILLIPS INSERT, ASMADE BY CONSTRUCTION FASTENERS CO.) FOR INSTALLATION TO METAL. WHEN USINGPOP RIVETS ON FLASHING, STAINLESS STEEL RIVETS ARE RECOMMENDED TO AVOID RUST
FASTENERS, AS THIS WILL CAUSE THE CLIP AND/OR FLASHINGS TO BUCKLE OR BECOMERECESSED BELOW THE ELEVATION OF THE SUBSTRATE.
S. FASTENERS:
RUST STAINS.
**
NOTE: IF LOCAL CODES OR OTHER REGULATIONS DICTATE SPECIFIC WIND UPLIFTREQUIREMENTS, CONSULT THE BERRIDGE ENGINEERING DEPARTMENT, AS IT MAYBE NECESSARY TO USE A DIFFERENT CLIP SPACING OR FASTENER.
*
1. INSTALL CLIPS AS PER DETAILS.
2. CLIP SPACING ON SOLID SHEATHING NOT TO EXCEED 20" ON CENTER.
R. CLIP INSTALLATION:
3. WHEN INSTALLING PANEL OVER OPEN FRAMING, USE CLIPS ALONG EVERY PURLINAT 20" ON CENTER MAXIMUM.
*
*
USE OF ANY OTHER TYPE OF FASTENER.NOTE: CONSULT BERRIDGE MANFACTURING'S ENGINEERING DEPARTMENT REGARDING THE**
BERRIDGE MANUFACTURING COMPANY STRIVES TO PROVIDE ITS CUSTOMERS WITH THEHIGHEST QUALITY STRETCHER LEVELED STEEL AVAILABLE. THE LATEST TECHNOLOGY ISALSO INCORPORATED IN BERRIDGE'S HIGH-PRECISION COIL HANDLING AND ROLL FORMINGEQUIPMENT TO MINIMIZE THE STRESS ON METAL DURING PRODUCTION. FURTHERMORE,BERRIDGE UTILIZES HEAVIER 24 GAUGE METAL RATHER THAN 26 GAUGE STEEL OR LIGHTGAUGE ALUMINUM AS OFFERED BY MANY COMPETITORS. ALL THESE MEASURES HAVE BEENTAKEN TO MINIMIZE THE AMOUNT OF "OIL-CANNING" (WAVINESS) WHICH IS NATURALLYINHERENT IN FLAT SHEET METAL. MANY TIMES, HOWEVER, THE CAUSE OF WAVINESS OR"OIL-CANNING" CAN BE TRACED TO UNEVEN SHEATHING, IMPROPER FELT INSTALLATION,IMPROPER HANDLING, OR FOOT TRAFFIC ON THE PANELS.
ALL ARCHITECTURAL PANELS REQUIRE CARE IN HANDLING AND INSTALLATION TO AVOID
THESE INSTALLATION INSTRUCTIONS AND THE FOLLOWING TYPICAL DETAILS ARE INTENDEDTO PROVIDE OUR CUSTOMERS WITH THE INFORMATION REQUIRED FOR AN AESTHETICALLYPLEASING AND FUNCTIONAL INSTALLATION OF THE BERRIDGE BERMUDA PANEL SYSTEM.
WITHOUT NOTICE. FOR SPECIFIC PROJECT DETAILS, CONTACT BERRIDGE.NOTE: ALL PRODUCTS, SPECIFICATIONS, DETAILS, AND INSTRUCTIONS SUBJECT TO CHANGE
DAMAGING OR DEFORMING THE PANELS.
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BPI-4
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
INSTALLATION INSTRUCTIONS
BPI-5
DATE: 10-30-17
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-4
INTRODUCTION TO TYPICAL DETAILS
THE DETAILS CONTAINED IN THE FOLLOWING PAGES ARE MERELY RECOMMENDATIONS ASTO HOW BERRIDGE MANUFACTURING MATERIALS SHOULD BE INSTALLED. THEY MAY REQUIREADAPTATIONS OR MODIFICATIONS FOR A SPECIFIC PROJECT AS CONDITIONS VARY IN BOTHBUILDING DESIGN AND LOCAL WEATHER PECULIARITIES.
BERRIDGE MANUFACTURING COMPANY SHALL BE HELD HARMLESS FROM ANY AND ALLCLAIMS ARISING FROM LACK OF WATERTIGHTNESS AS A RESULT OF FOLLOWING THESERECOMMENDED DETAILS. ENSURING WATERTIGHTNESS ON ANY GIVEN PROJECT IS THEFUNCTION OF THE INSTALLER. THE ARCHITECT/GENERAL CONTRACTOR/INSTALLER MUSTACCEPT THE RESPONSIBILITY TO ADAPT THESE DETAILS TO MEET PARTICULAR BUILDINGREQUIREMENTS AND TO ASSURE ADEQUATE WATERTIGHTNESS.
THE INSTALLER CAN VIRTUALLY ASSURE WATERTIGHTNESS IF THESE FLASHING DETAILSHAVE BEEN PROPERLY ADAPTED, ADEQUATE LAPS HAVE BEEN PROVIDED, CORRECT TYPEOF SEALANT USED, ALL JOINTS ADEQUATELY CAULKED, AND PROFESSIONAL WORKMANSHIPEMPLOYED.
TYPICAL DETAILSINTRODUCTION TO
BERMUDA PANEL SYSTEM BP-4
PAGE\FILE
DATE: 8-15-06
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-5
PANEL OVERVIEW
ANCHOR CLIP
BERMUDA ROOF PANEL
1"
WEATHERSEALOPTIONAL VINYL
11" E
XPOSU
RE
BERMUDA ROOF PANEL
CLIPS 20" O.C.
CLIPS 20" O.C.
BP-5
CLIPS 20" O.C.
PANEL OVERVIEWDATE: 8-15-06
PAGE\FILE
BERMUDA PANEL SYSTEM
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-6
SPLICE PLATE DETAILSOLID SHEATHING
SPLICE PLATE DETAILDATE: 8-15-06
PAGE\FILE
BERMUDA PANEL SYSTEM
SOLID SHEATHING
BP-6
ON PAGE BPI-5
# 30 FELT UNDERLAYMENT
ANCHOR CLIP 4" O.C.AT SPLICE PLATE
SOLID SHEATHING
LINEAR EXPANSION CHARTREFER TO NOMINAL
OF CAULK ALONG EACH SIDEAPPLY 2 CONTINUOUS BEADS
BETWEEN SPLICE PLATE ANDBERMUDA ROOF PANELS
BERRIDGEBERMUDA ROOF PANEL
SPLICE PLATE FOREXPANSION AND
PATTERN
STAGGER JOINTS IN A
FLAT BEAD OF CAULK
BERMUDA PANELS
CONTRACTION OF PANELS
DIAGONAL OR STRAIGHTRANDOM PATTERN, NOT A
BETWEEN SPLICE PLATE &
OVER 30'-0" LONG
RIVETS TO BE PLACED SO THAT
ANCHOR CLIP 20" O.C. MAX.
POP RIVET 4" O.C.
THEY ARE "NOT EXPOSED".
BERMUDA ROOF PANEL
ROOF SPLICE PLATE
24 GA. FURRING SECTION12" LONG
BERRIDGE
FASTENERS 4" O.C.
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-10
EAVE DETAIL
CONTINUOUS STARTER STRIPALIGN WITH EAVE FLASHING
BERRIDGE BERMUDA PANEL
LAPS WITH CONTINUOUS EAVE FLASHING 4" END
FASTENERS 20" O.C. MAX.
# 30 FELT
EAVE FLASHING STARTER STRIP
F = FINISH SIDE
F
EAVE DETAILDATE: 8-15-06PAGE\FILE
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.
FURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BE
OF THE ARCHITECT.
SOLID SHEATHING
CAULK AT LAPS
UNDERLAYMENT
F
BP-10BERMUDA PANEL SYSTEM
3/8"
1/8"
1 3/4"
1/2"
1/2"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-11
EAVE DETAIL
CONTINUOUS STARTER STRIPALIGN WITH EAVE FLASHING
BERRIDGE BERMUDA PANEL
LAPS WITH CONTINUOUS EAVE FLASHING 4" END FASTENERS 20" O.C. MAX.
BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.1. ALL CAULKING AND FASTENERS ARE ITEMS TO BE FURNISHED AND INSTALLED
EAVE STRUTCAULK AT LAPS
FASCIA PANELBERRIDGE WALL PANEL OR
STARTER STRIP
F
F = FINISH SIDE
EAVE FLASHING
1/2" 1/8"
3/8"
F
1/2"
1 3/4"
EAVE DETAIL
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BP-11
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-20
RIDGE DETAILSOLID SHEATHING
RIDGE FLASHING
F
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT
IN STRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BE
FURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION
F = FINISH SIDE
BERMUDA PANEL SYSTEM
RIDGE DETAIL DATE: 8-15-06PAGE\FILE
BP-20
OF THE ARCHITECT.
F
ZEE CLOSURE
FASTENER 20" O.C. MAX.
SOLID SHEATHING
CONTINUOUS CAULK AT LAPSZEE CLOSURE 4" END LAPS WITH
CLOSURE 40" O.C., AND AT LAPS.AT LAPS, POP RIVET TO ZEELAPS WITH CONTINUOUS CAULKRIDGE FLASHING 4" END
BERRIDGE BERMUDA PANEL
CAULK RIVET HEADS
# 30 FELT UNDERLAYMENT
OF CAULKCONTINUOUS BEAD
SOLID SHEATHING
1/2" 1/2"
1" 1"
1 1/8"
OPEN HEM
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-22
RIDGE DETAILSOLID SUBSTRATE
RIDGE FLASHING
F
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BEFURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION
F = FINISH SIDE
1/2" 1/2"
OF THE ARCHITECT.
BERMUDA PANEL SYSTEM
RIDGE DETAILSOLID SUBSTRATE
DATE: 8-15-06
PAGE\FILE
BP-22
SOLID SHEATHING
# 30 FELTUNDERLAYMENT
AT LAPS, POP RIVET TO BERMUDA
CONTINUOUS BEADOF CAULK
PANEL 40" O.C., AND AT LAPS.CAULK RIVET HEADS
LAPS WITH CONTINUOUS CAULKRIDGE FLASHING 4" END
BERRIDGE BERMUDA PANEL
FASTENER 20" O.C. MAX.
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-23
SHED ROOF RIDGE CAP DETAIL
AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED
STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN
RIDGE CAP
OPEN HEM
BARRIDGE BERMUDA PANEL
4" END LAP WITH
CAULK AT LAPS, POP RIVET TO ZEE CLOSURERIDGE CAP; 4" END LAPS WITH CONTINUOUS
ZEE CLOSURE
AT 40" O.C. MAX. CAULK RIVET HEADS
F = FINISH SIDE
ZEE CLOSURE
SOLID SHEATHINGUNDERLAYMENT
MAX. CAULKFASTENERS; 40" O.C.
FASTENERS; 20" O.C. MAX.
LAP FELT OVER RIDGE
CAULKCONTINUOUS BEAD OF
# 30 FELT
FASTENER HEAD
CONTINUOUS CAULKAT LAPS
BERMUDA PANEL SYSTEM
SHED ROOF RIDGEDATE: 8-15-06
PAGE\FILE
BP-23
1" 1"
1/2"F
F
1/2"
CAP DETAIL
1 1/8"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-24
HIP DETAIL
AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELTING UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED
STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN
BERRIDGE BERMUDA PANEL
COURSE OF PANEL (SEE BELOW)HIP CAP; INSTALL WITH EACH
SOLID SHEATHING
# 30 FELT UNDERLAYMENT
HIP DETAIL DATE: 8-15-06PAGE\FILEBP-24BERMUDA PANEL SYSTEM
LINE OF HIP
HIP CAPNAIL EACH SIDE OF
BERRIDGE BERMUDA PANEL
HIP CAP; INSTALL WITH EACHCOURSE OF PANEL
ABOVE HIP CAP, FIELD CUT
UNDER HIP CAPBERRIDGE BERMUDA PANEL
TO ALIGN WITH LINE OF HIP 3/4"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-26
RIDGE TERMINATION AT DORMER VALLEY
DATE: 8-15-06
PAGE\FILE
BP-26BERMUDA PANEL SYSTEM
SECTION VIEW
FIELD FORM END OF RIDGE FLASHINGAND EXTEND UNDER CONTINUOUS CLEAT
RIDGE FLASHING; 4" END LAPSWITH CONTINUOUS CAULK AT LAPS
BP-20
FIELD TAPERED ZEE CLOSURE
CONTINUOUS CLEAT;
BERRIDGE BERMUDA PANEL
FASTENERS; 20" O.C. MAX.
# 30 FELTUNDERLAYMENT
PLACE A DAB OF CAULK
PLAN VIEW
PANELSMAIN ROOF
RIDGE FLASHING
CONTINUOUS CLEAT
VALLEY FLASHING
DORMER PANEL
WITH CONTINUOUS CAULK UNDERZEE CLOSURE
DO NOT CAULK ONOR UNDER CLEAT
RIDGE TERMINATIONAT DORMER VALLEY
SOLID SHEATHINGVALLEY FLASHING; 12" LAPS WITHCONTINUOUS CAULK AT LAPS
AT FASTENER LOCATIONDRIVE FASTENER ANDCAULK FASTENER HEAD
SLOPE SLOPE
SLO
PE
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-30
GABLE DETAILSOLID SUBSTRATE
3/4"
1 1/8"
1/2"
4 1/4"
F
4"
1/2"
F
SPECIAL CHANNEL CLOSURE GABLE FLASHING
FASTENERS; 20" O.C.MAX. STAGGERED
SOLID SHEATHING
FASTENERS; 20" O.C. MAX.
# 30 FELT UNDERLAYMENT
BERRIDGE BERMUDA PANEL
4" END LAPS WITHCONTINUOUS CAULK AT LAPS
CONTINUOUS BEADS OF CAULK
GABLE FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
F = FINISH SIDE
BERMUDA PANEL SYSTEM
GABLE DETAILSOLID SUBSTRATE
DATE: 8-15-06PAGE\FILE
BP-30
PLACE A DAB OF CAULKAT FASTENERS LOCATION,DRIVE FASTENER, ANDCAULK FASTENER HEADS
TOP LAYER OF FELT TOBE PARALLEL WITH ROOFSLOPESPECIAL CHANNEL CLOSURE
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-40
HEAD WALL DETAIL
AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED
STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN
OPEN HEM
COUNTER FLASHING SUB-FLASHING
F
BERRIDGE BERMUDA PANEL
# 30 FELT UNDERLAYMENT
CONTINUOUS CAULK AT LAPS.SUB-FLASHING; 4" END LAPS WITH
POP RIVET TO ZEE CLOSURE 40" O.C. MAX.AND AT LAPS. CAULK RIVET HEADS.
WITH CONTINUOUS CAULK AT LAPS.COUNTER FLASHING; 4" END LAPS
ZEE CLOSURE
F = FINISH SIDE
F
20" O.C. MAX.FASTENERS;
SOLID SHEATHING
OF CAULKCONTINUOUS BEAD
1" 1"
1 1/8"
CONTINUOUS CAULK AT LAPS.ZEE CLOSURE; 4" END LAPS WITH
# 30 FELT
BERIDGE WALL ORFASCIA PANEL
CHANNEL CLOSURE; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS.
20" O.C. MAX.FASTENERS;
UNDERLAYMENT
CHANNEL CLOSURE
F
HEAD WALL DETAIL DATE: 8-15-06
PAGE\FILE
BP-40BERMUDA PANEL SYSTEM
1/2"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-42
HEAD WALL DETAILSOLID SUBSTRATE
BERMUDA PANEL SYSTEM
HEAD WALL DETAILSOLID SUBSTRATE
DATE: 8-15-06
PAGE\FILE
BP-42
1/2"
1" 1"
1 1/8"
1/2"
OPEN HEM
COUNTER FLASHING ZEE CLOSURE
F
F
F = FINISH SIDE
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
FASTENERS; 20" O.C.
CONTINUOUS BEAD OFCAULK BETWEEN ZEECLOSURE AND BERMUDAPANEL
FASTENERS; 20" O.C.MAX.
SOLID SHEATHING
MAX.
# 30 FELT UNDERLAYMENT
COUNTER FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS. POP RIVETTO ZEE CLOSURE 40" O.C. AND AT LAPS.
BERRIDGE BERMUDA PANEL
SUB-FLASHING
SUB-FLASHING;
CONTINUOUS BEAD OF CAULK AT REGLET
REGLET FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS.
ZEE CLOSURE; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS.
WITH CONTINUOUS 4" END LAPS
CAULK AT LAPS
F
REGLET FLASHING
CAULK RIVET HEADS.
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-43
PARAPET DETAIL
AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED
STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN
OPEN HEM
COUNTERFLASHING SUB-FLASHING
F
BERRIDGE BERMUDA PANEL
# 30 FELT UNDERLAYMENT
CONTINUOUS CAULK AT LAPS.SUB-FLASHING; 4" END LAPS WITH
POP RIVET TO ZEE CLOSURE 40" O.C. MAX. AND AT LAPS. CAULK RIVET HEADS.
WITH CONTINUOUS CAULK AT LAPS.COUNTERFLASHING; 4" END LAPS
FASTENERS; 20" O.C. MAX.
O.C. MAX. CAULK ALL RIVET HEADS.POP RIVET TO COUNTER FLASHING 40"WITH CONTINUOUS CAULK AT LAPS.CAP FLASHING; 4" END LAPS
CAP FLASHING
F
ZEE CLOSURE
F = FINISH SIDE
F
20" O.C. Max.FASTENERS;
SOLID SHEATHING
OF CAULKCONTINUOUS BEAD
O.C. MAX. CAULK
CAULK FASTENER
FASTENERS; 40"
UNDERLAYMENT# 30 FELT
20" O.C. ANDSTAGGERED;LAPS ANDFASTENERS AT
HEADS
1 ON 121" 1"
1 1/8"
FASTENER HEADS
1 ON 12
CONTINUOUS CAULK AT LAPS.ZEE CLOSURE; 4" END LAPS WITH
PARAPET DETAILDATE: 8-15-06
PAGE\FILE
BP-43 BERMUDA PANEL SYSTEM
1/2"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-50
RAKE WALL DETAIL COUNTER FLASHING SOLID SUBSTRATE
COUNTERFLASHING CLOSURE CHANNEL
F = FINISH SIDE
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
# 30 FELT UNDERLAYMENT
FASTENERS; 20" O.C. MAX.
CLOSURE CHANNEL; 4" ENDLAPS WITH CONTINUOUSCAULK AT LAPS
CONTINUOUS BEAD OF CAULK
SUB-FLASHING; 4" END LAPS
AT LAPSWITH CONTINUOUS CAULK
SOLID SHEATHING
FASTENERS; 20" O.C. MAX.
BERRIDGE WALL OR FASCIA PANEL
COUNTERFLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS
BERRIDGE BERMUDAPANEL
# 30 FELTUNDERLAYMENT; TOPLAYER TO BEPARALLEL WITHROOF SLOPE
SUB-FLASHING
OPEN HEM
4"
1 1/
8"
3/4"
F F
BERMUDA PANEL SYSTEM
RAKE WALL DETAILCOUNTERFLASHINGSOLID SUBSTRATE
DATE: 8-15-06
PAGE\FILE
BP-50
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-51
RAKE WALL DETAIL COUNTER FLASHING SOLID SUBSTRATE
COUNTERFLASHING CLOSURE CHANNEL
F = FINISH SIDE
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
# 30 FELT UNDERLAYMENT
FASTENERS; 20" O.C. MAX.
CLOSURE CHANNEL; 4" ENDLAPS WITH CONTINUOUSCAULK AT LAPS
CONTINUOUS BEAD OF CAULK
SUB-FLASHING; 4" END LAPS
AT LAPSWITH CONTINUOUS CAULK
SOLID SHEATHING
FASTENERS; 20" O.C. MAX.
CONTINUOUS CAULK AT REGLET
COUNTERFLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS
BERRIDGE BERMUDAPANEL
# 30 FELTUNDERLAYMENT(TOP LAYER MUSTBE PARALLELWITH ROOF SLOPE
SUB-FLASHING
OPEN
4"
1 1/
8"
3/4"
F
F
REGLETFLASHING
F1/2"
CONTINUOUS CAULK AT LAPSREGLETFLASHING; 4" END LAPS WITH
CONTINUOUS BEAD OF CAULK
REGLET
HEM
BERMUDA PANEL SYSTEM
RAKE WALL DETAILCOUNTERFLASHINGSOLID SUBSTRATE
DATE: 8-15-06
PAGE\FILE
BP-51
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-53
RAKE WALL DETAILSTEP FLASHING
SOLID SUBSTRATE
STEP FLASHING
F = FINISH SIDE
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
BERRIDGE WALL OR FASCIA PANEL
STEP FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS, SET
BERRIDGE BERMUDA PANEL;
# 30 FELTUNDERLAYMENT; TOP LAYER TO BEPARALLEL WITHROOF SLOPE
SUB-FLASHING
F
LOCATION OF MALE/FEMALE JOINT
CAULK AT LAPS
PANELVERTICAL EDGE OF BERMUDACONTINUOUS CAULK ALONG
PANEL MINIMUM 2"
LAPS WITH CONTINUOUS SUB-FLASHING; 4" END
CAULK
UP VERTICAL LEG AT END OF
CONTINUOUS BEAD OF
FIELD CUT PANEL AND TURN
FASTENERS EVERY 11" O.C. AT
FASTENERS; 20" O.C. MAX.
FASTENERS; 20" O.C. MAX.
DRIP FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS
FLASHING TIGHT ON TO PANEL
DRIP FLASHING
F
CONTINUOUS BEAD OFCAULK
FASTENERS; 2 PER PANEL LEG
# 30 FELT UNDERLAYMENT
BERMUDA PANEL SYSTEM
RAKE WALL DETAILSTEP FLASHING
SOLID SUBSTRATE
DATE: 8-15-06
PAGE\FILE
BP-53
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-60
SLOPE TRANSITION DETAIL SOLID SUBSTRATE
BERMUDA PANEL SYSTEM
SLOPE TRANSITION DETAILSOLID SUBSTRATE
DATE: 8-15-06
PAGE\FILE
BP-60
1/2"
1" 1"
1 1/8"
OPEN
SLOPE TRANSITION ZEE CLOSURE
F
F
F = FINISH SIDE
1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
SUB-FLASHING
1/2"
STARTER STRIP
1/8"F
3/8"
1 3/4"
FLASHING
BERRIDGE BERMUDA PANEL
CONTINUOUS STARTER STRIP
ZEE CLOSURE; 4" END LAPS WITH
FASTENERS; 20" O.C.
# 30 FELT UNDERLAYMENT
MAX.
CONTINUOUS BEAD OF
CONTINUOUS CAULK AT LAPS.
CAULK
SLOPE
SLOPE TRANSITION FLASHING; 4" END LAPS WITH
CAULK RIVET HEADS.
CONTINUOUS CAULK AT LAPS. POP RIVETTO ZEE CLOSURE 40" O.C. AND AT LAPS.
# 30 FELT
BERRIDGE BERMUDA PANEL
SOLID SHEATHING
SUB-FLASHING;
WITH CONTINUOUS CAULK AT LAPS
4" END LAPS
FASTENERS;
UNDERLAYMENT
20" O.C. MAX.
HEM
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-70
VALLEY DETAIL
1. SOLID SHEATHING (BY OTHERS) TO BE A MINIMUM OF 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
CONTINUOUS BEAD OF CAULK
# 30 FELT
VALLEY DETAIL
UNDERLAYMENT
DATE: 8-15-06PAGE\FILE
BP-70BERMUDA PANEL SYSTEM
SOLID SHEATHING; MUST BE USEDAT ALL VALLEYS SEE DETAIL BP-74
BUTT AND LAP UNDER OPPOSITE PANELBERMUDA PANEL FIELD CUT OFF2 BEADS CONTINUOUS CAULK AT LAPS,
VALLEY FLASHING; 12" END LAPS WITH
VALLEY LEGS MIN. 21" EACH SIDE.
TO VALLEY ANGLEFIELD FABRICATED BREAK
SPECIAL VALLEY CAP;
BUTT AND LAP UNDER OPPOSITE BERMUDA PANEL FIELD CUT OFF
PANEL LAP AS PER BP-71PANEL CONTINUOUS CAULK AT
BERRIDGE BERMUDA PANEL
BEFORE VALLEY CAP.TO BUTT END OF PANEL
1" X 1" ANGLE FASTEN
BERRIDGE BERMUDA PANEL
SPECIAL VALLEY CAP; PLACE INTOFEMALE LOCK OF PANEL ABOVE AND FASTENTO BUTT OF PANELS BEING COVERED
1'-6" MIN
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-71
VALLEY DETAILDATE: 8-15-06
PAGE\FILE
BP-71 BERMUDA PANEL SYSTEM
VALLEY DETAIL
BERMUDA PANEL FIELD CUT AND LAP PANELS AT VALLEYCONTINUOUS CAULK AT LAPS
FIELD FORM PANEL TO VALLEY
NOTE; REFER TO BP-70 FOR VALLEY DETAIL
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-72
VALLEY DETAIL DATE: 8-15-06
PAGE\FILE
BP-72BERMUDA PANEL SYSTEM
1. SOLID SHEATHING (BY OTHERS) TO BE A MINIMUM OF 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.
2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
# 30 FELT
BERRIDGE BERMUDA PANEL
SPECIAL CHANNEL CLOSURE;
VALLEY DETAIL
UNDERLAYMENT
SOLID SHEATHING; MUST BE USEDAT ALL VALLEYS SEE DETAIL BP-74
SET TIGHT UP TO VALLEY FLASHING
2 BEADS CONTINUOUS CAULK AT LAPS,VALLEY FLASHING; 12" END LAPS WITH
FASTEN UNDER LAPS ONLY
DO NOT USE FASTENERS AT SPECIAL CHANNEL CLOSURE
CONTINUOUS BEAD OF CAULK BETWEEN VALLEY FLASHINGAND FELT UNDERLAYMENT
ANCHOR CLIP (18" O.C. MAX.)
NOTE: DO NOT USE ANY FASTENERS THROUGH THE VALLEY FLASHING, EXCEPTAT LAPS (SEE DETAIL BP-73)
F = FINISH SIDE
F
F
SPECIAL CHANNEL CLOSURE
VALLEY FLASHING
19 1/4"
3/8"
1 1/8"
3/8"
4"
3/4"
1 1/8"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-73
VALLEY DETAILISOMETRICDATE: 8-15-06
PAGE\FILE
BP-73 BERMUDA PANEL SYSTEM
VALLEY DETAIL
2 CONTINUOUS BEADS OF CAULK AT LAPSANCHOR CLIP
F = FINISH SIDE
F
ONLY AT TOP OF FLASHING
TOP (OVERLAPPING) VALLEYARE TO BE EXPOSED ONUNDER LAP, NO FASTENERS
FASTEN THROUGH VALLEY
VALLEY FLASHING LAP
12" LAP
CLOSURESPECIAL CHANNEL
CONTINUOUS BEAD OF CAULKVALLEY FLASHING# 30 FELT UNDERLAYMENT
SOLID SHEATHING; MUST BE USED
BERRIDGE BERMUDA PANEL
ISOMETRIC
AT VALLEY SEE DETAIL BP-74
OPEN HEM
ANCHOR CLIP
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-80
PIPE PENETRATION OPEN FRAMING AND SOLID SUBSTRATE
CUT PANEL 1" SMALLER THANPENETRATION, BACK CUT TABS,FOLD TABS UP AROUNDPENETRATION, AND CAULK.
1. CUT HOLE TO ALLOW FOR THERMAL MOVEMENT IF PANELS ARE 30'-0" OR LONGER.
# 30 FELT UNDERLAYMENT
BERRIDGE BERMUDAPANEL
PIPE PENETRATION TOBE IN PAN OF PANEL ONLY
RUBBERIZED "BOOT"FLASHING
ROOF PIPE PENETRATIONOF 4" DIA. OR LESS
CONTINUOUS CAULK OR
SET RUBBERIZED BOOTINTO CONTINUOUS BEADOF CAULK. USE FASTENERSAS SPECIFIED BY BOOTMANUFACTURER. CAULK
2. IF PIPE IS MADE OF METAL, IT MUST BE PAINTED TO PREVENT RUST RUN-OFFFROM STAINING PANELS.
FASTENER HEADS.
SOLID SHEATHING
PIPE PENETRATIONOPEN FRAMING AND SOLID SUBSTRATE
3. POSITION SQUARE BASED BOOTS IN A DIAMOND ORIENTATION WHERE POSSIBLE TOAID IN DIVERTING WATER.
STAINLESS STEEL HOSECLAMP
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BP-80
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-81
ROOF PENETRATION RECTANGULAR/SQUARE
BERRIDGE BERMUDA PANELAROUND PENETRATIONFIELD CUT TO FIT TIGHTNOTE: PANELS ARE TO BE
FLASHING, FROM BP-82VERTICAL LEG OF COUNTER
TURN CORNER WITH
TURN CORNER WITH VERTICAL LEG OF STEP FLASHING,FROM BP-83
# 30 FELT UNDERLAYMENTWRAP CURB WITH
AND SUB FLASHING
BP-83 UNDER FLASHINGCARRY STEP FLASHING FROM
FROM BP-82
BP-83
BP-82
VERTICAL LEG OF FLASHINGFROM BP-82
TURN CORNER WITH
VERTICAL LEG OF STEP FLASHING,FROM BP-83
TURN CORNER WITH
VERTICAL LEG TO FORMTIGHT TO PANEL, 4" LAP
FIELD FORM STEP FLASHING
WITH CONTINUOUS CAULKAT LAPS
BERRIDGE BERMUDA PANEL
CONTINUOUS CAULKAT ALL FLASHING LAPS
SLO
PE
ROOF PENETRATIONRECTANGULAR/SQUARE
DATE: 8-15-06
PAGE\FILE
BP-81 BERMUDA PANEL SYSYEM
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-82
SQUARE PENETRATION SECTION A
SOLID SUBSTRATE AND OPEN FRAMING
1. SOLID SHEATHING IS REQUIRED AT THIS CONDITION WHEN THE BERMUDA PANEL ISUSED OVER OPEN FRAMING (SEE DETAIL BP-84).
2. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS. (METAL CORRUGATED SHEATHING MAYBE USED IN LIEU OF PLYWOOD).
3. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.
COUNTERFLASHING & FLASHING
F
F = FINISH SIDE
ANCHOR CLIP; 20" O.C. MAX.
# 30 FELT UNDERLAYMENT
POP RIVET TO PANEL20" O.C. MAX.
ANCHOR CLIP; 20" O.C. MAX.
COUNTERFLASHING
OF CAULK
WITH CONTINUOUS CAULK AT LAPSSUB FLASHING; 4" END LAPS
BERRIDGE BERMUDA PANEL; FORM TO CURB
UNDERLAYMENT
CURB MATERIAL
CONTINUOUS BEAD
BERRIDGE BERMUDA PANEL;FORM TO CURB
# 30 FELT
20" O.C. MAX.FASTENERS;
FASTEN TO CURB 20" O.C. MAX.
CONTINUOUS BEADOF CAULK
FLASHING;
20" O.C. MAX.FASTENERS;
FLASHING BY EQUIPMENT MANUFACTURE
SUB FLASHING
F
SQUARE PENETRATIONSECTION A
SOLID SUBSTRATE AND OPEN FRAMING
BERMUDA PANEL SYSTEM
DATE: 8-15-06
PAGE\FILE
BP-82
3/4"1/2"
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-83
SQUARE PENETRATION SECTION B
SOLID SUBSTRATE AND OPEN FRAMING
STEP FLASHING
F = FINISH SIDE
STEP FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS, SET
BERRIDGE BERMUDA PANEL;
# 30 FELTUNDERLAYMENT; TOP LAYER TO BEPARALLEL WITHROOF SLOPE
SUB-FLASHING
F
LOCATION OF MALE/FEMALE JOINT
CAULK AT LAPS
PANELVERTICAL EDGE OF BERMUDACONTINUOUS CAULK ALONG
PANEL MINIMUM 2"
LAPS WITH CONTINUOUS SUB-FLASHING; 4" END
CAULK
UP VERTICAL LEG AT END OF
CONTINUOUS BEAD OF
FIELD CUT PANEL AND TURN
FASTENERS EVERY 11" O.C. AT
FASTENERS; 20" O.C. MAX.
FASTENERS; 20" O.C. MAX.
FLASHING TIGHT ON TO PANELCONTINUOUS BEAD OFCAULK
FASTENERS; 2 PER PANEL LEG
EQUIPMENT MANUFACTUREFLASHING BY
AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.3. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED
STRENGTH FOR HOLDING POWER OF FASTENERS. (METAL CORRUGATED SHEATHING MAY2. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN
USED OVER OPEN FRAMING (SEE DETAIL BP-84).1. SOLID SHEATHING IS REQUIRED AT THIS CONDITION WHEN THE BERMUDA PANEL IS
BE USED IN LIEU OF PLYWOOD).
BERMUDA PANEL SYSTEM
SQUARE PENETRATIONSECTION B
DATE: 8-15-06
PAGE\FILE
BP-83
SOLID SUBSTRATE AND OPEN FRAMING
BERRIDGEMANUFACTURINGCOMPANY
DATE: 08-15-06
Bermuda Panel SystemPAGE/FILE
BP-90
U.L. 90 CONST. NO. 405BERRIDGE BERMUDA ROOF PANEL
OVER SOLID WOOD SHEATHING
BERMUDA PANEL SYSTEM
BerridgeManufacturingCompany
Roofs of DistinctionBP-90
U.L. 90 CONST. NO. 405BERRIDGE BERMUDA ROOF PANEL
OVER SOLID WOOD SHEATHING
6
2
3
45
1
BERRIDGE BERMUDA ROOF PANEL OVER SOLID WOOD SHEATHING WITH CLIPS
COMPONENTS:
1. BERRIDGE BERMUDA PANEL: 24 GA. (MIN. YIELD 40,000 PSI) COATED STEEL, 11" W X 1" HIGH.
FABRICATED FROM 24 GA. (MIN. YIELD 2. BERMUDA PANEL CLIPS: ONE PIECE,
40,000 PSI) COATED STEEL. LOCATEDAT PANEL LAPS, 2'-0" MAX. SPACING.
3. FASTENERS: USE ONE (1) NO. 10
STEEL SCREW PER CLIP LOCATION.PANCAKE HEAD "TEKS" SCREW
4. DECK: 5/8" APA 40/20 PLYWOOD.
5. JOISTS: 2" X 4" @ 2'-0" O.C. MAX.
CONNECTION AND AT PLYWOOD ENDS.@ 12" O.C. MAX. @ PLYWOOD TO JOISTW/#12 X 2" PAN HEAD WOOD SCREWS
FELT, LAID HORIZONTALLY, EAVE TO 6. FELT PAPER: 1 LAYER # 30 ROOFING
RIDGE.
1
2 3
4
5
6
12
4
5
PAGE\FILE
DATE: 8-15-06