BERMUDA PANEL INSTALLATION DETAILS

35
BERMUDA PANEL INSTALLATION DETAILS BERRIDGE MANUFACTURING COMPANY 800-669-0009 • www.Berridge.com

Transcript of BERMUDA PANEL INSTALLATION DETAILS

Page 1: BERMUDA PANEL INSTALLATION DETAILS

BERMUDA PANELINSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

800-669-0009 • www.Berridge.com

Page 2: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

INDEX

BP-1

DATE: 8-15-06

PAGE\FILE

BP-1BERMUDA PANEL SYSTEM

INDEX

INSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONS

INTRODUCTION TO TYPICAL DETAILSOVERVIEW BP PANEL

EAVE DETAIL; EAVE DETAIL;

RIDGE DETAIL; (SOLID SHEATHING)RIDGE DETAIL; (OPEN FRAMING)

GABLE DETAIL; (SOLID SUBSTRATE)GABLE DETAIL; (OPEN FRAMING)

HEAD WALL; HEAD WALL; (OPEN FRAMING)

RAKE WALL; (SOLID SUBSTRATE)

RAKE WALL; (OPEN FRAMING)

SLOPE TRANSITION WITH FLASHING

BP-1

BPI-1BPI-2BPI-3

BP-4BP-5

BP-10BP-11

BP-20BP-21

BP-30BP-31

BP-40BP-41

BP-50

BP-52

BP-60

INDEX

INSTALLATION INSTRUCTIONS BPI-4

RIDGE DETAIL; (SOLID SUBRATE) BP-22SHED RIDGE DETAIL BP-23

HEAD WALL; (SOLID SUBSTRATE) BP-42

RAKE WALL; (SOLID SUBSTRATE) BP-51

INDEX BP-2

SPLICE PLATE DETAIL (SOLID SHEATHING) BP-6SPLICE PLATE DETAIL (OPEN FRAMING) BP-7

RIDGE TERMINATION AT DORMER VALLEY BP-26

NOMINAL LINEAR EXPANSION BPI-5

RIDGE DETAIL; (SOLID SHEATHING)RIDGE DETAIL; (OPEN FRAMING)

BP-24BP-25

HEAD WALL; WITH PARAPET BP-43

RAKE WALL; STEP FLASHING (SOLID SHEATHING) BP-53

Page 3: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

INDEX

BP-2

DATE: 8-15-06

PAGE\FILE

BP-2 BERMUDA PANEL SYSTEM

U.L. 90 CONST. NO. 405 (SOLID WOOD SHEATHING) BP-90

INDEX

BP-84

BP-82BP-83

BP-81

ROOF PENETRATION; OPEN FRAMING

ROOF PENETRATION; SECTION AROOF PENETRATION; SECTION B

ROOF PENETRATION; SQUARE (PLAN VIEW)ROOF PENETRATION; PIPE PENETRATION BP-80

VALLEY; VALLEY BP-70

BP-71

VALLEY; ISOMETRICVALLEY BP-72

BP-73VALLEY; OPEN FRAMING BP-74

Page 4: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

INSTALLATION INSTRUCTIONS

BPI-1

BE USED AS AN UNDERLAYMENT FOR ALL CORRUGATED DECKS.BERRIDGE MANUFACTURING RECOMMENDS GRACE ICE AND WATERSHIELD OR EQUAL TODUE TO # 30 FELTS TENDENCY TO TEAR WHEN USED OVER CORRUGATED DECKING,

IN "OIL-CANNING" IN PANELS. SUBSTRATE SHOULD BE LEVEL TO 1/4" IN 20'-0".4. USE SHIMS TO KEEP ENTIRE SUBSTRATE EVEN. UNEVEN SUBSTRATE WILL RESULT

REMAIN FLAT UNDER THE WEIGHT OF WORKMEN.3. BLOCKING OR "H" CLIPS SHOULD BE USED ON PLYWOOD IF JOINTS DO NOT

2. ALL END JOINTS SHOULD MEET AT EITHER A JOIST OR RAFTER.

1. SHEATHING END JOINTS SHOULD BE STAGGERED.

ENGINEERING DEPARTMENT FOR USE OF ANY OTHER TYPE OF SOLID SHEATHING.SUFFICIENT HOLDING POWER FOR FASTENERS. CONTACT BERRIDGE MANUFACTURING'Sx 11/16" DEPTH) OR A MINIMUM OF 1/2" PLYWOOD SHEATHING TO PROVIDETHE USES OF EITHER BERRIDGE 24 GA. CORRUGATED METAL (NOMINAL 2-1/2" PITCH

BERRIDGE MANUFACTURING COMPANY RECOMMENDS

PROTECTS THE FINISH DURING FABRICATION AND TRANSIT. THIS FILM MUST BEBERRIDGE PREFINISHED PRODUCTS, PANELS, FLASHINGS, COILS AND FLAT SHEETS

THE STRIPPABLE PLASTIC FILM WHICH IS APPLIED OVER MOST

STRIPPABLE PLASTIC FILM TO ADHERE TO THE METAL PERMANENTLY AND DISCOLOREXPOSURE TO DIRECT SUNLIGHT AND/OR MOISTURE MAY CAUSE THE FACTORY APPLIED

WITH ADEQUATE VENTILATION AND OUT OF DIRECT SUNLIGHT.TO INSTALLATION. KEEP ALL BERRIDGE PREFINISHED MATERIAL IN A DRY LOCATION

CAUTION MUST BE EXERCISED IN STORAGE OF MATERIALS PRIOR

FOR 3 IN 12 SLOPES.GREATER. A DOUBLE LAYER OF 30# FELT UNDERLAYMENT IS RECOMMENDED

PANELS ARE RECOMMENED FOR ROOF SLOPES OF 3 IN 12 OR

PANEL DEPTH OF 1".ROLL FORMER. PANELS ARE FORMED TO A CONSTANT EXPOSURE WIDTH OF 11" AND A

CAN BE FACTORY OR FIELD FABRICATED USING A PORTABLE

REMOVED PRIOR TO INSTALLATION.

THE FINISH.

INSTALLATIONINSTRUCTIONS

B. MINIMUM SLOPE:

C. MATERIAL STORAGE:

A. BERMUDA PANEL SYSTEM:

D. STRIPPABLE FILM:

E. SOLID SHEATHING REQUIREMENTS:

F. SHEATHING INSPECTION:

NOTE: FOR PROJECTS REQUIRING UL 90 ASSEMBLY, REFER TO UL 90 DETAILS.

(30 # FELT UNDERLAYMENT OR EQUAL MUST BE USED OVER ANY SOLID SHEATHING).

5. ALL CUTS AT PENETRATIONS SHOLUD BE TIGHT, WITHOUT GAPS.

6. USE WOOD FRAMED CRICKETS AT LARGE PENETRATIONS.

7. MAKE SURE SUBSTRATE JOINTS ARE TIGHT AT ALL HIPS, VALLEYS AND RIDGES.

REMOVED PRIOR TO INSTALLATION.THIS FILM MUST BE

DIAPHRAGM CAPABILITIES AND PURLIN STABILITY ARE MINIMAL AS PROVIDED BY THEBERMUDA PANEL SYSTEM, THEREFORE OTHER BRACING MAY BE REQUIRED TO CONFORM

G. INSTALLATION OVER OPEN FRAMING;

TO A.I.S.C. OR A.I.S.I. SPECIFICATIONS.

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BPI-1

Page 5: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BPI-2

INSTALLATION INSTRUCTIONS

TOLERANCE OF 1/4" IN 20'-0". UNEVENNESS IN THE TOP PLANE OF THE PURLINS1. PURLINS SHOULD BE ALIGNED WITH TOP FLANGES IN THE SAME PLANE TO A

INSTALLATIONINSTRUCTIONS

H. OPEN FRAMING INSPECTION:

ADEQUATELY BRACED.WILL RESULT IN ABNORMAL "OIL CANNING" OF PANELS. PURLINS SHALL BE

AROUND ROOF PENETRATIONS. DO NOT APPLY PANELS ON OPEN FRAMING AT VALLEYSOR ROOF PENETRATIONS WITHOUT REFERRING TO DETAILS

2. BERRIDGE MANUFACTURING COMPANY REQUIRES SOLID SHEATHING IN VALLEY AND

EXTREME CARE IS NOT USED.ARE DESIGNED FOR AESTHETICS AND CAN BE EASILY DAMAGED OR DEFORMED IF

3. FOOT TRAFFIC ON THE PANELS MUST BE KEPT TO A MINIMUM. ARCHITECTURAL PANELS

A SINGLE LAYER OF NUMBER THIRTY FELT UNDERLAYMENT (OREQUAL) MUST BE APPLIED OVER SOLID SHEATHING AS SHOWN IN THE BERRIDGEMANUFACTURING COMPANY TYPICAL UNDERLAYMENT DETAILS. THE USE OF ADDITIONAL LAYERS OF NUMBER THIRTY FELT IS RECOMMENDED ON LOW-SLOPED ROOFS, AT ALL VALLEY CONDITIONS, AT ROOF PENETRATIONS, AND CERTAIN OTHER FLASHING CONDITIONS AS DEPICTED IN THE BERRIDGE TYPICAL UNDERLAYMENT DETAILS. GRACE ICE AND WATER SHIELD MAY BE

1. DO NOT USE RED ROSIN PAPER UNDER METAL ROOFING PANELS.

3. USE FLAT HEAD GALVANIZED ROOFING NAILS x 1-1/4" LONG WITH BERRIDGE

5. INSTALL FELT PARALLEL TO EAVE (2 LAYERS REQUIRED AT EAVE), STARTING ATEAVE AND USING MINIMUM 6" LAPS. USE TWO LAYERS OF FELT ON ENTIRE ROOFDECK IF ROOF SLOPE IS 3:12 OR LESS. 2 LAYERS REQUIRED AT EAVE REGARDLESS

6. INSULATE BETWEEN WOOD BLOCKING AND METAL WITH FELT OR ICE AND WATER SHIELD.

OF SLOPE.

J. FELT UNDERLAYMENT:

K. FELTING INSTALLATION:

2. SWEEP ROOF AREA CLEAN.

GALVANIZED FELT CAPS.

4. INSTALL VALLEY FELT FIRST.

1. STRIKE A LINE THE FULL LENGTH OF THE FASCIA OR RAKE. IF NOT STRAIGHT,CORRECT WITH SHIMS.

2. MAKE SURE FASCIA/RAKE IS FLUSH WITH SHEATHING.

I. FASCIA/RAKE INSPECTION:

REQUIRED ON LOW SLOPED ROOFS OR AT CERTAIN FLASHING CONDITIONS.

7. REFER TO UNDERLAYMENT DETAILS. WHEN VALLEYS OR ROOFPENETRATIONS ARE INVOLVED ON OPEN FRAMING CONDITIONS.

1. PANELS OVER 30'-0" LONG REQUIRE EXPANSION JOINTS SEE DETAIL BP-6 AND BP-7.

PANELS TO DISENGAGE FROM THE FLASHING, ALLOW OIL-CANNING IN PANEL AND/ORTHERMAL MOVEMENT OF THE PANELS. IMPROPERLY DESIGNED FLASHING CAN ALLOWAND PANELS. PLEASE REFER TO THE CHART ON PAGE BPI-5 TO DETERMINE ANTICIPATEDFEET IN LENGTH CAN BE A FACTOR IN THE DESIGN AND INSTALLATION OF FLASHING

EXPANSION AND CONTRACTION OF PANELS WHICH EXCEED THIRTYL. THERMAL MOVEMENT:

CAUSE FLASHING TO WORK LOOSE FROM ITS ANCHORAGE.

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BPI-2

Page 6: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

INSTALLATION INSTRUCTIONS

BPI-3

INSTALLATIONINSTRUCTIONS

AVOID ALLOWING FLASHING AND PANELS TO COME INTO CONTACT WITHEITHER LEAD OR COPPER, AND PREVENT EXPOSURE TO WATER RUNDOWN FROM

IF BERRIDGE MANUFACTURING COMPANY IS TO SUPPLY FLASHING, ALLFLASHINGS WILL BE FABRICATED IN 10'-0" LENGTHS WITH SQUARE END CUTS ONLY.THE PURCHASER MUST PROVIDE ALL DIMENSIONS AND DEGREE OF ANGLES.

M. ELECTROLYSIS:

COPPER AND/OR LEAD.

N. FLASHING:

1. REMOVE STRIPPABLE PLASTIC FILM FROM ALL FLASHINGS PRIOR TO INSTALLATION.

2. ALWAYS STAGGER JOINTS WHEN ONE FLASHING IS INSTALLED OVER OTHER FLASHINGS.

3. INSTALL ALL FLASHINGS AS PER BERRIDGE TYPICAL DETAILS.

4. ALL FLASHINGS ARE TO BE DESIGNED AND INSTALLED TO NOT TRAP WATER.

BERRIDGE MANUFACTURING COMPANY WILL PROVIDE SQUARE END CUTS ONLYON ALL BERMUDA PANELS. COMPUTATION OF ALL QUANTITIES AND DIMENSIONS ARE THE

2. REMOVE STRIPPABLE PLASTIC FILM FROM EACH PANEL PRIOR TO INSTALLATION.

3. START AT EAVE WITH PANEL AND WORK TOWARD THE RIDGE. PANEL END CUTS NEED

4. KEEP PANELS ALIGNED SO THAT PANELS MATCH AT HIPS AND VALLEYS. DO NOTINSTALL LONG CONTINUOUS RUNS OF PANELS ALL AT ONE TIME WHERE PANEL LINESMUST MATCH. INSTALL TEN TO TWELVE PANELS IN ONE ELEVATION AND THEN FOLLOWWITH A LIKE NUMBER OF PANELS ON THE OTHER ELEVATION. WHEN YOU INSTALL

5. INSTALL CLIPS AS PER CLIP INSTALLATION NOTES.

6. EACH PANEL IS TO BE KEPT TIGHT AGAINST THE ADJOINING PANEL. NEVER PERMITA GAP BETWEEN THE MALE/FEMALE JOINT ANY CRIMPS IN MALE LEG MUST BESTRAIGHTENED (TOTALLY STRAIGHT WITH OUT ANY BENDS, CRIMPS, CREASES, ETC.)PRIOR TO PANEL INSTALLATION.

P. PANELS:

RESPONSIBILITY OF THE PURCHASER.

Q. PANEL INSTALLATION:

TO BE ACCURATE WHEN USING THE VINYLWEATHERSEAL.

TREMCO, INC. "SPECTREM 1" SILICONE SEALANT.O. SEALENT RECOMMENDATIONS:

1. INSTALL STARTER STRIP CONTINUOUS AT EAVE.

PANELS IN THIS MANNER, YOU WILL BE ABLE TO MAKE ANY ADJUSTMENTS REQUIRED TO INSURE PANEL MATCHING.

DO NOTDO NOT

MUST MUST

FINISHES. DO NOT MIX LOTS.EFFECT OF THE PIGMENTS IN THE FINISH.WILL APPEAR, FROM A DISTANCE, A DIFFERENT SHADE DUE TO THE GRANULARPANEL IS REVERSED (ARROWS POINTING OPPOSITE OF THOSE ON OTHER PANELS) ITTHE ARROWS ON EVERY PANEL ARE ALL POINTING IN THE SAME DIRECTION. IF APANEL. ALL PANELS MUST BE INSTALLED IN A CONSISTENT MANNER, MEANING THATINSTALLATION: NOTE THE SERIES OF ARROWS PAINTED ON THE UNDERSIDE OF THE

7. COPPER-COTE, CHAMPAGNE, LEAD-COTE, AND PREWEATHERED GALVALUME PANELTM

METALLIC FINISHES ARE MATCH - LOT

TM R

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BPI-3

Page 7: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BPI-4

INSTALLATION INSTRUCTIONS

INSTALLATIONINSTRUCTIONS

MAKE SURE ALL FASTENERS ARE DRIVEN STRAIGHT AND SET FLAT. DO NOT OVERDRIVE

INSTALL FASTENERS AS PER TYPICAL DETAILS. USE 11 GAUGE 1-1/4"GALVANIZED ROOFING NAILS FOR INSTALLATION OVER WOOD SHEATHING AND USE #10PANCAKE HEAD TEKS FASTENERS (ZINC-PLATED SCREW WITH PHILLIPS INSERT, ASMADE BY CONSTRUCTION FASTENERS CO.) FOR INSTALLATION TO METAL. WHEN USINGPOP RIVETS ON FLASHING, STAINLESS STEEL RIVETS ARE RECOMMENDED TO AVOID RUST

FASTENERS, AS THIS WILL CAUSE THE CLIP AND/OR FLASHINGS TO BUCKLE OR BECOMERECESSED BELOW THE ELEVATION OF THE SUBSTRATE.

S. FASTENERS:

RUST STAINS.

**

NOTE: IF LOCAL CODES OR OTHER REGULATIONS DICTATE SPECIFIC WIND UPLIFTREQUIREMENTS, CONSULT THE BERRIDGE ENGINEERING DEPARTMENT, AS IT MAYBE NECESSARY TO USE A DIFFERENT CLIP SPACING OR FASTENER.

*

1. INSTALL CLIPS AS PER DETAILS.

2. CLIP SPACING ON SOLID SHEATHING NOT TO EXCEED 20" ON CENTER.

R. CLIP INSTALLATION:

3. WHEN INSTALLING PANEL OVER OPEN FRAMING, USE CLIPS ALONG EVERY PURLINAT 20" ON CENTER MAXIMUM.

*

*

USE OF ANY OTHER TYPE OF FASTENER.NOTE: CONSULT BERRIDGE MANFACTURING'S ENGINEERING DEPARTMENT REGARDING THE**

BERRIDGE MANUFACTURING COMPANY STRIVES TO PROVIDE ITS CUSTOMERS WITH THEHIGHEST QUALITY STRETCHER LEVELED STEEL AVAILABLE. THE LATEST TECHNOLOGY ISALSO INCORPORATED IN BERRIDGE'S HIGH-PRECISION COIL HANDLING AND ROLL FORMINGEQUIPMENT TO MINIMIZE THE STRESS ON METAL DURING PRODUCTION. FURTHERMORE,BERRIDGE UTILIZES HEAVIER 24 GAUGE METAL RATHER THAN 26 GAUGE STEEL OR LIGHTGAUGE ALUMINUM AS OFFERED BY MANY COMPETITORS. ALL THESE MEASURES HAVE BEENTAKEN TO MINIMIZE THE AMOUNT OF "OIL-CANNING" (WAVINESS) WHICH IS NATURALLYINHERENT IN FLAT SHEET METAL. MANY TIMES, HOWEVER, THE CAUSE OF WAVINESS OR"OIL-CANNING" CAN BE TRACED TO UNEVEN SHEATHING, IMPROPER FELT INSTALLATION,IMPROPER HANDLING, OR FOOT TRAFFIC ON THE PANELS.

ALL ARCHITECTURAL PANELS REQUIRE CARE IN HANDLING AND INSTALLATION TO AVOID

THESE INSTALLATION INSTRUCTIONS AND THE FOLLOWING TYPICAL DETAILS ARE INTENDEDTO PROVIDE OUR CUSTOMERS WITH THE INFORMATION REQUIRED FOR AN AESTHETICALLYPLEASING AND FUNCTIONAL INSTALLATION OF THE BERRIDGE BERMUDA PANEL SYSTEM.

WITHOUT NOTICE. FOR SPECIFIC PROJECT DETAILS, CONTACT BERRIDGE.NOTE: ALL PRODUCTS, SPECIFICATIONS, DETAILS, AND INSTRUCTIONS SUBJECT TO CHANGE

DAMAGING OR DEFORMING THE PANELS.

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BPI-4

Page 8: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

INSTALLATION INSTRUCTIONS

BPI-5

DATE: 10-30-17

Page 9: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-4

INTRODUCTION TO TYPICAL DETAILS

THE DETAILS CONTAINED IN THE FOLLOWING PAGES ARE MERELY RECOMMENDATIONS ASTO HOW BERRIDGE MANUFACTURING MATERIALS SHOULD BE INSTALLED. THEY MAY REQUIREADAPTATIONS OR MODIFICATIONS FOR A SPECIFIC PROJECT AS CONDITIONS VARY IN BOTHBUILDING DESIGN AND LOCAL WEATHER PECULIARITIES.

BERRIDGE MANUFACTURING COMPANY SHALL BE HELD HARMLESS FROM ANY AND ALLCLAIMS ARISING FROM LACK OF WATERTIGHTNESS AS A RESULT OF FOLLOWING THESERECOMMENDED DETAILS. ENSURING WATERTIGHTNESS ON ANY GIVEN PROJECT IS THEFUNCTION OF THE INSTALLER. THE ARCHITECT/GENERAL CONTRACTOR/INSTALLER MUSTACCEPT THE RESPONSIBILITY TO ADAPT THESE DETAILS TO MEET PARTICULAR BUILDINGREQUIREMENTS AND TO ASSURE ADEQUATE WATERTIGHTNESS.

THE INSTALLER CAN VIRTUALLY ASSURE WATERTIGHTNESS IF THESE FLASHING DETAILSHAVE BEEN PROPERLY ADAPTED, ADEQUATE LAPS HAVE BEEN PROVIDED, CORRECT TYPEOF SEALANT USED, ALL JOINTS ADEQUATELY CAULKED, AND PROFESSIONAL WORKMANSHIPEMPLOYED.

TYPICAL DETAILSINTRODUCTION TO

BERMUDA PANEL SYSTEM BP-4

PAGE\FILE

DATE: 8-15-06

Page 10: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-5

PANEL OVERVIEW

ANCHOR CLIP

BERMUDA ROOF PANEL

1"

WEATHERSEALOPTIONAL VINYL

11" E

XPOSU

RE

BERMUDA ROOF PANEL

CLIPS 20" O.C.

CLIPS 20" O.C.

BP-5

CLIPS 20" O.C.

PANEL OVERVIEWDATE: 8-15-06

PAGE\FILE

BERMUDA PANEL SYSTEM

Page 11: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-6

SPLICE PLATE DETAILSOLID SHEATHING

SPLICE PLATE DETAILDATE: 8-15-06

PAGE\FILE

BERMUDA PANEL SYSTEM

SOLID SHEATHING

BP-6

ON PAGE BPI-5

# 30 FELT UNDERLAYMENT

ANCHOR CLIP 4" O.C.AT SPLICE PLATE

SOLID SHEATHING

LINEAR EXPANSION CHARTREFER TO NOMINAL

OF CAULK ALONG EACH SIDEAPPLY 2 CONTINUOUS BEADS

BETWEEN SPLICE PLATE ANDBERMUDA ROOF PANELS

BERRIDGEBERMUDA ROOF PANEL

SPLICE PLATE FOREXPANSION AND

PATTERN

STAGGER JOINTS IN A

FLAT BEAD OF CAULK

BERMUDA PANELS

CONTRACTION OF PANELS

DIAGONAL OR STRAIGHTRANDOM PATTERN, NOT A

BETWEEN SPLICE PLATE &

OVER 30'-0" LONG

RIVETS TO BE PLACED SO THAT

ANCHOR CLIP 20" O.C. MAX.

POP RIVET 4" O.C.

THEY ARE "NOT EXPOSED".

BERMUDA ROOF PANEL

ROOF SPLICE PLATE

24 GA. FURRING SECTION12" LONG

BERRIDGE

FASTENERS 4" O.C.

Page 12: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-10

EAVE DETAIL

CONTINUOUS STARTER STRIPALIGN WITH EAVE FLASHING

BERRIDGE BERMUDA PANEL

LAPS WITH CONTINUOUS EAVE FLASHING 4" END

FASTENERS 20" O.C. MAX.

# 30 FELT

EAVE FLASHING STARTER STRIP

F = FINISH SIDE

F

EAVE DETAILDATE: 8-15-06PAGE\FILE

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.

FURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BE

OF THE ARCHITECT.

SOLID SHEATHING

CAULK AT LAPS

UNDERLAYMENT

F

BP-10BERMUDA PANEL SYSTEM

3/8"

1/8"

1 3/4"

1/2"

1/2"

Page 13: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-11

EAVE DETAIL

CONTINUOUS STARTER STRIPALIGN WITH EAVE FLASHING

BERRIDGE BERMUDA PANEL

LAPS WITH CONTINUOUS EAVE FLASHING 4" END FASTENERS 20" O.C. MAX.

BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.1. ALL CAULKING AND FASTENERS ARE ITEMS TO BE FURNISHED AND INSTALLED

EAVE STRUTCAULK AT LAPS

FASCIA PANELBERRIDGE WALL PANEL OR

STARTER STRIP

F

F = FINISH SIDE

EAVE FLASHING

1/2" 1/8"

3/8"

F

1/2"

1 3/4"

EAVE DETAIL

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BP-11

Page 14: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-20

RIDGE DETAILSOLID SHEATHING

RIDGE FLASHING

F

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT

IN STRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BE

FURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION

F = FINISH SIDE

BERMUDA PANEL SYSTEM

RIDGE DETAIL DATE: 8-15-06PAGE\FILE

BP-20

OF THE ARCHITECT.

F

ZEE CLOSURE

FASTENER 20" O.C. MAX.

SOLID SHEATHING

CONTINUOUS CAULK AT LAPSZEE CLOSURE 4" END LAPS WITH

CLOSURE 40" O.C., AND AT LAPS.AT LAPS, POP RIVET TO ZEELAPS WITH CONTINUOUS CAULKRIDGE FLASHING 4" END

BERRIDGE BERMUDA PANEL

CAULK RIVET HEADS

# 30 FELT UNDERLAYMENT

OF CAULKCONTINUOUS BEAD

SOLID SHEATHING

1/2" 1/2"

1" 1"

1 1/8"

OPEN HEM

Page 15: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-22

RIDGE DETAILSOLID SUBSTRATE

RIDGE FLASHING

F

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING AND FASTENERS ARE ITEMS TO BEFURNISHED AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION

F = FINISH SIDE

1/2" 1/2"

OF THE ARCHITECT.

BERMUDA PANEL SYSTEM

RIDGE DETAILSOLID SUBSTRATE

DATE: 8-15-06

PAGE\FILE

BP-22

SOLID SHEATHING

# 30 FELTUNDERLAYMENT

AT LAPS, POP RIVET TO BERMUDA

CONTINUOUS BEADOF CAULK

PANEL 40" O.C., AND AT LAPS.CAULK RIVET HEADS

LAPS WITH CONTINUOUS CAULKRIDGE FLASHING 4" END

BERRIDGE BERMUDA PANEL

FASTENER 20" O.C. MAX.

Page 16: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-23

SHED ROOF RIDGE CAP DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

RIDGE CAP

OPEN HEM

BARRIDGE BERMUDA PANEL

4" END LAP WITH

CAULK AT LAPS, POP RIVET TO ZEE CLOSURERIDGE CAP; 4" END LAPS WITH CONTINUOUS

ZEE CLOSURE

AT 40" O.C. MAX. CAULK RIVET HEADS

F = FINISH SIDE

ZEE CLOSURE

SOLID SHEATHINGUNDERLAYMENT

MAX. CAULKFASTENERS; 40" O.C.

FASTENERS; 20" O.C. MAX.

LAP FELT OVER RIDGE

CAULKCONTINUOUS BEAD OF

# 30 FELT

FASTENER HEAD

CONTINUOUS CAULKAT LAPS

BERMUDA PANEL SYSTEM

SHED ROOF RIDGEDATE: 8-15-06

PAGE\FILE

BP-23

1" 1"

1/2"F

F

1/2"

CAP DETAIL

1 1/8"

Page 17: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-24

HIP DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELTING UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

BERRIDGE BERMUDA PANEL

COURSE OF PANEL (SEE BELOW)HIP CAP; INSTALL WITH EACH

SOLID SHEATHING

# 30 FELT UNDERLAYMENT

HIP DETAIL DATE: 8-15-06PAGE\FILEBP-24BERMUDA PANEL SYSTEM

LINE OF HIP

HIP CAPNAIL EACH SIDE OF

BERRIDGE BERMUDA PANEL

HIP CAP; INSTALL WITH EACHCOURSE OF PANEL

ABOVE HIP CAP, FIELD CUT

UNDER HIP CAPBERRIDGE BERMUDA PANEL

TO ALIGN WITH LINE OF HIP 3/4"

Page 18: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-26

RIDGE TERMINATION AT DORMER VALLEY

DATE: 8-15-06

PAGE\FILE

BP-26BERMUDA PANEL SYSTEM

SECTION VIEW

FIELD FORM END OF RIDGE FLASHINGAND EXTEND UNDER CONTINUOUS CLEAT

RIDGE FLASHING; 4" END LAPSWITH CONTINUOUS CAULK AT LAPS

BP-20

FIELD TAPERED ZEE CLOSURE

CONTINUOUS CLEAT;

BERRIDGE BERMUDA PANEL

FASTENERS; 20" O.C. MAX.

# 30 FELTUNDERLAYMENT

PLACE A DAB OF CAULK

PLAN VIEW

PANELSMAIN ROOF

RIDGE FLASHING

CONTINUOUS CLEAT

VALLEY FLASHING

DORMER PANEL

WITH CONTINUOUS CAULK UNDERZEE CLOSURE

DO NOT CAULK ONOR UNDER CLEAT

RIDGE TERMINATIONAT DORMER VALLEY

SOLID SHEATHINGVALLEY FLASHING; 12" LAPS WITHCONTINUOUS CAULK AT LAPS

AT FASTENER LOCATIONDRIVE FASTENER ANDCAULK FASTENER HEAD

SLOPE SLOPE

SLO

PE

Page 19: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-30

GABLE DETAILSOLID SUBSTRATE

3/4"

1 1/8"

1/2"

4 1/4"

F

4"

1/2"

F

SPECIAL CHANNEL CLOSURE GABLE FLASHING

FASTENERS; 20" O.C.MAX. STAGGERED

SOLID SHEATHING

FASTENERS; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

BERRIDGE BERMUDA PANEL

4" END LAPS WITHCONTINUOUS CAULK AT LAPS

CONTINUOUS BEADS OF CAULK

GABLE FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

F = FINISH SIDE

BERMUDA PANEL SYSTEM

GABLE DETAILSOLID SUBSTRATE

DATE: 8-15-06PAGE\FILE

BP-30

PLACE A DAB OF CAULKAT FASTENERS LOCATION,DRIVE FASTENER, ANDCAULK FASTENER HEADS

TOP LAYER OF FELT TOBE PARALLEL WITH ROOFSLOPESPECIAL CHANNEL CLOSURE

Page 20: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-40

HEAD WALL DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

OPEN HEM

COUNTER FLASHING SUB-FLASHING

F

BERRIDGE BERMUDA PANEL

# 30 FELT UNDERLAYMENT

CONTINUOUS CAULK AT LAPS.SUB-FLASHING; 4" END LAPS WITH

POP RIVET TO ZEE CLOSURE 40" O.C. MAX.AND AT LAPS. CAULK RIVET HEADS.

WITH CONTINUOUS CAULK AT LAPS.COUNTER FLASHING; 4" END LAPS

ZEE CLOSURE

F = FINISH SIDE

F

20" O.C. MAX.FASTENERS;

SOLID SHEATHING

OF CAULKCONTINUOUS BEAD

1" 1"

1 1/8"

CONTINUOUS CAULK AT LAPS.ZEE CLOSURE; 4" END LAPS WITH

# 30 FELT

BERIDGE WALL ORFASCIA PANEL

CHANNEL CLOSURE; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS.

20" O.C. MAX.FASTENERS;

UNDERLAYMENT

CHANNEL CLOSURE

F

HEAD WALL DETAIL DATE: 8-15-06

PAGE\FILE

BP-40BERMUDA PANEL SYSTEM

1/2"

Page 21: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-42

HEAD WALL DETAILSOLID SUBSTRATE

BERMUDA PANEL SYSTEM

HEAD WALL DETAILSOLID SUBSTRATE

DATE: 8-15-06

PAGE\FILE

BP-42

1/2"

1" 1"

1 1/8"

1/2"

OPEN HEM

COUNTER FLASHING ZEE CLOSURE

F

F

F = FINISH SIDE

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

FASTENERS; 20" O.C.

CONTINUOUS BEAD OFCAULK BETWEEN ZEECLOSURE AND BERMUDAPANEL

FASTENERS; 20" O.C.MAX.

SOLID SHEATHING

MAX.

# 30 FELT UNDERLAYMENT

COUNTER FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS. POP RIVETTO ZEE CLOSURE 40" O.C. AND AT LAPS.

BERRIDGE BERMUDA PANEL

SUB-FLASHING

SUB-FLASHING;

CONTINUOUS BEAD OF CAULK AT REGLET

REGLET FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS.

ZEE CLOSURE; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS.

WITH CONTINUOUS 4" END LAPS

CAULK AT LAPS

F

REGLET FLASHING

CAULK RIVET HEADS.

Page 22: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-43

PARAPET DETAIL

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS.1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

OPEN HEM

COUNTERFLASHING SUB-FLASHING

F

BERRIDGE BERMUDA PANEL

# 30 FELT UNDERLAYMENT

CONTINUOUS CAULK AT LAPS.SUB-FLASHING; 4" END LAPS WITH

POP RIVET TO ZEE CLOSURE 40" O.C. MAX. AND AT LAPS. CAULK RIVET HEADS.

WITH CONTINUOUS CAULK AT LAPS.COUNTERFLASHING; 4" END LAPS

FASTENERS; 20" O.C. MAX.

O.C. MAX. CAULK ALL RIVET HEADS.POP RIVET TO COUNTER FLASHING 40"WITH CONTINUOUS CAULK AT LAPS.CAP FLASHING; 4" END LAPS

CAP FLASHING

F

ZEE CLOSURE

F = FINISH SIDE

F

20" O.C. Max.FASTENERS;

SOLID SHEATHING

OF CAULKCONTINUOUS BEAD

O.C. MAX. CAULK

CAULK FASTENER

FASTENERS; 40"

UNDERLAYMENT# 30 FELT

20" O.C. ANDSTAGGERED;LAPS ANDFASTENERS AT

HEADS

1 ON 121" 1"

1 1/8"

FASTENER HEADS

1 ON 12

CONTINUOUS CAULK AT LAPS.ZEE CLOSURE; 4" END LAPS WITH

PARAPET DETAILDATE: 8-15-06

PAGE\FILE

BP-43 BERMUDA PANEL SYSTEM

1/2"

Page 23: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-50

RAKE WALL DETAIL COUNTER FLASHING SOLID SUBSTRATE

COUNTERFLASHING CLOSURE CHANNEL

F = FINISH SIDE

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

# 30 FELT UNDERLAYMENT

FASTENERS; 20" O.C. MAX.

CLOSURE CHANNEL; 4" ENDLAPS WITH CONTINUOUSCAULK AT LAPS

CONTINUOUS BEAD OF CAULK

SUB-FLASHING; 4" END LAPS

AT LAPSWITH CONTINUOUS CAULK

SOLID SHEATHING

FASTENERS; 20" O.C. MAX.

BERRIDGE WALL OR FASCIA PANEL

COUNTERFLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS

BERRIDGE BERMUDAPANEL

# 30 FELTUNDERLAYMENT; TOPLAYER TO BEPARALLEL WITHROOF SLOPE

SUB-FLASHING

OPEN HEM

4"

1 1/

8"

3/4"

F F

BERMUDA PANEL SYSTEM

RAKE WALL DETAILCOUNTERFLASHINGSOLID SUBSTRATE

DATE: 8-15-06

PAGE\FILE

BP-50

Page 24: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-51

RAKE WALL DETAIL COUNTER FLASHING SOLID SUBSTRATE

COUNTERFLASHING CLOSURE CHANNEL

F = FINISH SIDE

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

# 30 FELT UNDERLAYMENT

FASTENERS; 20" O.C. MAX.

CLOSURE CHANNEL; 4" ENDLAPS WITH CONTINUOUSCAULK AT LAPS

CONTINUOUS BEAD OF CAULK

SUB-FLASHING; 4" END LAPS

AT LAPSWITH CONTINUOUS CAULK

SOLID SHEATHING

FASTENERS; 20" O.C. MAX.

CONTINUOUS CAULK AT REGLET

COUNTERFLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS

BERRIDGE BERMUDAPANEL

# 30 FELTUNDERLAYMENT(TOP LAYER MUSTBE PARALLELWITH ROOF SLOPE

SUB-FLASHING

OPEN

4"

1 1/

8"

3/4"

F

F

REGLETFLASHING

F1/2"

CONTINUOUS CAULK AT LAPSREGLETFLASHING; 4" END LAPS WITH

CONTINUOUS BEAD OF CAULK

REGLET

HEM

BERMUDA PANEL SYSTEM

RAKE WALL DETAILCOUNTERFLASHINGSOLID SUBSTRATE

DATE: 8-15-06

PAGE\FILE

BP-51

Page 25: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-53

RAKE WALL DETAILSTEP FLASHING

SOLID SUBSTRATE

STEP FLASHING

F = FINISH SIDE

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

BERRIDGE WALL OR FASCIA PANEL

STEP FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS, SET

BERRIDGE BERMUDA PANEL;

# 30 FELTUNDERLAYMENT; TOP LAYER TO BEPARALLEL WITHROOF SLOPE

SUB-FLASHING

F

LOCATION OF MALE/FEMALE JOINT

CAULK AT LAPS

PANELVERTICAL EDGE OF BERMUDACONTINUOUS CAULK ALONG

PANEL MINIMUM 2"

LAPS WITH CONTINUOUS SUB-FLASHING; 4" END

CAULK

UP VERTICAL LEG AT END OF

CONTINUOUS BEAD OF

FIELD CUT PANEL AND TURN

FASTENERS EVERY 11" O.C. AT

FASTENERS; 20" O.C. MAX.

FASTENERS; 20" O.C. MAX.

DRIP FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS

FLASHING TIGHT ON TO PANEL

DRIP FLASHING

F

CONTINUOUS BEAD OFCAULK

FASTENERS; 2 PER PANEL LEG

# 30 FELT UNDERLAYMENT

BERMUDA PANEL SYSTEM

RAKE WALL DETAILSTEP FLASHING

SOLID SUBSTRATE

DATE: 8-15-06

PAGE\FILE

BP-53

Page 26: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-60

SLOPE TRANSITION DETAIL SOLID SUBSTRATE

BERMUDA PANEL SYSTEM

SLOPE TRANSITION DETAILSOLID SUBSTRATE

DATE: 8-15-06

PAGE\FILE

BP-60

1/2"

1" 1"

1 1/8"

OPEN

SLOPE TRANSITION ZEE CLOSURE

F

F

F = FINISH SIDE

1. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

SUB-FLASHING

1/2"

STARTER STRIP

1/8"F

3/8"

1 3/4"

FLASHING

BERRIDGE BERMUDA PANEL

CONTINUOUS STARTER STRIP

ZEE CLOSURE; 4" END LAPS WITH

FASTENERS; 20" O.C.

# 30 FELT UNDERLAYMENT

MAX.

CONTINUOUS BEAD OF

CONTINUOUS CAULK AT LAPS.

CAULK

SLOPE

SLOPE TRANSITION FLASHING; 4" END LAPS WITH

CAULK RIVET HEADS.

CONTINUOUS CAULK AT LAPS. POP RIVETTO ZEE CLOSURE 40" O.C. AND AT LAPS.

# 30 FELT

BERRIDGE BERMUDA PANEL

SOLID SHEATHING

SUB-FLASHING;

WITH CONTINUOUS CAULK AT LAPS

4" END LAPS

FASTENERS;

UNDERLAYMENT

20" O.C. MAX.

HEM

Page 27: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-70

VALLEY DETAIL

1. SOLID SHEATHING (BY OTHERS) TO BE A MINIMUM OF 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

CONTINUOUS BEAD OF CAULK

# 30 FELT

VALLEY DETAIL

UNDERLAYMENT

DATE: 8-15-06PAGE\FILE

BP-70BERMUDA PANEL SYSTEM

SOLID SHEATHING; MUST BE USEDAT ALL VALLEYS SEE DETAIL BP-74

BUTT AND LAP UNDER OPPOSITE PANELBERMUDA PANEL FIELD CUT OFF2 BEADS CONTINUOUS CAULK AT LAPS,

VALLEY FLASHING; 12" END LAPS WITH

VALLEY LEGS MIN. 21" EACH SIDE.

TO VALLEY ANGLEFIELD FABRICATED BREAK

SPECIAL VALLEY CAP;

BUTT AND LAP UNDER OPPOSITE BERMUDA PANEL FIELD CUT OFF

PANEL LAP AS PER BP-71PANEL CONTINUOUS CAULK AT

BERRIDGE BERMUDA PANEL

BEFORE VALLEY CAP.TO BUTT END OF PANEL

1" X 1" ANGLE FASTEN

BERRIDGE BERMUDA PANEL

SPECIAL VALLEY CAP; PLACE INTOFEMALE LOCK OF PANEL ABOVE AND FASTENTO BUTT OF PANELS BEING COVERED

1'-6" MIN

Page 28: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-71

VALLEY DETAILDATE: 8-15-06

PAGE\FILE

BP-71 BERMUDA PANEL SYSTEM

VALLEY DETAIL

BERMUDA PANEL FIELD CUT AND LAP PANELS AT VALLEYCONTINUOUS CAULK AT LAPS

FIELD FORM PANEL TO VALLEY

NOTE; REFER TO BP-70 FOR VALLEY DETAIL

Page 29: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-72

VALLEY DETAIL DATE: 8-15-06

PAGE\FILE

BP-72BERMUDA PANEL SYSTEM

1. SOLID SHEATHING (BY OTHERS) TO BE A MINIMUM OF 1/2" PLYWOOD OR EQUIVALENTIN STRENGTH FOR HOLDING POWER OF FASTENERS.

2. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

# 30 FELT

BERRIDGE BERMUDA PANEL

SPECIAL CHANNEL CLOSURE;

VALLEY DETAIL

UNDERLAYMENT

SOLID SHEATHING; MUST BE USEDAT ALL VALLEYS SEE DETAIL BP-74

SET TIGHT UP TO VALLEY FLASHING

2 BEADS CONTINUOUS CAULK AT LAPS,VALLEY FLASHING; 12" END LAPS WITH

FASTEN UNDER LAPS ONLY

DO NOT USE FASTENERS AT SPECIAL CHANNEL CLOSURE

CONTINUOUS BEAD OF CAULK BETWEEN VALLEY FLASHINGAND FELT UNDERLAYMENT

ANCHOR CLIP (18" O.C. MAX.)

NOTE: DO NOT USE ANY FASTENERS THROUGH THE VALLEY FLASHING, EXCEPTAT LAPS (SEE DETAIL BP-73)

F = FINISH SIDE

F

F

SPECIAL CHANNEL CLOSURE

VALLEY FLASHING

19 1/4"

3/8"

1 1/8"

3/8"

4"

3/4"

1 1/8"

Page 30: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-73

VALLEY DETAILISOMETRICDATE: 8-15-06

PAGE\FILE

BP-73 BERMUDA PANEL SYSTEM

VALLEY DETAIL

2 CONTINUOUS BEADS OF CAULK AT LAPSANCHOR CLIP

F = FINISH SIDE

F

ONLY AT TOP OF FLASHING

TOP (OVERLAPPING) VALLEYARE TO BE EXPOSED ONUNDER LAP, NO FASTENERS

FASTEN THROUGH VALLEY

VALLEY FLASHING LAP

12" LAP

CLOSURESPECIAL CHANNEL

CONTINUOUS BEAD OF CAULKVALLEY FLASHING# 30 FELT UNDERLAYMENT

SOLID SHEATHING; MUST BE USED

BERRIDGE BERMUDA PANEL

ISOMETRIC

AT VALLEY SEE DETAIL BP-74

OPEN HEM

ANCHOR CLIP

Page 31: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-80

PIPE PENETRATION OPEN FRAMING AND SOLID SUBSTRATE

CUT PANEL 1" SMALLER THANPENETRATION, BACK CUT TABS,FOLD TABS UP AROUNDPENETRATION, AND CAULK.

1. CUT HOLE TO ALLOW FOR THERMAL MOVEMENT IF PANELS ARE 30'-0" OR LONGER.

# 30 FELT UNDERLAYMENT

BERRIDGE BERMUDAPANEL

PIPE PENETRATION TOBE IN PAN OF PANEL ONLY

RUBBERIZED "BOOT"FLASHING

ROOF PIPE PENETRATIONOF 4" DIA. OR LESS

CONTINUOUS CAULK OR

SET RUBBERIZED BOOTINTO CONTINUOUS BEADOF CAULK. USE FASTENERSAS SPECIFIED BY BOOTMANUFACTURER. CAULK

2. IF PIPE IS MADE OF METAL, IT MUST BE PAINTED TO PREVENT RUST RUN-OFFFROM STAINING PANELS.

FASTENER HEADS.

SOLID SHEATHING

PIPE PENETRATIONOPEN FRAMING AND SOLID SUBSTRATE

3. POSITION SQUARE BASED BOOTS IN A DIAMOND ORIENTATION WHERE POSSIBLE TOAID IN DIVERTING WATER.

STAINLESS STEEL HOSECLAMP

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BP-80

Page 32: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-81

ROOF PENETRATION RECTANGULAR/SQUARE

BERRIDGE BERMUDA PANELAROUND PENETRATIONFIELD CUT TO FIT TIGHTNOTE: PANELS ARE TO BE

FLASHING, FROM BP-82VERTICAL LEG OF COUNTER

TURN CORNER WITH

TURN CORNER WITH VERTICAL LEG OF STEP FLASHING,FROM BP-83

# 30 FELT UNDERLAYMENTWRAP CURB WITH

AND SUB FLASHING

BP-83 UNDER FLASHINGCARRY STEP FLASHING FROM

FROM BP-82

BP-83

BP-82

VERTICAL LEG OF FLASHINGFROM BP-82

TURN CORNER WITH

VERTICAL LEG OF STEP FLASHING,FROM BP-83

TURN CORNER WITH

VERTICAL LEG TO FORMTIGHT TO PANEL, 4" LAP

FIELD FORM STEP FLASHING

WITH CONTINUOUS CAULKAT LAPS

BERRIDGE BERMUDA PANEL

CONTINUOUS CAULKAT ALL FLASHING LAPS

SLO

PE

ROOF PENETRATIONRECTANGULAR/SQUARE

DATE: 8-15-06

PAGE\FILE

BP-81 BERMUDA PANEL SYSYEM

Page 33: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-82

SQUARE PENETRATION SECTION A

SOLID SUBSTRATE AND OPEN FRAMING

1. SOLID SHEATHING IS REQUIRED AT THIS CONDITION WHEN THE BERMUDA PANEL ISUSED OVER OPEN FRAMING (SEE DETAIL BP-84).

2. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT INSTRENGTH FOR HOLDING POWER OF FASTENERS. (METAL CORRUGATED SHEATHING MAYBE USED IN LIEU OF PLYWOOD).

3. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHEDAND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.

COUNTERFLASHING & FLASHING

F

F = FINISH SIDE

ANCHOR CLIP; 20" O.C. MAX.

# 30 FELT UNDERLAYMENT

POP RIVET TO PANEL20" O.C. MAX.

ANCHOR CLIP; 20" O.C. MAX.

COUNTERFLASHING

OF CAULK

WITH CONTINUOUS CAULK AT LAPSSUB FLASHING; 4" END LAPS

BERRIDGE BERMUDA PANEL; FORM TO CURB

UNDERLAYMENT

CURB MATERIAL

CONTINUOUS BEAD

BERRIDGE BERMUDA PANEL;FORM TO CURB

# 30 FELT

20" O.C. MAX.FASTENERS;

FASTEN TO CURB 20" O.C. MAX.

CONTINUOUS BEADOF CAULK

FLASHING;

20" O.C. MAX.FASTENERS;

FLASHING BY EQUIPMENT MANUFACTURE

SUB FLASHING

F

SQUARE PENETRATIONSECTION A

SOLID SUBSTRATE AND OPEN FRAMING

BERMUDA PANEL SYSTEM

DATE: 8-15-06

PAGE\FILE

BP-82

3/4"1/2"

Page 34: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-83

SQUARE PENETRATION SECTION B

SOLID SUBSTRATE AND OPEN FRAMING

STEP FLASHING

F = FINISH SIDE

STEP FLASHING; 4" END LAPS WITHCONTINUOUS CAULK AT LAPS, SET

BERRIDGE BERMUDA PANEL;

# 30 FELTUNDERLAYMENT; TOP LAYER TO BEPARALLEL WITHROOF SLOPE

SUB-FLASHING

F

LOCATION OF MALE/FEMALE JOINT

CAULK AT LAPS

PANELVERTICAL EDGE OF BERMUDACONTINUOUS CAULK ALONG

PANEL MINIMUM 2"

LAPS WITH CONTINUOUS SUB-FLASHING; 4" END

CAULK

UP VERTICAL LEG AT END OF

CONTINUOUS BEAD OF

FIELD CUT PANEL AND TURN

FASTENERS EVERY 11" O.C. AT

FASTENERS; 20" O.C. MAX.

FASTENERS; 20" O.C. MAX.

FLASHING TIGHT ON TO PANELCONTINUOUS BEAD OFCAULK

FASTENERS; 2 PER PANEL LEG

EQUIPMENT MANUFACTUREFLASHING BY

AND INSTALLED BY THE ROOFING INSTALLER AT THE DISCRETION OF THE ARCHITECT.3. ALL FELT UNDERLAYMENT, CAULKING, AND FASTENERS, ARE ITEMS TO BE FURNISHED

STRENGTH FOR HOLDING POWER OF FASTENERS. (METAL CORRUGATED SHEATHING MAY2. SOLID SHEATHING (BY OTHERS) TO BE MINIMUM 1/2" PLYWOOD OR EQUIVALENT IN

USED OVER OPEN FRAMING (SEE DETAIL BP-84).1. SOLID SHEATHING IS REQUIRED AT THIS CONDITION WHEN THE BERMUDA PANEL IS

BE USED IN LIEU OF PLYWOOD).

BERMUDA PANEL SYSTEM

SQUARE PENETRATIONSECTION B

DATE: 8-15-06

PAGE\FILE

BP-83

SOLID SUBSTRATE AND OPEN FRAMING

Page 35: BERMUDA PANEL INSTALLATION DETAILS

BERRIDGEMANUFACTURINGCOMPANY

DATE: 08-15-06

Bermuda Panel SystemPAGE/FILE

BP-90

U.L. 90 CONST. NO. 405BERRIDGE BERMUDA ROOF PANEL

OVER SOLID WOOD SHEATHING

BERMUDA PANEL SYSTEM

BerridgeManufacturingCompany

Roofs of DistinctionBP-90

U.L. 90 CONST. NO. 405BERRIDGE BERMUDA ROOF PANEL

OVER SOLID WOOD SHEATHING

6

2

3

45

1

BERRIDGE BERMUDA ROOF PANEL OVER SOLID WOOD SHEATHING WITH CLIPS

COMPONENTS:

1. BERRIDGE BERMUDA PANEL: 24 GA. (MIN. YIELD 40,000 PSI) COATED STEEL, 11" W X 1" HIGH.

FABRICATED FROM 24 GA. (MIN. YIELD 2. BERMUDA PANEL CLIPS: ONE PIECE,

40,000 PSI) COATED STEEL. LOCATEDAT PANEL LAPS, 2'-0" MAX. SPACING.

3. FASTENERS: USE ONE (1) NO. 10

STEEL SCREW PER CLIP LOCATION.PANCAKE HEAD "TEKS" SCREW

4. DECK: 5/8" APA 40/20 PLYWOOD.

5. JOISTS: 2" X 4" @ 2'-0" O.C. MAX.

CONNECTION AND AT PLYWOOD ENDS.@ 12" O.C. MAX. @ PLYWOOD TO JOISTW/#12 X 2" PAN HEAD WOOD SCREWS

FELT, LAID HORIZONTALLY, EAVE TO 6. FELT PAPER: 1 LAYER # 30 ROOFING

RIDGE.

1

2 3

4

5

6

12

4

5

PAGE\FILE

DATE: 8-15-06