Bearing Capacity of Strip Footings by FEA
-
Upload
breeeeezzzzze -
Category
Documents
-
view
45 -
download
1
description
Transcript of Bearing Capacity of Strip Footings by FEA
2004 ABAQUS Users’ Conference 777
Bearing Capacity of Strip Footings on Two-layer Clay Soil by Finite Element Method
Ming Zhu
Department of Civil and Environmental Engineering, University of Michigan, Ann Arbor
Abstract: Parametric study was carried out to evaluate the ultimate bearing capacity of a rough
strip footing resting on two-layer clay soil. Computations were performed by the commercial finite
element analysis software ABAQUS. The computational results are compared with published
lower bound and upper bound solutions by limit analysis.
Keywords: Bearing Capacity, Strip Footings, Two-layer Soil, Finite Element Method.
1. Introduction
Geotechnical engineers often deal with layered foundation soil, which is non-homogeneous in
nature but can be simplified in representation as distinct homogeneous layers for engineering
purposes. The failure mechanism of layered soil depends on the thickness and soil properties of
each layer. In some cases where the top layer is relatively thick and consists of weak soil, the
failure mechanism may be limited in the top layer only and the strength of the remaining lower
layers has no influence. In many other cases, however, the failure mechanism may involve two or
more layers.
Bearing capacity of strip footings on two-layer soil has received much attention in the literature.
Terzaghi and Peck (1948) first applied the concept of load spreading to analyze a strip footing on
sand overlying clay. This was followed by many other researchers. The methods can be classified
into four major groups: limit equilibrium method (Button, 1953; Reddy and Srinivasan, 1967;
Meyerhof, 1974), limit analysis approach (Chen and Davidson, 1973; Florkiewicz, 1989;
Michalowski and Shi, 1995; Merifield, et al., 1999; Michalowski, 2002; Shiau, et al., 2003), semi-
empirical approach (Brown and Meyerhof, 1969; Meyerhof and Hanna, 1978; Hanna and
Meyerhof, 1980), and finite element method (Griffiths, 1982; Burd and Frydman, 1997).
This paper focuses on the application of finite element method. Parametric study was carried out
to evaluate the ultimate bearing capacity of a rough strip footing resting on two-layer clay soil.
Computations were performed by the commercial finite element analysis software ABAQUS
(Version 6.3). The computational results are presented and compared with published lower bound
and upper bound solutions by limit analysis.
778 2004 ABAQUS Users’ Conference
2. Problem definition
In the following, the problem definition and the finite element model are discussed. A schematic
diagram of the plain strain problem is shown in Figure 1. The footing is sitting on a half space of
soil. The width of the footing is B. The thickness of the top layer is H. Clay is homogenous in each
layer with undrained shear strength c1 and c2 respectively. Soil is assumed to be weightless.
Figure 1. Schematic diagram of the problem.
Finite element mesh is illustrated in Figure 2. Due to symmetry, only half of the problem is
modeled. The width of the footing B is 2 m. The length of the finite element model is 12.5B, and
the height is 7.5B. The size of the finite element model is large enough to keep the boundary
conditions at the bottom and the right side from restricting the soil movement due to the footing
load.
Figure 2. Finite element mesh.
2004 ABAQUS Users’ Conference 779
Soil is discretized with eight-node plane strain quadrilateral element with reduced integration
technique (element type CPE8R in ABAQUS). Soil immediately under the position of the footing
is discretized into 6 elements. Mesh near the edge of the footing is refined because of significant
displacement change in this region. The rough rigid footing is represented by appropriate
boundary conditions: to model the rough footing-soil interface, the horizontal displacement at the
nodes immediately under the position of the footing is restrained; to simulate the footing as a rigid
body, uniform downward displacement is applied at the nodes immediately under the position of
the footing so that they move downward by the same amount. The base of the mesh is fixed in
both horizontal and vertical directions. The two vertical sides are restrained in horizontal direction
only, allowing vertical movement.
Soil is modeled as an isotropic elastic-perfectly plastic material satisfying the Tresca failure
criterion. The following elastic properties are assumed (note that these values do not influence the
ultimate bearing capacity): Young’s modulus E = 20000kN/m2, Poisson’s ratio ν = 0.3. The
undrained shear strength of the top layer c1 is 20kN/m2. The undrained shear strength of the
second clay layer c2 varies according to the ratio c1/c2.
Analysis is performed under displacement control. Increments of vertical displacement are applied
at the nodes immediately under the position of the footing. The footing load is computed as the
summation of the vertical reaction forces at these nodes divided by the footing area, which is
expressed as
22
2
wB
RFq
+
=∑
(1)
where, q is the footing load, RF2 is the vertical component of the reaction force at each node
immediately under the position of the footing, B is the footing width, w is the width of the element
immediately adjacent to the edge of the footing, as shown in Figure 2. Equation (1) implies that
the edge of the strip footing is extended to the middle of the element immediately adjacent to the
edge of the footing. This is to account for the true footing area as a consequence of the finite
element model. A similar approach of radius extension for circular footings can be found in the
paper by Erickson and Drescher (2001). The loading process continues until the load-displacement
curve reaches a clear plateau which indicates soil failure. The load corresponding to the plateau is
the ultimate bearing capacity qu of the footing. The bearing capacity factor Nc* is then calculated
by
1
*
c
qN u
c = (2)
where, c1 is the undrained shear strength of the top clay.
The selection of the element size w affects the finite element solutions. Smaller elements around
the edge of footing will yield more accurate solutions because of the above-mentioned significant
displacement change (Day and Potts, 2000). However, this requires larger computational time.
Furthermore, divergence of the solutions was observed as the element size w becomes very small.
780 2004 ABAQUS Users’ Conference
Homogenous clay soil, where c1 equals c2, was studied in order to investigate the influence of w.
The exact solution of Nc* for a strip footing over homogenous clay soil is (π+2). Study shows Nc
*
increases as w decreases: w=B/16 yields a factor of 5.086, which is 1.08% lower than the exact
solution, w=B/20 yields a factor of 5.127, which is 0.28% lower, and w=B/24 yields a factor of
5.150, which is 0.16% higher. Bearing capacity factors for w/B less than 1/24 are not available
because of divergence of the solutions. Element width w=B/22.2 has been adopted in this study,
which yields a factor of 5.146.
3. Results and discussion
Parametric study was carried out to investigate the bearing capacity factor Nc* as a function of H/B
and c1/c2. Seven ratios of H/B were considered: 0.125, 0.25, 0.5, 0.75, 1.0, 1.25, and 2.0. Nine
ratios of c1/c2 were considered: 5, 4, 3, 2, 1.5, 1, 0.8, 0.5, and 0.2. In total, 63 computations were
performed. The bearing capacity factors Nc* are presented in Table 1, and also shown graphically
in Figures 3.
0
1
2
3
4
5
6
7
8
9
10
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2
H/B
Nc
*
C1/C2=0.2
C1/C2=0.5
C1/C2=0.8
C1/C2=1
C1/C2=1.5
C1/C2=2
C1/C2=3
C1/C2=4
C1/C2=5
Figure 3. Bearing capacity factor*
cN .
For cases where the top layer is weaker than the bottom layer (c1/c2 < 1), Nc* decreases as H/B
increases. For cases where the top layer is stronger than the bottom layer (c1/c2 > 1), Nc* increases
as H/B increases. Nc* approaches 5.146 for all cases, which indicates that the failure mechanism is
limited in the top layer and the whole soil can be treated as a homogenous soil using the properties
of the top soil only. According to Michalowski (2002), there exists a so-called critical depth where
the strength of the bottom layer does not affect the bearing capacity. In Figure 3, the critical depth
is the depth H where the curve of Nc* reaches 5.146. For strong-over-soft clay profile (c1/c2 > 1),
the larger the ratio c1/c2 is, the larger the critical depth. Whereas, for soft-over-strong clay profile
(c1/c2 < 1), the critical depth seems to be a constant around 0.75B. This observation is consistent
with the finding by Michalowski (2002).
2004 ABAQUS Users’ Conference 781
(a) H/B=0.125 (b) H/B=0.75
(c) H/B=1.25 (d) H/B=2
Figure 4. Zones of plastic strain at failure for strong-over-soft clay (c1/c2 = 2).
(a) H/B=0.125 (b) H/B=0.50
(c) H/B=0.75 (d) H/B=1
Figure 5. Zones of plastic strain at failure for soft-over-strong clay1 (c1/c2 = 0.8).
1 Bright color inside the failure zones indicates region with lager plastic strain
782 2004 ABAQUS Users’ Conference
Figure 4 illustrates the zones of plastic strain at failure for strong-over-soft clay profile. First, the
failure mechanism goes deeper and wider as H/B increases with both layers being involved. After
the thickness of the top layer exceeds a critical depth, the failure mechanism shrinks into the top
layer. For situations where the top layer is weaker than the bottom layer, the failure mechanism
does not change very much, as shown in Figure 5. The failure mechanism tends to be limited in
the top layer as H/B increases.
(a) strong-over-soft clay (c1/c2 = 2)
(b) soft-over-strong clay (c1/c2 = 0.8)
Figure 6. Vectors of displacement at failure (H/B = 0.75).
2004 ABAQUS Users’ Conference 783
Displacement fields at failure for both strong-over-soft clay and soft-over-strong clay are shown in
Figure 6. The vectors indicate both the direction and the magnitude of soil movement. Given the
same thickness of the top layer, strong-over-soft clay has a larger area of soil movement than soft-
over-strong clay. Inspection of Figure 6(b) shows that the displacement at the top surface of the
first element adjacent to the edge of the footing changes direction abruptly, from vertically
downward to more than 45○ to the horizontal axis. The displacement change is smoother in the
case where the top clay is stronger than the bottom clay and less heave at the soil surface is
observed, as shown in Figure 6(a).
The finite element solutions are compared with published lower bound and upper bound solutions
by limit analysis in Table 1 and also in Figure 7. As is expected, the finite element solutions are
lying between the lower bound and upper bound solutions and show a favorable agreement with
their averages.
4. Final remarks
Parametric study was carried out to evaluate the bearing capacity of a strip footing over two-layer
clay soil. Finite element solutions for different combinations of layer thickness and soil strength
are presented in both tabular and graphical forms. At the same strength ratio, the bearing capacity
factor decreases as thickness of the top layer increases for a soft-over-strong clay profile, whereas
an inverse trend for a strong-over-soft clay profile. There exists a critical depth where the shear
strength of the bottom layer does not affect the bearing capacity and failure mechanism is
restricted only in the top layer. Different failure mechanisms and displacement fields are observed
for strong-over-soft clay profile and soft-over-strong clay profile. A comparison of the finite
element solutions with published limit analysis solutions shows a good agreement.
(a) H/B=0.125
0
1
2
3
4
5
6
7
8
9
10
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merif ield, 1999)
Upper bound (Merif ield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
(b) H/B=0.25
0
1
2
3
4
5
6
7
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merifield, 1999)
Upper bound (Merif ield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
784 2004 ABAQUS Users’ Conference
(c) H/B=0.50
0
1
2
3
4
5
6
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merif ield, 1999)
Upper bound (Merif ield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
(d) H/B=0.75
0
1
2
3
4
5
6
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merif ield, 1999)
Upper bound (Merif ield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
(e) H/B=1.0
0
1
2
3
4
5
6
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merif ield, 1999)
Upper bound (Merif ield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
(f) H/B=1.5
0
1
2
3
4
5
6
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merif ield, 1999)
Upper bound (Merifield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
(g) H/B=2.0
0
1
2
3
4
5
6
0 1 2 3 4 5
C1/C2
Nc
*
FEM
Low er bound (Merif ield, 1999)
Upper bound (Merif ield, 1999)
Average of low er and upper bounds
(Merif ield, 1999)
Figure 7. Comparison of bearing capacity factors.
2004 ABAQUS Users’ Conference 785
Table 1. Bearing capacity factor *
cN
H/B C1/C2 Finite Element
Method Lower bound
(Merifield, 1999) Upper bound
(Merifield, 1999) Average (Merifield, 1999)
Upper bound (Michalowski, 2002)
5 1.387 1.30 1.55 1.43 1.520 4 1.656 1.56 1.82 1.69 1.766 3 2.083 1.97 2.27 2.12 2.166 2 2.896 2.73 3.09 2.91 2.933
1.5 3.674 3.45 3.93 3.69 3.681 1 5.146 4.94 5.32 5.13 5.141
0.8 6.173 5.87 6.36 6.11 6.217 0.5 8.560 7.78 8.55 8.16 9.391
0.125
0.2 9.355 7.78 8.55 8.17 9.842
5 1.655 1.60 1.85 1.73 1.906 4 1.944 1.87 2.12 1.99 2.149 3 2.376 2.27 2.56 2.42 2.533 2 3.159 3.01 3.34 3.17 3.246
1.5 3.875 3.65 4.08 3.87 3.912 1 5.146 4.94 5.32 5.13 5.141
0.8 5.932 5.51 6.25 5.88 5.991 0.5 6.519 5.99 6.52 6.26 6.561
0.25
0.2 6.520 5.99 6.52 6.26 6.561
5 2.212 2.16 2.44 2.30 2.579 4 2.500 2.44 2.74 2.59 2.817 3 2.933 2.84 3.16 3.00 3.177 2 3.656 3.52 3.89 3.70 3.800
1.5 4.256 4.07 4.48 4.28 4.329 1 5.146 4.94 5.32 5.13 5.141
0.8 5.411 4.98 5.49 5.24 5.313 0.5 5.427 4.98 5.49 5.24 5.313
0.5
0.2 5.427 4.98 5.49 5.24 5.313
5 2.743 2.64 2.98 2.81 3.190 4 3.039 2.96 3.28 3.12 3.420 3 3.462 3.36 3.72 3.54 3.750 2 4.122 4.00 4.37 4.18 4.299
1.5 4.614 4.44 4.94 4.69 4.708 1 5.146 4.94 5.32 5.13 5.141
0.8 5.163 4.98 5.49 5.24 5.141 0.5 5.163 4.98 5.49 5.24 5.141
0.75
0.2 5.163 4.98 5.49 5.24 5.141
5 3.259 3.10 3.54 3.32 3.768 4 3.559 3.46 3.83 3.65 3.988 3 3.966 3.89 4.24 4.07 4.299 2 4.557 4.44 4.82 4.63 4.746
1.5 4.942 4.77 5.18 4.97 5.046 1 5.146 4.94 5.32 5.13 5.141
0.8 5.146 4.94 5.30 5.12 5.141 0.5 5.146 4.94 5.30 5.12 5.141
1.00
0.2 5.146 4.94 5.30 5.12 5.141
786 2004 ABAQUS Users’ Conference
Table 1. Bearing capacity factor *
cN (continued)
H/B C1/C2 Finite Element
Method Lower bound
(Merifield, 1999) Upper bound
(Merifield, 1999) Average (Merifield, 1999)
Upper bound (Michalowski, 2002)
5 3.765 4.295 4 4.060 4.497 3 4.431 4.767 2 4.926 5.141
1.5 5.145 5.141 1 5.146 5.141
0.8 5.146 5.141 0.5 5.146 5.141
1.25
0.2 5.146 5.141
5 4.233 3.89 4.56 4.23 4.863 4 4.494 4.24 4.84 4.54 4.965 3 4.816 4.69 5.15 4.92 5.187 2 5.145 4.87 5.31 5.09 5.141
1.5 5.145 4.87 5.31 5.09 5.141 1 5.146 4.94 5.32 5.13 5.141
0.8 5.146 4.94 5.30 5.12 5.141 0.5 5.146 4.94 5.30 5.12 5.141
1.50
0.2 5.146 4.94 5.30 5.12 5.141
5 4.956 4.61 5.32 4.96 4 5.142 4.81 5.32 5.06 3 5.145 4.81 5.27 5.04 2 5.145 4.81 5.27 5.04
1.5 5.145 4.81 5.26 5.04 1 5.146 4.94 5.32 5.13
0.8 5.146 4.94 5.30 5.12 0.5 5.146 4.94 5.30 5.12
2.00
0.2 5.146 4.94 5.30 5.12
5. References
1. Brown, J. D. and G. G. Meyerhof, “Experiment Study of Bearing Capacity in Layered Clays,”
Proc. of 7th Int. Conf. on Soil Mechanics and Foundation Engineering, Mexico, vol. 2, pp. 45-
51, 1969.
2. Burd, H. J. and S. Frydman, “Bearing Capacity of Plane-strain Footings on Layered Soils,”
Can. Geotech. J. Vol. 34, pp. 241-253, 1997.
3. Button, S. J., “the Bearing Capacity of Footings on a Two-layer Cohesive Subsoil,” Proc. of
the 3rd Int. Conf. on Soil Mechanics and Foundation Engineering, Zurich, vol. 1, pp. 332-335,
1953.
4. Chen, W. F. and H. L. Davidson, “Bearing Capacity Determination by Limit Analysis,” J.
Soil Mech. Found. Div., ASCE, vol. 99, no. 6, pp. 433-449, 1973.
5. Day, R.A. and D. M. Potts, “Discussion on ‘Observations on the computation of the Bearing
Capacity Factor Nγ by Finite Elements’ by Woodward & Griffiths, Geotechnique, Vol. 50,
No. 3, pp. 301-303.
2004 ABAQUS Users’ Conference 787
6. Erickson, H. L. and A. Drescher, “Bearing Capacity of Circular Footings,” J. Geotech. Engrg.,
ASCE, vol. 128, no. 1, pp. 38-43, 2001.
7. Florkiewicz, A., “Upper Bound to Bearing Capacity of Layered Soils,” Can. Geotech. J., vol.
26, no. 4, pp. 730-736, 1989.
8. Griffiths, D. V., “Computation of Bearing Capacity on Layered Soil,” Proc. of 4th Int. Conf.
Num. Meth. Geomech., Z. Eisenstein, Ed., Balkema, Rotterdam, the Netherlands, pp. 163-
170, 1982.
9. Hanna, A. M. and G. G. Meyerhof, “Design Charts for Ultimate Bearing Capacity of
Foundations on Sand Overlying Soft Clay,” Can. Geotech. J., vol. 17, pp. 300-303, 1980.
10. Merifield, R. S., S. W. Sloan, and H. S. Yu, “Rigorous Plasticity Solutions for the Bearing
Capacity of Two-layered Clays,” Geotechnique, London, England, vol. 49, no. 4, pp. 471-
490, 1999.
11. Meyerhof, G. G., “Ultimate Bearing Capacity of Footings on Sand Layer Overlaying Clay,”
Can. Geotech. J., vol. 11, no. 2, pp. 223-229, 1974.
12. Meyerhof, G. G. and A. M. Hanna, “Ultimate Bearing Capacity of Foundations on Layered
Soils under Inclined Load,” Can. Geotech. J., vol. 15, pp. 565-572, 1978.
13. Michalowski, R. L., “Collapse Loads over Two-layer Clay Foundation Soils,” Soils and
Foundations, Vol. 42, No. 1, pp. 1-7, 2002.
14. Michalowski, R. L. and L. Shi, “Bearing Capacity of Footings over Two-layer Foundation
Soils,” J. Geotech. Engrg., ASCE, vol. 121, no. 5, pp. 421-428, 1995.
15. Reddy, A. S. and R. J. Srinivasan, “Bearing Capacity of Footings on Layered Clays,” J. Soil
Mech. Found. Div., ASCE, vol. 93, no. 2, pp. 83-99, 1967.
16. Shiau, J. S., A. V. Lyamin, and S. W. Sloan, “Bearing Capacity of a Sand Layer on Clay by
Finite Element Limit Analysis,” Can. Geotech. J., Vol. 40, pp. 900-915, 2003.
17. Terzaghi, K. and R. B. Peck, “Soil Mechanics in Engineering Practice,” New York:Wiley,
1948.