    APPLICATION GUIDE

    AIR SYSTEMS ENERGY SERIES

    Energy Recovery Wheels

    Supercedes: Nothing Form 102.20-AG6 (305)

    INTRODUCTION

    As fossil fuel reserves are depleted, the cost of energycontinues to rise. According to the US Department ofEnergy, the cost of energy used in US commercial build-ings increased by more than 200% between 1979 and1995 and conservative DOE estimates predict an addi-tional 46% increase between 2001 and 2025. Given thisand the fact that, on average, HVAC systems consume39% of the energy used in commercial buildings, en-ergy-efficient HVAC systems represent potentially sig-nificant savings in building operating costs.

    Increased ventilation rates, which are required to satisfythe ventilation standard ASHRAE 62.1-2004, mean agreater expenditure of energy to condition outside air.One way that savings can be realized in an HVAC sys-tem is through the use of exhaust air energy recovery.Exhaust air energy recovery can take many formsro-tary heat exchangers, heat-pipes, plate heat exchangers,etc., but all of the devices operate on the same principlethey use exhaust air to condition supply air through atransfer of energy. This application guide examines therotary heat exchangeralso called an energy wheel, orenergy recovery wheeland the benefits of incorporat-

    ing such a device in an air handling unit.

    PRINCIPLES OF ENERGY RECOVERY

    Energy recovery involves a transfer of energy betweenan exhaust airstream and a supply airstream. Figure 1illustrates the heat transfer process of an energy recov-ery wheel where OA is outside air; SA is supply air;RA is return air from the conditioned space and EA isexhaust air.

    As the two airstreams pass through the energy recov-ery wheel, the rotation of the wheel facilitates the trans-fer of energy from the higher energy airstream to thelower energy airstream. This means that the exhaustair preheats the supply air in the winter and precoolsthe supply air in the summer. Some systems use en-ergy recovery wheels to reheat supply air after it hasbeen cooledan effective means of humidity control.

    Some energy recovery wheels transfer only sensibleenergy, while others transfer sensible and latent (i.e.total) energy.

    Sensible Heat TransferWhen sensible heat is transferred, the dry-bulb tem-perature of the colder airstream increases and the dry-bulb temperature of the warmer airstream decreasesNo moisture is transferred, so the humidity ratio of thetwo airstreams remains unchanged unless the dry-bulbtemperature of the warmer airstream is decreased be-low its dew point, allowing condensation to occur.

    Total Heat Transfer

    This process involves the transfer of sensible and la-tent heat energy. Latent heat energy is dependent onthe amount of water vapor in the air and therefore totaheat transfer can only occur when water vapor is trans-ferred from one airstream to the other. In an energyrecovery wheel this transfer is accomplished throughthe use of a desiccant which absorbs/adsorbs watervapor from the higher vapor pressure airstream andreleases it to the lower vapor pressure airstream. Onlyenergy recovery wheels and certain types of fixed-plateheat exchangers with permeable membranes can trans-fer latent, and therefore total, energy.

    EffectivenessThe ratio of the amount of energy transferred by theenergy recovery device to the difference in energy lev-els of the two incoming airstreams is called effective-ness. The total amount of energy transferred by thewheel is a function of the effectiveness of the wheelthe airflow volumes of the two airstreams and the dif-ference in energy levels between the two airstreams

    FIGURE 1.STANDARD AIRFLOW CONVENTIONS

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    2/12YORK INTERNATIONAL2

    FORM 102.20-AG6 (305)

    Equation 1 shows the calculation of effectiveness asdefined by ASHRAE Standard 84-1991:

    Equation 1:= [Vs (x1- x2)] / [Vmin (x1- x3)]

    Where:

    = Sensible, or total effectiveness

    x1 = OA temp (Fdb) or enthalpy (btu/lb.)

    x2 = SA temp (Fdb) or enthalpy (btu/lb.)

    x3 = RA temp. (Fdb) or enthalpy (btu/lb.)

    Vs = Supply (or outside) air volume (cfm)

    Vmin = The lower of the exhaust or supply air

    volume (cfm)

    Amount of Heat TransferredThe sensible and total energy transferred by the energyrecovery wheel can be calculated using Equations 2and 3:

    Equation 2: Qs= 1.08 Vmin (t1 - t3)

    Equation 3: Qt= 4.5 Vmin (h1 - h3)

    Where:

    Qs = Sensible heat transferred (btu/hr)

    Qt = Total heat transferred (btu/hr)

    = Sensible, or total effectiveness

    Vmin = The lower of the exhaust or supply

    air volumes (cfm)

    t1 = Outside air temperature (F)

    t3 = Return air temperature (F)

    h1 = Outside air enthalpy (btu/lb.)

    h3 = Return air enthalpy (btu/lb.)

    1.08 = Conversion factor

    4.5 = Conversion factor

    If the effectiveness of the wheel is known, Equation 1can be solved for x

    2to determine the supply air leaving

    enthalpy and/or temperature. In Example 1 the outsideair and return air volumes are equal, or balanced(V

    s= V

    min). Optimal energy transfer occurs at balanced

    flow conditions, however building exfiltration andexhaust sources such as bathroom fans reduce the re-turn air volume below the supply air volume.This unbalanced flow reduces heat transfer, even thoughit increases the effectiveness factor of the energyrecovery wheel.

    Example 1:Calculate the supply air conditions leav-

    ing a total heat recovery wheel with 12,000 cfm of

    outside air at 94Fdb and 77Fwb; and 12,000 cfm of

    return air at 75Fdb and 50% RH, if both the sensible

    & latent effectiveness of the wheel is 60%. Calculate

    the reduction in required cooling energy.

    At the conditions given above:

    x3= the return air enthalpy = 28.15 btu/lb. = h 3

    x1= the outside air enthalpy = 40.38 btu/lb. = h1

    From Equation 1:

    h2= h1- [ Vmin (h1- h3)]/Vs

    h2= 40.38 - [0.6 12000 (40.38 - 28.15)] / 12000

    h2= 33.04 btu/lb.

    Also from Equation 1:

    t2= t1- [ Vmin (t1- t3)]/Vs

    t2= 94 - [0.6 12000 (94 - 75)] / 12000

    t2= 82.6F.

    Therefore, the supply air leaving the heat recovery

    wheel will be: 82.6Fdb / 68.9Fwb

    From Equation 3:

    Qt= 4.5 Vmin (h1- h3)

    Qt= 0.6 4.5 12000 (40.38 - 28.15)

    Qt= 396,252 btu/hr = 33 tons

    Figure 2 shows the effect of unbalanced airflow on ef-

    fectiveness.

    Example 2 indicates that despite a 7% increase in ef-fectiveness, the overall heat transfer of the wheel de-creased by 10% in relation to the balanced flow condi-tions of Example 1.

    FIGURE 2EFFECT OF UNBALANCED AIRFLOW

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    3/12

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    4/12YORK INTERNATIONAL4

    FORM 102.20-AG6 (305)

    turer, but it is important to understand how these fac-tors affect, and are affected by, system design. Themagnitude of the EATR and OACF affects fan sizing,while the positions of the supply and exhaust fans, andthe air pressure drops they develop, affect the magni-tude of the EATR and OACF. Figures 5 through 8 showthe four possible fan arrangements along with the ad-vantages and precautions associated with each.

    Proper fan arrangement and control of the static pres-sure minimizes the air transfer caused by leakagethrough the gaskets and seals of the wheel, howeverthese practices will not reduce the transfer of air causedby carryover. As Figure 9 shows, some of the air fromthe return/exhaust path remains in the matrix of thewheel as it rotates to the outside/supply airstream. Thiscarryover air mixes with the incoming outside air and

    FIGURE 5 BLOW-THRU SUPPLY/BLOW-THRUEXHAUST

    Advantages

    Minimal leakage when supply and exhaust pathstatic pressures are nearly equal.

    Precautions

    Direction of leakage depends on relative staticpressures.

    FIGURE 6 BLOW-THRU SUPPLY/DRAW-THRUEXHAUST

    Advantages

    Minimizes leakage of air from exhaust path tosupply path.

    Precautions

    Leakage from supply path to exhaust path can beexcessive if static pressure differences are not mini-mized.

    FIGURE 7 DRAW-THRU SUPPLY/DRAW-THRU

    EXHAUST

    Advantages

    Minimal leakage when supply and exhaust pathstatic pressures are nearly equal.

    Good air distribution across the face of the wheel.

    Precautions

    Direction of leakage depends on relative staticpressure.

    FIGURE 8 DRAW-THRU SUPPLY/BLOW-THRU

    EXHAUST

    Advantages

    None.

    Precautions

    Significant leakage from exhaust air path to supplyair path.

    DO NOT USE.

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    5/12

    FORM 102.20-AG6 (305

    5YORK INTERNATIONAL

    enters the supply air path. For most applications, suchas comfort cooling, carryover is of little concern. How-ever, if there were high concentrations of hazardoussubstances such as VOCs or carcinogens in the air, theywould enter the supply airstream via the carryover airand may present a health hazard to occupants. For thisreason, energy recovery wheels should not be usedin applications where high concentrations of haz-

    ardous substances may be present in the exhaust air,for example laboratories or hospital operatingrooms.

    PurgeA mechanical purge section can be used to reduce thevolume of carryover air. (See Figure 10.) Mechanicalpurge isolates a section of the wheel on the boundarybetween the RA/EA path and the OA/SA path at thepoint where the wheel rotates from the RA/EA path intothe OA/SA path.

    Placing a block-off over this section of the wheel onthe RA/SA side forces outside air that has traveledthrough the wheel to flow back into it in the oppositedirection. This prevents air from the RA/EA path fromentering the last few degrees of the wheel before it ro-tates into the OA/SA path. The return air that enteredthe wheel prior to the purge section has time to exit thewheel on the exhaust side. The angle of the purge sec-tion - how large a slice of the wheel it covers deter-mines how effective it is. The larger the angle, thegreater is the reduction in carryover. Purge should not,however, be counted on to eliminate carryover com-pletely; therefore, even energy recovery wheels

    equipped with purge sections should not be usedwhen high concentrations of hazardous substancesare likely in the exhaust airstream.

    Frost Control

    Frost formation is always a concern when HVAC equip-ment operates in sub-freezing weather. Heat recoveryequipment is no exception, but the likelihood of frostformation is greater on sensible-only heat transfer de-vices, including sensible-only energy wheels, than ontotal energy transfer devices. Consider both processeson the psychrometric chart:

    During the heating season a total energy recovery de-vice transfers heat and moisture from the warm, moistreturn air to the cold, dry outside air. This lowers the

    exhaust air dewpoint - the temperature at which con-densation and frost formation occurs. Figure 12 com-pares typical frost threshold temperatures of total energy recovery wheels and sensible-only heat exchang-ers. Condensation and frost begin to form to the left othe respective boundary lines. The dewpoint depres-sion achieved with total energy devices can lower thefrost formation threshold well below 0F when the in-door air relative humidity is low.

    Total energy recovery wheels located in climates withextreme winter conditions, and/or where indoor air rela-

    FIGURE 9 AIR TRANSFER DUE TO CARRYOVER

    FIGURE 10 ENERGY RECOVERY WHEEL WITH

    PURGE SECTION

    FIGURE 11 EFFECT OF TOTAL ENERGY TRANSFER

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    6/12YORK INTERNATIONAL6

    FORM 102.20-AG6 (305)

    tive humidities are high may still require some meansof frost prevention. There are four common methodsof frost prevention - three of which are generally fa-vored over the fourth.

    On-Off controlis the least expensive and least com-plicated method of preventing frost. When the wheel

    is not rotating, no energy transfer takes place and themoisture in the exhaust airstream is in no danger ofcondensing and freezing. The drawbacks to this methodare that when the energy recovery wheel is not operat-ing, no energy savings are realized and heating elementsmust be sized for design winter conditions. On-Offfrost prevention control is best suited for mixed airsystems with a low minimum outside air requirementand in climates where the outdoor air temperature dropsbelow the frost threshold mainly during the unoccu-pied period when ventilation is not required.

    Bypassing the outside airor a portion of it is anothercommon tactic for preventing frost formation. Thismethod consists of mounting a bypass damper in theOA/SA path that opens to divert some of the outsideair around the energy recovery wheel when outside airconditions are below the frost threshold. This reducesthe heat transfer capacity of the wheel and prevents theleaving exhaust air from reaching saturation. Propermixing is crucial to prevent stratification, which couldfreeze downstream coils in the air handler. The heat-ing elements must be somewhat larger in this type ofsystem than a system in which the wheel operates at100% during winter design conditions, but do not nec-essarily have to be sized for design winter conditions.

    Bypass systems are best suited for climates with veryfew hours per year below the frost threshold and forsystems that do not include humidifiers. Systems withairside economizers are required to have OA bypass totake full advantage of economizer operation.

    Entering air preheatis a widely accepted method offrost control that has the additional advantage of al-lowing the wheel to operate at maximum air volumeduring design heating conditions. The approach to thisfrost control method is to mount a heating device on

    either the OA entering side of the wheel (position 1) oron the RA entering side of the wheel (position 3); seeFigure 13. When the heating device is mounted in po-sition 1, the temperature of the outside air is raisedabove the frost threshold temperature of the wheel, pre-venting the exhaust air from getting cold enough to formfrost. When the heating element is placed in position3, enough energy is added to the RA path to prevent

    the heat transfer to the OA/SA path from lowering theexhaust air temperature below the saturation point.

    This method of frost control is well suited to climates

    with extreme winter conditions, and for systems thatinclude some form of mechanical humidification. Ifthe preheat device consists of a steam or hydronic coilmounted in the outside airstream, some form of freezeprotection for the coil must be included. No such pre-caution is necessary if a steam or hydronic coil is used

    to preheat the return air. Although a heating devicemounted in position 3 (RA) will typically require agreater capacity than a device mounted in position 1(OA) to provide the same degree of frost prevention,adding heat to the return air path increases the sensibleheat transfer to the supply air path. When a preheatelement is used in position 3, caution should be exer-cised so that the temperature of the entering return airdoes not exceed the recommended operating tempera-ture of the energy recovery wheel.

    Variable speed control can be used to reduce the rota-tional speed of the wheel, which reduces its ability to

    transfer energy. Because of all the variables involved,this method of frost control requires a sophisticatedcontrol strategy, which if not followed correctly canactually increase the likelihood of frost formation.Reducing the wheel speed can also lead to significantreductions in performance and the need for supplemen-tary freeze protection for downstream coils. For thesereasons, the previous three methods of frost preven-tion are generally favored over variable wheel speedcontrol.

    FIGURE 12 FROST THRESHOLD TEMPERATURES

    FIGURE 13 PREHEAT FROST CONTROL

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    7/12

    FORM 102.20-AG6 (305

    7YORK INTERNATIONAL

    Capacity Control

    Maximum heat transfer is not always necessary, nordesirable. The two most common methods of control-ling the energy transfer rate of the wheel are variablespeed control and bypass of exhaust or outside air.

    Variable speed control consists of using a speed con-troller, such as a variable frequency drive (VFD) or

    silicon controlled rectifier (SCR), attached to the drivemotor of the wheel. As the rotational speed of the wheeldecreases, the heat transfer capacity also decreases.There are limits to this type of capacity control, how-ever. The reduction in capacity is not proportional tothe reduction in wheel speed; therefore, reducing thespeed of the wheel by 50% may only result in a 10%reduction in energy transfer.

    Exhaust or outside air bypass requires a bypass dampermounted in the OA/SA path or the RA/EA path andhas several advantages over variable speed capacitycontrol. Air bypass results in more linear control ofthe energy wheel capacity making the control strategymore reliable. Also, a greater overall reduction in ca-pacity can be achieved by using bypass than by usingvariable speed control, and the pressure drop of thesystem is reduced as the volume of air passing throughthe wheel is reduced.

    Placing the bypass damper in a position to divert ex-haust air in lieu of outside air will minimize the possi-bility of stratification in 100% outside air systems. Thisdamper could also be placed in the exhaust airstreamto control the capacity of the wheel by reducing thevolume of exhaust air available to transfer energy to orfrom. However, in an air hander with an airside econo-

    mizer, when the system modulates from minimum out-side air operation to 100% economizer mode, somemeans of diverting the outside air around the wheelmust be included to prevent excessive pressure dropand unwanted preheating. In this arrangement theeconomizer bypass damper could be used as a capacitycontrol damper in the minimum outside air mode, al-though proper mixing of treated and bypassed air wouldbe essential to prevent freezing of hydronic coils down-stream of the energy recovery wheel.

    ENERGY RECOVERY APPLICATIONS

    There are three application categories for air-to-air en-ergy recovery based on the type of system the energyrecovery device serves, and two subcategories based onhow the device is used in the system. The applicationcategories are process-to-process, process-to-comfort andcomfort-to-comfort. Examples of these applications aregiven in Table 1. The subcategories are preconditioningof outside air and tempering of supply air.

    Method Typical Application

    Process-to-process Dryers

    and Ovens

    Process-to-comfort Flue stacks

    Burners

    Furnaces

    Incinerators

    Paint exhaustWelding

    Comfort-to-comfort Swimming pools

    Locker rooms

    Residential

    Smoking exhaust

    Operating rooms

    Nursing homes

    Animal venti lation

    Plant ventilation

    General exhaust

    2000 ASHRAE Handbook - HVAC Systems and Equipmen

    Table 1. Applications for Air-to-Air Energy Recovery

    Process-to-process (PTP) and process-to-comfort (PTC)applications generally only require heating. The energy recovery device transfers the heat generated bythe process from the exhaust airstream back into theprocess supply airstream or building makeup airstreamrespectively. Because excess humidity is detrimentato many process applications, PTP systems typicallyonly require sensible heat transfer. Process-to-com-fort applications may use total energy recovery devicesto humidify dry outside air in the winter and to reduce

    the likelihood of frost formation. Comfort-to-comfort(CTC) heat recovery systems operate during both theheating and cooling seasons and may transfer sensible-only or total heat from the building exhaust sources tothe makeup airstream.

    For PTP and PTC applications a plate-type heat ex-changer may be more appropriate than an energy re-covery wheel. This is due to the fact that in most casescross leakage must be eliminated, also plate exchang-ers may be more resistant to the temperatures of theprocess exhaust and usually only sensible energy re-covery is required. Energy recovery wheels are com-

    monly used for CTC applications, except in cases wherethe possibility of cross contamination precludes theiruse.

    Preconditioning of Outside Air

    A primary use of exhaust air energy recovery is to pre-condition outside air. Preheating/humidifying in win-ter and precooling/dehumidifying in summer reduces

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    8/12YORK INTERNATIONAL8

    FORM 102.20-AG6 (305)

    annual operating costs and may decrease first cost asthe required heating and cooling capacity is reduced.Figure 14 illustrates one possible configuration of anoutside air preconditioning system.

    Example 1 on page 2 illustrates a potential 33 ton (42%)equipment capacity reduction of an outside air precon-

    ditioning system in the cooling mode. Using the en-ergy recovery wheel to preheat and humidify the out-side air in the heating season can achieve similar sav-ings and capacity reductions.

    In systems with airside economizers, the energy recov-ery wheel should be sized for minimum outside air-flow only and provisions should be included to bypassor otherwise prevent operation of the wheel duringeconomizer mode. Operation of an energy recoverywheel during economizer mode increases energy con-sumption.

    Tempering of Supply AirUsing an energy recovery wheel to temper supply airis an energy efficient way to control humidity. In thepast, humidity control involved cooling the air belowthe temperature required to satisfy the sensible loadand then reheating it. While this simultaneous heatingand cooling provided fine temperature and humiditycontrol, it wasted a great deal of energy. ASHRAEStandard 90.1-2004 prohibits simultaneous heating andcooling unless, among other specific exceptions, at least75% of the reheating energy is provided from a site-recovered energy source.

    Two methods of tempering the supply air are shown inFigures 15 and 16. The parallel arrangement uses theenergy recovery wheel to reheat the supply air duringthe cooling mode by transferring energy from the re-turn airstream to the supply airstream. During the heat-ing mode, the wheel preheats the outside or mixed airby transferring energy to the supply airstream. Thismay help reduce the winter heating load, but any hy-dronic coils upstream of the wheel may require someof form of freeze protection, particularly in 100% out-side air systems.

    In the series arrangement, energy is not actually re-covered, but simply transferred from the upstream tothe downstream side of the cooling coil. This transferreheats the supply air and preconditions the outside airsimultaneously. Since the goal of a series arrangementsupply air tempering system is dehumidified supply air,sensible-only energy recovery devices. Series type sys-tems as shown in Figure 16 are not used during theheating season.

    In both of the supply air tempering arrangements thecooling system is designed to accommodate the peakcooling (i.e. sensible) design load, which, as Figure 17shows, occurs at a higher dry bulb temperature thanthe design dehumidifying condition. The energy re-

    covery wheel is not used during peak sensible coolingconditions because it is not desirable to add heat to thesupply air when sensible cooling is the main concern.Therefore, using an energy wheel for supply air tem-pering will not reduce the design capacity of the cool-ing system.

    Supply air tempering is used at the peak dehumidify-ing (i.e. latent) design load when the sensible load inthe space is lower and the latent load is higher than the

    FIGURE 14 OUTSIDE AIR PRECONDITIONING

    MIXED AIR

    100% OUTSIDE AIR

    FIGURE 15 SUPPLY AIR TEMPERATING (PARALLEL)

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    9/12

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    10/12YORK INTERNATIONAL10

    FORM 102.20-AG6 (305)

    Care should be taken in the design of the system toallow sufficient access space for the inspection andcleaning processes.

    INDUSTRY STANDARDS

    The HVAC industry has published several documentsthat deal with the testing, rating and use of exhaust air

    energy recovery devices.

    ASHRAE Standard 84-1991

    ASHRAE Standard 84-1991, The Method of TestingAir-to-Air Heat Exchangers is an ANSI approved stan-dard that was published in 1992. The purpose of thisstandard is to establish a uniform method of testingair-to-air heat exchangers. The standard specifies thetest set-ups and test equipment required. It also speci-fies the data that must be collected, the calculationsthat can be used and the acceptable procedures for re-porting test results.

    ARI Standard 1060-2000

    Published by the Air-Conditioning and RefrigerationInstitute in 2000, ARI 1060 is the Standard for RatingAir-to-Air Energy Recovery Ventilation Equipment.The purpose of this standard is similar to that ofASHRAE 84-1991 in that it establishes definitions;test requirements; rating requirements; requirements formarking and nameplate data; and conformance require-ments. The test procedures referenced in ARI-1060are the ones that are specified in ASHRAE 84-1991.

    There are a few differences between the standards how-ever. For example, ASHRAE 84-1991 includes run-around loop heat exchangers - that is a closed loop sys-tem consisting of two or more heat transfer coilsmounted in different airstreams. ARI 1060 excludesthis type of heat exchanger and instead applies only toheat pipes, plate heat exchangers and rotary heat ex-changers. Also, the ratings outlined in ARI 1060 onlyapply to the performance of the energy recovery de-vice, as it is used to precondition outside air, not as it isused to recondition, or temper supply air.

    The most important difference between the two stan-dards is that ARI administers a certification programin conjunction with Standard 1060; ASHRAE has no

    such certification program. This means that any en-ergy recovery equipment manufacturer can apply forlisting in ARIs Air-to-Air Energy Recovery Ventila-tion Equipment Certified Product Directory. Manu-facturers who are listed in the ARI directory have cer-tified that their equipment has been tested using theprocedures stipulated in Standard 1060 and that thepublished ratings of the equipment conform to the re-quirements of the standard.

    To verify the ratings of a certified manufacturer, ARIrandomly selects samples of the rated equipment on a

    regular basis and has the samples tested in accordancewith Standard 1060 at an independent laboratory thatis under contract to ARI. Manufacturers whose equip-ment passes these tests are permitted to use the ARI1060 certification seal shown in Figure 18 on their cer-tified models, specification sheets and other literatureand advertising that pertains to equipment ratings.

    Specifying ARI 1060 certified energy recovery equip-

    ment has several advantages. It facilitates the com-parison of certified products from various manufactur-ers by standardizing the ratings methods used by thosemanufacturers. It also adds credibility to publishedperformance data by ensuring that it is based on stan-dardized test procedures rather than estimates and cal-culations, as may have been the case in the past. Pur-chasing non-certified energy recovery equipment ex-poses the customer to the possibility of receiving equip-ment that will not perform as specified.

    ASHRAE Standard 90.1-2004Unlike the previous two standards, ASHRAE 90.1-

    2004, Energy Standard for Buildings Except Low-RiseResidential Buildings does not regulate the performanceof energy recovery equipment, but rather when it shouldbe used. The purpose of this standard is to provideminimum requirements for the energy efficient designof buildings. As previously mentioned, exhaust airenergy recovery provides the opportunity to conserveenergy in the HVAC system.

    Section 6.5.6.1 of Standard 90.1-2004 requires exhaustair energy recovery in Individual fan systems that haveboth a design supply air capacity of 5000 cfm or greaterand have a minimum outdoor air supply of 70% or

    greater of the design supply air quantity... Most com-fort cooling applications only require 15-25% minimumoutside air. However, even if energy recovery is notrequired by 90.1, its still a good idea because the en-ergy it saves means it has a very short payback time.

    Section 6.5.6.1 also requires a 50% or greater effec-tiveness in either the heating or cooling mode based onEquation 1. When the system includes an air econo-mizer, the standard requires that provisions be made toprevent the energy recovery device from increasingenergy usage during economizer mode. Several ex-

    FIGURE 18 ARI 1060 CERTIFICATION SEAL

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    11/12

    FORM 102.20-AG6 (305

    11YORK INTERNATIONAL

    ceptions to the energy recovery requirement exist, andfor more information on those exceptions, please referto the Standard.

    Energy recovery is also referenced in Section 6.5.2 -Simultaneous Heating and Cooling. This section al-lows simultaneous heating and cooling for tempera-ture or humidity control if site-recovered energy (in-

    cluding exhaust air energy recovery) or solar energyprovides at least 75% of the heat energy used to reheatthe air.

    ARI Guideline V

    This guideline, titled, Calculating the Efficiency ofEnergy Recovery Ventilation and its Effect on Effi-ciency and Sizing of Building HVAC Systems was pub-lished in 2003. It establishes an industry-approvedmethod of determining the efficiency of an HVAC sys-tem that includes energy recovery equipment. It alsoprovides guidance on how to size heating and coolingcomponents in an energy recovery system.

    Like ARI Standard 1060, Guideline V applies only toheat pipes, fixed plate exchangers and rotary heat ex-changers; it excludes run-around loop heat exchang-ers. Unlike ARI 1060, this guideline includes perfor-mance calculations for supply air tempering systems.Since such systems are not certified under Standard1060, ARI advises that results obtained using Guide-line V should not be considered certified.

    Guideline V introduces the concepts of Recovery Effi-ciency Ratio and Combined Efficiency to assist in ana-lyzing the performance of the HVAC system. Recov-ery Efficiency Ratio (RER), which is the efficiency of

    the energy recovery component in recovering energyfrom the exhaust airstream, is defined as, the energyrecovered divided by the energy expended in the re-covery process. The recovered energy can be relatedto humidification, dehumidification heating or cooling.The energy expended includes the added fan powerrequired to move the air through the heat exchangerand, in the case of an energy wheel, the wheel drivemotor power consumption.

    The Combined Efficiency (CEF) is a means of deter-mining the overall efficiency of an HVAC system in-corporating an energy recovery component and a uni-

    tary device such as a packaged air conditioner or heatpump. Depending on the conditioning device, the CEFcan be expressed in either Btu/(Wh) or W/W. An ex-ample in Appendix C of the guideline shows that a to-tal energy recovery device with an effectiveness of 70%can improve the cooling efficiency of an HVAC sys-tem from an EER of 10 Btu/(Wh) to a CEF of 13.46Btu/(Wh).

    LEED

    The Leadership in Energy and Environmental Design(LEED(tm)) rating system is the U.S. Green BuildingCouncils effort to provide a national standard forgreen buildings. Optimizing building energy usageis a key step in achieving certification and energy re-covery wheels are a key component in reducing HVAC

    system energy consumption. For building owners, eco-nomic incentives of LEED certification include higherrental rates than comparable buildings and possible taxbreaks for operating a green building.

    SUMMARY

    Exhaust air energy recovery technology provides a valu-able opportunity for engineers to reduce the first costsand operating costs of buildings. Owners benefit notonly in these initial and annual savings, but may alsoreceive incentives for operating a green building insome areas. Finally, the use of energy recovery reduce

    the use of non-renewable resources and promotes acleaner environment. Therefore, whether mandated bystate or local building codes, or not, proper applicationof energy recovery wheels and heat recovery in gen-eral is a win-win proposition.

    References

    Energy Information Agency, 2001. Commercial Build-ings Energy Consumption Survey.Washington, DCU.S. Department of Energy.

    ASHRAE. 2000. ASHRAE Handbook - 2000 HVACSystems & Equipment,chapter 44. Atlanta, GA: American Society of Heating, Refrigerating and Air-Condi-tioning Engineers, Inc.

    ASHRAE. 2001. ASHRAE Handbook - 2001 Fundamentals,chapter 27. Atlanta, GA: American Society ofHeating, Refrigerating and Air-Conditioning EngineersInc.

    Besant, Robert W., and Simonson, Carey J. Air-ToAir Energy Recovery.ASHRAE Journal,Volume 42Number 5, May 2000 - pp. 31 - 42.

    Besant, Robert W., and Simonson, Carey J. Air-ToAir Exchangers.ASHRAE Journal,Volume 45, Num-ber 4, April 2003 - pp. 42 - 52.

    ASHRAE. 2004.ANSI/ASHRAE/IESNA Standard 90.1- 2004 Energy Standard for Buildings Except Low-RiseResidential Buildings.Atlanta, GA: American Societyof Heating, Refrigerating and Air-Conditioning Engi-neers, Inc.

  • 7/24/2019 BE AppGuide EnergyRecoveryWheel AHU

    12/12

    ASHRAE 2002. ASHRAE Standard 90.1 User sManual,chapter 6. Atlanta, GA: American Society ofHeating, Refrigerating and Air-Conditioning Engineers,Inc.

    ASHRAE. 2004.ANSI/ASHRAE Standard 62 - 2004 -Ventilation for Acceptable Indoor Air Quality.Atlanta,GA: American Society of Heating, Refrigerating and

    Air-Conditioning Engineers, Inc.

    ASHRAE. 2001. ANSI/ASHRAE Standard 84 - 1991Method of Testing Air-To-Air Heat Exchangers.Atlanta,GA: American Society of Heating, Refrigerating andAir-Conditioning Engineers, Inc.

    Tele. 800-861-1001

    www.york.com

    P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA

    Copyright by York International Corporation 2001 ALL RIGHTS RESERVED

    Form 102.20-AG6 (305)

    ARI. 2000. Standard 1060 - 2000 Rating Air-To-AirEnergy Recovery Ventilation Equipment.Arlington, VA:Air-Conditioning and Refrigeration Institute.

    ARI. 2003. Guideline V - Guideline for Calculatingthe Efficiency of Energy Recovery Ventilation and ItsEffect on Efficicency and Sizing of Building HVAC Sys-tems.Arlington, VA: Air-Conditioning and Refrigera-

    tion Institute.

    ARI. 2003. Air-To-Air Energy Recovery VentilationEquipment Certified Product Directory.Arlington, VA:Air-Conditioning and Refrigeration Institute.