Basics of Power System Protection

download Basics of Power System Protection

of 17

Transcript of Basics of Power System Protection

  • 7/31/2019 Basics of Power System Protection

    1/17

    Power System Protection

    Why do we need system protection: Detect fault

    Isolate faulted component

    Restore faulted component

    Aims:

    Continued supply for rest of system

    Protect faulted part from damage

  • 7/31/2019 Basics of Power System Protection

    2/17

    Power System Protection

  • 7/31/2019 Basics of Power System Protection

    3/17

    3GE Consumer & Industrial

    Multilin

    1. Generator or Generator-Transformer Units

    2. Transformers

    3. Buses

    4. Lines (transmission and distribution)

    5. Utilization equipment (motors, static loads, etc.)

    6. Capacitor or reactor (when separately protected)

    Unit Generator-Tx zone

    Bus zone

    Line zone

    Bus zone

    Transformer zoneTransformer zone

    Bus zone

    Generator

    ~

    XFMR Bus Line Bus XFMR Bus Motor

    Motor zone

    ProtectionZones

  • 7/31/2019 Basics of Power System Protection

    4/17

    Zones of Protection

    Zones are defined for:

    Generators

    Transformers

    Buses

    Transmission and distribution lines

    Motors

  • 7/31/2019 Basics of Power System Protection

    5/17

    Zones of Protection

    For fault anyway within the zone, the

    protection system responsible to isolate

    everything within the zone from the rest of

    the system.

    Isolation done by CB

    Must isolate only the faulty equipment or

    section

  • 7/31/2019 Basics of Power System Protection

    6/17

    Zones of Protection

  • 7/31/2019 Basics of Power System Protection

    7/17

    Overlapped of Protection

    No blind spot:

    Neighboring zones are overlapped to avoid the

    possibility of unprotected areas

    Use overlapping CTs:

    Isolation done by CB. Thus, it must be inserted in

    each overlap region to identify the boundary of

    protective zones.

  • 7/31/2019 Basics of Power System Protection

    8/17

    Overlapped of Protection

    Overlap accomplish by having 2 sets of

    instrument transformers and relays for each CB.

    Achieved by the arrangement of CT and CB.

  • 7/31/2019 Basics of Power System Protection

    9/17

    9GE Consumer & Industrial

    Multilin

    1. Overlap is accomplished by the locations of CTs, the key source for protective

    relays.

    2. In some cases a fault might involve a CT or a circuit breaker itself, which

    means it can not be cleared until adjacent breakers (local or remote) are

    opened.

    Zone A Zone B

    Relay Zone A

    Relay Zone B

    CTs are located at both sides of CB-faultbetween CTs is cleared from both remote sides

    Zone A Zone B

    Relay Zone A

    Relay Zone B

    CTs are located at one side of CB-fault between CTs is sensed by both relays,

    remote right side operate only.

    Zone Overlap

  • 7/31/2019 Basics of Power System Protection

    10/17

    Primary & Back-up Protection

    Primary protection is the protection provided

    by each zone to its elements.

    However, some component of a zone

    protection scheme fail to operate.

    Back-up protection is provided which take

    over only in the event of primary protection

    failure.

  • 7/31/2019 Basics of Power System Protection

    11/17

    11

    GE Consumer & IndustrialMultilin

    Selection of protective relays requires compromises: Maximum and Reliable protection at minimum equipment

    cost

    High Sensitivity to faults and insensitivity to maximum load

    currents

    High-speed fault clearance with correct selectivity

    Selectivity in isolating small faulty area

    Ability to operate correctly under all predictable power

    system conditions

    Power System Protection

  • 7/31/2019 Basics of Power System Protection

    12/17

    12

    GE Consumer & IndustrialMultilin

    Cost of protective relays should be balancedagainst risks involved if protection is not sufficient

    and not enough redundancy.

    Primary objectives is to have faulted zonesprimary protection operate first, but if there are

    protective relays failures, some form of backup

    protection is provided.

    Backup protection is local (if local primary

    protection fails to clear fault) and remote (if remote

    protection fails to operate to clear fault)

    Power System Protection

  • 7/31/2019 Basics of Power System Protection

    13/17

    Power System Protection

    Simplicity

    Economy

    Speed

    Sensitivity

    Selectivity

    Reliability

  • 7/31/2019 Basics of Power System Protection

    14/17

    Power System Protection

    Reliability Operate dependably and in healthy operating condition

    when fault conditions occur, even after remaining idle formonths or years.

    Selectivity Clearly discriminate between normal and abnormal system

    condition to avoid unnecessary, false trips.

    Sensitivity Ability to distinguish the fault condition, although the

    different between fault and normal condition is small.

  • 7/31/2019 Basics of Power System Protection

    15/17

    Power System Protection

    Speed Fault at any point in the system must be detected and

    isolated rapidly to minimize fault duration and equipmentdamage. Any intentional time delays should be precise.

    Economy Provide maximum protection at minimum cost

    Simplicity Minimize protection equipment and circuitry

  • 7/31/2019 Basics of Power System Protection

    16/17

    Power System Protection

  • 7/31/2019 Basics of Power System Protection

    17/17

    Power System Protection