Basics of Power System Protection
-
Upload
sharadbpatel -
Category
Documents
-
view
224 -
download
2
Transcript of Basics of Power System Protection
-
7/31/2019 Basics of Power System Protection
1/17
Power System Protection
Why do we need system protection: Detect fault
Isolate faulted component
Restore faulted component
Aims:
Continued supply for rest of system
Protect faulted part from damage
-
7/31/2019 Basics of Power System Protection
2/17
Power System Protection
-
7/31/2019 Basics of Power System Protection
3/17
3GE Consumer & Industrial
Multilin
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Transformer zoneTransformer zone
Bus zone
Generator
~
XFMR Bus Line Bus XFMR Bus Motor
Motor zone
ProtectionZones
-
7/31/2019 Basics of Power System Protection
4/17
Zones of Protection
Zones are defined for:
Generators
Transformers
Buses
Transmission and distribution lines
Motors
-
7/31/2019 Basics of Power System Protection
5/17
Zones of Protection
For fault anyway within the zone, the
protection system responsible to isolate
everything within the zone from the rest of
the system.
Isolation done by CB
Must isolate only the faulty equipment or
section
-
7/31/2019 Basics of Power System Protection
6/17
Zones of Protection
-
7/31/2019 Basics of Power System Protection
7/17
Overlapped of Protection
No blind spot:
Neighboring zones are overlapped to avoid the
possibility of unprotected areas
Use overlapping CTs:
Isolation done by CB. Thus, it must be inserted in
each overlap region to identify the boundary of
protective zones.
-
7/31/2019 Basics of Power System Protection
8/17
Overlapped of Protection
Overlap accomplish by having 2 sets of
instrument transformers and relays for each CB.
Achieved by the arrangement of CT and CB.
-
7/31/2019 Basics of Power System Protection
9/17
9GE Consumer & Industrial
Multilin
1. Overlap is accomplished by the locations of CTs, the key source for protective
relays.
2. In some cases a fault might involve a CT or a circuit breaker itself, which
means it can not be cleared until adjacent breakers (local or remote) are
opened.
Zone A Zone B
Relay Zone A
Relay Zone B
CTs are located at both sides of CB-faultbetween CTs is cleared from both remote sides
Zone A Zone B
Relay Zone A
Relay Zone B
CTs are located at one side of CB-fault between CTs is sensed by both relays,
remote right side operate only.
Zone Overlap
-
7/31/2019 Basics of Power System Protection
10/17
Primary & Back-up Protection
Primary protection is the protection provided
by each zone to its elements.
However, some component of a zone
protection scheme fail to operate.
Back-up protection is provided which take
over only in the event of primary protection
failure.
-
7/31/2019 Basics of Power System Protection
11/17
11
GE Consumer & IndustrialMultilin
Selection of protective relays requires compromises: Maximum and Reliable protection at minimum equipment
cost
High Sensitivity to faults and insensitivity to maximum load
currents
High-speed fault clearance with correct selectivity
Selectivity in isolating small faulty area
Ability to operate correctly under all predictable power
system conditions
Power System Protection
-
7/31/2019 Basics of Power System Protection
12/17
12
GE Consumer & IndustrialMultilin
Cost of protective relays should be balancedagainst risks involved if protection is not sufficient
and not enough redundancy.
Primary objectives is to have faulted zonesprimary protection operate first, but if there are
protective relays failures, some form of backup
protection is provided.
Backup protection is local (if local primary
protection fails to clear fault) and remote (if remote
protection fails to operate to clear fault)
Power System Protection
-
7/31/2019 Basics of Power System Protection
13/17
Power System Protection
Simplicity
Economy
Speed
Sensitivity
Selectivity
Reliability
-
7/31/2019 Basics of Power System Protection
14/17
Power System Protection
Reliability Operate dependably and in healthy operating condition
when fault conditions occur, even after remaining idle formonths or years.
Selectivity Clearly discriminate between normal and abnormal system
condition to avoid unnecessary, false trips.
Sensitivity Ability to distinguish the fault condition, although the
different between fault and normal condition is small.
-
7/31/2019 Basics of Power System Protection
15/17
Power System Protection
Speed Fault at any point in the system must be detected and
isolated rapidly to minimize fault duration and equipmentdamage. Any intentional time delays should be precise.
Economy Provide maximum protection at minimum cost
Simplicity Minimize protection equipment and circuitry
-
7/31/2019 Basics of Power System Protection
16/17
Power System Protection
-
7/31/2019 Basics of Power System Protection
17/17
Power System Protection