Basic Generator Control Loops

21
SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK BASIC GENERATOR CONTROL LOOPS In an interconnected power system, load frequency control (LFC) and automatic voltage regulator (AVR) equipment are installed for each generator. Figure2.1 represents the schematic diagram of the load frequency control (LFC) loop and the automatic voltage regulator (AVR) loop. The controllers are set for a particular operating condition and take care of small changes in load demand to maintain the frequency and voltage magnitude within the specified limits. Small changes in real power are mainly dependent on changes in rotor angle “δ” and, thus, the frequency. The reactive power is mainly dependent on the voltage magnitude (i.e., on the generator excitation). The excitation system time constant is much smaller than the prime mover time constant and its transient decay much faster and does not affect the LFC dynamics. Thus, the cross-coupling between the LFC loop and the AVR loop is negligible, and the load frequency and excitation voltage control are analyzed independently.

Transcript of Basic Generator Control Loops

Page 1: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

BASIC GENERATOR CONTROL LOOPS

In an interconnected power system, load frequency control (LFC) and automatic

voltage regulator (AVR) equipment are installed for each generator. Figure2.1

represents the schematic diagram of the load frequency control (LFC) loop and the

automatic voltage regulator (AVR) loop. The controllers are set for a particular

operating condition and take care of small changes in load demand to maintain the

frequency and voltage magnitude within the specified limits. Small changes in real

power are mainly dependent on changes in rotor angle “δ” and, thus, the frequency.

The reactive power is mainly dependent on the voltage magnitude (i.e., on the

generator excitation). The excitation system time constant is much smaller than the

prime mover time constant and its transient decay much faster and does not affect the

LFC dynamics. Thus, the cross-coupling between the LFC loop and the AVR loop is

negligible, and the load frequency and excitation voltage control are analyzed

independently.

Figure 2.1 Schematic diagram of LFC and AVR of a synchronous generator

Page 2: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Page 3: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

3. LOAD FREQUENCY CONTROL

The operation objectives of the LFC are to maintain reasonably uniform frequency, to divide the

load between generators, and to control, and to control the tie-line interchange schedules. The

change in frequency and tie-line real power are sensed, which is a measure of the change in rotor

angle ‘δ’, i.e., the error ‘Δδ’ to be corrected. The error signal, i.e., Δf and ΔP tie, are amplified,

mixed, and transformed into a real power command signal ΔPv, which is sent to the prime mover

to call for an increment in the torque.

The prime mover, therefore, brings change in the generator output by an amount ΔPg which will

change the values of Δf and ΔPtie within the specified tolerance.

The first step in the analysis and design of a control system is mathematical modeling of the

system. The two most common methods are the transfer function method and the state variable

approach. The state variable approach can be applied to the portray linear as well as nonlinear

systems. In order to use the transfer function the system must first be linearized. The transfer

function models for following components are obtained.

Page 4: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

3. LOAD FREQUENCY CONTROL

The operation objectives of the LFC are to maintain reasonably uniform frequency, to divide the

load between generators, and to control, and to control the tie-line interchange schedules. The

change in frequency and tie-line real power are sensed, which is a measure of the change in rotor

angle ‘δ’, i.e., the error ‘Δδ’ to be corrected. The error signal, i.e., Δf and ΔP tie, are amplified,

mixed, and transformed into a real power command signal ΔPv, which is sent to the prime mover

to call for an increment in the torque.

The prime mover, therefore, brings change in the generator output by an amount ΔPg which will

change the values of Δf and ΔPtie within the specified tolerance.

The first step in the analysis and design of a control system is mathematical modeling of the

system. The two most common methods are the transfer function method and the state variable

approach. The state variable approach can be applied to the portray linear as well as nonlinear

systems. In order to use the transfer function the system must first be linearized. The transfer

function models for following components are obtained.

3.1 GENERATOR MODEL

One of the essential components of power systems is the three phase ac generator known as

synchronous generator or alternator. Synchronous generators have two synchronously rotating

fields: one field is produced by the rotor driven at synchronous speed and excited by dc current.

The other field is produced in the stator windings by the three-phase armature currents. The dc

current for the rotor windings is provided by excitation systems. Today system use ac generators

with rotating rectifiers, known as brushless excitation systems. The generator excitation system

maintains generator voltage and controls the reactive power flow.

Page 5: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

ΔPm(s) 1/2Hs ΔΩ(s)

_

ΔPe(s)

Figure 3.1 Transfer function model for generator model

In a power plant, the size of generators can vary fro 50 MW to 1500 MW.

3.2 LOAD MODELThe load on a power system consists of a variety of electrical devices. For resistive loads, such as

lighting and heating loads, the electrical power is independent of frequency. Motor loads are

sensitive to changes in frequency. How sensitive it is to frequency depends on the composite of

the speed-load characteristics of all the driven devices. Including the load model in the generator

block diagram, results in the block diagram of Figure 3.2.

ΔPL(s)

_

Page 6: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

ΔPm(s) 1/(2Hs+D) ΔΩ(s)

Figure 3.2 Transfer function model for load model

3.3 PRIME MOVER MODELThe source of mechanical power, commonly known as prime mover, may be hydraulic turbines

at waterfalls, steam turbines whose energy comes from the burning of coal, gas, nuclear fuel, and

gas turbines. The model of the turbines relates change in mechanical power output ΔPm to

changes in steam valve position ΔPv. Different types of turbines vary widely in characteristics.

The simplest prime mover model for the nonreheat steam turbine can be approximated with a

single time constant TT. The time constant TT is in the range of 0.2 to 2.0 seconds.

ΔPV(s) 1/(1+TTs) ΔPm(s)

Figure 3.3 block diagram for a simple nonreheat steam turbine

3.4 GOVERNOR MODEL

When the generator electrical load is suddenly increased, the electrical power exceeds the

mechanical power input. This power deficiency is supplied by the kinetic energy stored in the

rotating system. The reduction in kinetic energy causes the turbine speed and, consequently, the

generator frequency to fall. The change in speed is sensed by the turbine governor which acts to

Page 7: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

adjust the turbine input valve to change the mechanical power output to bring the speed to a new

steady-state. The earliest governors were the watt governors which sense the speed by means of

rotating flyballs and provide mechanical motion in response to speed changes. However, most

modern governors use electronic means to sense speed changes. Figure 3.4 shows schematically

the essential elements of a conventional Watt governor which consists of the following major

parts.

1. Speed governor: The essential parts are centrifugal flyballs driven directly or through

gearing by the turbine shaft. The mechanism provides upward and downward vertical

movements proportional to the change in speed.

2. Linkage Mechanism: These are links for transforming the flyballs movement to the turbine

valve through a hydraulic amplifier and providing a feedback from the turbine valve movement.

Page 8: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Figure 3.4 Speed governing system

3. Hydraulic Amplifier: Very large mechanical forces are needed to operate the steam valve.

Therefore, the governor movements are transformed into high power forces via several stages of

hydraulic amplifiers.

4. Speed Charger: the speed charger consist of servomotor which can be operated manually or

automatically for scheduling load at nominal frequency.

By adjusting this set point, a desired load dispatch can be scheduled at nominal frequency.

ΔPL(s)

Page 9: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

_

ΔPref(s) ΔPg ΔPV ΔPm

1/(1+Tgs) 1/(1+TTs) 1/(2Hs+D)

_

Governor Turbine Rotating mass

and load

1/R

Figure 3.5 LFC block diagram of an isolated system

ΔΩ(s)

Page 10: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Page 11: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

4. AUTOMATIC GENERATION CONTROL

When the load on the system is increased, the turbine speed drops before the governor can adjust

the input of the steam to the new load. As the change in the value of speed diminishes, the error

signal becomes smaller and position of the governor falls gets closer to the point required to

maintain a constant speed. However the constant speed will not be the set point, and there will be

offset. One way to restore the speed or frequency to its nominal value is to add an integrator.

The integral unit monitors the average error over a period of time and will overcome the offset.

Because of its ability to return a system to its set point, integral action is known as the rest

action. Thus, as the system load change continuously, the generation is adjusted automatically to

restore the frequency to the nominal value .This scheme is known as the “automatic generation

control” (AGC).

In an interconnected system consisting of several pools, the role of the automatic generation

control (AGC) is to divide the loads among system, station generators so as to achieve maximum

economy and correctly control the scheduled interchanges of tie-line power while maintaining a

reasonably uniform frequency. During large transient disturbances and emergencies, AGC is

bypassed and other emergency controls are applied.

Modern power system network consists of a number of utilities interconnected together & power

is exchanged between utilities over tie-lines by which they are connected. Automatic generation

control (AGC) plays a very important role in power system as its main role is to maintain the

system frequency and tie line flow at their scheduled values during normal period and also when

the system is subjected to small step load perturbations. Many investigations in the field of

automatic generation control of interconnected power system have been reported over the past

few decades.

Page 12: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

4.1 AGC IN A SINGLE AREA SYSTEMWith the primary LFC loop, a change in the system load will result in a steady-state frequency

deviation, depending on the governor speed regulation. In order to reduce the frequency

deviation to zero, we must provide a reset action. The rest action can be achieved by introducing

an integral controller to act on the load reference setting to change the speed set point. The

integral controller increases the system type by one which forces the final frequency deviation to

zero. The LFC system, with addition the addition of the secondary Figure 4.1. The integral

controller gain KI must be adjusted for a satisfactory transient response.

ΔPL(s)

_

ΔPref(s) ΔPg ΔPV ΔPm

1/(1+Tgs) 1/(1+TTs) 1/(2Hs+D)

Governor Turbine Rotating mass

and load

1/R

KI/s

Page 13: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Figure 4.1 AGC for an isolated power system

4.2 AGC IN MULTIAREA SYSTEMIn many cases, a group of generators are closely coupled internally and swing in unison.

Furthermore, the generator turbines tend to have the same response characteristics. Such a group

of generators are said be coherent. Then it is possible to let the LFC loop represent the whole

system, which is referred to as control area. The AGC of a multiarea system can be realized by

studying first the AGC for a two-area system. Consider two areas represented by an equivalent

by an equivalent generating unit interconnected by a lossless tie line with reactance X tie. Each

area is represented by a voltage source behind an equivalent reactance as shown in Figure 4.2.

Figure 4.2 Equivalent network for two area power system

During normal operation, the real power transferred over the tie line is given by

P12 = |E1| |E2| sinδ12

X12

Page 14: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Where X12 = X1+ Xtie+ X2, and δ12= δ1 - δ2.

The tie line power deviation then takes on the form

ΔP12 = Ps(Δδ1 - Δδ2)

The tie line power flow appears as a load increase in one area and a load decrease in the other

area, depending on the direction of the flow. The direction of the flow. The direction of flow is

dictated by phase angle difference; if Δδ1 > Δδ2, the power flows from area 1 to area 2. A block

diagram representation for the two-area system with LFC containing only the primary loop is

shown in Figure 4.3.

Page 15: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Figure 4.3 Two area system with primary LFC loop

4.3 TIE-LINE BIAS CONTROLIn the normal operating state, the power system is operated so that the demands of the areas are

satisfied at the nominal frequency. A simple control strategy for the normal mode is

Keep frequency approximately at nominal value.

Maintain the tie-line flow at about schedule.

Each area should absorb its own load charges.

Page 16: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Conventional LFC is based upon tie-line bias control, where each area tends to reduce the area

control error (ACE) to zero. The control error for each area tends to consists of linear

combination of frequency and tie-line error.

ACEi = Σnj=1 ΔPij +Ki Δω

The area bias Ki determines the amount of interaction during a disturbance in the neighboring

areas. An overall satisfactory performance is achieved when K is selected equal to the frequency

bias factor of that area, i.e., Bi =1/Ri +Di . Thus, the ACEs for a two area systems are

ACE1 = ΔP12 +B1 Δω1

ACE1 = ΔP21 +B2 Δω2

Where ΔP12 and ΔP21 are departures from scheduled interchanges. ACEs are used as actuating

signals to activate changes in the reference power set points, and when steady state is reached,

ΔP12 and Δω will be zero. The integrator gain constant must be chosen small enough so as not

cause the area to go into a chase mode. The block diagram of a simple AGC for two area system

is shown in Figure 4.4

Page 17: Basic Generator Control Loops

SIMULATION OF TWO AREA CONTROL SYSTEM USING SIMULINK

Figure 4.4 AGC block diagram for two area system