Publication Number -- Date Copyright © 2009 Rockw ell Automation, Inc. N999 – Basic Drive Programming PowerFlex 753 Presenter: <<Your name>> Rockwell Automation Drives Business For Classroom Use Only! N999 – Your lab title goes here Presenter: <<Your name>> <<Your business group>>

description

treinamento drives rockwell automation,

Transcript of Basic drive programing pf753

Page 1: Basic drive programing   pf753

Publication Number -- Date Copyright © 2009 Rockw ell Automation, Inc.

N999 – Basic Drive Programming PowerFlex 753

Presenter: <<Your name>> Rockwell Automation Drives Business

For Classroom Use Only!

N999 – Your lab title goes here

Presenter: <<Your name>> <<Your business group>>

Page 2: Basic drive programing   pf753
Page 3: Basic drive programing   pf753

3 of 68

PowerFlex 753 Basic Start Up for Speed Controlled

Applications

Contents

Before you begin .............................................................................................................................. 5

Tools ................................................................................................................................................. 5

About this lab ..................................................................................................................................... 5

About the Demo ................................................................................................................................ 6

Lab Setup.......................................................................................................................................... 7

Lab Objective .................................................................................................................................... 8

Using the Human Interface Module (H.I.M)........................................................................................ 9

Disabling DeviceLogix Program – IF LOADED & RUNNING ............................................................ 10

Preparing the PowerFlex 753 Demo To Run In Simulation Mode .................................................... 14

Assisted Startup using the Human Interface Module (H.I.M)........................................................... 16

Resetting factory defaults .................................................................................................................. 17

Setting the Motor Control Mode ......................................................................................................... 20

Entering Motor Nameplate Data......................................................................................................... 21

Setting the Speed Feedback Device .................................................................................................. 24

Setting the Speed Limits ................................................................................................................... 24

Direction Auto Tune and Inertia Tests ................................................................................................ 25

Configuring the Speed Reference and Ramp rates ............................................................................. 28

Configuring the Inputs and Outputs .................................................................................................... 30

Page 4: Basic drive programing   pf753

4 of 68

Drive Programming via Software Tool (Optional) ........................................................................... 32

About This Section............................................................................................................................ 32

Using Drive Explorer with PF753 ....................................................................................................... 32

Starting Drive Explore and Connect To Drive ...................................................................................... 33

Reset Drive to Defaults ..................................................................................................................... 36

Displaying The Status View ............................................................................................................... 39

Displaying Parameters with the Linear List View ................................................................................. 43

Displaying Parameters with the File / Group View ............................................................................... 44

Using the Startup Wizard................................................................................................................... 45

Using the Control Bar Tool ................................................................................................................ 62

Using Off-line Files ........................................................................................................................... 64

Page 5: Basic drive programing   pf753

5 of 68

Before you begin

Tools

PowerFlex 753 Training Demo

Windows XP PC with DriveExplorer (full version 6.02 or greater); for optional section

About this lab

This session provides you with an opportunity to explore the PowerFlex 753 AC drive. In this session you

will learn to:

Use the Assisted Startup for simple Speed Controlled Applications

Control the Drive and simulate spinning a motor

This lab takes approximately 45 minutes to complete.

Page 6: Basic drive programing   pf753

6 of 68

About the Demo

The DHQ packaged PowerFlex 753 Demo is a reduced size, packaged demo kit for demonstrating

programming of PowerFlex 753, as well as Premier Integration, and DeviceLogix. On board I/O facilitates

user input as well as feedback.

This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives

internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production

drive the demo itself was not designed to run an actual motor. There are no user connections to apply an

external motor nor was the internal step up transformer or fusing sized to run anything greater then the

drive rated current w/o any loading.

The image below labels the switches, push buttons and the potentiometer required in this lab session.

DRIVE POWER Circuit Breaker

Di 1 – Normally Closed Pushbutton

Di 0 – Normally Open Pushbutton

0- 10 V Analog Input

Di 2 – Selector Switch

Page 7: Basic drive programing   pf753

7 of 68

Lab Setup

1. On the PowerFlex 753 demo case, verify position switch Di 2 is selected to the left (OFF)

2. Energize the drive demo; switch the single-pole breaker labeled ‘POWER’, located on the front of

the demo, to the on position.

Page 8: Basic drive programing   pf753

8 of 68

Lab Objective

At the end of this lab, you should have successfully completed the Assisted Startup routine of the PF753

drive and

1. Programmed the Drive to start the drive/motor using the green pushbutton labeled ‘Di 1’.

2. Programmed the Drive to stop the drive/motor using the red pushbutton labeled ‘Di 0’.

3. Programmed the Drive to forward or reverse the drive/motor using the selector switch labeled ‘Di

2’.

4. Programmed the Drive to get Speed Reference from an Analog Source, the potentiometer

labeled ‘0-10 INPUT’.

Page 9: Basic drive programing   pf753

9 of 68

Using the Human Interface Module (H.I.M)

The image below shows some of the essential keys which you will be using in this session. Please

familiarize yourself with these keys (buttons)

PowerFlex 753

20F . . . B4P2

240V 4.2A

00

Soft Keys

Navigation Keys

Enter Key

Stop Key

Start Key Folders Key

Page 10: Basic drive programing   pf753

10 of 68

Disabling DeviceLogix Program – IF LOADED & RUNNING

If a DeviceLogix Program is loaded and running in the PowerFlex 753 demo, the logic needs to be

disabled and the drive reset prior to conducting the lab. If the DeviceLogix program has not been

properly disabled, the drive will not operate according to the lab procedure.

Consult with your instructor before performing the following procedure:

1. From the Status screen which is displayed on HIM PowerUp. Use the left or right

arrow keys to navigate to the DeviceLogix option.

PowerFlex 753

20F . . . B4P2

240V 4.2A

DeviceLogix

LogicEnabled

Embedded

14

2. The HIM screenshot above shows the display if the DeviceLogix is enabled ‘LogicEnabled’. If the

logic is disabled ‘LogicDisabld’ then disabling of the DeviceLogix is not required, skip to the next

section.

3. Press the ‘PAR#’ soft key and enter the number 53 followed by the ‘ENTER’ soft key to goto

parameter 53

Devi ceLogi xJump t o Par am #

5314

LogicEnabled 6

DLX Operation

Por t 14 Host Par am 53

Page 11: Basic drive programing   pf753

11 of 68

4. Use the ‘EDIT’ soft key followed by the scroll down or scroll up arrow soft keys to change

parameter #53 to DisableLogic then the ‘ENTER’ soft key to confirm.

Edi t DLX Oper at i on

0 << 6

DisableLogic 1

LogicDisabld 5

DLX Operation

Por t 14 Host Par am 53

Parameter 53 [DLX Operation] is of the parameter type that contains both operation commands as well as status information. Setting it to disable logic is option 1, however once the ‘ENTER’ key is pressed to confirm the display is option 5 “LogicDisabled”.

5. Press the ‘ESC’ soft key to return the display to the top level DeviceLogix screen

DeviceLogix

LogicDisabld

Embedded

14

6. Use the left or right arrow keys to navigate to the drives initial screen (Main

Control Board Slot 0)

PowerFlex 753

20F . . . B4P2

240V 4.2A

Page 12: Basic drive programing   pf753

12 of 68

7. Press the ‘Folders’ button on the HIM keypad. The button is located on the bottom row of

the HIM Keypad (shown circled in the left image below).Pressing the ‘Folders’ button changes the

HIM screen display to the Folders screen ( see right image below)

PowerFlex 753

20F . . . B4P2

240V 4.2A

00

PORTS

06 20- COMM- E

00 Power Fl ex 75301 20- HI M- x6

14 Devi ceLogi x

8. Use the left or right arrow keys to scroll through the different folders, to locate the

folder called ‘DIAGNOSTIC’.

DI AGNOSTI C

Faul t s

Reset Devi ce

Al ar ms

Di agnost i c I t ems

Page 13: Basic drive programing   pf753

13 of 68

9. Use the down arrow key to highlight ‘ Reset Device’ then press the Enter key

located in the center of the HIM keypad to make this your selection.

DI AGNOSTI C

Reset Devi ce

Faul t s

Al ar ms

Di agnost i c I t ems

10. A confirmation screen follows press the ‘ENTER’ soft key to confirm your selection.

C O N F I R M

Ar e you sur e you want t or eset t he devi ce

11. The drive will then reset, upon completion the drive maybe faulted; press the ‘CLR’ soft key to

clear acknowledge and clear fault.

Page 14: Basic drive programing   pf753

14 of 68

Preparing the PowerFlex 753 Demo To Run In Simulation Mode

This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives

internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production

drive the demo itself was NOT designed to run an actual motor. In order to complete the lab the feedback

mode needs to changed to simulate.

1. From the Status screen which is displayed on HIM PowerUp. Press the ‘PAR#’ soft key and

enter the number 301 using the numeric keypad followed by the ‘ENTER’ soft key to goto

parameter 301 [Access Level]

PowerFlex 753

20F . . . B4P2

240V 4.2A

Expert 2

Access Level

Por t 00 Dev Par am 301

2. Verify that P301 [Access Level] is set to ‘Expert’ if not press the ‘EDIT’ soft key followed by the

scroll down or scroll up arrow soft keys to change the parameter to Expert then the

‘ENTER’ soft key to confirm.

Edi t Access Level

0 << 2

Basic 0

Expert 2

Access Level

Por t 00 Dev Par am 301

Page 15: Basic drive programing   pf753

15 of 68

3. Press the ‘PAR#’ soft key and enter the number 125 followed by the ‘ENTER’ soft key to goto

parameter 125 [Pri Vel Fdbk Sel]

Power Fl ex 753Jump t o Par am #

12500

Pri Vel Fdbk Sel

Por t 00 Dev Par am 125

Por t Power Fl ex 753

P0137P00

EDI T

4. Press the ‘EDIT’ soft key, the default (and only choice) for ‘Edit Spd Ref A Sel’ is PowerFlex 753.

Make this selection using the ‘Enter’ soft key

Edi t Spd Ref A SelSel ect Par m To Use

Power Fl ex 753Port 00

5. For ‘Pri Vel Fdbk Sel’ selection use the down arrow key to select ‘Simulator Fdbk’. Then

make this selection using the ‘Enter’ soft key.

Edi t Pr i Vel Fdbk SelSel ect Par m To Use

Si mul at or FdbkPar 0137Par 0138

Open Loop Fdbk

6. Press the ‘ESC’ soft key to return the display to the top level Status Screen.

Page 16: Basic drive programing   pf753

16 of 68

Assisted Startup using the Human Interface Module (H.I.M)

One of the ways to perform an Assisted Startup on the PowerFlex 753 is using the Startup routine in the

H.I.M. The following steps will lead you through that:

1. Access the Status screen which is displayed on HIM PowerUp.

PowerFlex 753

20F . . . B4P2240V 4.2A

2. Press the ‘Folders’ button on the HIM keypad. The button is located on the bottom row of

the HIM Keypad (shown circled in the left image below).Pressing the ‘Folders’ button changes the

HIM screen display to the Folders screen ( see right image below)

PowerFlex 753

20F . . . B4P2

240V 4.2A

00

PORTS

06 20- COMM- E

00 Power Fl ex 75301 20- HI M- x6

14 Devi ceLogi x

Page 17: Basic drive programing   pf753

17 of 68

Resetting factory defaults

3. Use the left or right arrow keys to scroll through the different folders, to locate the

folder called ‘MEMORY’.

MEMORY

HI M CopyCat

Set Def aul t s

4. Use the down arrow key to highlight ‘ Set Defaults’ if necessary and press the Enter key

located in the center of the HIM keypad to make this your selection.

5. The screen which follows after completion of the previous step is shown. Use the down arrow key

to highlight ‘This Port only’. Press the Enter key located in the center of the HIM

keypad to make this your selection.

ESC INFO

Por t 00 Set Def aul t s

Host and Por t s ( Pr ef er r ed)

Thi s Por t Onl y

Page 18: Basic drive programing   pf753

18 of 68

6. Use the soft key labeled ‘ALL’ to reset default all parameter settings in the Drive.

W A R N I N G

Use MOST t o r eset t ypi cal

set t i ngs on t hi s por t

( pr ef er r ed) . Use ALL t o

r eset al l set t i ngs

ALL MOST

7. Use the ‘CLR’ soft key to acknowledge and clear the ‘Module Defaulted’ fault.

8. If you receive a screen that confirms that setting factor defaults is complete press the ‘ENTER’

soft key to confirm.

9. Press the ‘Folders’ button on the HIM keypad again to access the Folders Menu.

10. Now use the left or right arrow keys to scroll through the different folders, to

locate the folder called ‘START UP’.

START UP

Begi n St ar t Up

11. The first item listed in the ‘START UP’ folder is ‘Begin Start Up’ and this is highlighted by default.

Press the Enter key located in the center of the HIM keypad to make this your selection.

Page 19: Basic drive programing   pf753

19 of 68

12. The startup routine starts with an Introduction screen. Press the ‘ENTER’ soft key to continue.

The ‘ENTER’ soft key is located on the top row of the HIM keypad.

Power Fl ex 753 St ar t up

St ar t - Up consi st s of sever al

st eps t o conf i gur e t he dr i ve.

Pr ess ENTER

ABORT ENTER

Note: You can always use the ESC soft key to return to a previous step.

13. Pressing the ‘ENTER’ soft key in the previous step has led you to a new screen, which allows you

to select the type of startup you wish to perform. For this lab session, we will choose ‘General

Startup’. This is highlighted by default. Press the ‘ENTER’ soft key located on the top row of the

HIM keypad to make this your selection.

Power Fl ex 753 St ar t up

ABORT ENTER

Gener al St ar t up

Appl Speci f i c

Exi t St ar t up

Page 20: Basic drive programing   pf753

20 of 68

Setting the Motor Control Mode

14. Pressing the ‘ENTER’ soft key in the previous step has led you to the ‘General Startup Main

Menu’. You will go through steps listed in this menu to configure your drive. Press ‘ENTER’ soft

key to enter the first section ‘Motor Control’.

ABORT ENTER

Gener al St ar t up

Mot or Cont r ol

Mot or Dat a

Feedback

Mai n Menu

Li mi t s

Compl et e t hese st eps i n or der :

15. The introduction screen provides information about the ‘Motor Control section. Press the ‘ENTER’

soft key to continue.

Thi s sect i on sel ect s t he t ype

of Mot or Cont r ol t he dr i ve wi l l

use.

Pr ess ENTER

ABORT ENTER

St ar t up

Mot or Cont r ol

Page 21: Basic drive programing   pf753

21 of 68

16. Pressing the ‘ENTER’ soft key in the previous step leads you to a screen which lists the available

motor control modes in the PowerFlex 753. For this lab session, we will choose the Flux Vector

mode. Use the down arrow key to navigate and select ‘Flux Vector’. Press the ‘ENTER’

soft key to make this your selection.

ABORT ENTER

Sensor l ess Vect

V/ Hz

Fl ux Vect or

St ar t up

Mot or Cont r ol

Pl ease Sel ect :

17. Pressing the ‘ENTER’ soft key in the previous step leads you to a screen which lists the available

Control Modes in the PowerFlex 753. For this lab session, we will choose the default selection of

‘Speed’. Press the ‘ENTER’ soft key to make this your selection

Entering Motor Nameplate Data

18. After selecting the motor control mode in the previous step, you are directed back to the General

Startup Main Menu. ‘Motor Data’ should be highlighted now. Press the ‘ENTER’ soft key to

make this your selection. The next few steps will require you to input the nameplate information

of the motor you are doing a Startup on.

ABORT ENTER

Gener al St ar t up

Mot or Cont r ol

Mot or Dat a

Feedback

Mai n Menu

Li mi t s

Compl et e t hese st eps i n or der :

Page 22: Basic drive programing   pf753

22 of 68

19. Pressing the ‘ENTER’ soft key in the previous step has led you to the ‘Startup Motor Data Entry’

screen. The first information you will provide is the Motor Nameplate (NP) Volts. The Motor in the

demo is rated for 230 V. This should be the default value for this parameter. Press the ‘ENTER’

soft key to confirm your input and move to the next screen.

Edi t Mot or NP Vol t s

0.10 << 264.50

230.00 VAC

St ar t up

Mot or Dat a Ent r y

20. The next information you need to provide is the Power Units. By default the value of the

parameter should be set to ‘HP’. Press the ‘ENTER’ soft key to confirm your selection and move

to the next screen.

ABORT ENTER

St ar t up

HP

kW

Mot or Dat a Ent r y

Sel ect t ype of power uni t s

Shown on mot or namepl at e:

Page 23: Basic drive programing   pf753

23 of 68

21. You will now be required to input the Motor Nameplate (NP) Power. Since there actually is no

motor connected use the default of 1.00 HP Press the ‘ENTER’ soft key to confirm your input and

move to the next screen.

Edi t Mot or NP Power

0.01 << 2000.00

1.00 HP

St ar t up

Mot or Dat a Ent r y

22. You will now be required to input the Motor Nameplate (NP) Amperes. Again accept the default

value here. Press the ‘ENTER’ soft key to confirm your input and move to the next screen.

Edi t Mot or NP Amps

0.01 << 42.00

2.90 Amps

St ar t up

Mot or Dat a Ent r y

23. Continue through the Startup / Motor Data Entry section choosing the default values. Once all

the Motor Data Entry steps are complete you will be brought back to the General Startup Main

Menu with “Feedback” being highlighted.

Page 24: Basic drive programing   pf753

24 of 68

Setting the Speed Feedback Device

24. Setting the Speed Feedback Device will be skipped in this lab – going back to “About The Demo”

section there is physically no actually motor and the demo unit was selected to a simulated

feedback. Selecting this option now would force a feedback selection that is NOT valid for

simulation mode.

Setting the Speed Limits

25. In the previous step configuring your feedback device was skipped; configuring the limits is the

next step in the Startup routine. Use the down arrow key to navigate to the ‘Limits’ step.

. Press the ‘ENTER’ soft key to access ‘Limits’ section.

ABORT ENTER

Gener al St ar t up

Mot or Cont r ol

Mot or Dat a

Feedback

Mai n Menu

Li mi t s

Compl et e t hese st eps i n or der :

26. For this lab session, we will not be changing the limits but verify the following selections in the

‘Limits’ section. Use the number keys to input the values listed for each item and press the

‘ENTER’ soft key to move forward to the next screen. After the four values have been entered,

you will be exited out of this section.

Max Fwd Speed = 60 Hz

Max Rev Speed = -60 Hz (you can directly enter a value of ‘60’; the negative sign is defaulted)

Min Fwd Speed = 0.00 Hz

Min Rev Speed = 0.00 Hz

Page 25: Basic drive programing   pf753

25 of 68

Direction Auto Tune and Inertia Tests

27. You should now have been directed back to the General Startup Main Menu. The ’Tests’ section

is next and should be highlighted by default at this stage. Press the ‘ENTER’ soft key to access

‘Tests’ section.

ABORT ENTER

Gener al St ar t up

Test s

Mot or Dat a

Feedback

Mai n Menu

Li mi t s

Compl et e t hese st eps i n or der :

28. There are two tests which are part of the Startup Routine. You will perform these tests in the next

few steps. You will run the Direction test first. The ‘Direction Test’ list item should be highlighted

by default. Press the ‘ENTER’ soft key to make this your selection. Press the Start key to

start the motor.

29. The next screen asks the question ‘Is the direction of rotation forward?’ To demonstrate the

ability of the PowerFlex 753 to electronically swap motor leads to change motor direction, let us

choose ‘No’ as the answer to this question. Use the down arrow key to select and

highlight ‘No’ and press the Press the ‘ENTER’ soft key.

St ar t up

Di r ect i on Test

Yes

No

I s t he di r ect i on of r ot at i on

f or war d?

Page 26: Basic drive programing   pf753

26 of 68

30. The next screen asks the question ‘How would you like to fix motor polarity? ’. Select the default

highlighted option ‘Automatic change’ by using the ‘ENTER’ soft key.

St ar t up

Di r ect i on Test

Change mt r wi r es

How woul d you l i ke t o f i x t he

mot or pol ar i t y?

Aut omat i c Change

31. The screen that follows asks you to stop the drive so this change in direction, initiated in the

previous step, can take place. Press the ‘STOP’ key to stop the drive.

St ar t up

Di r ect i on Test

Pr ess STOP

St ar t up wi l l t hen aut omat i cal l y

change r ot at i on as i f mot or

l eads wer e r ever sed

32. Follow the direction on the next screen which asks you to ‘START’ the drive. You can start the

drive and by using the START key.

33. The next screen asks the question ‘Is the direction of rotation forward?’ and requires confirmation

that the changes to direction are acceptable. Select ‘Yes’ by pressing the ‘ENTER’ soft key.

34. Press the Stop key .This should successfully complete the Direction test.

35. You should now be back in the ‘Motor Test Menu’ screen. Now use the ‘ENTER’ soft key to select

the ‘Auto tune’ Test. Read the important information on the screen and press the ‘ENTER’ soft

key.

Page 27: Basic drive programing   pf753

27 of 68

36. Pressing the ‘ENTER’ soft key in the previous step has directed you to the ‘Select the tuning

mode’ screen. For this lab session, we will perform a rotate tune on the demo motor. Select the

default highlighted option ‘Rotate Tune’ by pressing the ‘ENTER’ soft key.

37. As directed by the HIM screen information, press the START key to start the ‘Auto tune’

Test. Notice the changing information on the HIM (as the different parts of the Auto tune tests are

completed).Wait till the test is completed.

St ar t up

Aut o Tune

Test i n pr ogr ess:St at or Resi st ance

Pl ease Wai t

Pr ess STOP t o abor t t est

St ar t up

Aut o Tune

Test i n pr ogr ess:Fl ux Cur r ent

Pl ease Wai t

Pr ess STOP t o abor t t est

38. The completion of the test is indicated by the ‘Test Completed Successfully’ screen. Press the

‘ENTER’ soft key.

39. Select the ‘Inertia Test’ using the ‘ENTER’ soft key and use the ‘ENTER’ soft key again to confirm

that the load is connected to the motor.

40. As directed by the HIM screen information, press the START key to start the ‘Inertia’ Test.

Page 28: Basic drive programing   pf753

28 of 68

41. The completion of the test is indicated by the ‘Test Completed Successfully’ screen . Press the

‘ENTER’ soft key. This will bring up the ‘Edit Speed Reg BW’ entry screen. Select the ‘ENTER’

soft key to accept the default value of 10.00 R/S.

Edi t Speed Reg BW

0.00 << 100.00

10.00 R/S

St ar t up

I ner t i a Test

42. Pressing the ‘ENTER’ key in the previous step has directed you back to the ‘Motor Test Menu’.

Use the ‘ENTER’ soft key to select ‘Done’ in the ‘Motor Test Menu’ screen.

Configuring the Speed Reference and Ramp rates

43. At this time you should be in the ‘General Startup Main Menu’. The next item on the Startup

menu list’ Ref Ramp Stop’ should be highlighted by default. Press the ‘ENTER’ soft key to make

this your selection.

44. The ‘Edit Direction Mode’ box should be on the screen now. We will use the default parameter

value of ‘Unipolar’ for this lab session. Press the ‘ENTER’ soft key to confirm and save your

selection.

45. You should be on the ‘speed reference source’ selection screen. Use the down arrow or

up arrow keys to highlight ‘Analog Input’ as your Speed Reference source. Use the

‘ENTER’ soft key to make this your selection.

Page 29: Basic drive programing   pf753

29 of 68

46. In the window ‘Select Port to Use’ that appears following the previous step, use the down arrow

or up arrow keys to highlight ‘Port 00 PowerFlex 753’. Press the ‘ENTER’ soft key

to confirm and save your selection.

St ar t up

Ref er ence Sel ect i on

Edi t Spd Ref A SelSel ect Por t To Use

Power Fl ex 753Port 00Zer o Speed

47. Use the down arrow and up arrow keys, to highlight ‘Par 0260 Anlg In0 Value’. The

selected choice is the last in the list and pressing the once will get you there faster. Press

the ‘ENTER’ soft key to confirm and save your selection.

St ar t up

Ref er ence Sel ect i on

Edi t Spd Ref A Sel

Par 0878

Sel ect Par m To Use

Anl g I n0 Val uePor t 14 Ref er ence

Par 0876

Par 0260

Por t 6 Ref er ence

48. The next few steps will configure the Analog Input you chose as Speed Reference. For this lab

session we will use the 0-10V potentiometer (labeled 0-10 Input) on the demo as our Analog

Input speed reference. Pressing the ‘ENTER’ soft key in the previous step has led you to the first

item required to configure the Analog Input. You should be in ‘Edit Anlg In0 Hi’ screen. Press the

‘ENTER’ soft key to accept the default value of ‘10.000’ Volt.

49. In the ’Edit Anlg In0 Lo’ screen that follows, press the ‘ENTER’ soft key to accept the default

value of ‘0.000’ Volt.

50. In the next few screens input these values

‘Speed Ref A Anlg Hi’ = 60Hz and

‘Speed Ref A Anlg Lo’ = 0Hz. Press the ‘ENTER’ soft key.

51. You should be in the ‘Startup / Stop Config’ screen now, press the ‘ENTER’ soft key to accept the

default selection of ‘Ramp’ to be used as ‘Stop Stop Mode A’.

Page 30: Basic drive programing   pf753

30 of 68

52. Pressing the ‘ENTER’ key in the previous step has directed you to the screen to configure the

‘Bus Reg Mode A’. Select the default of ‘Adjust Freq’ using the ‘ENTER’ soft key

53. Following the step to set bus regulation you will now set Ramp (Accel and Decel) times. In the

‘Edit Accel Time 1’ screen, use the appropriate number key to enter a value of ‘3’ seconds. Press

the ‘ENTER’ soft key.

54. Similarly enter a value of 3 seconds for the deceleration time in the ‘Edit Decel Time 1’ screen.

Press the ‘ENTER’ soft key.

55. The next screen continues the ramp speed configuration and asks the question ‘Do you want to

perform S-curve for Accel/Decel? ‘. We will select ‘No’ as the answer for this lab session. You can

select ‘No’ by highlighting it using the down and up arrow keys and then using the

‘ENTER’ soft key to confirm and save your selection.

Configuring the Inputs and Outputs

56. Completing the previous step successfully has led you to the ‘General Startup Main Menu’ with

the item ‘I/O’ highlighted. Press the ‘ENTER’ soft key to enter the ‘I/O’ section.

57. You should be in the ‘Start Stop I/O’ screen now. The first item to configure on this lis t is ‘Start

Stop & Dir’. Press the ‘ENTER’ soft key to enter this section. Read the Introductory screen to this

section and press the ‘ENTER’ soft key to continue.

58. The next screen requires you to answer the question ‘Will a Digital Input be used as a START

Source? Select ‘Yes’ using the down and up arrow keys and then using ‘ENTER’

soft key to confirm and save your selection. We will use the green push button labeled ’Di 1’ in

the demo as our Start Source in a later step.

59. The next screen will ask the question ‘Is Reverse required from a digital input?’? Select ‘Yes’

using the down and up arrow keys and then using ‘ENTER’ soft key to confirm and

save your selection. We will use the switch labeled ’Di 2’ in the demo as forward/reverse in a

later step.

60. Select ‘3 wire’ as your choice for the question ‘Enter Choice for the control method’.

61. In the ‘Edit DI Start / Select Port To Use’ window use the up and down arrow keys to highlight

‘Port 00 PowerFlex 753’. Press the ‘ENTER’ soft key to make this your selection.

62. In the ‘Edit DI Start / Select Parm To Use’ window. Press the Enter soft key to select and confirm

‘Par 0220 Digital In Sts’ selection.

63. The ‘Edit DI Start’ window will be displayed first; select the bit/Digital Input you want to use as

your START. We are going to use the green push button labeled ‘Di 1’ as our start input. To do

this scroll to ‘Digital Input 1’ and press the Enter soft key.

Page 31: Basic drive programing   pf753

31 of 68

64. Follow procedures similar to the previous steps to select the red push button labeled ‘Di 0’ as

your stop switch and the selector switch labeled ‘Di 2’ as your Forward/Reverse switch in that

order.

65. You should now be back in the ‘Start Stop I/O’ menu screen. This is all we will configure in this

section so use the down arrow keys to scroll down to the last item on the list ‘Done’. After

‘Done’ is highlighted, use the ‘ENTER’ soft key to make this your selection.

66. You should now be back in the General Startup Main Menu screen .you have finished with the

Startup routine steps required for this lab session. Select ‘Done’ using the ‘ENTER’ soft key to

exit out this screen.

67. Select ‘Exit Startup’ using the ‘ENTER’ soft key to exit out of the Startup routine.

68. You can now test your drive to perform the functions you configured during the startup routine

namely, Start using the green push button Di 1, Stop using the red push button Di 0, change

direction using Di 2 and provide speed reference using the ‘0-10V Input’ pot.

Again, remember that there is no physical motor connected to this demo unit however the speed

and status are being simulated on the top lines of the HIM display.

Page 32: Basic drive programing   pf753

32 of 68

Drive Programming via Software Tool (Optional)

Besides the HIM the drive parameters and programming can be accessed via software tool. These tools

include DriveTools SP, Drive Explorer, or RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater).

About This Section

In this lab, we will introduce you to DriveExplorer software and some of the features that are common

across all the software tools. In this lab you will:

Connect to a PowerFlex drive using DriveExplorer software

Display the Status View

Display and edit parameters with the Linear List View

Display and edit parameters with the File / Group View

Use the Control Bar to control a drive

Use a Wizard

Upload configuration from drive to PC

Download configuration to drive from PC

Using Drive Explorer with PF753

1. Verify that the PowerFlex 753 drive is connected to the computer.

2. When using DriveExplorer, it may be necessary to shutdown RSLinx if it has the serial or USB

driver configured. If RSLinx is running, it will display an icon in the Systray on the PC’s desktop.

Page 33: Basic drive programing   pf753

33 of 68

3. Right click on the RSLinx Icon in the Systray.

4. Select Shutdown RSLinx Classic on the Pop-up menu.

Starting Drive Explore and Connect To Drive

1. Double-click the DriveExplorer icon to start the software.

2. If the Danger dialog appears, read it and click OK.

3. Maximize the DriveExplorer window, so it fills the entire screen

4. Click on the “Connect Ethernet” icon in the taskbar.

Page 34: Basic drive programing   pf753

34 of 68

a. If the ‘Connect Serial” icon has focus instead; DriveExplorer is configured to

communicate serially; configuration path needs to be changed to Ethernet. Go to Explore

Configure communication Select Ethernet ok.

b. The following screen will appear. Select yes to accept the communication interface

change

c. At this point the “Connect Ethernet” icon will now have focus, select it by clicking on it

Page 35: Basic drive programing   pf753

35 of 68

5. When the node selection window opens, highlight the node with IP address 192.168.1.21 and

click the ‘Connect’ button to connect to the drive.

a. If the IP Address of the drive is not in the window then select Add Node, type in the IP

address then click OK.

b. Click Yes to the following message windows.

6. Wait for the parameters to be read and populated.

Page 36: Basic drive programing   pf753

36 of 68

7. Once the parameters are read and populated, by default Port 0 PowerFlex 753 240V 4.2 A

should be highlighted, as shown in the following graphic.

Reset Drive to Defaults

8. Navigate to Actions Non Volatile Memory and click on Non Volatile Memory.

Page 37: Basic drive programing   pf753

37 of 68

9. This will open a new window. Use the default selection of ‘Host and Ports to Defaults (Preferred)

and click on the button ‘Load Defaults’

10. Observe the prompted warning then click ‘Yes’ to the question “Do you wish to continue?” in the

next window.

Page 38: Basic drive programing   pf753

38 of 68

11. A pop window confirms that loading of parameter defaults was successful. Click ‘OK’.

12. You will be returned to the Non-Volatile Memory window, Click ‘Close’

Page 39: Basic drive programing   pf753

39 of 68

Displaying The Status View

13. If you have not already expanded the Drive Explorer application do so now by clicking on

the lower right corner of the window and drag it so the entire Status View area can be

seen (you can also maximize the window using the Maximize icon if desired)

The Status View displays the drive’s User Text (“PowerFlex 753” in the image above) as

well as important drive information, such as voltage and amp ratings, series, revision,

and operational status. The Status View is automatically displayed the first time you

connect to a drive. You can also display it at any time by clicking on the drive name in

the device tree (PowerFlex 753 in the above image).

Page 40: Basic drive programing   pf753

40 of 68

14. You can display the status view for any peripheral (e.g. the DeviceLogix adapter or other

communication adapter) by selecting the peripheral in the device tree.

15. Return to the drives status view; Click on the drive’s User Text (in the image, it is “PowerFlex

753”) to edit it. Enter new text such as “PowerFlex Rocks!” and click Apply

16. The new User Text is now displayed.

Page 41: Basic drive programing   pf753

41 of 68

17. Click on the Pencil icon for the middle display item.

18. This is where you select, scale and assign text to Display Item 1.

19. Change Process Display Item 1 to the following values and click Apply

Page 42: Basic drive programing   pf753

42 of 68

20. Close the Process Display Item 1 window.

21. Note the change you made to Process Display Item 1. Adjust the 0-10V Input potentiometer on

the drive demo to change the value on the screen.

The PowerFlex 753 has six Process Display items displayed. Other products may have more or less and each will be display on theirs in the Status View.

Page 43: Basic drive programing   pf753

43 of 68

Displaying Parameters with the Linear List View

22. Click on Parameter List in the device tree to display a linear list of the drive parameters.

23. Scroll down to view Parameter 260 [Anlg In0 Value] and then double-click on this parameter to

view it.

This is a read-only parameter that displays the value of Analog In0, which is connected to the

potentiometer (0-10V INPUT) on the demo unit. Adjust the potentiometer to see the value

change. Click Close.

Page 44: Basic drive programing   pf753

44 of 68

24. Scroll down even further to Parameter 535 [Accel Time 1]. and then double-click on this

parameter to view and edit it

This is a writeable parameter that determines the acceleration rate it takes to go from 0 Hz to

P27[Motor NP Hertz] or P28[Motor NP RPM), according to the setting in P300[Speed Units]. To

edit this parameter, a new value would be entered followed by clicking either ‘OK’ or ‘Apply’.

Click ‘Cancel’.

Displaying Parameters with the File / Group View

25. In the device tree, click on the ‘Speed Control’ file and then the ‘Speed Ramp Rates’ group to

display those parameters.

See how getting to the same parameter as what was previously scrolled to using the Linear List

function can be accessed by its grouping. If you do not know a parameter’s number, it maybe

easier to find it with the File / Group view.

Page 45: Basic drive programing   pf753

45 of 68

Using the Startup Wizard

The Startup Wizards eliminate the need to search for setup parameters because commonly used

parameters are contained in a single wizard. Configuration becomes a guided, step-by-step process

using graphics and parameter names (not numbers!), which simplifies drive setup.

1. Click on the Wizard Browser icon to launch the Wizard Browser and display the available

wizards.

The PowerFlex 753 Startup Wizard is similar to performing the HIM Assisted Startup. Configuration parameters that are common to most applications are displayed in text / graphic

forms and presented in a sequential step-by-step process. The DPI/DSI Tech Support Wizard is used to collect information for a remote support person to

help troubleshoot a problem. Drive and peripheral information such as series and revision is collected along with changed parameters, fault & event queues, diagnostic items, etc. This information is saved to a text file which can be emailed to RA Tech Support, the OEM that

supplied the machine, or the Corporate Engineer responsible for the remote plant, etc. Additional wizards will be available in the future and can be added to DriveExplorer v6.02 (and

higher) at any time. New wizards will be posted on the AB Drives Web Updates page for free download:

http://www.ab.com/support/abdrives/webupdate/index.html

Note: The same wizards also work with DriveTools SP v6.02 and higher and RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater).

Page 46: Basic drive programing   pf753

46 of 68

26. Select the PowerFlex 753 Startup Wizard and click ‘Select’.

The wizard will first upload the parameters for each of the wizard pages.

27. The first step in the wizard is the Welcome page. It explains the wizard and gives hints and tips

for using the wizard. Click ‘Next’.

Page 47: Basic drive programing   pf753

47 of 68

28. The Reset Parameters step is next. It allows you to reset the drive’s parameters back to factory

defaults. Verify ‘High Voltage’ and ‘Normal Duty’ is selected from the pull down menus. Then

click ‘Reset Parameters’.

In the confirmation window, click ‘Yes’.

Observe the on screen confirmation of the parameters being reset.

Click Next> to continue; viewing the sequential process and continuing to click Next> until you reach the Motor Control Step of the Wizard

Page 48: Basic drive programing   pf753

48 of 68

29. Perform the Motor Control Step of the PowerFlex 753 Startup Wizard. Make the selections shown:

Motor Control Mode = Select ‘Induction Flux Vector’ Primary Speed Feedback = Slot 0 (PowerFlex 753); Parameter 138 (Simulator Fdbk)

Click Next> to the Motor Data Step of the Wizard.

Page 49: Basic drive programing   pf753

49 of 68

30. The Motor Data is next. This step assists in entering the data from your motor’s nameplate into

the drive. No selections need to be changed on this step, keep the default selections.

Click Next> to the Stop Mode Step of the Wizard.

Page 50: Basic drive programing   pf753

50 of 68

31. The Stop Mode step is next. This step assists in selecting the drive’s stop mode and Dynamic

Brake (DB) resistor type. No selections need to be changed on this step, keep the default

selections.

Click Next> to the Direction Test Step of the Wizard.

Page 51: Basic drive programing   pf753

51 of 68

32. The Direction Test step is next. It helps you determine if the motor is rotating in the proper

direction for your application. No selections need to be changed on this screen.

Direction Tests are not needed for this example; however they can be ran if you desire. If you do

perform the autotune note the following:

Click the button and hold it for a few seconds to run the drive. As long as you hold the jog

button, the drive will run. Once you let go of the button, the drive will stop. After the motor stops,

click the Yes radio button. Observe how clicking the Yes radio button updated the screen with a

“Test Passed” status as well as adding ‘Change Direction’ option.

Click Next> to the AutoTune Step of the Wizard.

Page 52: Basic drive programing   pf753

52 of 68

33. The AutoTune step is next. This step is where you can use automatic tuning algorithms

(AutoTune). When running these algorithms the drive energizes the motor and makes

measurements, which are used to make parameter settings.

AutoTune tests are not needed for this example; however they can be ran if you desire. If you do

perform the autotune note the test status:

leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not

leave AutoTune test page until test completes:

Click Next> to the Inertia AutoTune Step of the Wizard.

Note: Clicking <Back, Next>, or leaving step by any means will about the test.

Page 53: Basic drive programing   pf753

53 of 68

34. The Inertia AutoTune is next. This step is where you can use an automatic tuning algorithm to

determine the load’s inertia. When running this algorithm the drive spins the motor and makes

measurements, which are used to make parameter settings

AutoTune tests are not needed for this example; however they can be ran if you desire.

If you do perform the autotune note the test status:

leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not

leave AutoTune test page until test completes:

Click Next> to the Ramp Rates / Speed Limits Step of the Wizard.

Note: Clicking <Back, Next>, or leaving step by any means will about the test.

Page 54: Basic drive programing   pf753

54 of 68

24. Perform the Ramp Rates/Speed Limits Step of the PowerFlex 755 Startup Wizard.

Enter: Max Forward / Reverse Speed 60 Hz

Min Forward / Reverse Speed 0 Hz

Enter a non-zero value for the S Curve to see what happens with the graphic.

Then reset it back to 0.

Click Next> to the Speed Reference Step of the Wizard.

Page 55: Basic drive programing   pf753

55 of 68

35. The Speed Reference step is next. It helps you select where the drive gets its speed reference.

Observe the screen with the default value for speed reference selected to Port 0.

Now select the reference to be from P260 [Anlg In0], observe how the wizard shows the pertinent

parameters and for this analog input.

Click Next> to continue; viewing the sequential process, continue to click Next> until you reach

the Start / Stop step of the Wizard.

Page 56: Basic drive programing   pf753

56 of 68

36. Perform the Start / Stop step of the PowerFlex 753 Startup Wizard. Make the selections shown.

DI Start = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 1)

DI Stop = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 0)

DI Forward / Reverse = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 2)

Click Next> to the Other Digital Inputs Step of the Wizard.

Page 57: Basic drive programing   pf753

57 of 68

37. The Other Digital Inputs step is next. This step helps you configure the drive’s most commonly

used digital inputs. No selections need to be changed on this step, keep the default selections

Click Next> to the Digital Output Port 0 Step of the Wizard.

There are other digital inputs available to user; however the Wizard shows the most commonly programmed inputs. All the available digital inputs can be accessed via the HIM or software tool (parameters 150 – 201).

Page 58: Basic drive programing   pf753

58 of 68

38. Perform the Digital Relay Out 0 step of the PowerFlex 753 Startup Wizard. This step helps you

configure the drive’s digital outputs. Make the selections shown

Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 16 (Running)

Click Next> to the Digital Output Port 0 Step of the Wizard.

There are no I/O options installed in this demo; however if there were an additional digital option card installed more Digital Output and Analog Output steps would become available to user and would be designated by

their associated port.

Page 59: Basic drive programing   pf753

59 of 68

39. Perform the Digital Transistor Out 0 Step of the PowerFlex 753 Startup Wizard. This step helps

you configure the drive’s digital outputs. Make the selections shown

Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 7 (Faulted)

Click Next> to the Analog Output Port 0 Step of the Wizard.

Page 60: Basic drive programing   pf753

60 of 68

40. The Analog Out 0 step is next. It helps you configure the drive’s analog outputs. No selections

need to be changed on this step, keep the default selections.

Click Next> to the Pending Changes Step of the Wizard.

Page 61: Basic drive programing   pf753

61 of 68

41. The Applied and Pending Changes page will appear. The purpose of this step is to verify all of

the changes you made in the wizard, and then apply the changes to the drive. The below screen

is for reference (your changes may differ from what is shown below).

Click Finish >>. The wizard will write your changes to the drive.

The Pending Changes step can be used as a reference tool. You can print

the summary with the print button at the bottom of the window. You can refer to the printed summary when commissioning duplicate drives or replacing a faulted drive.

Page 62: Basic drive programing   pf753

62 of 68

Using the Control Bar Tool

42. Click on the button in the tool bar at the top of the window

43. Read Caution advisory and click OK

Page 63: Basic drive programing   pf753

63 of 68

44. Use the buttons on the left-hand side of the control bar to start, stop, jog and control the direction

of the drive

The speed reference was selected to the Analog In0 in the previous step. To allow the control

bar to have control of the speed reference; Parameter 545[Spd Ref A Sel] will need to be

changed (while the drive is not running). Stop the drive and change Parameter 545 setting to

Port ‘PowerFlex 753’, Parameter ‘876 - Port 6 Reference’.

Start the Drive again and use the slider on the right-hand side to control the speed reference.

45. Stop the Drive and turn off the control bar by clicking the button again. Observe the Caution

pop up window and click Yes.

Page 64: Basic drive programing   pf753

64 of 68

Using Off-line Files

This feature allows you to save your drive configuration to a computer. It is useful for several reasons:

You can use the configuration if you replace the drive or install an identical one.

You can use the configuration to troubleshoot the drive if it begins to malfunction because the

settings have been changed.

Uploading and Saving the Drive’s Configuration to a PC

46. Select the drive in the device tree.

47. From the Actions menu, select Upload/Download All.

48. On the Upload/Download All window choose Upload.

Page 65: Basic drive programing   pf753

65 of 68

49. By selecting the Upload/Download All you now are prompted to select with ports to upload.

Deselect port 1 (20-HIM-x6) and Port 6 (20-COMM-E) and then click Upload.

50. Each of the ports parameters will be uploaded. As indicated by the below screen, each port will

be displayed as its parameters are uploaded.

51. In the Save As window define the filename and location of the file. Take note of the name and

remember where you save this file, it will be needed later.

52. After choosing the name and location to save file the Uploading… screen will regain focus; click

Close.

Page 66: Basic drive programing   pf753

66 of 68

53. Again the Upload/Download All window will appear, click Close.

This section had described how to upload all the ports in the drive into one file. Also available on the Actions menu is the option to select Upload and Save. Doing this will upload and save the parameters for the selected port in the device tree.

Downloading Configuration to Drive from a PC

54. Change the value of a parameter that you can easily verify (e.g. P535 [Accel Time 1]).

55. From the Actions menu, select Upload/Download All.

56. On the Upload/Download All window choose Download.

57. Select Yes. To the resulting dialog window.

58. Select the same file you created in the section above and click the Open button.

Page 67: Basic drive programing   pf753

67 of 68

59. Notice on the Select Sets To Download window that only the chosen option ports that were

selected to upload in the previous steps are available. Click Download.

60. The saved parameter file values will be downloaded. Close the Download Complete!

Acknowledgement.

61. Again the Upload/Download All window will appear, click Close.

62. Verify that the value of the parameter you changed a few steps back has returned to its original

value.

Page 68: Basic drive programing   pf753

68 of 68

Notes: