Balanced-Unbalanced Converter for Audio Work _ DIY Electronics Projects
Balanced Unbalanced Polyphase Systems 1 23 13
-
Upload
wyatt-c-lewis -
Category
Documents
-
view
153 -
download
6
description
Transcript of Balanced Unbalanced Polyphase Systems 1 23 13
Balanced & Unbalanced Polyphase Systems
Single Phase Power Equations
Apparent Power or Complex Power
P: real power (W) Q: reactive power (VAR) S: apparent power (VA)
• Power Factor
• Real Power
• Reactive Power
1-2
For the following circuit, find the (a) real power, and (b) reactive power. (c) Draw the power triangle.
Example: Single-Phase Power
1-3
For the following circuit, find the (a) real power, and (b) reactive power. (c) Draw the power triangle.
(a) The real power is:
(b) The reactive power is:
P = VR2
R= (120 V)2
10 Ω= 1440 W
Q = VL2
XL
= (120 V)2
4 Ω= 3600 VAR
Example: Single-Phase Power
1-4
(c) The power triangle is:
In this example, the impedance of the inductor has a lagging current, so the current has a negative phase angle. The complex conjugate of the current has a positive phase angle, so the reactive power, Q, is positive and the power triangle is in the first quadrant. For a leading current (which has a positive phase angle compared to the voltage) the power triangle has a negative imaginary part and a negative power angle, so it is in the fourth quadrant.
1-5
Current I creates drop (+) (-) as shown VAB defined as the rise B A
Polyphase Circuits E.E. element convention
ABC (+) sequence Find VAB Via KVL
(+) (-) V
A B I
←“VAB”
3031200
0
∠=−∠−∠=
−==+−+
PPP
BNANAB
BNANAB
VVV
VVVVVV
(+120 )
(150 )
(30 )
(0 )
(-120 )
- +
-
-
+
+
+ (-90 )
+
1-6
Note: Voltages as given are line to line voltages unless otherwise specified
ACB (-) sequence Find VAC via KVL
In both examples VA is the reference phasor. If VB or VC are designated the reference phasor then the phasor relationships will differ. (Try CBA)
(+120 )
(150 )
(30 )
(0 )
CNV(-120 )
- +
-
- +
(-90 )
+ +
- 0
0 120
3 30
AC AN CN
AC AN CN
P P
AC
V V V
V V V
V V
V Vp
+ − + =
= −
= ∠ − ∠ −
= ∠
1-7
Three-Phase Systems
Three-phase power systems have three wires to transmit power. Some systems also have a neutral wire. In a balanced three-phase system, the voltages on the three wires are all the same magnitude but are out of phase by 120 degrees. In a balanced system, the currents are also the same magnitude but are out of phase by 120 degrees. The vector sum of the voltages and currents in a balanced three-phase system are zero.
1-8
Example: Three-Phase System
The voltage on phase A of a balanced, three-phase power system is: °∠37220
What are the voltages and angles of the other phases?
(Assume that the phase sequence is ABC)
( ) °−∠=°∠−°∠= 8322012037220BV
( ) °∠=°∠+°∠= 15722012037220CV
°−∠= 83220BV°∠= 37220AV
°∠= 157220BV
1-9
Three-Phase Wye System A three-phase wye configuration has three phases and a neutral wire. The “phase” voltages are between the legs and are named VAB, VBC, and VCA. The line to neutral voltages are between the lines and the neutral and are designated VAN, VBN and VCN.
Generator Load
line-lineline-neutral 3
VV =
Line-to-line voltages and line-to-neutral voltages are 30 degrees out of phase. The phase voltage leads the line-neutral voltage by 30 degrees and the line-neutral voltage lags the phase voltage by 30 degrees.
°∠= 303 ANAB VV °−∠= 303
ABAN
VV
1-10
Problem: Three-Phase Wye
1-11
How do we know it’s a wye system?
Problem: Three-Phase Power
Key Points to Remember •Answer (A) has the
correct amplitude but does not include the phase in the equation.
• In answers (C) and (D), the line-to-line voltage equations are used Answer is (B)
1-12
Three-Phase Delta System
Three-phase delta configuration has three phases and no neutral wire. The only voltages to be considered are the line-to-line voltages. There are two currents to be considered: the line currents which flow in the lines, and the phase currents which flow in the resistors, shown as load in the diagram.
Generator Load
The line currents are out of phase with the line-line (phase) currents:
°−∠= 303 ABA II °∠= 303A
ABII
1-13
Example: Delta System
PROBLEMS
1-14
Example: Delta System
SOLUTIONS
PROBLEMS
1-15
Wye Delta Conversions
To convert balanced Wye to Delta:
For balanced loads where all the impedances are equal, the conversion from Delta to Wye and vice versa is simplified.
WyeDelta RR 3=
To convert balanced Delta to Wye: DeltaWye RR
31
=
In the figure to the right, in order for the two loads to be equivalent:
131 RRA = ARR 31 =
1-16
Power in Three-Phase Systems For balanced systems, three-phase power can be computed using any of the following equations:
jQPS += LineLineLine IVS −= 3LineLineLine IVS *3 −=
In a balanced load where the load is the same in all three phases, the three-phase real power can be computed as three times the power in any single phase.
θCosIVP LineLineLineLine −= Cos θ is the power factor
3LineLine
NeutralLineVV −
− = LineTotal PP 3=θCosIVP LineLineLine
Line 3−=
1-17
Example: Power Computation
PROBLEMS
1-18
Example: Power Computation
SOLUTIONS
PROBLEMS
1-19
Balanced Polyphase Example
3 Ø motor takes 10 kVA at 0.6PF lagging from a 220 V source. The motor is in parallel with a balanced Δ load with an impedance of R = 16 xc = 12 in each phase. Find the total VA, power, power factor.
For the load I phase AjV
ZVI LL 87.3611
1216220
∠=−
==
IMOTOR
x
R
R
x MOTOR
x R
LOAD
ILOAD LINE
ILOAD PHASE
1-20
VAAVIVS LINELLLOAD 87.362420)87.3611)(220(*1 −∠=−∠==φ
Note that the angle of reactive power is given by load
9.361612tan 1 == −θ
So )(9.367260 leadingSLOAD∠=
leading because capacitive
is given as 10KVA @ 0.6PF lagging
Angle of SMOTOR is a cos-1 0.6 = 53.13 (lagging)
15.17357,1287.36726013.531010 3 −∠=∠+−∠=+= xSSS LOADMOTORTOTAL
Note: This is a leading power factor diagram. It is not a phasor diagram.
12
16
20
1-21
VAVASS LOADLOAD 87.36726087.36342033 13 ∠=∠•== φφ
Problem can also be solved by converting delta to wye and computing parallel impedance.
Impedance of motor Ω=== 84.424.26
3/220
C
LC
IVZ
Ω=== 904.2)6.0)(84.4(cosθzRMOTOR Ω== 872.3sin84.4 θMOTORx
Parallel impedance
AIT 13.1742.3213.1793.33/220
−∠=∠
=
VAIVS LLL 13.17357,12)13.1744.32)(220(33 * ≅∠==
1-22
Alternate Solution Method
Unbalanced Polyphase Example Unbalanced Polyphase Load Delta
Find phase currents 100 0 100 0 10 53.1 A6 8 10 53.1
ABab
ab
VIZ j
∠ ∠= = = = ∠ −
+ ∠
100 120 5 120 A20
CAca
cc
VIZ
∠= = = ∠
IC
IB
A
B
C c
IA Iab Ica Ibc
b a
1-23
13.832087.365
12010034120100
−∠=−∠
−∠=
−−∠
==jZ
VIbc
BCbc
Compute line currents via KCL at nodes
1-24
Unbalanced Wye Example Unbalanced Wye Connected Load, Four Wire A three phase four wire 150Y, CBA system has a Y connected load. VAN has an angle of -90 The load impedances are
Obtain all the line currents and neutral current
A
N
B
C IC
IB
IA
IN VAN
1-25
16721.1010532.17043.149043.14
10532.174551506.86
043.14306
306.86
9043.1406
906.86
1506.861503
1501503
306.86303
150303
906.86903
150903
−∠=∠+∠+−∠=++=
∠=∠∠
==
∠=∠
∠==
−∠=∠
−∠==
∠=∠=∠=
∠=∠=∠=
−∠=−∠=−∠=
CBAN
C
CNC
B
BNB
A
ANA
LNCN
LNBN
LNAN
IIIIZVI
ZVI
ZVI
VV
VV
VV
1-26
Unbalanced Three Wire, Wye Connection Unbalanced Three Wire Connection, Wye Load.. 150V CBA system, & connected load,
A
B
C IC
IB
IA
N (-120 )
(0 )
'BNV
NAV ′
(120 )
30
1-27
What types of loads are these?
Find the all voltages and currents °∠= 16.2767.66:Given 'BNV
1-28
120150
0150
120150
∠=
∠=
−∠=
CA
BC
AB
VVV
The line to line voltages may be determined by inspection:
Find VAN’ using KVL:
96.987.100
16.2767.66120150
0
−∠=
∠+−∠=
+==−−
′
′
′′
′′
NA
NA
NBABNA
NBABNA
VV
VVVVVV
Find VCN’ using KVL:
4.16159.95
16.2715092.9864.100
0
∠=
∠+−∠=
+==−−
′
′
′
′′
NC
NC
CAANNC
NACANC
VV
VVVVVV
92.9878.1606
96.987.100∠=
∠−∠
== ′
A
NAA Z
VI
84.213.11306
16.2767.66−∠=
∠∠
== ′
B
NBB Z
VI
1-29
( ) 01 =++ ′′′
C
NC
B
NB
A
NA
ZV
ZV
ZV
Find the currents via KCL at central node:
4.11612.19455
4.16159.95∠=
∠∠
== ′
B
NBC Z
VI
How far is the neutral offset?
41.39197.2096.987.100906.86
96.987.1009053
150
∠=
−∠−∠=
−∠−∠=
′NNV
1-30
What happens if you connect the neutral of the load to the neutral of the generator (supply)?
Power Afternoon Sample Questions A 3-phase, 4-wire, neutral-grounded wye-connected utility line has a phase-to-phase voltage of 13.2 kV. A complex load of (200 + ƒ100) kVA is connected between Phase A and neutral; identical load is connected between Phase B and neutral. The neutral current (amperes) is nearly: (A) 0 (B) 9.8 (C) 16.9 (D) 29.3
56.14634.29120
3102.13
10)100200(
56.2634.290
3102.13
10)100200(
3
3
3
3
∠=−∠
+==
∠=∠
+==
VxVAxj
VSI
VxVAxj
VSI
B
BB
A
AA
Neutral current is the sum of IA + IB + IC =IN
Answer (0)
Note that answer (C) is the result of incorrectly using VLL rather than VLN
1-31
Power Afternoon Sample Questions
A 3-phase, 3-wire, ungrounded, 13.2kV (phase-to-phase) wye-connected course is connected to a balanced delta load that is grounded on Corner A. The voltage measured between Corner B and ground is most nearly: (A) Half the phase-to-phase voltage (B) 7.62 kV (C) 13.2 kV (D) cannot be determined
Use KVL:
(sign independent) Answer (C)
A A
C B
B
Grounding
C
VAB -
+
- + VAB
1-32
Power Afternoon Sample Questions
The only load on a 3-phase, 4-wire system is placed between Phase B and Phase C. The phase-to-phase voltage is 13.2 kV. The load is 500kVA at 0.85 lagging power factor. The magnitude of the line current in Phase C amperes is most nearly: (A) 65.6 (B) 55.8 (C) 37.9 (D) 32.2
Power factor not relevant
VxVAx
VSI 3
3
102.1310500
==
500KVA 0.85 lag
A
B
C
1-33
Voltage Regulation
Voltage regulation is a measure of the degree to which the voltage at a load is held constant as the amount of load varies from no load to full load.
100% ×−
=FL
FLNLR V
VVVVNL is the no load voltage
VFL is the full load voltage
The concept of regulation can be applied to a problem with a component designed to hold steady voltage (voltage regulator) or to a problem with a general source without a regulator supplying load.
Line regulation measures the ability to maintain a constant output voltage regardless of changes in the input voltage.
Load regulation measures the ability to maintain a constant output voltage regardless of changes in size of the load (current draw).
1-34
Example: Voltage Regulation
A transmission line supplies 60 MVA of load at 0.8 power factor, lagging. The voltage at the receiving end of the line is 138 kV. The transmission line impedance is 10+j30. What is the % regulation? (Use Per-Phase Analysis)
20 MVA 0.8 Lag
10+j30 Ω
PROBLEM
1-35
Example: Voltage Regulation
A transmission line supplies 60 MVA of load at 0.8 power factor, lagging. The voltage at the receiving end of the line is 138 kV. The transmission line impedance is 10+j30. What is the % regulation?
20 MVA 0.8 Lag
10+j30 Ω
Solve the problem considering only one phase of the system. The 60 mVA load is 20 mVA per phase.
kVVVLN 67.79310138 3
=×
= Load line to neutral voltage
*1 LLN IVS =φ A
VVA
VSI
LNL 87.36251
1067.7987.361020
3
61
*
−∠=×−∠×
== φ
°== − 87.368.0cos 1θ Finding phase angle
Sending end voltage
VjVS °∠×=°∠×+°−∠+= 31031.8601067.79)87.36251)(3010( 33
%33.810067.79
67.7931.86% =×−
=RV
SOLUTION
PROBLEM
1-36