Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

41
Backflow Backflow Prevention for Prevention for Fire Sprinkler Fire Sprinkler Systems Systems State of Illinois State of Illinois Plumbing Code Plumbing Code

Transcript of Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Page 1: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Backflow Prevention Backflow Prevention for Fire Sprinkler for Fire Sprinkler

Systems Systems

State of Illinois Plumbing Code State of Illinois Plumbing Code

Page 2: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Backflow PreventionBackflow Prevention

Fire safety systems connected Fire safety systems connected to a public water supply will to a public water supply will

require a backflow prevention require a backflow prevention device between the fire safety device between the fire safety system and the public water system and the public water

supply.supply.

Page 3: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Types of ValvesTypes of Valves

CheckCheck

Double CheckDouble Check

Reduced Pressure Reduced Pressure

Page 4: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Check ValveCheck Valve

A valve which permits flow A valve which permits flow in one direction, from the in one direction, from the supply to the end use.supply to the end use.

Page 5: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 6: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

State of Illinois Plumbing State of Illinois Plumbing CodeCode

The State of Illinois requires a The State of Illinois requires a DDC (Double Detector Check) DDC (Double Detector Check) valve on all fire protection valve on all fire protection systems.systems.

Page 7: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Double Check Valve Double Check Valve Assembly-DDC or DCVAAssembly-DDC or DCVA

This assembly consists of two internally This assembly consists of two internally loaded check valves, either spring or loaded check valves, either spring or internally loaded, weighted, installed internally loaded, weighted, installed as a unit between two tightly closing as a unit between two tightly closing resilient-seated shutoff valves as an resilient-seated shutoff valves as an assembly, and fittings with properly assembly, and fittings with properly located resilient seated test ports or located resilient seated test ports or cocks.cocks.

Page 8: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

DiagramDiagram

Page 9: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 10: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 11: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 12: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 13: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 14: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Reduce Pressure Zone (RPZ) orReduce Pressure Zone (RPZ) orReduced Pressure Backflow Assembly Reduced Pressure Backflow Assembly

(RPBA)(RPBA)

Two independently acting check valves together Two independently acting check valves together with a hydraulically operating, mechanically with a hydraulically operating, mechanically independent pressure differential relief valve independent pressure differential relief valve located between the check valves and below located between the check valves and below the first check valve. These units are located the first check valve. These units are located between two tightly closed resilient seated between two tightly closed resilient seated shutoff valves, as an assembly, and are shutoff valves, as an assembly, and are equipped with properly located resilient equipped with properly located resilient seated test cocks.seated test cocks.

Page 15: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

State of Illinois Plumbing State of Illinois Plumbing CodeCode

The State of Illinois requires an The State of Illinois requires an RPZ/RPBA valve on all fire protection RPZ/RPBA valve on all fire protection systems when the following systems when the following conditions exist.conditions exist.

Page 16: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

If the system contains anti-freeze or If the system contains anti-freeze or other chemicals, then an RPZ device is other chemicals, then an RPZ device is required.required.

If water can be pumped from a non-If water can be pumped from a non-potable water supply such as a retention potable water supply such as a retention pond or lake then an RPZ is requiredpond or lake then an RPZ is required

If there is a permanent or emergency If there is a permanent or emergency connection whereby water can be connection whereby water can be pumped into the fire safety system-RPZpumped into the fire safety system-RPZ

Page 17: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 18: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 19: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 20: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 21: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 22: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Location of the DDC or RPZLocation of the DDC or RPZ

Normally the DDC or RPZ is located Normally the DDC or RPZ is located on the incoming water supply before on the incoming water supply before connection to the fire systemconnection to the fire system

If there is a Fire Pump, the RPZ or If there is a Fire Pump, the RPZ or DDC should be located on the DDC should be located on the dischargedischarge side of the pump side of the pump

Page 23: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Graph’s: compliments of FSI

Page 24: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.
Page 25: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Retrofitting DDC’s or RPZ’sRetrofitting DDC’s or RPZ’s

The devices will add from 4 -15 psi The devices will add from 4 -15 psi on the average to the fire protection on the average to the fire protection system hydraulic calculation system hydraulic calculation demand.demand.

Most sprinkler systems are Most sprinkler systems are hydraulically calculated to within 5 hydraulically calculated to within 5 psi of the available water supply.psi of the available water supply.

Page 26: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Who Can Test or Repair an Who Can Test or Repair an RPZ or DDCRPZ or DDC

A licensed plumber who is also a A licensed plumber who is also a certified cross control detector certified cross control detector inspector.inspector.

Page 27: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

DiagramDiagram

Page 28: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

NFPA 25- Backflow Preventors NFPA 25- Backflow Preventors Section 9-6Section 9-6

MaintenanceMaintenance– Conducted by trained individual following Conducted by trained individual following

manufacturer’s instructions Certified manufacturer’s instructions Certified Cross Control Detector Inspector (CCCDI).Cross Control Detector Inspector (CCCDI).

– Rubber parts replaced in accordance with Rubber parts replaced in accordance with frequency required by authority having frequency required by authority having jurisdiction and manufacturer’s jurisdiction and manufacturer’s instructionsinstructions

Page 29: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

NFPA 25- Backflow PreventorsNFPA 25- Backflow PreventorsSection 9-6Section 9-6

InspectionInspection– Weekly for valves supervised with sealsWeekly for valves supervised with seals– Monthly for other supervision methodsMonthly for other supervision methods– Verify: in normal open positionVerify: in normal open position– All RPZ devices must be inspected All RPZ devices must be inspected

weekly to determine that the relief port weekly to determine that the relief port is not dischargingis not discharging

Page 30: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

1998 NFPA 251998 NFPA 257-3.8 Other Devices7-3.8 Other Devices

Other devices, such as check valves, Other devices, such as check valves, detector check, and backflow detector check, and backflow preventors that are installed on the preventors that are installed on the fire sprinkler system shall be fire sprinkler system shall be inspected and maintained so that inspected and maintained so that they do not impede the flow of water they do not impede the flow of water and fire main pressure.and fire main pressure.

Page 31: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

9-6.2 Testing, Backflow9-6.2 Testing, Backflow

9-6.2.1 All backflow preventors shall 9-6.2.1 All backflow preventors shall be tested annuallybe tested annually– A) A forward flow test shall be A) A forward flow test shall be

conducted at the system demandconducted at the system demand– B) A backflow certification test, as B) A backflow certification test, as

required by the authority having required by the authority having jurisdiction shall be conducted at jurisdiction shall be conducted at the completion of the forward flow the completion of the forward flow test.test.

Page 32: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Sample of Backflow Test form

Page 33: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

NFPA 25- Control ValvesNFPA 25- Control ValvesSection 9-3Section 9-3

Annual TestAnnual Test– Forward flow test at system demandForward flow test at system demand

Exceptions to Forward Flow TestExceptions to Forward Flow Test– When connections for system demand are not When connections for system demand are not

available, run test at maximum flowavailable, run test at maximum flow– For 2 inch or smaller valves, run test without For 2 inch or smaller valves, run test without

measuring flowmeasuring flow– Where water rationing is in effect for more than 1 Where water rationing is in effect for more than 1

year, internal inspection can substitute for flowyear, internal inspection can substitute for flow– Flow Test not required where pump testing Flow Test not required where pump testing

causes demand flow through backflow devicecauses demand flow through backflow device– Backflow certification test (after flow test)Backflow certification test (after flow test)

Page 34: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Forward Flow TestForward Flow TestNFPA 13 1999 10-2.6NFPA 13 1999 10-2.6

The backflow prevention assembly The backflow prevention assembly shall be forward flow tested to shall be forward flow tested to ensure proper operation. The ensure proper operation. The minimum flow rate shall be the minimum flow rate shall be the system demand, including hose system demand, including hose stream where applicable.stream where applicable.

This is a requirement also called out This is a requirement also called out in NFPA 25 1998 Editionin NFPA 25 1998 Edition

Page 35: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Underground Piping TestsUnderground Piping Tests

HYDROSTATIC TESTHYDROSTATIC TEST

200 PSI FOR 2 HOURS200 PSI FOR 2 HOURS

From the street line non-indicating From the street line non-indicating valve to the first supply side valve in valve to the first supply side valve in the protected building.the protected building.

Page 36: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Underground Flush TestUnderground Flush Test

This test is to be conducted before This test is to be conducted before the underground pipe is connected to the underground pipe is connected to the fire sprinkler system.the fire sprinkler system.

Flow the required rate of water listed Flow the required rate of water listed by the AWWA until the water is clear by the AWWA until the water is clear and there is no collection of material and there is no collection of material in a burlap bag which is to be placed in a burlap bag which is to be placed on the end of the pipe.on the end of the pipe.

Flow rates shown on the next slide…Flow rates shown on the next slide…

Page 37: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Sprinkler Pipe TestsSprinkler Pipe Tests

Flow rates:Flow rates:– 390 gpm for a 4” line390 gpm for a 4” line– 880 gpm for a 6” line880 gpm for a 6” line– 1,560 gpm for a 8” line1,560 gpm for a 8” line– 2,440 gpm for a 10” line2,440 gpm for a 10” line– 3,520 gpm for a 12” line3,520 gpm for a 12” line

Page 38: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Why is this Important? Why is this Important?

Page 39: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

To remove any sand, grit, or To remove any sand, grit, or debris from underground that debris from underground that may disturb valves or obstruct may disturb valves or obstruct fire sprinkler head water flowfire sprinkler head water flow

Page 40: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

To insure that the To insure that the PROPER PROPER water water supply is available as it was designedsupply is available as it was designed

Page 41: Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code.

Thank you Thank you

Any questions?Any questions?