User Manual
DBW Series
Single Isolate Regulate System
10-160KVA
1. Safety Guide 1
2. Descriptions 3 2.1 RELIABILITY AND QUALITY STANDARDS ............................................................... 3 2.2 DBW SERIES ............................................................................................................. 3 2.3 WARRANTY ............................................................................................................... 3 2.4 EXTENDED WARRANTY........................................................................................... 4
3. System analysis 3.1 MAIN CHARACTERISTICS. ....................................................................................... 5 3.2 PRINCIPLE OF WORK............................................................................................... 5 3.3 BASIC COMPONENTS AND CIRCUIT ...................................................................... 7 3.4 DBW SERIES ELECTRONIC AVR TECHNOLOGY SPECIFICATION ....................... 8
4. Installation 4.1 INTRODUCTION ........................................................................................................ 9
4.1.1 RECEIPT OF THE AVR ..................................................................................... 9 4.1.2 NAMEPLATE ..................................................................................................... 9
4.2 EQUIPMENT TRANSPORT AND STORAGE............................................................. 9 4.3 UNPACKING............................................................................................................. 10 4.4 POSITIONING .......................................................................................................... 10 4.5 CABLING.................................................................................................................. 13
4.5.1 PREPARATION FOR THE CABLE .................................................................. 13 4.5.2 EARTHING ...................................................................................................... 14 4.5.3 CONNECTING THE IN/OUTPUT CABLE........................................................ 15
5. Operation 17 5.1 COMMISSIONING.................................................................................................... 17
6. Maintenance 19 6.1 INTRODUCTION ...................................................................................................... 19 6.2 USER RESPONSIBILITIES...................................................................................... 19 6.3 ROUTINE MAINTENANCE....................................................................................... 19
7. Troubleshooting 20
Content
USER MANUAL
Page 1 sur 23
Please keep the manual for reference. THIS Motor-regulator AVR MUST NOT BE STARTED UP OR PUT INTO USE WITHOUT HAVING BEEN COMMISSIONED BY A FULLY TRAINED AND AUTHORISED PERSON.
Regular professional electrician must do all maintenance work, DO NOT ATTEMPT TO SERVICE THE AVR YOURSELF. BY OPENING OR REMOVING THE AVR-COVERS YOU RUN RISK OF EXPOSURE TO DANGEROUS VOLTAGES!
IN CASE OF ANY KIND OF DOUBT REGARDING THIS AVR, PLEASE CONTACT:
LDC TECHNOLOGY INC
Tel. +86 532 87882666、87883999、87980999
Fax. +86 532 87885388
e-mail: [email protected]
http:// www.LDC.com.cn
LDC ASSUME NEITHER RESPONSIBILITY NOR LIABILITY DUE TO INCORRECT OPERATION OR MANIPULATION OF THE Motor-regulator AVR. LDC Has taken every precaution to produce an accurate,
complete and easy to Understand manual and will
therefore assume neither responsibility nor liability for
Direct indirect or accidental personal or material damage
due to any misinterpetation Or undesired mistakes in this
manual. This manual may not be copied nor reproduced
prior to written permission of LDC.
1. Safety Guide
USER MANUAL
Page 3 sur 23
2.1 Reliability and quality stantards
Congratulation on your purchase of the DBW series Motor-regulator AVR. The DBW series Electronic AVR will provide your critical equipment with a steady and reliable power supply for many years. LDC Technology INC is situated in California U.S.A and is specialized in the design and manufacture of Power products. The criteria and methods implemented at LDC for the design and manufacture correspond to the most stringent quality standards.
2.2 DBW series Electronic AVR
DBW series Motor-regulator AVR consists of two models: Standard: Standard Motor-Regulator, I/O non Isolation. Especial: Motor Isolation Regulator, I/O Isolation, customized as the User requirement.
2.3 WARRANTY
The DBW series Electronic AVR is supplied with a limited
warranty that the AVR and its Component parts are free from
defects in materials for a period of 12 months from The date of
original commissioning or 15 months from the date of original
delivery, whichever is the sooner. Transportation cost is not
included in the warranty and has to be paid by the end-user.
Do not return anything without written authorization from LDC or
your closest service centre. LDC or the closest service centre will
then give you further Instructions how to proceed. Any product
must be returned with transportation charges prepaid and must be
accompanied by a description of the failure. Products without
description will not be handled.
This warranty is invalidated if the AVR is put into use without
having been commissioned by a fully trained and by LDC
authorized person. This warranty does not apply to any damage or
losses caused by misuse, abuse, negligence, neglect,
2. Descriptions
USER MANUAL
Page 4 sur 23
unauthorized repair or modification, incorrect installation,
inappropriate environment, accident, act of God or inappropriate
application. If the AVR fails to conform to the above within the
warranty period then LDC or an authorized service centre will, at its
sole option, repair or replace the AVR or parts of it. All repaired or
replaced parts will remain the property of LDC or of the authorized
service centre. LDC is not liable for any costs, such as loss of
profits or revenue, loss of equipment, loss of data or software, cost
of substitutes, claims by third parties or otherwise. As general
policy, LDC does not recommend the use of any of its products in
life support applications where failure or malfunction of the LDC
product can be reasonably expected to cause failure of the life
support device or to significantly.
Affect us safety or effectiveness. LDC does not recommend the
use of any of its products in direct patient care. LDC will not
knowingly sell its products for use in such applications unless it
receives in writing assurances satisfactory to LDC that the risks of
injury or damage have been minimized, the customer assumes all
such risks and the liability of LDC is adequately protected under
the circumstances.
2.4 EXTENDED WARRANTY
User can require that extend the WARRANTY, please contact with the closest agent if you want to know the details.
USER MANUAL
Page 5 sur 23
3.1 Main Characteristics
The DBW series compensates power Regulator, is the new generation of power
Regulator of our company introduces the American technology, the union domestic
electrical network voltage actual situation, develops the development together after
this company Chinese and foreign technical personnel When outside power supply
electrical network voltage undulation or load fluctuation, uses this Regulator to be able
to keep the output voltage stability automatically.
This Regulator has the Characteristics of big capacity, the wide range, loses lowly
(is energy conservation), the high precision, the quick regulate voltage speed, non-
waveform distortion and so on;
This Regulator voltage regulation is steady, can withstand the instantaneous
overload, is suitable each kind of linearity, the non-linear load;
Because the human nature Chinese LCD, enable this Regulator to have of the
volume slightly, weight light, installs the use maintenance conveniently.
It can be used widely at the industry, agricultural, exchange, posts and
telecommunications, military, railroad, scientific research culture large-scale
electromechanical device, the metal working equipment, the production assembly line,
the architectural engineering equipment, the elevator, the medical instrument, the
printing packing equipment, the computer control device, situation and so on textile
printing equipment, as well as air conditioning, broadcast television, guesthouse and
domestic electric appliances illumination and so on, places that all need constant
voltages.
3.2 Work principle The DBW series Motor-Regulator AVR is composed by Isolation transformer,
Compensate transformer,Motor-Regulator transformer, , Contactor operation
circuit, the LCD and so on.
Electric principle Diagram as below:
3. System Analysis
USER MANUAL
Page 6 sur 23
Cont r ol Sy s t em
Vol t age Regul at or
Compens at i on Tr ans f or mer
Ser vo mot or
LiN
LoN
Figure 1
Voltage regulator primary winding connected to the output of Regulator, the secondary
winding connect the primary winding of the compensation transformer, and the
secondary winding of compensation transformer is connected in series in the main
circuit.
Vol t age Regul at or
Compensat i on Tr ansf or mer
Ui Uo
Uc
Figure 2
If except the compensation transformer impedance pressure drop, as the second chart shows that: UO=UI+UC expressions: UI--- Regulator Input Voltage;
UO---Regulator Output Voltage;
UC---Regulator compensation voltage; The principle is: When the input voltage increases ΔUI in the UI, the
compensation voltage UC has been a corresponding change in voltage ΔUC, and UC =- UI, so that the output voltage UO remain unchanged. Its regulators process: In accordance with the output voltage changes, by the voltage
detection unit sampling, detect and output signal to control Servo Motor M rotation,
through the slowdown institutions and the chain led the brush Group slid (or scroll) to
regulate The secondary voltage of regulator transformer, to change the compensation
voltage polarity and size, to achieve Output automatic stability is during in the voltage
USER MANUAL
Page 7 sur 23
regulator precision, in order to reach the automatic voltage regulator.
3.3 Components
(1)Compensation Transformer When the size and polarity of the Voltage in the Primary winding changes,
it can make Secondary winding that is connected in series on the road loop produce the compensation voltage transformer with amplitude and variable polarity.
(2)Isolation Transformer
Isolation transformer is used to isolate input and output winding each other on the electrical transformer, to prevent dangers accidental touching live body (or as a result of damage to the insulation and metal parts may be charged) and the earth at the same time.
(3)Voltage Regulator
Voltage Regulator is a three-phase autotransformer that can adjust the second voltage. It has two pairs brush that can slide symmetrical automatically. Servo motor driven brush by the chain along the winding-cylinder autotransformer of the exposed part of (the slide) slide, adjust the second voltage smoothly to achieve the change compensation voltage and maintain output voltage stability.
(4)Circuit switch devices and operation circuit Regulators in the main circuit set up a contactor and a changeover switch, set up for
the automatic voltage compensation system can easily input and exit and. Into Regulators running, as long as the change-over switch handle at 'REGULATOR' position, press the 'ON' button on the operation panel, AC contactor can be closed; needs AC direct, as long as the knife switch handle is on 'AC 'Location. (5) Voltage detection and regulation unit
Detect and regulate the sampling control transformer on the printed circuit boards, takes out the sampling voltage and control voltage from the voltage regulator output, through the transformer, rectifier, filter and regulator, the control voltage get the upper and lower limits voltage by the potentiometer. Through the voltage transformer, rectifier, the filter,Sampling voltage get the signal voltage that change follow with the output voltage into the comparator compared, when the output voltage changes over the accuracy permitted, the voltage detection will be issued instructions regulating the output voltage until the output voltage to return to precision tuning Permitted.
(6)The overshoot’s, protection device Voltage automatic compensation system set up the overshoot’s protection.
The overshoot’s protection composed by the limit switch, when the brush slide and hit
the both ends of the limit switch, the normal close contact disconnected, the servo
motor stopped.
USER MANUAL
Page 8 sur 23
3.4 DBW Series MOTOR-REGULATOR AVR technology Specification
Type Rated Capacity
(KVA)
Output Current
(A)
Input Voltage
(V)
Output Voltage
(V)
Phase
No
Withstand
voltage
(V)
Insulated resistance
(MΩ)
Efficiency
Harmonic Distortion
Frequency(Hz)
Regulator precision
DBW-10 10 16 DBW-20 20 31 DBW-30 30 46 DBW-50 50 76 DBW-100 100 152 DBW-180 180 274 DBW-225 225 342 DBW-320 320 487 DBW-400 400 608 DBW-500 500 761 DBW-600 600 913 DBW-800 800 1217
DBW-1000 1000 1521 DBW-1200 1200 1825 DBW-1600 1600 2434
ⅠType
304~456
ⅡType
285~475
ⅢType
266~494
380V±5%
Adjustable
3 phase
2000V 1 minuteNon-Run
away
DBW-10 10 46 DBW-20 20 91 DBW-30 30 137 DBW-40 40 182 DBW-50 50 228 DBW-60 60 274 DBW-80 80 365 DBW-100 100 455 DBW-120 120 548 DBW-180 180 818 DBW-225 225 1013 DBW-300 300 1364
176~264 220±5%
Adjustable
Single phase
2000V 1minuteNon-Run
away
≥3 ≥99% Non 50~60 ±(1~5)%
Adjustable
Note: Because of company's R&D improvement unceasingly, so all specifications mentioned above are subjected to change without prior notice.
USER MANUAL
Page 9 sur 23
4.1. INTRODUCTION
This section contains all the necessary information for the correct unpacking, stocking, positioning, cabling and installation of the DBW Series AVR.
ALL THE OPERATIONS IN THIS SECTION MUST BE
PERFORMED BY the LDC authorized person. Who is
professional engineering person. If don’t connect or
operation as this manual result in damage of person or
equipment. LDC wills no responsibility.
4.1.1 Receipt of the AVR
Received the AVR, please carefully check visually the packing
and the outlook of AVR whether any physical damage was
made during the transport. If damaged or doubt damaged,
Please inform immediately:
a) Freight Forwarder
b) LDC Corporation
Confirm whether the AVR received is identical to the description
of INVOICE.
The Packing of DBW Series AVR mainly protects AVR. Which
can’t be damaged by mechanism and environment. In order to
improve the protection level, AVR is packed in plastic film.
4.1.2 Nameplate
The main Technology Specifications of DBW Series AVR are all
written at the Nameplate in front of AVR. Check whether the
content of Nameplate is identical to the product you purchased. 4.2 Equipment transport and Storage
4. Installation
USER MANUAL
Page 10 sur 23
After transportation, check equipment for damages that may have
occurred during the transport. The conveyance and your agency
must be notified in writing about the damages caused in transport,
including a detailed description of the visual defects. If you don’t
wish to install the equipment immediately, please observe the
following storage recommendations:
a). Store equipment in a vertical position in a well-conditioned room,
protected against humidity. Do not store the equipment in close
proximity to frequently used passageways and keep it away from
movable parts.
b). If the AVR system is already unpacked, please ensure storage
in a clean environment protected from dust.
4.3 Unpacking Carefully take off all the packaging material of the AVR, and then
pay attention to the arrow of the packaging.
Please unpack the packaging as follows.
Snip the packing tape, take off the packaging material upwards
Take off the plastic film on the surface of AVR
Keep the wrapper to be used for transportation in future
Check whether the AVR with any damage or not, if that Please
inform your transportation company or supplier immediately
Unpack the front door of the AVR, check the accessories as
packing list
Finally, check whether the specification of the AVR is identical
to the specification of your order. The key item in the specification
you must check is:
- RATED POWER OF THE AVR,
- INPUT VOLTAGE & FREQUENCY
- OUTPUT VOLTAGE & FREQUENCY
- NO. OF OUTPUT PHASES
4.4 Positioning The following precautions and recommendations should be
USER MANUAL
Page 11 sur 23
checked in considering the site and environment of the AVR:
a) The AVR should be located on the place with adequate
ventilation (refer to the specification of the heat dissipation of the
AVR). If the AVR is installed indoors, care must be taken in insuring
the evacuation of heat from the closed room.
b) Adequate space (at least 1M) should be allowed to open the
door without obscured by other objects for operation or
maintenance. Adequate space (at least 1M) should be allowed
at the top of the AVR; because heat dissipation is ventilated
through the top openings (ventilation booth is available upon
request). And other sides of AVR no need allowed the space,
because it doesn’t include the dissipation holes in these sides.
So it can be arrange together with other AVR near these sides
to save pace.
c) Don’t put any objects on the top of the AVR to obscure the
ventilation. Don’t locate the AVR near to any heat source or the
other machinery, which produce metallic coil dust or powder, or
facility that will produce corrosive substances or vapor.
d) Don’t locate the AVR below the shower of fire extinguishing
system (In abnormal conditions, the AVR should be protected
by cutoff the power supply).
e) It is necessary to guarantee the temperature and humidity
values of the site into which the AVR will be installed should be
within the range allowed by the specification. The AVR is
capable of continuous normal operation within a temperature
range of -5℃(23℉) to 40℃(104℉). For optimal performance
and reliability to prolong the lifetime of AVR, it is recommended
to keep the environment temperature below 25℃, and humidity
below 80%.
f) If the AVR is installed outdoor, please avoid direct exposure of
the AVR to the sunlight or rain. Avoid direct confrontation with
sand, dust or wind.
g) The floor loading capacity should be big enough to endure the
weight of the AVR Four tough right angled steel foot stands are
USER MANUAL
Page 12 sur 23
attached with the AVR, please insert the corresponding screw
nut into the floor for securing the AVR on the floor when it is
locate on territory where earthquake is expected or moving
vehicle, or tanker etc. These four nuts on the floor to secure the
AVR are shown below. 下。(10-80KVA AVR Fixed hole position
Drawing is single cabinet)
Fig 3.100-160KVA AVR Fixed hole position Drawing(double cabinet)
(h) The walls, the ceilings, the floors or anything near to the AVR
should be preferably constructed of non-combustible materials.
The portable fire extinguisher should be accessible nearby in case
of hazard.
(i) Avoid accumulating litter or trash of any sort in or around the
AVR system. The floor area surrounding the AVR should be
kept clean so that metallic powder and filings are not sucked
into the unit thus causing a short circuit and damage to the
system.
(j) Access to the AVR room should be limited to a minimum
number of operation and maintenance personnel only. The doors
should be kept locked and the keys should be confined to
authorized personnel only.
(k) Personnel who operate or maintain the AVR system should be
proficient in normal and emergency operational procedures.
USER MANUAL
Page 13 sur 23
New personnel should be trained and qualified prior to operate
the equipment.
(l) Although the AVR has past the international EMC tests, it is not
recommended to install the AVR near to any equipment, which
is susceptible to electro-magnetic interference, such as the
computer system, the monitors or the radio etc.
(m) It is more preferable to place the AVR near to the source than
to the load.
4.5 Cabling
To ensure correct operation of the AVR and its ancillary equipment it
is necessary to provide the mains cables with appropriate fuse
protection. QUALIFIED INTERNAL PERSONNEL MUST PERFORM BY
AUTHORISED ELECTRICIANS OR ALL THE OPERATIONS IN
THIS MANUAL.
DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE. BY OPENING OR REMOVING THE AVR-COVERS YOU RUN RISK OF EXPOSURE TO DANGEROUS VOLTAGES!
4.5.1 Preparation for the cable
Before you start connecting the AVR, ensure that:
MAINS VOLTAGE (INPUT VOLTS) AND FREQUENCY (FREQUENCY)
CORRESPOND TO THE VALUES INDICATED ON THE NAMEPLATE OF THE AVR.
EARTHING IS PERFORMED IN ACCORDANCE WITH THE PRESCRIBED IEC STANDARDS OR WITH LOCAL REGULATIONS;
AVR IS CONNECTED TO THE MAINS THROUGH A LV-DISTRIBUTION BOARD WITH A SEPARATE MAINS LINE (PROTECTED WITH ACIRCUIT BREAKER OR FUSE) FOR THE AVR
Provide input fuses and cables according to Figure 4-1 or in
accordance with the described IEC Standards or with the local
regulations.
USER MANUAL
Page 14 sur 23
The AVR input must meet on circuit breaker or similar protective
device. The circuit breaker installs between AC and AVR, its
function is R provides the extra protection for AVR under the
situation of overloads and short-circuits.
The Fig as below only for reference, please follow the location
electrician law to make the finally decision.
Capacity INPUT
(Specification×QTY)UNIT:mm2 Output
(Specification×QTY)UNIT:mm2 Input/output earthing(Specification×
QTY)UNIT:mm2
(3φ) 6.0 10K
(1φ) 10.0 (1φ) 10.0 4.0
(3φ) 10.0 20K
(1φ) 25.0 (1φ) 25.0 6.0
(3φ) 16.0 30K
(1φ) 35.0 (1φ) 35.0 6.0
(3φ) 16.0 40K
(1φ) 50.0 (1φ) 50.0 6.0
(3φ) 25.0 60K
(1φ) 70.0 (1φ) 70.0 6.0
(3φ) 35.0 80K
(1φ) 95.0 (1φ) 95.0 6.0
(3φ) 35.0 100K (1φ) 100.0
(1φ) 100.0 6.0
(3φ) 50.0 120K
(1φ) 70.0×2 pieces (1φ) 70.0×2 pieces 6.0
(3φ) 70.0 160K
(1φ) 95.0×2 pieces (1φ) 95.0×2 pieces 6.0
Fig4-1 Cable Specification
4.5.2 Earthing
ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED ELECTRICIANS OR BY QUALIFIED TRAINED INTERNAL PERSONNEL.
To ensure protection of personnel during the installation of AVR make sure that The connections are performed under the following conditions: • No mains voltage is present;
• Loads are shut down and disconnected;
USER MANUAL
Page 15 sur 23
• DBW series is shut down and voltage-free.
Connect the earthing wire coming from the LV-Distribution Board to the terminal "GND".
4.5.3 Connecting the in/output cable
After the AVR has been unpacked and brought to its final
position the authorized professional electrician can start to
connect the cabling.
ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL
To ensure protection of the personnel during the installation of the AVR make sure that the connections are performed under the following conditions:
• NO mains voltage is present;
• All loads are shut down and disconnected;
• DBW series is shut down and voltage-free Remove the
terminal cover of the AVR;
Before connecting the input power cables make sure that:
• All the switches are open in position OFF.
Connect the input power cable coming from the LV-Distribution Board to the terminals of the AVR showed in the following pages.
I sol at i on Cabi net I nput
TIR TIT
Figure 4. 100-160KVA AVR isolation cabinet connecting terminal row
USER MANUAL
Page 16 sur 23
Output N
TOR TON
Output L
GND
Figure 5. 100-160KVA AVR regulator cabinet connecting terminal row
TOR TON
Out put L
GNDTIR TIT
Wor k Power I nput
Out put N
Figure 6. 10-80KVA AVR isolation- regulator cabinet connecting terminal row
USER MANUAL
Page 17 sur 23
5.1 Commissioning
The DBW Series AVR is a high quality electronic Equipment that must be commissioned by a fully trained and authorized LDC field service engineer before being put into use.
The commissioning of the AVR involves the connection of the AVR, the checking of the electrical installation and operating environment of the AVR, the controlled start-up and testing of the AVR and customer training.
Any AVR system not commissioned by a LDC field service engineer or authorized service centre must be considered an electrical hazard and LDC accepts no responsibility for its safe operation or the safety of any personnel. Additionally, the manufacturer’s warranty is immediately invalidated if the AVR is put into use before it has been correctly commissioned.
ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.
Before turn on any switch or breaker, check once again the
following points listed below:
(a) Check the input voltage if it conforms to the AVR’s rated
input voltage.
(b) Check the input frequency if it conforms to the AVR’s rated input
frequency.
(c) Check if all loads at the output are switched off.
(d) Check if all air switches are switched off.
(e) If there is anything not belongs to the AVR exits inside the AVR.
This procedure is only suitable for the AVR, 10~160KVA. Please refer to the brief instruction label stuck in front of
5. Operation
USER MANUAL
Page 18 sur 23
the PCB holder.
Introduce how to turn on/off AVR now
(a) BYP SWITCH on “REGULATOR” place.
(b) Turn on INPUT SWITCH,regulator get power,key-press on
LCD “ON”,output relay closed, means that finished the Input
power electric experimentation.
(c) Index on the front panel, can see input voltage、frequency、
output voltage、output current and other related information,
key-press the “OFF” on the front panel will turn off regulator.
(d) BYP SWITCH on the “AC” Position, and closed the INPUT
SWITCH, Can get the ‘AC’ Output.
(e) The Auto / Manual switch on the front panel can choose
regulate mode.
(f) The Auto Changeover switch (on the front panel) can choose
to start-up mode.
(g) When you select manual regulator mode, key-press the
manually step-up voltage button on the front panel can
increase output voltage manually, key-press the manual
step-down voltage button on the front panel can low the
output voltage manually
(h) When the AC input but Bypass no output, the red warning
lights on the front panel.
USER MANUAL
Page 19 sur 23
6.1 INTRODUCTION
ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.
To ensure an optimum operation of the DBW series AVR and a
continuous and efficient protection of the connected load it is
recommended to check the batteries Every 6 months, depending
on the ambiance temperature.
6.2 USER RESPONSIBILITIES There are no users serviceable parts contained within the AVR so the maintenance Responsibilities of the user are minimal. To maximize the useful working life and Reliability of the AVR and its batteries, the environment in which the AVR operates should be kept cool, dry, dust and vibration free. The batteries should be holding fully charged.
6.3 ROUTINE MAINTENANCE
The AVR is designed to receive regular preventative maintenance inspections. These preventative maintenance inspections are essential to ensure that both the useful working life and the reliability of the AVR are maximized.
Preventative maintenance inspections involve working inside the
AVR, which contains hazardous AC and DC voltages. Only LDC
trained or agreed service personnel and authorized field service
engineers are fully aware of all of the hazardous areas within the
AVR.
During a preventative maintenance inspection the field service engineer will carry out the following checks: • Site/environment conditions;
• Integrity of electrical installation; • Cooling airflow;
• Regulator operation and calibration;
• Load characteristics; • Integrity of alarm and monitoring systems;
• Operation of all installed options;
6. Maintenance
USER MANUAL
Page 20 sur 23
NO Trouble Reason ACTION
1 Cannot Start-up
Input power-supply wiring mistake or electrical network abnormal
Built-in breaker open or damage
Exchanges two power wiring at will or inspects power line
Closing or replacing Breaker
2 Cannot Regulate Voltage
Voltage testing or adjust board damage
Mechanical system breakdown
Repair or the replacement
3 Voltage has not output
Voltage testing or adjust board damage
Output Relay damage Replacement
4 Frequently appears trips
Voltage testing or adjust board damage
Other protection function The specialist repairs
NOTE:
7. Troubleshooting
LDC Technology INC www.ldcups.com, www.ldctech.com
LDC Technology INC. USA 2010 BATSON AVE #252 Rowland Heights, CA 91748, USA
Tel: 001-626-8317086
Fax: 001-626-8563981