Automatic Water Flow Control
Transcript of Automatic Water Flow Control
-
7/30/2019 Automatic Water Flow Control
1/18
AUTOMATIC WATER FLOW CONTROL
For
HIGH RISE BUILDING
BY:
ABNER V. PAHILANGA
BSEE , BSME , MBA
P.E.E , RMP
-
7/30/2019 Automatic Water Flow Control
2/18
PUMP-PIPING SYSTEMS
System Curve When a pump is connected with a pipe system, it forms a pump-piping
system. A water system may consist of one pump-pumping system or acombination of several pump-piping system.
The speed of variables-speed pump in a variable-flow water
system is often controlled by a pressure-differentialtransmitter installed at the end of the supply main, with a set
point normally between 15 and 20 ft. WC ( 4.5 and 6 m WC )6.5 PSI AND 8.6 PSI. This represent the head loss resultingfrom the control valve, pipe fittings, and pipe friction
between the supply and return mains at the farthest branchcircuit from the variable-speed pump. Therefore, the headlosses of a pump piping system can be divided into two parts:
-
7/30/2019 Automatic Water Flow Control
3/18
Constant, or fixed, head loss Hfix, remains constant as the
water flow varies. Its magnitude is equal to the set point of
the pressure-differential transmitterHset, or the difference
between the suction and the discharge levels of the pump in
open systems Hsd [ft. WC (m WC )].
Variable head loss Hvar, which varies as the water flow
changes. Its magnitude is the sum of the head losses causedby pipe friction Hpipe,pipe fittings Hfit, equipment Heq,,
and components Hcp, all in ft WC (m WC), that is,
Hvar= Hpipe + Hfit + Heq + Hcp
-
7/30/2019 Automatic Water Flow Control
4/18
Head losses Hfix and Hvar. The relationship between thepressurelossp [ft WC (kpa)]; flow headHvar[ft WC ( m WC)]; flow
resistance of the water systemR var[ft WC/(gpm)2 (m WC.s2/m6)];and water volume flow rateVw [gpm (m
3/s], can be exprssed as
Hvar = p [ gc/pwg ]
p = Rvar
V2w
Hvar =R varV2w
Where pw ( RHO) = density of water, lb/ft3 (kg/m3)
g = gravitational acceleration, ft/s2 (m/s2)
gc = dimensional constant, 32.2lbm ft/lbfs2
-
7/30/2019 Automatic Water Flow Control
5/18
The curve that indicates between the flow head, flow resistance, and
water volume flow rate is called thesystemcurve of a pumping
system, or a water system.
SYSTEM OPERATING POINT
The intersection of the pump performance curve and water systemcurve is the operating point of this variable-flow water system as shown
by pointP. Its volume flow rate is representedby Vr[gpm ( m3/s)],and
its total head is Hp = Hfix + Hvar[ ft WC (m WC)].
Usually, the calculated head lossis over estimated,and the
selected pump is oversized with higher pump head, so thatthe actual system operation point is point P.
-
7/30/2019 Automatic Water Flow Control
6/18
Therefore, for a variable-flow water system installed with a
constant-speed pump, the design system operating point is
preferably located to the left of the region of pump maximumefficiency, because the system operating point of an oversized pump
moves into or nearer to the region of pump maximum efficiency.
COMBINATIONOF PUMP PIPING SYSTEM
When two pump-piping system 1 and 2 are connected in series, the
volume flow rate that combined pump-piping system, Vcom [ gpm
(m3/s)] is
Vcom = V1 = V2
-
7/30/2019 Automatic Water Flow Control
7/18
TWO PUMP IN SERIES
H1
H2
Ht
P1 + P2
P1
P2
Vt
R
R
R
Operating
point
Hfix
-
7/30/2019 Automatic Water Flow Control
8/18
Where V1 and V2 are the flow rate of pump-piping systems 1 and 2, gpm(m3/s). The total head lift of the combined system H
com[ ft WC (m WC)]
is
Hcom = H1 + H2
where H1
and H2 are the head of the pump-piping systems 1 and 2, ft
WC ( m WC ).
It is simpler to use one system curve to represent the wholesystem, to use a combined system curve. The system operating pointof the combined pump-piping system is illustrated by pontPwith avolume flow ofVp and head ofHp. The purpose of pump-piping
system in series is to increase the system head.
-
7/30/2019 Automatic Water Flow Control
9/18
When a pump-piping system has a parallel-connected water pimps,
its volume flow rate V[gpm (m3/s)] is the sum of the volume flow
rates of the consumed pumps V1
, V2
,etc.. The head of each
constituent pump and head of the combined pump-piping system are
equal. It is more convenient to draw a combined pump curve and
one system curve to determine their intersection, the system
operating pointP. The purpose of equipping a water system with
parallel-connected pumps is to increase its volume flow rate.
-
7/30/2019 Automatic Water Flow Control
10/18
PUMP IN PARALLEL OPERATION
P1P1
P2
P3
Q1
Q2
Q3
gpm
H
Q1
Q1 + Q2
Q1 + Q2 + Q3
-
7/30/2019 Automatic Water Flow Control
11/18
MODULATION OF PUMP-PIPING SYSTEM
Modulation of the volume flow rate of a pump-piping system can
be done by means of the following:
Throttle the volume flow by using a valve. As the valve closes is
opening, the flow resistance of the pump-piping system increases. A
new system curve is form, which results in having new systemoperating point that moves along the pump curves to the left-hand
side of the original curve, with a lower volume rate and higher total
head. Such behavior is known as riding on the curve. Using the
valve to modulate the volume flow rate of a pump-piping system
always wastes energy because of the head loss across the valveHval.
-
7/30/2019 Automatic Water Flow Control
12/18
Turn the water pumps on or off in sequence for pump-piping
systems that have multiple pumps in a parallel connection.
Modulation of the volume flow rate by means of turning waterpumps on and off often result in a sudden drop or increase in the
volume flow rate and head, as shown by system operating pointsP,
Q and T.
Vary the pump speed to modulate the volume flow and head of the
pump-piping system. When the speed of the pump is varied from n1ton2 and then to n3 , new pump curvesP2 andP3 are formed. the
system operating point will move from point Pto Q and then to T
along the system curve, with a lower volume flow rate, head, andinput pump power. The system curve become modulating curve and
approaches Hfix = Hsetis the set point of pressure-differential
transmitter,
-
7/30/2019 Automatic Water Flow Control
13/18
Ft WC ( m WC). Varying the pump speed requires the lower pump
power input in comparison with other modulatiopn methods.
METHOD OF MODULATION
GPM
INVTR
FREQ
GPM
n1
n2
n3
H
H
-
7/30/2019 Automatic Water Flow Control
14/18
PUMP LAWS
The performance of geometrically and dynamically similar
pump-piping systems 1 and 2 can be expressed as follows:
V2/V2= D32n2/ D
31n1
H2 /H1 = n22 /n21
P2/ P1 = n32/n
31
Where V = volume flow rate of pump-piping system, gpm
(m3/s)
H1 = total head lift, ft WC (m WC)
P = pump over input at shaft, hp (kW) D = outside diameter of pump impeller, ft (m)
n = speed of pump impeller, rpm
-
7/30/2019 Automatic Water Flow Control
15/18
WIRE-TO-WATER EFFICIENCY
A pump may be directly driven by a motor, or it may be driven by
a motor and belts. When the energy cost of water system isevaluated, the pump total efficiency p, the motor efficiency mot,
and the efficiency of the variable-speed drives drshould all be
considered.
The wire-to-water efficiency of a water system ww, expressed
either in dimensionless in form as a percentage, is defined as the
ratio of energy output from water to energy input to the electric wire
connected to the motor. It can calculated as
ww = p drmot
-
7/30/2019 Automatic Water Flow Control
16/18
The total efficiency of the centrifugal pump p can be obtain from
the manufacturer or calculated. The pump efficiency p depends on
the type and size of pump as well as the percentage of the designvolume flow rate during operation. Pump efficiency usually varies
from 0.7 to 0.85 at the design volume flow rate. Drive efficiency dr
indicates the efficiency of to direct drive, belt drive, and various
type of speed drives. For direct drive, dr= 1. among variable-speed
drives, an adjustable-frequency alternating-current (AC) has thehighest drive efficiency. For a 25hp (18.7-kw) motor, dr often
varies from 0.80 at 20 percent design flow. Motor efficiency mot
depends on the type and size of motor. It normally varies from 0.91
for a 10-hp ( 7.5-kw ) high efficiency motor to 0.96 for a 250-hp (
187-kw ) motor.
-
7/30/2019 Automatic Water Flow Control
17/18
MULTI ZONE APPLICATION FIRE PUMP
150psi 150psi
150psi
max
max
max
LOW ZONE
MED ZONE HI ZONE
PUMP 1PUMP 2 PUMP 3
Vp1 = Vp2 = Vp3
H1 + H2 + H3 = Htotal
LOW ZONE
P1-RUNMED ZONE P1& P2 - RUN
HI ZONE- P1& P2 & P3 - RUN
-
7/30/2019 Automatic Water Flow Control
18/18
WISDOM IS THE PRINCIPAL THING,
THEREFORE GET WISDOM.
AND IN ALL YOUR GETTING , GET
UNDERSTANDING
PROVERBS 4 : 7
GOD BLESS AND THANK YOU