Automatic Water Flow Control

download Automatic Water Flow Control

of 18

Transcript of Automatic Water Flow Control

  • 7/30/2019 Automatic Water Flow Control

    1/18

    AUTOMATIC WATER FLOW CONTROL

    For

    HIGH RISE BUILDING

    BY:

    ABNER V. PAHILANGA

    BSEE , BSME , MBA

    P.E.E , RMP

  • 7/30/2019 Automatic Water Flow Control

    2/18

    PUMP-PIPING SYSTEMS

    System Curve When a pump is connected with a pipe system, it forms a pump-piping

    system. A water system may consist of one pump-pumping system or acombination of several pump-piping system.

    The speed of variables-speed pump in a variable-flow water

    system is often controlled by a pressure-differentialtransmitter installed at the end of the supply main, with a set

    point normally between 15 and 20 ft. WC ( 4.5 and 6 m WC )6.5 PSI AND 8.6 PSI. This represent the head loss resultingfrom the control valve, pipe fittings, and pipe friction

    between the supply and return mains at the farthest branchcircuit from the variable-speed pump. Therefore, the headlosses of a pump piping system can be divided into two parts:

  • 7/30/2019 Automatic Water Flow Control

    3/18

    Constant, or fixed, head loss Hfix, remains constant as the

    water flow varies. Its magnitude is equal to the set point of

    the pressure-differential transmitterHset, or the difference

    between the suction and the discharge levels of the pump in

    open systems Hsd [ft. WC (m WC )].

    Variable head loss Hvar, which varies as the water flow

    changes. Its magnitude is the sum of the head losses causedby pipe friction Hpipe,pipe fittings Hfit, equipment Heq,,

    and components Hcp, all in ft WC (m WC), that is,

    Hvar= Hpipe + Hfit + Heq + Hcp

  • 7/30/2019 Automatic Water Flow Control

    4/18

    Head losses Hfix and Hvar. The relationship between thepressurelossp [ft WC (kpa)]; flow headHvar[ft WC ( m WC)]; flow

    resistance of the water systemR var[ft WC/(gpm)2 (m WC.s2/m6)];and water volume flow rateVw [gpm (m

    3/s], can be exprssed as

    Hvar = p [ gc/pwg ]

    p = Rvar

    V2w

    Hvar =R varV2w

    Where pw ( RHO) = density of water, lb/ft3 (kg/m3)

    g = gravitational acceleration, ft/s2 (m/s2)

    gc = dimensional constant, 32.2lbm ft/lbfs2

  • 7/30/2019 Automatic Water Flow Control

    5/18

    The curve that indicates between the flow head, flow resistance, and

    water volume flow rate is called thesystemcurve of a pumping

    system, or a water system.

    SYSTEM OPERATING POINT

    The intersection of the pump performance curve and water systemcurve is the operating point of this variable-flow water system as shown

    by pointP. Its volume flow rate is representedby Vr[gpm ( m3/s)],and

    its total head is Hp = Hfix + Hvar[ ft WC (m WC)].

    Usually, the calculated head lossis over estimated,and the

    selected pump is oversized with higher pump head, so thatthe actual system operation point is point P.

  • 7/30/2019 Automatic Water Flow Control

    6/18

    Therefore, for a variable-flow water system installed with a

    constant-speed pump, the design system operating point is

    preferably located to the left of the region of pump maximumefficiency, because the system operating point of an oversized pump

    moves into or nearer to the region of pump maximum efficiency.

    COMBINATIONOF PUMP PIPING SYSTEM

    When two pump-piping system 1 and 2 are connected in series, the

    volume flow rate that combined pump-piping system, Vcom [ gpm

    (m3/s)] is

    Vcom = V1 = V2

  • 7/30/2019 Automatic Water Flow Control

    7/18

    TWO PUMP IN SERIES

    H1

    H2

    Ht

    P1 + P2

    P1

    P2

    Vt

    R

    R

    R

    Operating

    point

    Hfix

  • 7/30/2019 Automatic Water Flow Control

    8/18

    Where V1 and V2 are the flow rate of pump-piping systems 1 and 2, gpm(m3/s). The total head lift of the combined system H

    com[ ft WC (m WC)]

    is

    Hcom = H1 + H2

    where H1

    and H2 are the head of the pump-piping systems 1 and 2, ft

    WC ( m WC ).

    It is simpler to use one system curve to represent the wholesystem, to use a combined system curve. The system operating pointof the combined pump-piping system is illustrated by pontPwith avolume flow ofVp and head ofHp. The purpose of pump-piping

    system in series is to increase the system head.

  • 7/30/2019 Automatic Water Flow Control

    9/18

    When a pump-piping system has a parallel-connected water pimps,

    its volume flow rate V[gpm (m3/s)] is the sum of the volume flow

    rates of the consumed pumps V1

    , V2

    ,etc.. The head of each

    constituent pump and head of the combined pump-piping system are

    equal. It is more convenient to draw a combined pump curve and

    one system curve to determine their intersection, the system

    operating pointP. The purpose of equipping a water system with

    parallel-connected pumps is to increase its volume flow rate.

  • 7/30/2019 Automatic Water Flow Control

    10/18

    PUMP IN PARALLEL OPERATION

    P1P1

    P2

    P3

    Q1

    Q2

    Q3

    gpm

    H

    Q1

    Q1 + Q2

    Q1 + Q2 + Q3

  • 7/30/2019 Automatic Water Flow Control

    11/18

    MODULATION OF PUMP-PIPING SYSTEM

    Modulation of the volume flow rate of a pump-piping system can

    be done by means of the following:

    Throttle the volume flow by using a valve. As the valve closes is

    opening, the flow resistance of the pump-piping system increases. A

    new system curve is form, which results in having new systemoperating point that moves along the pump curves to the left-hand

    side of the original curve, with a lower volume rate and higher total

    head. Such behavior is known as riding on the curve. Using the

    valve to modulate the volume flow rate of a pump-piping system

    always wastes energy because of the head loss across the valveHval.

  • 7/30/2019 Automatic Water Flow Control

    12/18

    Turn the water pumps on or off in sequence for pump-piping

    systems that have multiple pumps in a parallel connection.

    Modulation of the volume flow rate by means of turning waterpumps on and off often result in a sudden drop or increase in the

    volume flow rate and head, as shown by system operating pointsP,

    Q and T.

    Vary the pump speed to modulate the volume flow and head of the

    pump-piping system. When the speed of the pump is varied from n1ton2 and then to n3 , new pump curvesP2 andP3 are formed. the

    system operating point will move from point Pto Q and then to T

    along the system curve, with a lower volume flow rate, head, andinput pump power. The system curve become modulating curve and

    approaches Hfix = Hsetis the set point of pressure-differential

    transmitter,

  • 7/30/2019 Automatic Water Flow Control

    13/18

    Ft WC ( m WC). Varying the pump speed requires the lower pump

    power input in comparison with other modulatiopn methods.

    METHOD OF MODULATION

    GPM

    INVTR

    FREQ

    GPM

    n1

    n2

    n3

    H

    H

  • 7/30/2019 Automatic Water Flow Control

    14/18

    PUMP LAWS

    The performance of geometrically and dynamically similar

    pump-piping systems 1 and 2 can be expressed as follows:

    V2/V2= D32n2/ D

    31n1

    H2 /H1 = n22 /n21

    P2/ P1 = n32/n

    31

    Where V = volume flow rate of pump-piping system, gpm

    (m3/s)

    H1 = total head lift, ft WC (m WC)

    P = pump over input at shaft, hp (kW) D = outside diameter of pump impeller, ft (m)

    n = speed of pump impeller, rpm

  • 7/30/2019 Automatic Water Flow Control

    15/18

    WIRE-TO-WATER EFFICIENCY

    A pump may be directly driven by a motor, or it may be driven by

    a motor and belts. When the energy cost of water system isevaluated, the pump total efficiency p, the motor efficiency mot,

    and the efficiency of the variable-speed drives drshould all be

    considered.

    The wire-to-water efficiency of a water system ww, expressed

    either in dimensionless in form as a percentage, is defined as the

    ratio of energy output from water to energy input to the electric wire

    connected to the motor. It can calculated as

    ww = p drmot

  • 7/30/2019 Automatic Water Flow Control

    16/18

    The total efficiency of the centrifugal pump p can be obtain from

    the manufacturer or calculated. The pump efficiency p depends on

    the type and size of pump as well as the percentage of the designvolume flow rate during operation. Pump efficiency usually varies

    from 0.7 to 0.85 at the design volume flow rate. Drive efficiency dr

    indicates the efficiency of to direct drive, belt drive, and various

    type of speed drives. For direct drive, dr= 1. among variable-speed

    drives, an adjustable-frequency alternating-current (AC) has thehighest drive efficiency. For a 25hp (18.7-kw) motor, dr often

    varies from 0.80 at 20 percent design flow. Motor efficiency mot

    depends on the type and size of motor. It normally varies from 0.91

    for a 10-hp ( 7.5-kw ) high efficiency motor to 0.96 for a 250-hp (

    187-kw ) motor.

  • 7/30/2019 Automatic Water Flow Control

    17/18

    MULTI ZONE APPLICATION FIRE PUMP

    150psi 150psi

    150psi

    max

    max

    max

    LOW ZONE

    MED ZONE HI ZONE

    PUMP 1PUMP 2 PUMP 3

    Vp1 = Vp2 = Vp3

    H1 + H2 + H3 = Htotal

    LOW ZONE

    P1-RUNMED ZONE P1& P2 - RUN

    HI ZONE- P1& P2 & P3 - RUN

  • 7/30/2019 Automatic Water Flow Control

    18/18

    WISDOM IS THE PRINCIPAL THING,

    THEREFORE GET WISDOM.

    AND IN ALL YOUR GETTING , GET

    UNDERSTANDING

    PROVERBS 4 : 7

    GOD BLESS AND THANK YOU