Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ......

21
ATC5300 Automatic Transfer Controller Remote Control Software Manual Edition 03/2011 A5E02469028-02 General Information 1 Connection 2 User Interface 3 Menus 4 s

Transcript of Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ......

Page 1: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

ATC5300

Automatic Transfer Controller

Remote Control Software Manual

Edition 03/2011A5E02469028-02

General Information 1

Connection 2

User Interface 3

Menus 4

s

Page 2: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Legal information

Warning notice system

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel

The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation for the specific task, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

Proper use of Siemens products

Note the following:

Trademarks

All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Disclaimer of Liability

We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

DANGER

indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING

indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION

with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.

CAUTION

without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.

NOTICE

indicates that an unintended result or situation can occur if the corresponding information is not taken into account.

WARNING

Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be adhered to. The information in the relevant documentation must be observed.

Siemens AGIndustry SectorPostfach 48 4890026 NÜRNBERGGERMANY

® 03.2011Copyright © Siemens AG 2010.Technical data subject to change

Page 3: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 1

Table of Contents

Table of Contents

1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.2 Minimum Resources of the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.4 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.1 Activation of the PC-ATC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.1.1 RS 232 Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52.1.2 RS 485 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3 User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.1 Main Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3.2 System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.2.1 Configuration-Options-General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93.2.2 Configuration-Options-Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

3.3 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113.3.1 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113.3.2 New Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

3.4 Real Time Clock Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

3.5 Access to Setup Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3.6 Online Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

3.7 Offline Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

3.8 Parameters Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

4 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4.1 Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

4.2 View Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164.2.1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164.2.2 Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.2.3 Statistical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184.2.4 Inputs-Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194.2.5 Keyboard Lock-Unlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Page 4: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Table of Contents

ATC53002 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

Page 5: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 3

General Information 1General Information

1.1 Introduction

With SENTRON SOFTWARE ATC remote control software, you can connect one or several ATC transfer switches to a PC via a RS 232 serial port or a RS 485 serial bus.

It can be used for commissioning of the controller, for troubleshooting in case of problems and also for continuous supervision.

The software provides the following functions:

• Graphic display of all the measurements returned by the device

• Access to the Setup menus

• Access to ATC Real time clock

• Access to ATC statistic data

• Possibility of set-up parameter save/load/printout

• Display of virtual front panel of the controller with the possibility of activating the keys

• Switching between operation modes

• ATC device keypad lock

• Display of the Event log, showing the most recent 100 events with date and time

1.2 Minimum Resources of the PC

• Windows® 95/98/2000/XP operating system

• Graphic card with 1024x768 or higher resolution

• A free standard RS 232 serial interface (COM:)

• 64 Mb of RAM

• Pentium® class or higher processor

• CD-ROM drive for installation

Page 6: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

General Information

1.3 Installation

ATC53004 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

1.3 Installation

To install the software, you need a PC with the operating system already installed and running and the program setup CD. You should also have at least a basic knowledge of the PC and be familiar with Windows® operating system commands.

1. Close all applications running

2. Insert the CD in the drive.

3. From the CD, start the ATC_Setup.exe program.

4. If a previous installation is already present on the hard drive, then the installation program will automatically start a procedure to remove the older revision. After this, the installation process will start.

5. A window is displayed asking you to specify the directory in which you want to install the program. To change directory, enter the new name in the specific box.

6. Follow the instructions that will be shown until the end of installation.

7. Reboot the PC.

1.4 Technical Support

For further assistance, refer to:

Technical Support on the Internet:

Internet address of Technical Support

http://www.siemens.com/lowvoltage/technical-support

Page 7: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 5

Connection 2Connection

2.1 Activation of the PC-ATC Connection

To operate the remote control program, it is essential the PC and ATC can communicate by serial interface.

The connection can be realized in different ways, since the ATC is provided with two independent serial interfaces:

2.1.1 RS 232 Direct Connection

• Connect the ATC and the PC using the connection cable.

• Can be used to quickly connect the device during commissioning / maintenance.

• It is possible to connect only one device at a time.

2.1.2 RS 485 Connection

• Connect the ATC through a COM-Interface (e.g. RS 232 / RS 485 converter) to the PC.

• Connect all ATC RS 485 interface terminals in parallel with the twisted-pair cable and then to the interface converter, as shown in the following wiring diagram. Make sure the polarity of RS 232 / RS 485 is correct (A and B terminals).

• The interface converter must be insulated and have an automatic enable line control circuit.

• In case you have connected more than one device, from the front keyboard of each device, enter the Function setup and set one different RS 485 serial address for each ATC, starting from address 01. Make sure that the PC speed and parity settings match the ATC RS 485 setting.

Page 8: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Connection

2.1 Activation of the PC-ATC Connection

ATC53006 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

VOLTAGE INPUTSLINE 2

VOLTAGE INPUTSLINE 2

LINE 1VOLTAGE INPUTS VOLTAGE INPUTS

LINE 1

AC SUPPLY AC SUPPLY

SG

B

A

TR

RS 485

SG

B

A

TWISTED-PAIR CABLE TWISTED-PAIR CABLE

ATC 53001st or last device in network

ATC 5300

INPUTSDIGITAL

3.3

250V 5A

250V 5AAC1

B300

AC1

B300

3.6

3.8

3.7

3.5

3.4

4.4

4.2

4.3

4.6

4.5

4.7

4.8

250V 5A

250V 12A

250V 12A

250V 5A

250V 5A

2.1

AC1

B300

B300

AC1

AC1

3.1

3.2

2.2

2.3

B300

AC1

B300

B300

AC1

1.3

1.2

1.1

4.19.1

RS485

TR 6.4

A 6.3

B 6.2

SG 6.1

RS232

9.3

9.4N

L3

9.2L2

L1

220-240V

0V

+DC SUPPLY

-- 5.3

5.2

5.1

8.4N

L38.3

8.2L2

L18.1

7.3

7.2

7.1

3.2

3.7250V 5AAC1

3.8

B300

3.6

3.5

B300

AC1250V 5A

3.3

3.4

2.3250V 5A

B300

AC1250V 5A

AC1

3.1

B300

B300

AC1250V 12A

2.2

2.1

1.1250V 12A

B300250V 5A

AC1

AC1

1.3

1.2

B300

N8.4

4.8 TR 6.4

4.6

4.7

4.5

4.4

4.2

4.3

4.1

RS485

B 6.2

A 6.3

SG 6.1

RS232

9.4N

9.2

9.3L3

L2

9.1L1

220-240V

DIGITALINPUTS

+DC SUPPLY

5.2-- 5.3

5.1L2

8.3L3

L1

8.2

8.1

7.3

7.2

0V 7.1

100-690VAC50 / 60 Hz 50 / 60 Hz

100-690VAC

L MAX = 1200m

RS 485

TR

HAZARDOUS VOLTAGEWill cause death or seriousinjury.

Turn off and lock out all powersupplying this device.Replace all covers before powersupplying this device is turnedon.

DANGERHAZARDOUS VOLTAGEWill cause death or seriousinjury.

Turn off and lock out all powersupplying this device.Replace all covers before powersupplying this device is turnedon.

DANGER

Page 9: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 7

User Interface 3User Interface

3.1 Main Window

The main window displays all the various measurements returned by the device, providing a complete overview of the panel status.

All the functions are accessible from the drop-down menus, and those used most frequently are also shown on the toolbar. Some of these functions are blocked and can be accessed only after entering the modifiable password (at the first setting, the default password is "SIEMENS").

The following are displayed in the main window:

• Voltage and frequency of both Line 1 and Line 2 sources

• Switching devices status

• ATC supply status

• Alarm status

Lastly, the following are indicated from left to right on the status bar, close to the lower edge of the main window:

• Model and release of the internal firmware of the ATC connected

• Serial communication status (ONLINE = connection active, OFFLINE = connection not active)

• ATC operating mode

• Any alarm conditions

• Page refresh rate

Page 10: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.1 Main Window

ATC53008 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

¿ AC and DC power supply status Ë Switches to ONLINE mode (communication on)

À Alarms status Ì Switches to OFFLINE mode (communication off)

Á Page refresh time Í Selects operation mode on the ATC

 Live alarms ΠReal time clock setting

à Current ATC operating mode Ï Accessess the setup menu programming

Ä Serial connection status Ñ Displays the virtual front panel

Å Device model and software revision Ò Displays the event log window

Æ In MAN mode, double-clicking on this box will initiate a manual transfer between power sources

Ó Displays statistic data

Ç Line status indicators Displays Inputs - Outputs status

È Frequency reading Switches locking of the ATC keypad ON/OFF

É Voltage readings Drop-down box to select the controller in RS 485 multi-drop networks

Ê Icon (Utility / genset)

21

22

23

Page 11: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.2 System Configuration

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 9

3.2 System Configuration

To access the configuration window it is necessary to enter the password. After the first installation, by default, the password is "SIEMENS" (the user can change it later).

1. Click on Password menu, type "SIEMENS" and then confirm with OK.

2. Now, to open the configuration window click on Configuration-Options menu. The configuration phase is a very important step to correctly define the program operation. In particular, in the case in which more than one device are connected, the user will have to pay attention to the setting of each ATC connected to the network.

Before proceeding with the explanation of the various functions of the software, we will examine the configuration window, looking at the meaning of all settings.

3.2.1 Configuration-Options-General

In the general window there are some generic settings of the software. Particular attention must be paid to the serial port setting, that must be used to select the PC serial port, and to the serial interface settings, which must be the same as the ones programmed into the controllers Function setup.

¿ PC serial port settings

À Software language selection

Page 12: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.2 System Configuration

ATC530010 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

3.2.2 Configuration-Options-Controllers

When using a RS 485 multidrop network, it is necessary to specify how many controllers are connected to the PC. Using this window it is possible to configure the total number of ATC, and to give a name to each of them. In case one controller is not to be accessed, it is possible to disable it using the dedicated checkbox.

Total number of configures ATCs

Add a new ATC to the network configuration

Removes the last ATC from the network configuration

Selects the previous / next ATC

Description of the ATC. It is used to identify the controller in the main page, data log, events and more.

Enables / disables the serial communication with the selected ATC

Selected ATC

Page 13: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.3 Password

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 11

3.3 Password

When the software is started some of the functions are disabled. By means of the Password menu it is possible to type the password that will allow access to all functions, including:

• Modifying remote control software setting

• Entering a new password

• Delete records from Data log databases

• Modify the ATC settings from the remote control

• Operate the virtual front panel keys

• Reset MAX values, event log, operation counters etc.

3.3.1 Password

After the first installation the password is "SIEMENS". Later, the user will be able to customize its password, using the New Password button and then entering the new desired password two times.

3.3.2 New Password

3.4 Real Time Clock Setting

To view and set the RTC (real time clock) of the ATC, click on the dedicated icon on the toolbar. The following window will be shown, allowing to check and eventually modify the clock setting.

Clicking here will transmit the current PC clock to the ATC

Transmits the setting previously manually entered in the fields above

Actual ATC clock setting

Page 14: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.5 Access to Setup Menus

ATC530012 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

3.5 Access to Setup Menus

Device settings are entered via the setup parameters, which you can display and modify from the specific Parameters menu, or directly from the toolbar by clicking on the matching icon. If you have not entered the password previously, only the current settings are displayed without transmission of modifications to the device.

This method of accessing ATC settings is handier and more immediate compared with direct access from the front keypad using the PC; the following are displayed:

• Code of the parameter

• Description in the language set

• Value set

• Graphic box or drop-down box with possible options

The ATC device's parameters have been grouped in several menus that reflect the organization described in the operations manual.

• P1 - Rated data menu

• P2 - General data menu

• P3 - Line 1 voltage control

• P4 - Line 2 voltage control

• P5 - Programmable inputs

• P6 - Programmable outputs

• P7 - Serial interface ports

• P8 - Automatic test

You can save the complete series of settings of a device in a file, to re-use them to set another device with the same settings. You can save the complete series of settings of a ATC on the disk of the PC in an ASCII text file for fast, easy reloading in another device. This function is useful when programming a number of control units with the same settings, or in order to maintain a master file of the original settings of a system.

3.6 Online Programming

When the PC is connected to a device (Online mode) the parameter transfer is always done from / to the device internal memory. In this mode, the user can:

• View and modify the parameter values into the device (menu Parameters-Edit setup parameters then use buttons Transmit and Receive)

• Load a file from disk and transmit it to the device (Parameters-Load file)

• Download the device settings and save them into a file (Parameters-Save file)

• Print the device settings (Parameters-Print)

Page 15: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.7 Offline Programming

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 13

3.7 Offline Programming

When the user is working without an ATC device connected to the PC (Offline mode), then all the transfers are from / to the hard disk. In this mode it is possible to:

• Load an existing file from disk, show its content on the setup table window (Parameters-Load file). From the setup table window is then possible to edit parameters and save them back to disk (button Save) or print them (button Print).

• Create a new parameter file with the factory default settings (Parameters-New default file). In this case the user will be prompted to specify the device model and the software revision level of the destination device (shown on the device display at power-up). The default revision is the most recent.

• Re-open the setup table to edit parameters (Parameters-Edit setup parameters). If the user tries to edit parameters before having loaded a file, the system will act like when creating a new file.

3.8 Parameters Files

The following are saved in each .PAR file:

• Type and internal release of the ATC device

• Setup parameters of all menus

The online file transfer to an ATC can be done only if the file to be uploaded was created for the same ATC model and has a compatible software revision, otherwise the software will give an alarm indication.

Page 16: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

User Interface

3.8 Parameters Files

ATC530014 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

Page 17: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 15

Menus 4Menus

4.1 Setup Menu

Graphic bar. Drag this with the mouse to modify the setting Transmits the values displayed in the window to the ATC and saves them. Enabled only in online mode, with password.

Setting of the parameter. Highlighted in yellow if different from the factory-set default value. Double-clicking on this box, the parameter can be set using the numeric keypad.

Scroll down box with possible options

Scroll bar to access the parameters below Parameter descriptionCloses the setup window Code of the parametersResets the values to the factory-set default Menu titleReceives the values of the parameters from the ATC and displays these in the window. Enabled only in online mode.

Page 18: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Menus

4.2 View Menu

ATC530016 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

4.2 View Menu

4.2.1 Front Panel

Using the programming software, you can also display a "virtual" representation of the front panel of the ATC on the monitor of the PC; this is useful, for example, if you want to demonstrate functioning by projecting the image of the monitor of the PC. Accessing this window from the Display-Front Panel menu, the front panel of the device connected is shown, with real-time display of the readouts and LEDs in their current status. When working in a multi-drop network, in the title bar of the window it is reported the name of the unit currently selected.

Clicking with the mouse on the keys (after having entered the password), you can select the measurements and functions in the same way as on the physical device. However, you cannot access those functions (such as parameter programming, reset statistics, etc.) that require simultaneous pressing and/or holding down of the keys.

Note

The quality of the graphic representation of the front panel may vary according to the graphic resolution of your PC and/or the monitor settings used.

Possibility of clicking on the keys

Real-time display of the status of the readouts and LEDs

Name of the currently selected unit.

Page 19: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Menus

4.2 View Menu

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 17

4.2.2 Event Log

The event log window shows what happened to the system in the past, keeping trace of the last 40 events, each of them with date and time reference. Events history is stored in non-volatile memory, so it is kept even without power supply.

Events include:

• Source lines present / not present

• Switching devices opening / closing

• Alarms begin and end

• Change of operation mode

• Change of setup parameters

• Remote communication on / off

• Power supply on / off

Event number à Print event history

À Event time stamp Ä Export to ASCII file.

Á Code and description of the event Å Clear events history. Available only after entering the password.

 Close Event log window

Page 20: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Menus

4.2 View Menu

ATC530018 Remote Control Software Manual, Edition 03/2011, A5E02469028-02

4.2.3 Statistical Data

The statistical data window groups some time-meters and operation counters that keep track of the ATC operation history. These data are stored in a non-volatile memory so they are not lost when the ATC is powered down.

Two password-protected buttons allow to reset timers and counters.

¿ Reset buttons

À Time meters

Á Operation counters

Page 21: Automatic Transfer Controller - Siemens · PDF fileATC5300 Automatic Transfer Controller ... With SENTRON SOFTWARE ATC remote control ... ATC transfer switches to a PC via a RS 232

Menus

4.2 View Menu

ATC5300Remote Control Software Manual, Edition 03/2011, A5E02469028-02 19

4.2.4 Inputs-Outputs

This window shows the function programmed on ATC Input-Output terminals, and their current status. Please note that for the output relays, the status shown is the status of the relay coil (energized / not energized) that sometimes is opposite to the logic function of the relay (example: global alarm relay energized = conditions ok).

4.2.5 Keyboard Lock-Unlock

Using this function it is possible to lock or unlock the front panel keyboard of the device, preventing unauthorized access to setup settings, memory clearing etc. For further information see the ATC5300 operation manual.