Automatic Load Control Relay (DIN) ETC ® 1 of 2 Emergency Power Series GENERAL INFORMATION The Automatic Load Control Relay (ALCR) is a UL 924 listed emergency device that is powered from an always-available normal/ emergency source fed by an upstream emergency transfer switch. The ALCR provides power to emergency lighting load(s) by bypassing switches or other controls upon loss of utility power and ensuring a “lights on state” during loss of normal power while tracking the state of normal lighting loads during normal operation. In the DIN rail mount model, the ALCR also includes a method of accomplishing the same emergency functionality for directly- controlled 0-10V fixtures or ballasts. An integral relay positively disconnects 0-10V control upon loss of utility power assuring a “lights-on” override for both line voltage and 0-10V controlled emergency fixtures. APPLICATIONS • Conference centers • Hotels • Dorms • Office buildings • Government buildings • Restaurants • Schools • Houses of worship • Theaters FEATURES • 120V and 277V power systems • Automatically activates lighting upon loss of normal power • Provides remote activation by dry contact closure for connection to a fire alarm or building management system • Additional control output connection to activate 0-10V controled fixtures • Configurable “return-to-normal” delay of 0-15 minutes • Simple installation; attaches to standard DIN rail for permanent installation • Maintenance-free ORDERING INFORMATION Unison Aero ® Relay Controller Sensor MODEL DESCRIPTION ALCR-DIN Automatic Load Control Relay (DIN) SPECIFICATIONS GENERAL • UL 924 Listed • UL 2043 plenum-rated FUNCTIONAL • Automatic control of emergency power output to fixture or single zone emergency lighting upon loss of normal power • Supports fire alarm input activation of emergency power output • Configurable return to normal delay settings of instant, 10 seconds, 30 seconds, 10 minutes, or 15 minutes • Additional relay cuts 0-10V control loop for guaranteed full- on operation of 0-10V controlled fixtures MECHANICAL • DIN rail mount: 35mm; DIN43880 and EN60715 compliant • Constructed of UL94 V-0 approved injection-molded ABS • Remote and status LED’s • 2 buttons shall be available to select optional return to normal delay and output test ELECTRICAL • 120/277 VAC, 60Hz power input • Normally closed (NC), 20A ballast, 10A tungsten • 2 LEDs: - Status: Red for emergency active or Green for normal - Remote: Amber for state of normal control switch • Terminal wire sizing: 10-18 AWG • Remote activation switch can be located up to 1000 feet from ALCR THERMAL • Ambient room temperature: -10° to 45°C / 14° to 113°F • Ambient humidity: 5 to 95% non-condensing

Transcript of Automatic Load Control Relay (DIN) - fullcompass.com€¦ · ETC® Automatic Load Control Relay...

Page 1: Automatic Load Control Relay (DIN) - fullcompass.com€¦ · ETC® Automatic Load Control Relay (DIN) 1 of 2 Emergency Power Series GENERAL INFORMATION The Automatic Load Control

Automatic Load Control Relay (DIN)ETC®

1 of 2

Emergency Power Series

G E N E R A L I N F O R M A T I O N

The Automatic Load Control Relay (ALCR) is a UL 924 listed emergency device that is powered from an always-available normal/emergency source fed by an upstream emergency transfer switch. The ALCR provides power to emergency lighting load(s) by bypassing switches or other controls upon loss of utility power and ensuring a “lights on state” during loss of normal power while tracking the state of normal lighting loads during normal operation.

In the DIN rail mount model, the ALCR also includes a method of accomplishing the same emergency functionality for directly-controlled 0-10V fixtures or ballasts. An integral relay positively disconnects 0-10V control upon loss of utility power assuring a “lights-on” override for both line voltage and 0-10V controlled emergency fixtures.

APPLICATIONS• Conference centers• Hotels• Dorms• Office buildings• Government buildings• Restaurants• Schools• Houses of worship• Theaters

FEATURES• 120V and 277V power systems• Automatically activates lighting upon loss of normal power• Provides remote activation by dry contact closure for connection to a fire alarm or building management system• Additional control output connection to activate 0-10V controled fixtures• Configurable “return-to-normal” delay of 0-15 minutes • Simple installation; attaches to standard DIN rail for permanent installation • Maintenance-free

O R D E R I N G I N F O R M A T I O N

Unison Aero® Relay Controller SensorMODEL DESCRIPTION

ALCR-DIN Automatic Load Control Relay (DIN)

S P E C I F I C A T I O N S

GENERAL• UL 924 Listed• UL 2043 plenum-rated

FUNCTIONAL• Automatic control of emergency power output to fixture or single zone emergency lighting upon loss of normal power• Supports fire alarm input activation of emergency

power output• Configurable return to normal delay settings of instant, 10 seconds, 30 seconds, 10 minutes, or 15 minutes• Additional relay cuts 0-10V control loop for guaranteed full- on operation of 0-10V controlled fixtures

MECHANICAL• DIN rail mount: 35mm; DIN43880 and EN60715 compliant• Constructed of UL94 V-0 approved injection-molded ABS• Remote and status LED’s• 2 buttons shall be available to select optional return to normal delay and output test

ELECTRICAL• 120/277 VAC, 60Hz power input• Normally closed (NC), 20A ballast, 10A tungsten• 2 LEDs:

- Status: Red for emergency active or Green for normal - Remote: Amber for state of normal control switch

• Terminal wire sizing: 10-18 AWG• Remote activation switch can be located up to 1000 feet from ALCR

THERMAL • Ambient room temperature: -10° to 45°C / 14° to 113°F• Ambient humidity: 5 to 95% non-condensing

Page 2: Automatic Load Control Relay (DIN) - fullcompass.com€¦ · ETC® Automatic Load Control Relay (DIN) 1 of 2 Emergency Power Series GENERAL INFORMATION The Automatic Load Control

Automatic Load Control Relay (DIN)ETC®

2 of 2

Emergency Power Series

Corporate Headquarters • 3031 Pleasant View Rd, PO Box 620979, Middleton WI 53562 0979 USA • Tel +1 608 831 4116 • Fax +1 608 836 1736London, UK • Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK • Tel +44 (0)20 8896 1000 • Fax +44 (0)20 8896 2000Rome, IT • Via Pieve Torina, 48, 00156 Rome, Italy • Tel +39 (06) 32 111 683 • Fax +44 (0)20 8752 8486Holzkirchen, DE • Ohmstrasse 3, 83607 Holzkirchen, Germany • Tel +49 (80 24) 47 00-0 • Fax +49 (80 24) 47 00-3 00Hong Kong • Room 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong • Tel +852 2799 1220 • Fax +852 2799 9325Web • www.etcconnect.com • Copyright©2016 ETC. All Rights Reserved. All product information and specifications subject to change. 7180L1047 Rev. B USA 03/2016

P H Y S I C A L

Unison Aero Relay® Controller Dimensions*

MODEL HEIGHT WIDTH DEPTH

inches mm inches mm inches mm

ALCR-DIN 2.39 61 3.53 90 2.11 54

Unison Aero Relay Controller Weights*

MODEL WEIGHT SHIPPING WEIGHT

ounces grams ounces grams

ALCR-DIN 14.0 397 15.2 431

*Weights and dimensions typical

2.11”54mm

3.53”90mm

2.39”61mm

NORMALLY CLOSED: TEST SWITCH

FIRE ALARM PANEL

SECURITY SYSTEM

AUTOMATIC LOAD CONTROL RELAY

(ALCR-DIN)

Status LED

Option Button

Remote LED

NORMAL SWITCH SENSE

NORMAL NEUTRAL

NORMAL POWER SENSE

EMERGENCY POWER IN

EMERGENCY POWER OUT

EMERGENCY NEUTRAL

0-10V /FLO

RemoteLoop

Emergency

Out

Neu

tral

In

Normal

Sw

itch

Sen

se

Neu

tral

Normal Light Fixture

Emergency Light Fixture

ALCR

Dimmer Neutral (White)

Dimmer Hot Feed

Emergency LoadEmergency Hot

Emergency Neutral (Gray)

Dimmer Control with D20FB • When normal power is present, normal fixture(s) dim and emergency fixture(s) remain off • When normal power is lost or dimmer circuit breaker trips, emergency fixture(s) turns on

0-10V Fixture Control (ALCR-DIN only) • When normal power is present and switch is closed, both 0-10V controlled fixture(s) dim.

• When normal power is present and switch is open, both 0-10V controlled fixture(s) turn off.

• When normal power is lost or fire alarm connection is broken, all fixture(s) turn on to full - 0-10V connection is opened.

Dimmed CircuitETC D20FB module in Sensor or

Unison Dimmer Rack

Emergency Light Fixture

ALCR

Normal Neutral (White)

Normal Hot (Black)

Emergency LoadEmergency Hot

Emergency Neutral (Gray)

Backup Arrangement • When normal power is present, the emergency load is turned off • When normal power is lost, the emergency load turns on

Emergency Light Fixture

Normal Neutral (White)

Normal Hot (Black) Normal Switch(Red)

Emergency LoadEmergency Hot

Emergency Neutral (Gray)

ALCR Normal Light Fixture

Switch Control Arrangement • When normal power is present, switch controls both the normal and emergency light fixtures • When normal power is lost, the emergency light fixture(s) turn on regardless of the switch state

AUTOMATED LOAD CONTROL RELAY

(ALCR-DIN)

Status LED

Option Button

Remote LED

0-10V /FLO

RemoteLoop

Emergency

Out

Neu

tral

In

Normal

Sw

itch

Sen

se

Neu

tral

Emergency Load

Normal Neutral (White)

Normal Hot (Black)

Emergency Neutral (White)

Emergency Hot

0-10V signal0-10V signal

0-10V common0-10V

controller

0-10V Non-Emergency Fixture

0-10V Emergency Fixture