ATS BYPASS INSTRUCTIONS

Transcript of ATS BYPASS INSTRUCTIONS - Switchgear · 2020. 9. 17. · This unit adheres to European standard...

  • ATS BYPASSINSTRUCTIONS

  • All items are sold under Switchgear Systems Limited standard terms and conditions, a copy of whichcan be found on our website (www.switchgear-systems.com).

    It is the responsibility of the installer to ensure items are fitted to the requirements of BS 7671(Wiring Regulations) and best working practice.

    Issue: 100419

  • INDEX

    Dual Line 160A+ 20-23

    Dual Line 40-125A 16-19

    Single Line 160A+ 12-15

    Single Line 40-125A 08-11

    Switch ratings 06-07

    Installation 04-05

    Overview 02-03

  • Instructions for ATS bypass switches

    Test certificate number:

    Signature:

    The installer is responsible for ensuring that the installation conforms to the requirements of BS 7671 (Wiring regulations) and best safe working practice.

    Prior to installation ensure you have the correct device to meet withyour requirements.Please visit www.switchgear-systems.com for more information.

    These ATS bypass switches are compatible with our entire range of ATS panels and are designed to comply with the legislation for bypass of life safety systems included in BS9999 & BS8519:2010.

    We offer both single and dual line bypass solutions to accomodate the requirements of the installation. When ordered alongside an ATS panel we willcombine and test them in house but are also conveniently labeled for retro fitting on site.

    This unit adheres to European standard IEC60947-6-1 for changeover equipment. This units is fully mains tested prior to leaving Switchgear Systems Ltd.

    02

    OVERVIEW

  • SPECIALREQUIREMENT?JUST ASK!

    Single line ATS bypass

    • Integrated bypass and ATS panels suitable for life safety applications.

    • Total isolation of the ATS panel from load and sources for maintainance

    purposes.

    • In bypass position the primary supply is linked direct to load.

    • Normally open auxiliary for isolation of GenSet start signals.

    When ordered alongside out ATS panels Switchgear

    Systems Ltd will mechanically and electronically fit the

    ATS bypass to the bottom of the ATS panel.

    Alternative layouts are available upon request.

    Dual line ATS bypass

    • Integrated bypass and ATS panels suitable for life safety applications.

    • Total isolation of the ATS panel from load and sources for maintainance

    purposes.

    • In bypass position you can select primary or auxiliary supply to be linked

    to load via the selector switch.

    • Normally open auxiliary for isolation of GenSet start signals.

    03

    OVERVIEW

  • Installation Instructions

    1. Before beginning the installation please ensure you have ordered the correct type of bypass switch for your application. When purchased with an integrated ATS panel you should also check and confirm that the type and rating of the ATS panel is correct. b

    2. If the ATS includes a generator start signal you should wire it through the N/O contact built into the bypass switch. This will prevent the generator from starting up when the unit is switched into bypass mode. b3. The enclosure comes with 4 pre-drilled holes in the back for mounting; please see opposite page for dimension details for drilling. Alternatively, wall mounting brackets are also available to order.b

    4. Please refer to the cable installation instructions (pages 09, 13, 17 or 21 depending on the model you have) for details showing which terminals to connect your cables to.b

    5. Cables should be installed by a qualified electrician. Gland and make off cables to appropriate lengths, being sure to adhere to the requirements set in BS7671.b

    6. Terminate and connect cables with appropriate ferrules and lugs where necessary. Torque settings are shown in the table on the opposite page. Please see the Connection Diagram (pages 09, 13, 17 or 21 depending on the model you have) for details on where to terminate your cables.

    Please note: Before commissioning ensure all terminals are tightened, including those factory fitted, as these may loosen during transit and storage. Maintenance of the IP ingress protection is the responsibility of the installer. All Panels are mains tested before leaving Switchgear Systems Ltd.

    04

    INSTALLATION

  • 21mm

    21mm

    21mm

    21mm

    A C

    B

    9mm Ø

    Rating Max CableDimensionA

    (Width)B

    (Height)C

    (Depth)

    35mm cage70mm cage35mm cage35mm cage70mm cage

    125mm² M10

    200mm200mm200mm200mm200mm400mm

    600mm600mm600mm700mm700mm800mm

    400mm400mm400mm500mm500mm600mm

    63-100A (2 Pole)125A (2 Pole)63A (4 Pole)100A (4 Pole)125A (4 Pole)250A (4 Pole)

    Single Line (SL)

    Torque

    3Nm6Nm3Nm3Nm6Nm51Nm

    185mm² M10400mm800mm600mm400A (4 Pole) 51Nm

    35mm cage70mm cage35mm cage70mm cage

    125mm² M10185mm² M10

    300mm300mm300mm300mm400mm400mm

    800mm800mm800mm800mm1400mm1400mm

    600mm600mm600mm600mm800mm800mm

    63-100A (2 Pole)125A (2 Pole)

    63-100A (4 Pole)125A (4 Pole)250A (4 Pole)400A (4 Pole)

    Dual Line (DL)

    3Nm6Nm3Nm6Nm51Nm51Nm

    05

    INSTALLATION

  • Measured Frequency

    Common

    Loss Of Power In Each Conductor Ie

    Protection Against Contact

    Mechanical Endurance - Frequency of Operation

    Hz

    W

    °CPermitted Ambient Temperature

    passes per hour

    50...60

    2.2

    yes

    100,000

    -25...+55

    50...60

    4.5

    yes

    100,000

    -25...+55

    50...60

    LT40 LT63 LT125

    12

    yes

    100,000

    -25...+55

    Rated Operational Voltage Ue

    Rated Conditional Short-Circuit Current Uimp

    Rated Short-Time Withstand Current (r.m.s)

    Short-Circuit Protection, Max. Protection (gL)

    V AC

    kV

    A

    A

    Rated Uninterrupted Current Iu A

    AC-21A Circuit Breaker Switches rated operational current Ie A

    AC-3 Motor-Circuit Breaker In Operation 220...240V kW

    380...440V kW

    660/690V kW

    AC-23A Main Switch 220...240V kW

    380...440V kW

    660/690V kW

    690

    6

    640

    50

    40

    40

    7.5

    11.0

    11.0

    7.5

    20.0

    15.0

    690

    6

    1260

    63

    63

    63

    11.0

    18.5

    15.0

    11.0

    22.0

    18.5

    690

    LT40NLT Specific LT63 LT125

    6

    2000

    125

    125

    125

    22.0

    37.0

    30.0

    22.0

    45.0

    37.0

    Rated Operational Voltage Ue

    ULT Specific

    Rated Uninterrupted Current Iu

    V AC

    A

    Permanant Thermal Current Ith A

    Max. Rated Power (AC-3)

    AC Motors 40Hz...60Hz (HP=PS)

    240V HP

    480V HP

    600V HP

    600

    30

    40

    10

    20

    30

    600

    60

    63

    15

    40

    50

    600

    LT40 LT63 LT125

    125

    125

    40

    75

    100

    Switch Ratings: 40-125A models

    06

    SWITCH RATINGS

  • Note 1: Due to harmonics and tolerance of the capacitors, the rated values have been reduced by 33%

    4

    1000

    8000

    20

    80

    200

    100

    200

    8

    600

    1000

    200

    4.7

    1000

    8000

    25

    100

    250

    125

    250

    8

    600

    1000

    250

    11

    1000

    5000

    30

    150

    315

    160

    300

    8

    600

    1000

    315

    11

    1000

    5000

    30

    150

    400

    160

    400

    8

    600

    1000

    400

    25

    1000

    5000

    32

    250

    500

    200

    500

    8

    600

    1000

    500

    25

    1000

    5000

    32

    250

    630

    200

    630

    8

    600

    1000

    630

    22.5

    500

    3000

    63

    300

    800

    250

    800

    12

    600

    1000

    800

    34

    500

    3000

    66

    375

    1000

    315

    1000

    12

    600

    1000

    1000

    53

    500

    3000

    73.5

    450

    1250

    400

    1250

    12

    600

    1000

    1250

    W

    500V kA peak

    200A 250A 315A 400A 500A

    380V kVAr

    690V A

    690V A

    415V A

    kV

    D.C. V

    A.C. V

    Enclosed A

    number of operations

    number of operations

    Power Losses Per Pole

    Electrical Life

    Mechanical Endurance

    Rated Short Circuit Making Capacity Icm

    Reactive Power (see Note 1)

    Operational Current AC22A Ie

    Operational Current AC23A Ie

    Impulse Withstand Voltage

    Rated Voltage of Isolation Ui

    Rated Thermal Current at 40° Max A.T.

    Switch Rated Current 630A 800A 1000A 1250A

    Switch Ratings: 160-1250A models

    07

    SWITCH RATINGS

    Motorised Switch Ratings:

  • Single Line Installation Instructions (40-125A)

    When factory fitted:

    • Connect your incoming cables from the primary supply to the terminals

    marked ‘Primary Supply Input’.

    • Connect your incoming cables from the auxiliary supply to the terminals

    marked ‘Auxiliary Supply Input’.

    • Connect your outgoing supply cables to the load/distribution network to

    the terminals marked ‘Outgoing Supply’.

    When supplied alone:

    • Follow the instructions above.

    • Join the ‘Primary Supply Input’ terminals on the ATS to the ‘Primary

    Output To ATS’ terminals in the bypass switch.

    • Join the ‘Auxiliary Supply Input’ terminals on the ATS to the ‘Auxiliary

    Output To ATS’ terminals in the bypass switch.

    • The ‘Outgoing Supply’ terminals of the ATS should then be joined to the

    terminals in the bypass switch marked ‘Input From ATS’.

    08

    SINGLE LINE (40-125A)

  • PrimaryOutput to ATS

    AuxiliaryOutput to ATS

    Input fromATS

    09

    SINGLE LINE (40-125A)

  • Supply toload Open

    SupplyBypassed

    ATS SupplyingLoad

    Supply toATS Closed

    Supply toATS Open

    A

    B

    C

    D

    E

    Handle Operation

    Normal operation with ATS in circuit• ATS Supply Isolator (ASI) should be switched to position B.

    • Bypass switch (BS) should be switched to position C.

    To Bypass ATS• ATS Supply Isolator (ASI) should be switched to positon A.

    • Bypass switch (BS) should be switched to position E.

    Test Position (for commissioning ATS while supply is bypassed)• ATS Supply Isolator (ASI) should be switched to position B.

    • Bypass switch (BS) should be switched to position E.

    10

    SINGLE LINE (40-125A)

  • ATS

    (ASI)

    (BS)

    Bypass

    I

    I I

    II

    Auxiliary Supply In

    Primary Supply In

    Output

    Wiring Diagram

    11

    SINGLE LINE (40-125A)

  • Single Line Installation Instructions (160A+)

    When factory fitted:

    • Connect your incoming cables from the primary supply to the terminals

    marked ‘Primary Supply Input’ (terminals B).

    • Connect your incoming cables from the auxiliary supply to the terminals

    marked ‘Auxiliary Supply Input’ (terminals E).

    • Connect your outgoing supply cables to the load or distributing network

    to the terminals marked ‘Outgoing Supply’ (terminals A).

    When supplied alone:

    • Follow the instructions above.

    • Join the ‘Primary Supply Input’ terminals on the ATS to the ‘Primary

    Output To ATS’ terminals in the bypass switch (terminals F).

    • Join the ‘Auxiliary Supply Input’ terminals on the ATS to the ‘Auxiliary

    Output To ATS’ terminals in the bypass switch (terminals D).

    • The ‘Outgoing Supply’ terminals of the ATS should then be joined to the

    terminals in the bypass switch marked ‘Input From ATS’ (terminals C).

    12

    SINGLE LINE (160A+)

  • F

    B

    A

    PrimaryOutput to ATS

    PrimarySupply Input

    OutgoingSupply

    AuxiliaryOutput to ATS

    Input fromATSC

    E

    D

    AuxiliarySupply Input

    13

    SINGLE LINE (160A+)

  • BA C

    ON

    ON

    Handle Operation

    This is a single operation bypass switch with 3 positions.

    Normal operation with ATS in circuit• Turn handle to position A (ON I).

    To bypass ATS• Turn handle to position C (ON II).

    Test position (for commissioning ATS while supply is bypassed)• Turn handle to position B (T).

    T

    14

    SINGLE LINE (160A+)

  • ATS

    Bypass

    *I

    *I&T *I&T

    *II&T

    Auxiliary Supply In

    Primary Supply In

    Output

    *Closed in switch positions

    Wiring Diagram

    15

    SINGLE LINE (160A+)

  • Dual Line Installation Instructions (40-125A)

    When factory fitted:

    • Connect your incoming cables from the primary supply to the terminals

    marked ‘Primary Supply Input’.

    • Connect your incoming cables from the auxiliary supply to the terminals

    marked ‘Auxiliary Supply Input’.

    • Connect your outgoing supply cables to the load or distributing network

    to the terminals marked ‘Outgoing Supply’.

    When supplied alone:

    • Follow the instructions above.

    • Join the ‘Primary Supply Input’ terminals on the ATS to the ‘Primary

    Output To ATS’ terminals in the bypass switch.

    • Join the ‘Auxiliary Supply Input’ terminals on the ATS to the ‘Auxiliary

    Output To ATS’ terminals in the bypass switch.

    • The ‘Outgoing Supply’ terminals of the ATS should then be joined to the

    terminals in the bypass switch marked ‘Input From ATS’.

    16

    DUAL LINE (40-125A)

  • PrimaryOutput to ATS

    AuxiliaryOutput to ATS

    Input fromATS

    17

    DUAL LINE (40-125A)

  • A

    B

    C

    D

    E

    F

    G

    H

    I

    J

    K

    Primary SupplyContacts Open

    BypassPrimary Supply

    SupplyingATS

    Auxiliary SupplyContacts Open

    BypassAuxiliary Supply

    SupplyingATS

    Supply toload Open

    Auxiliary SupplyDuring Bypass

    Primary SupplyDuring Bypass

    Supply toATS Closed

    Supply toATS Open

    Handle Operation

    Normal operation with ATS in circuit• Bypass Supply Selector Switch (BSSS) should be switched to position A or C depending on which supply is desired.• Primary Supply Bypass Switch (PSBS) should be switched to position I.• Auxiliary Supply Bypass Switch (ASBS) should be switched to position D.• ATS Supply Isolator (ASI) should be switched to position H.

    To bypass ATS• Bypass Supply Selector Switch (BSSS) should be switched to position A or C depending on which supply is desired.• Primary Supply Bypass Switch (PSBS) should be switched to position K.• Auxiliary Supply Bypass Switch (ASBS) should be switched to position F.• ATS Supply Isolator (ASI) should be switched to position G.

    Test position (for commissioning ATS while supply is bypassed)• Bypass Supply Selector Switch (BSSS) should be switched to position A or C depending on which supply is desired. • Primary Supply Bypass Switch (PSBS) should be switched to position K.• Auxiliary Supply Bypass Switch (ASBS) should be switched to position F.• ATS Supply Isolator (ASI) should be switched to position H.

    18

    DUAL LINE (40-125A)

  • ATS

    Bypass

    I

    I

    I I

    I

    II

    II II

    Auxiliary Supply In

    Primary Supply In

    Output

    (ASI)

    (BSSS)

    (PSB

    S)

    (ASB

    S)

    Wiring Diagram

    19

    DUAL LINE (40-125A)

  • Dual Line Installation Instructions (160A+)

    When factory fitted:

    • Connect your incoming cables from the primary supply to the terminals

    marked ‘B’ (Primary Supply Input).

    • Connect your incoming cables from the auxiliary supply to the terminals

    marked ‘E’ (Auxiliary Supply Input).

    • Connect your outgoing supply cables to the load or distributing network

    to the terminals marked ‘A’ (Input from ATS).

    When supplied alone:

    • Follow the instructions above.

    • Join the ‘Primary Supply Input’ terminals on the ATS to the terminals

    marked ‘F’ (Primary Output To ATS) in the bypass switch.

    • Join the ‘Auxiliary Supply Input’ terminals on the ATS to the terminals

    marked ‘D’ (Input from ATS) in the bypass switch.

    • The ‘Outgoing Supply’ terminals of the ATS should then be joined to the

    terminals marked ‘C’ (Auxiliary Output to ATS) in the bypass switch.

    20

    DUAL LINE (160A+)

  • F

    B

    E

    A

    AuxiliaryOutput to ATS

    AuxiliarySupply Input

    PrimaryOutput to ATS

    PrimarySupply Input

    OutgoingSupply

    Please note: Although this is our standard plate layout for this unit we tend to build our Dual Line 160A+ custom for each job. As such your layout may differ depending on your spec.

    Input fromATS

    Input fromATS CD

    21

    DUAL LINE (160A+)

  • ON

    ON

    OFF

    BA

    IH J

    C

    Primaryin Test

    BypassPrimary Supply

    SupplyingATS

    Supply toload Open

    Auxiliary SupplyDuring Bypass

    Primary SupplyDuring Bypass

    ED F

    Auxiliaryin Test

    BypassAuxiliary Supply

    SupplyingATS

    T

    ON

    ON

    T

    ON

    ON

    Handle Operation

    Normal operation with ATS in circuit• Bypass Supply Selector Switch (BSSS) should be switched to position H or J depending on which supply is desired.• Primary Supply Bypass Switch (PSBS) should be switched to position A.• Auxiliary Supply Bypass Switch (ASBS) should be switched to position D.To bypass ATS• Bypass Supply Selector Switch (BSSS) should be switched to position H or J depending on which supply is desired.• Primary Supply Bypass Switch (PSBS) should be switched to position C.• Auxiliary Supply Bypass Switch (ASBS) should be switched to position F.

    Test position (for commissioning ATS while supply is bypassed)• Bypass Supply Selector Switch (BSSS) should be switched to position H or J depending on which supply is desired. • Primary Supply Bypass Switch (PSBS) should be switched to position B.• Auxiliary Supply Bypass Switch (ASBS) should be switched to position E.

    22

    DUAL LINE (160A+)

  • ATS

    Bypass

    I

    *I

    *I&T *I&T

    *I

    II

    *II&T *II&T

    Auxiliary Supply In

    Primary Supply In

    Output

    (BSSS)

    (PSB

    S)

    (ASB

    S)

    *Closed in switch positions

    Wiring Diagram

    23

    DUAL LINE (160A+)

  • Switchgear Systems Ltd.16 Woodside ParkWebb Ellis Industrial EstateRugby, WarwickshireCV21 2NP

    T 01788 577399F 01788 577899E [email protected] www.switchgear-systems.com

    Sheet Steel Enclosed Products

    Sheet Steel Enclosed Double Break Switchfuses

    Sheet Steel Enclosed Load Break Isolators

    Sheet Steel Busbar Chambers

    Sheet Steel Enclosed MCCBs & RCBOs

    Sheet Steel Enclosed 4 Pole Contactors

    Sheet Steel Enclosed Changeover Switches I-0-II

    Sheet Steel Junctions Boxes & Generator Hook-Ups

    Automatic Transfer Switch Panels

    Sheet Steel Enclosed Bypass Switches

    Panelboards & Section Boards

    Power Rated Earth & Neutral Bars

    PROVIDING A WIDE RANGE OFSWITCHGEAR PRODUCTS