At s Generator Wiring Diagrams
-
Upload
contactegypt2 -
Category
Documents
-
view
54 -
download
2
description
Transcript of At s Generator Wiring Diagrams
![Page 1: At s Generator Wiring Diagrams](https://reader035.fdocuments.us/reader035/viewer/2022073103/55cf9bd6550346d033a79122/html5/thumbnails/1.jpg)
“Smart” Automatic Power Transfer SystemsModels 1000, 1500, 3000, 3500
Wire Connections for Various Generators
Remove Nylon plug jacket to
inspect for proper Polarity
WHITE
BLACK
BROWNYELLOW
RED
GREEN
Cable provided
with Honda
Remote Start Kit
HONDA EM Series, EX Series
RED
WHITE
BLACK
GREEN
BROWN
YELLOW
RED
ORANGE
BLUE
BLACK
}GenTran
PowerStayLow
Voltage Cable
BLUE
ORANGE
BLACK
RED
ON/OFF
CRANK
BATT –
BATT +
Green Terminal Block on GenTran
PowerStayATS PC board
{
Black Remote
Start Box on GEN
Receptacle on Black Box
To connect the Honda Remote Start cable to the GenTran PowerStay ATS Low Voltage Cable, cut the Honda-furnished cable to a convenient length, and strip off approx. 3” of outer jacket, and strip the four conductors inside. Then connect with wire connectors to the GenTran PowerStayATS cable per the diagram below.
Ignition Switch on Generator:• Leave OFF for EM 3500, EM5000, EX4500 and EX5500• Turn to ON for EM6000GPA propane unit
NOTE: Jumpers on GenTran PowerStayATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
HONDA EB12D Diesel Portable
BLACK
YELLOW
GREEN
WHITE
ON/OFF
CRANK
BATT –
BATT +
Green Terminal Block on GenTran
PowerStayATS
PC board
Cable provided
with Honda
Remote Start Kit
{ }NOTE: Jumpers on GenTran PowerStayATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
IMPORTANT:• Output switch on generator should be ON• Ignition switch on generator should be ON
(NOTE: These instructions are not intended for Honda’s “i” models. Call GenTran for wiring instructions on Honda’s “i” models.)
![Page 2: At s Generator Wiring Diagrams](https://reader035.fdocuments.us/reader035/viewer/2022073103/55cf9bd6550346d033a79122/html5/thumbnails/2.jpg)
Automatic Power Transfer SystemsModels 1000, 1500, 3000, 3500
Wire Connections for Various Generators
Coleman PM400911, PM401211, and PM400911-001
NOTE: Jumpers on GenTran PowerStay ATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
ATS-1REDBATT + (plus)
Ground TerminalBLACKBATT – (minus)
Not UsedORANGECRANK/START
ATS-2BLUEON/OFF/RUN
Generator Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block
Coleman Model PM0621512 - 15KW Stationary Generator
2REDBATT + (plus)
Ground Terminal
BLACKBATT – (minus)
1ORANGECRANK/START
4BLUEON/OFF/RUN
Generator Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block NOTE: Jumpers on
GenTran PowerStay ATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
Coleman Model PM402511 - 25KW Stationary Generator
NOTE: Jumpers on GenTran PowerStayATS system PC board should be changed to "Pull-DOWN" position (see page 16-17 of Installation Manual).
(1) Run Red wire directly to BATT + terminal on generator battery
REDBATT + (plus)
ATS – (9) Ground TerminalBLACKBATT – (minus)
Not UsedORANGECRANK/START
ATS + (12)BLUEON/OFF/RUN
Generator Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block
![Page 3: At s Generator Wiring Diagrams](https://reader035.fdocuments.us/reader035/viewer/2022073103/55cf9bd6550346d033a79122/html5/thumbnails/3.jpg)
Cummins RS12000 with Onan engine
NOTE: Jumpers on GenTran PowerStay ATS system PC board should be changed to a "Pull-DOWN" position (see page 16-17 of Installation Manual).
TB 1-2REDBATT + (plus)
TB 1-13 GroundBLACKBATT – (minus)
NOT USEDORANGECRANK/START
TB 1-5BLUEON/OFF/RUN
Generator Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block
Cummins RS20000 with Ford engine
TB1-2REDBATT + (plus)
TB1-6BLACKBATT – (minus)
NOT USEDORANGECRANK/START
TB 1-3BLUEON/OFF/RUN
Generator Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block NOTE: Jumpers on
GenTran PowerStay ATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
Generac/Guardian – 7kW, 12kW, 15kW Stationary
#183REDBATT + (plus)
Ground TerminalBLACKBATT – (minus)
NOT USEDORANGECRANK/START
#178BLUEON/OFF/RUN
Generator Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block MODELS: 4673, 4674, 4675
NOTE: Jumpers on GenTran PowerStay ATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
Automatic Power Transfer SystemsModels 1000, 1500, 3000, 3500
Wire Connections for Various Generators
![Page 4: At s Generator Wiring Diagrams](https://reader035.fdocuments.us/reader035/viewer/2022073103/55cf9bd6550346d033a79122/html5/thumbnails/4.jpg)
NOTE: Winco engineers suggest that the 3/4 amp fuse in the Battery “+” line in the generator be changed to a 3 or 4 or 5 amp type AGC fuse so that the integrated charger in our ATS system will not blow the fuse. The 120-volt wire intended to be run from the house to the generator for the Winco charger does NOT need to be used since our integrated charger will charge the generator battery.
Winco – PSS8, PSS12, PSS15 Packaged Standby Generators
WT #5REDBATT + (plus)
WT #1BLACKBATT – (minus)
WT #22ORANGECRANK/START
WT #24BLUEON/OFF
Generator (WT) Junction Box
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block NOTE: Jumpers on
GenTran PowerStay ATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). NO need to change jumper position.
Kohler Models 8.5RES and 12RES Stationary Generators
P1-25 and P1-26 to Normally Open contacts
12 VDC Coil “–” (minus)
NOT USED
12 VDC coil “+” (plus)
External Relay*(See Note Below)
P1-24REDBATT + (plus)
P1-27BLACKBATT – (minus)
NOT USEDORANGECRANK/START
NOT USEDBLUEON/OFF
Kohler ADC Controller
Low Voltage Wire Color
GenTran PowerStayATS Terminal Block
*External Relay REQUIRED. Kohler’s remote start/stop circuit is a dry circuit that has blocking diodes. Normally, the GenTran PowerStay Automatic Transfer System (ATS) uses one of the two wires in this circuit to read the condition of the battery as well as to charge the battery. However, the blocking diodes prevent this system from working. Therefore, an external relay (Type SPNO w/ 12VDC coil) must be installed in the controller box to close and open this dry circuit. A suggested external relay and socket is available through Grainger –Part numbers # 5Z486 (relay) and # 6JG21 (socket) at an approximate cost of $17.
Onboard Battery Charger on Generator is NOT USED. Kohler provides a battery charger on the generator, and a separate 120 volt wire is supplied in the package. However, the GenTran PowerStay Automatic Transfer System has a built-in battery monitor and charger, this onboard charger included with the Kohler kit is not used.
NOTE: Jumpers on GenTran PowerStay ATS system PC board should already be set to "Pull-Up" position (see page 16 of Installation Manual). No need to change jumper position.
Automatic Power Transfer SystemsModels 1000, 1500, 3000, 3500
Wire Connections for Various Generators