Assumption University Thailand EE4503 Electrical Systems Design Branch circuit and Feeder (Lighting...

29
Assumption University Thailand EE4503 Electrical Systems Design Branch circuit and Feeder (Lighting and Appliances) 1

Transcript of Assumption University Thailand EE4503 Electrical Systems Design Branch circuit and Feeder (Lighting...

Assumption University Thailand

EE4503Electrical Systems Design

Branch circuit and Feeder (Lighting and Appliances)

1

Assumption University Thailand

Topics

• Characteristics of Loads

• Circuits Design

• Branch Circuit

• Feeder Circuit

• Load Schedule

2

Assumption University Thailand

Characteristics of Loads

3

• Continuous Load

– More than 3 hrs. of continuous usage e.g. lighting, air condition

• Non-continuous Load:

– Less than 3 hrs. of continuous usage e.g. electric oven, microwave

When not sure, add 25% more

Assumption University Thailand

Characteristics of LoadsDefinition

4

• Total Connected Load: total kVA or MVA listed

• Maximum Demand: the maximum kVA or MVA

used at the same time

Assumption University Thailand

Characteristics of LoadsDefinition

5

• Demand Factor (D.F.): ratio of “Maximum

Demand” to “Total Connected Load” ()

• Diversity Factor: summation of every branched

circuits’ maximum demand to the system’s maximum demand (always greater than or equal to 1.0)

Assumption University Thailand

Characteristics of LoadsDefinition

6

• Peak Load (P): the maximum kVA or MVA at the

given periond (e.g. 15 min)

• Load Factor (L.F.): ratio of “Average Load” to the

“Peak Load” (). is total energy for period of time

Assumption University Thailand

Characteristics of LoadsCommon Load

7

• Lighting: about 20-50% of total load or 20-100VA/m2

• Receptacle: if no specific information,

180-200VA/set (1, 2 or 3 outlets)

• HVAC: 1TR (12,000 BTU) is about 1.5-1.8kVA

• Motor

• Escalator: manufacturer’s specification

Assumption University Thailand

GroundingCommon Load - Lighting

8

http://www.g-w.com/pdf/sampchap/9781605255880_ch12.pdf

Assumption University Thailand

GroundingCommon Load - Escalator

9

http://www.elevatorbooks.com/Content/Site108/ProductContent/April2012Articl_00000012203.pdf

Assumption University Thailand

Circuit Design

10

• Branch Circuit

• Feeder Circuit

• Main Circuit

Assumption University Thailand

Branch Circuit

11

• Connect from a distribution panel to load or receptacle

• Lighting or Appliance Branch Circuit

– Lighting Branch Circuit

– Receptacle Branch Circuit

– Lighting & Receptacle Branch Circuit

– Individual Branch Circuit

Assumption University Thailand

Branch CircuitCalculation

12

• Load of a branch circuit (BC) at least the total load connected to that branch.

• Conductor Sizing Current Rating of CB

• Current Rating of CB Maximum Load

• Size of a BC goes by the current rating of CB: 15(16)A, 20A, 25A, 30(32)A, 40A, 50A, 63A

Assumption University Thailand

Branch CircuitDesign Procedure

13

• Find “Load”

• Calculate “Circuit Breaker” (% of BC)

• Calculate “Cable”

• Verify “Voltage Drop”: 1-2% of rated voltage

?? safety factor ??

Assumption University Thailand

Branch CircuitDesign Recommendations

14

• Lighting Circuit: continuous load

– 50-70% of BC (no more than 80%) or allowance of 10-30%

• Individual Branch Circuit: load is known

– Should be no more than 80% of BC

Assumption University Thailand

Branch CircuitDesign Recommendations

15

• Receptacles Circuit: single, duplex, triplex

– 180VA per set (200VA for ease)

• Individual Circuit with ELCB: heater, Jacuzzi

• Receptacles Circuit with ELCB: toilet, kitchen,

basement, outdoor, < 1.5m from water

?? Some recommendations can be relaxed ??

Assumption University Thailand

Branch CircuitDesign Recommendations

16

• Separate the type of load: lighting on one BC

• Future Load:

– 20% spare at least

– 40% if continuous load

• Cable size is no smaller than 2.5mm2

• BC for receptacles contains less than 10 sets

Assumption University Thailand

Branch CircuitDrawing

17

• # of hash marks is # of cables

• No hash mark means 2 cables

• One hash mark + number is the number of cables

• Arrow + Lx is connected to circuit breaker (phase) #x

Assumption University Thailand

Branch CircuitPanelboard

18

• No more than 42 circuit

• No longer than 50 m

• Easy to access (no higher than 1.8m)

• Rated is more than the rated of the cable

• At least one panel board per floor

• Must have protection equipment (CB)

Assumption University Thailand

Branch CircuitPanelboard

19

• Should be in the center: balance the voltage drop

• Should be close to the incoming: shortest feeder

• Three types

– Active Branch Circuit (60-80%)

– Spare Branch Circuit with CB (10-20%)

– Spare Branch Circuit (10-20%)

Assumption University Thailand

Branch CircuitFeeder

20

• Rated current of feeder is the total load deducted by the “demand factor”

• Feeder Cable Rating of CB

• Rating of CB Feeder’s Rated Current

Assumption University Thailand

Branch CircuitFeeder – Demand Factor

21

• Demand Factor is the ratio of the maximum usage power at any certain time to the total connected load.

• There are tables for the demand factor, e.g. receptacles in kitchen, lighting. If not specify, 0.8 is a good number

Assumption University Thailand

Branch CircuitFeeder – Neutral

22

• In single phase system, neutral cable will be the same size and line cable.

• In three phase, neutral cable can be reduced.

– Less than 200A, use the phase current

– More than 300A

• Without Harmonics,

• With Harmonics, use the phase current

Assumption University Thailand

Branch CircuitFeeder - Design Procedure

23

• Sum up total BCs’ load

• Calculate “Circuit Breaker”

• Calculate “Cable”: Phase then Neutral

• Verify “Voltage Drop”: 1-2% of rated voltage

Assumption University Thailand

Branch CircuitLoad Schedule

24

• List of connected load

• CB number start from 1(A), 3(B), 5(C), 2(A), 4(B), 6(C) then 7(A), 9(B), 11(C), 8(A), 10(B), 12(C)

• Consider the balance of load in all phases (less than 20% is recommended)

Assumption University Thailand

Branch CircuitLoad Schedule – Design Recommendation

25

• Load Calculation

– Non-continuous Load, no multiplier

– Continuous Load, 1.25 multiplier (or more in case of future expansion)

– If not sure, treat as continuous load.

• Then choose the circuit breaker

• Then choose the cable

Assumption University Thailand

Branch Circuit & FeederDesign Procedure

26

• Make the Load Schedule

– Design Branch Circuit

• Design Feeder (from the load schedule)

Assumption University Thailand

Branch Circuit & FeederDesign Examples

27

Assumption University Thailand

Branch Circuit & FeederDesign Examples

28

Assumption University Thailand

• Electrical Systems Design: ประสิ�ทธิ์�� พิ�ทยพิ�ฒน์�

Reference

29