Assets.pdf

download Assets.pdf

of 29

Transcript of Assets.pdf

  • 7/27/2019 Assets.pdf

    1/29

    Brandenburg University of Technology Cottbus

    Department of Power Distribution and High-Voltage Technology

    Electrical Distribution Systems I

    Dr. Klaus Pfeiffer

    LG 3

    Walther-Pauer-Strae 503046 Cottbus

    Phone: (0355) [email protected]

    September, 2005

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 1

    Script

    M.V. and L.V. electrical equipment

    Contents

    1 M.V. switching devices

    2 L.V. switching devices

    3 M.V switchgears

    4 L.V. switchgears

    5 Example short-circuit calculation

  • 7/27/2019 Assets.pdf

    2/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 2

    1. Medium-voltage switching devices

    1.1 Overview

    Switching capacity

    Short-circuit current

    Switching device Operating

    current

    Breaking

    capacity

    Making

    capacity

    Isolating

    distance

    Symbol

    Circuit breaker X X X X

    Switch X ___ X ___ X

    Switch disconnector X___

    X X

    Fuse-switch disconnector X X X X

    Disconnector ___ ___ ___ X

    Vacuum contactor X ___ ___ ___

    Earthing switch ___ ___ ___ ___

    H.V. HRC fuse ___ X ___ ___

    1.2 Medium-voltage circuit breaker

    Rated values

    English German

    Rated operating voltage Bemessungsbetriebsspannung Ue

    Rated operational current Bemessungsbetriebsstrom Ie

    Rated short-circuit breaking capacity Bemessungskurzschlussausschaltstrom Iar

    Rated short-circuit making capacity Bemessungskurzschlusseinschaltvermgen Icm

    Rated short-time withstand current Bemessungskurzzeitstrom fr 1s Icw(1s)

    Rated short-circuit duration Bemessungskurzschlussdauer tkr

  • 7/27/2019 Assets.pdf

    3/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 3

    Standard medium-voltage circuit breaker (commercially available)

    Rated operating voltage Ue = (3,6 36) kV

    Rated operational current Ie = (630 2500) A

    Rated short-circuit breaking capacity Iar= (16 50) kA

    Rated short-circuit making capacity Icm = (40 125) kA

    Rated short-time withstand current Icw(1s) = Iar

    Rated short-circuit duration tkr= (1 3) s

    Stress values

    Ib operational current

    ip prospective peak short-circuit current

    kI prospective initial short-circuit alternating current

    Ia prospective symmetrical short-circuit current at breaking time

    Ith(1s) thermal equivalent short-circuit current for 1s

    tk short-circuit duration

    ka II = Factor according VDE 0102

    kkth(1s) tnmII += m , n Factors according VDE 0102

  • 7/27/2019 Assets.pdf

    4/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 4

    Selection of M.V. circuit breakers

    Withstand > Stress

    Ue > UbIe > Ib

    Iar > Ia

    Icm > ip

    Icw(1s) > Ith(1s)

    tkr > tk

    Illustration of isolating distance

    At Umax no flash-over across the isolating distance between open contacts has to occur.

    Arc quenching

    Vacuum circuit breaker

    - vacuum is the arc quenching medium

    - hermetically closed arc quenching chamber

    - pressure: (10-3 10-6) Pa

    - distance between the contact elements: about 6 mm

    - recovery strength of the isolating distance between contacts of about 50 kV in 10 s

    after current zero

    - current chopping (some Amps) before current zero possible in that case switching

    overvoltages occur

    2grid1grid UUU YY = Umax in case of phase opposition

  • 7/27/2019 Assets.pdf

    5/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 5

    Oil-blast circuit breaker

    - thermal decomposition of the oil due to the arc hydrogen is produced (gas-vapour-

    bubble)

    - hydrogen has a very good thermal conductivity cooling of the arc and heatdissipation from the arc column

    - several designs: a) arc columns is blown crosswise

    b) arc column is blown lengthwise

    Main difference between the two arc quenching principles:

    An arc needs a plasma and therewith an ionized gas. This ionized gas isnt available in a

    vacuum. The vacuum arc is a complete metal vapour arc (metal vapour from the contact

    material surface).

    1.3 M.V. HRC fuses (HRC = High Rupturing Capacity)

    Rated values

    English German

    Nominal current Nennstrom In

    Minimum breaking current Mindestausschaltstrom Iamin

    Nominal breaking current Nennausschaltstrom Ia

    Note:

    The term rated (Bemessung) instead of nominal (Nenn) is not yet adopted for fuses.

    Fields of application

  • 7/27/2019 Assets.pdf

    6/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 6

    Time-current-characteristics

    Current limitation characteristics

  • 7/27/2019 Assets.pdf

    7/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 7

    Nominal current of M.V. HRC fuses in dependency of the rated apparent transformer power

    rated percentage impedance: ukr= 4% (with exception of SrT = 1000 kVA: ukr= 6%)

    Rated apparent transformer power SrT [kVA]

    100 250 630 1000

    Um [kV] Nominal current of the M.V. HRC fuse In [A]

    12 16 40 100 160

    24 10 25 50 80

    Nominal current of H.R.C.-fuses in dependency on the motor parameters

    Maximum permissible motor start-up current [A]Motor start-up

    duration at nominal current of M.V. HRC fuse

    ta [s]

    Number of

    start-upsper hour 50 A 160 A 250 A

    15 2 85 310 635

    15 8 70 260 530

    15 16 60 235 475

    2. Low-voltage switching devices

    2.1 Overview

    Switching capacity

    Short-circuit current

    Operating

    current

    Breaking

    capacity

    Making

    capacity

    Symbol

    Air circuit breaker X X X

    Moulded-case circuit breaker X X X

    Vacuum circuit breaker X X X

    Switch disconnector X ___ X

    Fuse-switch disconnector X X X

    L.V. HRC fuse ___ X ___

    Note:

    The term air circuit breaker is derived from the arc chamber, which is not completely closed

    but opened to the ambient.

  • 7/27/2019 Assets.pdf

    8/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 8

    2.2 Differences between air circuit breaker and moulded-case circuit breaker

    Air circuit breaker

    - circuit breaking after a certain time delay is possible

    - no short-circuit limitation

    - category B (according to EN 60947-2) particularly suitable for selectivity

    Moulded-case circuit breaker

    - undelayed circuit breaking

    - short-circuit limitation

    - category A (according to EN 60947-2) unsuitable or only restricted suitable for

    selectivity

    Category A B

    Circuit breaker type Moulded-case circuit breaker Air circuit breaker

    Breaking capacity high lower than at category A

    Short-time withstand current 0 breaking capacity

    Time delay not possible (or only few ms) possible

    Note:

    Moulded-case circuit breaker for category B are also available. For these circuit breakers

    Icw(1s) = 12 Iu applies.

    2.3 Air circuit breakers

    Rated values

    English German

    Rated continuous current (at 40C) Bemessungsdauerstrom (bei 40C) Iu

    Rated ultimate short-circuit breakingcapacitiy

    Bemessungsgrenzkurzschluss-ausschaltvermgen

    Icu

    Rated service short-circuit breakingcapacity

    Bemessungsbetriebskurzschluss-ausschaltvermgen

    Ics

    Rated short-time withstand currentfor 0,3s or 1s or 3s

    Bemessungskurzzeitstrom for 0,3s oder 1soder 3s

    Icw

    Rated short-circuit making capacity(peak value)

    Bemessungskurzschlusseinschaltvermgen Icm

    Note:

    Number of circuit breakings - at ultimate short-circuit breaking capacity Icu 1- at service short-circuit breaking capacity Ics 3

  • 7/27/2019 Assets.pdf

    9/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 9

    Dependence of the short-circuit breaking capacity on the rated operation voltage

    Ue = 400 V Ue = 690 V

    Air circuit breaker slight decrease

    Moulded-case circuit breaker strong decrease

    Standard L.V. circuit breakers (commercially available)

    Rated operating voltage Ue = (230 , 400 , 690) kV

    Rated continuous current Iu = (100 6300) A

    Rated service short-circuit breaking capacity Ics = (16 150) kA

    Rated ultimate short-circuit breaking capacity Icu Ics

    Rated short-circuit making capacity Icm = (55 300) kA

    Rated short-time withstand current Icw = (5 100) kA (for category B)

    Selection of L.V. circuit breakers

    Selection of category (A or B)

    Iu > Ib

    Ics > kI or Icu > kI

    Icm > ip

    Icw(1s) > Ith(1s)

    2.6 L.V. HRC fuses

    Current limitation

    ts pre-arcing time (melting time)

    tLi arcing time

    ta clearing time (total operation time)

    iD cut-off current

  • 7/27/2019 Assets.pdf

    10/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 10

    Cut-off characteristics

    Utilization category gL/gG for cable and line protection (general power supply application)

    full range breaking capacity

    for overload protection and short-circuit protection

    Utilization category aM for protection of motor circuits

    partial range breaking capacity

    only short-circuit protection

    no operation at motor start-up currents

    Rated voltages

    AC 400 V , 500 V , 690 V

    DC 250 V , 440 V , 750 V

    Sizes

    Nominal current [A]

    Size 500 V AC / 440 V DC 690 V AC

    00 6 100 6 100

    0 6 160 1) ----

    1 80 250 80 200

    2 125 400 125 315

    3 315 630 315 500

    4a 500 1250 500 - 800

    1) Not permitted for new plants.

    Time-current-characteristics

    Note:

    In time-current-characteristics the

    manufacturer always gives the pre-

    arcing time.

  • 7/27/2019 Assets.pdf

    11/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 11

    Time-current-characteristics

    Current limitation characteristics

  • 7/27/2019 Assets.pdf

    12/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 12

    Breaking capacity

    Un 690 V AC Ics = 120 kA (minimum value Ics = 50 kA)

    Un 750 V DC Ics = 25 kA

    Fields of application

    3. Medium-voltage switchgears

    Rated values

    English German

    Rated operational current Bemessungsbetriebsstrom Ie

    Rated short-time withstand current Bemessungskurzzeitstrom fr 1s Icw(1s)

    Rated peak short-circuit current Bemessungsstostrom Ipk

    Standard M.V. switchgear (commercially available)

    Rated operational current Ie = (630 1250) A

    Rated short-time withstand current Icw(1s) = (16 50) kA

    Rated peak short-circuit current Ipk = (40 125) kA

    Note:

    These parameters are applied for busbars and outgoing feeders.

  • 7/27/2019 Assets.pdf

    13/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 13

    Selection of M.V. switchgears

    Ie > Ib

    Icw(1s) > Ith(1s)

    Ipk > ip

    3.1 Air-insulated medium-voltage switchgears

    Unit design

    The units consist of functional compartments, segregated from each other by means of metal

    partitions:

    - Busbar compartment

    - Apparatus compartment

    - Feeder compartment

    (the feeder compartment sometimes is subdivided into two partitions, so that an

    additional transformer compartment results)

    - Auxiliary compartment or Low-voltage compartment

    (for protection devices, control and measurement equipment)

    The pressure-resistant compartments have been created as barriers to avoid the movement

    of an internal arc, which means to avoid the arc, pass over from one compartment into

    another. This internal subdivision reduces the effect of arc faults outside their point of origin

    to a minimum.

  • 7/27/2019 Assets.pdf

    14/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 14

    Switching devices

    - Circuit breaker

    - Fuse-switch disconnector

    - Switch-disconnector-fuse- Switch disconnector

    Example:

    Outgoing feeder to a transformer in a wind turbine

    - Fuse-switch disconnector or

    - Switch-disconnector-fuse

    Busbar bushing

    Switchgear unit (circuit breaker unit) without

    compartments

    1

    2

    4

    5

    7

    8

    9

    10

    11

    Low-voltage compartment

    Circuit breaker

    Withdrawable unit for moving thecircuit breaker in disconnectedposition

    Measuring sockets for capacitivevoltage indicator system

    Bar connection from busbar tobreak contact

    Circuit breaker

    Earthing switch

    Current transformer

    Cable termination

  • 7/27/2019 Assets.pdf

    15/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 15

    Switchgear (circuit breaker units) with removed circuit breaker.

    In this figure the circuit breaker is placed onto a handling truck. The truck is provided with a

    wheel system which makes the operations for racking the circuit breaker into and out of the

    switchgear unit possible.

    3.2 Gas-insulated medium-voltage switchgears

    All live parts (busbar, apparatus, current- and voltage transformer etc.) are arranged in a

    gas-filled chamber. This chamber has to be hermetically sealed and gas-tight. SF6 (sulphur

    hexafluoride) is used as insulating gas with a slight overpressure (p (2 3) bar; for

    comparison: air pressure: p 1 bar).

    Advantages of the SF6-insulation

    - higher withstand voltage compared with air

    switchgear units can be designed with smaller dimensions

    - protection against moisture and contamination

    the risk of arc occurrence is reduced

  • 7/27/2019 Assets.pdf

    16/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 16

    Unit design

    Switchgear unit (switch disconnector)

    Switchgear unit (Circuit breaker)

  • 7/27/2019 Assets.pdf

    17/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 17

    3.3 Arc protection

    The outer enclosure has to resist the very high pressures due to arcing faults. Arc tests are

    carried out to proof the following issues:- the compartment doors will remain closed

    - no components will be ejected from the switchgear

    - no flames or toxic gases will come out

    - no holes caused by a burning arc will appear in the outer enclosure

    Otherwise the requirements for operator protection are not met.

    Approximate value for arc power in a 10-kV-switchgear at kI = 15 kA: PB = 13 MW

    For stressing the switchgear the arc energy WB is decisive:

    agBB tPW =

    For limiting the arc energy the total fault duration has to be minimised as low as possible.

    With special arc detection devices the total fault duration can be decreased to tag 100 ms.

    These arc detection devices respond to pressure or light due to the arc.

    For our example the arc energy is WB = 13 MW 100 ms = 1,3 MWs. This arc energy is still

    unacceptable high.

    3.4 Some information about arcs

    Core temperature (15.000 20.000)C

    Possible ambient temperature 5000C

    Speed (15 50) m/s

    (Assumption: 15 m/s in 100 ms a distance of 1,5 m)

    Illuminance 106 Lux

    (for comparison the illuminance in a office is about 500 Lux)

    Possible arc energy some Megawattseconds

    Possible forces onto the cubicle enclosure 100 kN

    Pressure maximum (5 10) ms after fault begin

  • 7/27/2019 Assets.pdf

    18/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 18

    4. Low-voltage switchgears

    In L.V.-switchgears several function modules (outgoing feeders) are placed into one cubicle.

    Each cubicle with outgoing feeders is connected to the main busbar and has its owndistribution bar. The distribution bar provides the connection link between the main busbar

    and the function modules, which contains the electrical components belonging to one

    function unit.

    Three versions of function modules are available:

    - Fixed Technique

    - Plug-in-technique

    - Withdrawable technique

    Rated values

    Busbars, circuit breakers and function modules (withdrawable-technique or fixed-technique)

    have to be rated according to the following parameters:

    English German

    Rated operational current Bemessungsbetriebsstrom Ie

    Rated short-time withstand current Bemessungskurzzeitstrom fr 1s Icw(1s)

    Rated peak current Bemessungsstostrom Ipk

  • 7/27/2019 Assets.pdf

    19/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 19

    Standard L.V. switchgear Maximum rated values for busbars

    Distribution bar for connection ofMain

    busbarCircuitbreaker

    Withdraw.technique

    Plug-intechnique

    R. operational current Ie [A] 6300 6300 1000 2000

    R. short-time withstand current Icw(1s) [kA] 100 100 50 50

    R. peak current Ipk [kA] 250 220 110 110

    Maximum permissible operational currents of

    - Distribution modules Ie = 800 A

    - Motor starter modules Ie = 630 A

    Selection of L.V. switchgears

    Ie > Ib

    Icw(1s) > Ith(1s)

    Ipk > ip

  • 7/27/2019 Assets.pdf

    20/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 20

    4.1 Plug-in-technique

    Basic elements for this technique are supporting plates, where the electrical components are

    placed. Such a unit is called function module. Depending on the application the componentsin the module are installed in various combinations. The module height depends on the

    equipment (components) and the rated power.

    The modules are installed horizontally at the module frame in the equipment compartment of

    the cubicle. The removable modules have plug-in connections to the incoming supply from

    the distribution bar, whereas the outgoing cables are connected permanently direct to the

    module terminals. The auxiliary circuits are connected via multi-pole plug-in contact units.

    The modules can be combined with front modules for indicating, measuring, signalling and

    operating equipment.

    The distribution bars are arranged vertically.When modules will be replaced, retrofitted, or a module extension is carried out (e.g.

    subsequent installation in spare modules), the cubicle must be disconnected from the mains.

    Standard plug-in modules as motor starters,

    above two fuseless modules with current-

    limiting circuit breakers,

    below two modules with fuse-switch

    disconnector

    Replacing of a plug-in module with

    distribution bars dead

  • 7/27/2019 Assets.pdf

    21/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 21

    Strip-type outgoing energy modules

    Strip-type modules consist of a switch disconnector and L.V. HRC fuses. The switch

    disconnector is equipped with a spring-assisted mechanism, and the switching speed doesnot depend on the operation speed of the handle at the front. The switch is found on both

    sides of the fuses so that the fuses can be replaced under dead conditions.

    The modules are installed horizontally in the switchgear cubicle. The complete unit is

    mounted directly on the frame and connected through its own contact elements to the

    distribution bar. The outgoing cable connection is made with brackets or cable terminals.

    The switching state can be observed from outside through a transparent front cover and by

    the position of the handle. An interlocking device between the switch-disconnector and the

    front cover prevents the cover from being opened when the switch is closed.

    Switchgear cubicle with strip-type

    energy modules

  • 7/27/2019 Assets.pdf

    22/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 22

    4.2 Withdrawable technique

    In this technique, components belonging to one functional group are assembled to form a

    single mechanical and electrical module as withdrawable type.

    Depending on the requirements or design the cubicles are divided into functional

    compartments.

    Cubicle with incoming feeder

    - Busbar compartment

    - Circuit breaker compartment

    - Cable compartment

    Cubicle with outgoing feeders

    - Busbar compartment

    The busbar compartment contains

    - busbars

    - distribution bars

    - Equipment compartment

    The withdrawable function modules are situated there. Each module is a

    compartment themselves.

    - Cable compartment

    The cable compartment contains

    - incoming and outgoing cables

    - appropriate accessories for interconnecting the modules

    - auxiliary accessories (cable clamps, cable connectors, wiring ducts, etc.

    The busbars are arranged horizontally in the rear section of the cubicle.

    Busbar system with four conductors per phase

  • 7/27/2019 Assets.pdf

    23/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 23

    The distribution bar is embedded into a multi-function separator made of insulating material

    and held in place and covered by distribution bar covers. The multi-functional separator is

    resistant to accidental arcs and thus constitutes a partition between the equipment

    compartment and the busbar compartment.

    Withdrawable module compartment with

    multi-function separator and distribution bar

    covers

    Multi-functional separator with distribution

    bar covers and cable connection units (right

    side)

    Withdrawable modules consist of a compartment bottom plate, guide rails, front posts and

    the contacts. These modules have plug-in contact units at both, the incoming (from

    distribution bar) and outgoing sides. The module size depends on the rated power and the

    equipment.

    Standardized withdrawable modules are:

    - Energy distribution by means of switch disconnector or moulded-case circuit breaker

    - Motor starter with fuses

    - Motor starter without fuses

    The maximum rated current for withdrawable modules is Iemax = 630 A.

  • 7/27/2019 Assets.pdf

    24/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 24

    The withdrawable modules can be withdrawn

    when connected to mains.

    Single-line diagram for motor starter with fuses

    Description of the operating handle positions of a module

    Position ofswitch

    Position of module Main- and control circuits

    ON in cubicle All main- and control-circuits are connected

    OFF in cubicle All main- and control-circuits are disconnected

    TEST in cubicleAll main-circuits are disconnected, the control-circuitsare connected

    MOVE

    in cubicle--

    Isolated position--

    not in cubicle

    All main- and control-circuits are disconnected

    ISOLATEDThe module is 30 mm

    drawn out of thecubicle

    All main- and control-circuits are disconnected andthe isolated requirements are met

  • 7/27/2019 Assets.pdf

    25/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 25

    4.3 Arc protection

    In low-voltage switchgears very high arc energies occur. The arc energy depends on the

    prospective short-circuit current and the total fault duration (see chapter 3.3).

    Limit values for permissible arc energy

    - for switchgear protection WB = 100 kWs

    - for operator protection WB = 250 kWs

    For decreasing the arc energy it is necessary to reduce the total fault duration at least to

    tag 100 ms. For fault locations onto the busbar it is impossible to achieve this very short

    fault duration when using time selectivity (time staggering). Only application of the reversed

    interlocking selectivity (zone selectivity) yields to total fault durations of about 100 ms for allfault locations.

    To reduce the effects of arc faults outside to their point of origin, several versions of

    compartments / internal subdivision of the cubicle are suggested in German Standard

    VDE 0660 Part 500.

  • 7/27/2019 Assets.pdf

    26/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 26

    Version 1 Version 2

    Version 3a Version 3b

    Version 4

    Version 1 doesnt have any compartments. This version should not be applied.

  • 7/27/2019 Assets.pdf

    27/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 27

    5. Example short-circuit calculation

    Given:

    Grid Q Nominal voltage Un [kV] 20

    Short-circuit power kS [MVA] 6286

    R/X 0,035

    Transformer Rated voltage (H.V.).V.H

    rTU [kV] 20

    Rated voltage (L.V.).V.L

    rTU [kV] 10,5

    Rated apparent power SrT [MVA] 45

    Vector group Yy0

    Rated percentage impedance ukr [%] 10,8

    Rated percentage resistance uRr [%] 0,4

    R0/R1 1

    X0/X1 1

    Cable Number of parallel systems 5

    Length [m] 150

    R [/km] 0,056

    X [/km] 0,099

    bC [nF/km] 613

    0C [nF/km] 613

    R0/R1 10

    X0/X1 4

    Find:

    (according to standard DIN EN 60909-0 / VDE 0102:2002-07)

    - Maximum three-phase initial short-circuit current max3kI

    - Peak short-circuit current ip

    Fault location: Busbar at the end of the cable

  • 7/27/2019 Assets.pdf

    28/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    Brandenburg University of Technology

    Department of Power Distribution and High Voltage Technology Pfeiffer 28

    Solution:

    Grid: ( )m69,99

    MVA6286

    kV201,1

    S

    UcZ

    2

    kQ

    2

    nQQ =

    =

    =

    m69,9470,0351

    m69,99

    X

    R1

    ZX

    22

    Q

    Q

    QQ =

    +=

    +

    =

    ( ) ( ) m2,4569,947m69,99mXZR 222

    Q

    2

    QQ ===

    Transformer:( )

    0,2646MVA45

    kV10,50,108

    S

    U

    100

    uZ

    2

    rT

    2

    rTkr10T ===

    VDE 0102: correction factor kT for transformer impedances

    TTTk ZkZ = T

    maxT

    x0,61

    c0,95k

    +=

    c-factors according to VDE 0102

    Nominal voltage cmax cmin

    (100 1000) V1,05 1)1,10 2)

    0,95

    > 1kV 1,10 1,0

    1) Tolerance of nominal voltage: 6%2) Tolerance of nominal voltage: 10%

    0,9810,108)(0,61

    1,10,95

    x0,61

    c0,95k

    T

    maxT =+

    =+

    =

    0,25970,26460,981Z10Tk ==

    ( )0,0098

    MVA45

    kV10,50,004R

    210

    T=

    =

    ( ) ( ) 0,259570,00980,2597RZX 22210

    T

    210Tk

    10T ===

    Cable:

    m1,68km0,15km

    0,0565

    1RK ==

    m2km0,15km

    0,0995

    1XK 97,==

  • 7/27/2019 Assets.pdf

    29/29

    Electrical Distribution Systems Part I M.V. and L.V. electrical equipment

    R X

    Grid, referred to 20-kV-side 2,45 m 69,95 m

    905,15,10

    20 == 2 = 3,628

    Grid, referred to 10-kV-side 0,67 m 19,28 m

    Transformer, referred to 10-kV-side 9,80 m 259,57 m

    Cable 1,68 m 2,97 m

    12,15 m 281,82 m

    Zk = 282,1 m

    kA22,5m282,13

    kV101,1

    Z3

    UcI

    k

    nmaxk3max =

    =

    =

    k3maxp I2i =

    += XR

    3

    e0,981,02

    1,88e0,981,02281,82

    12,153

    =+=

    kA60,1kA22,61,882ip ==