Meeting and Exceeding High Performance
ASHRAE DL
Standards, Codes and Guidelines with Air-to-Air Energy Recovery Systems and Equipment
Presented byPaul Pieper, Eng., Marketing Manager, Venmar CES Inc.
Presenter BiographyPaul Pieper, Eng., has over 15 years of Sales and Product Management experience in designing high performance HVAC systems and equipment for commercial and industrial applications.
He holds a degree in Pure and Applied Science from Marianopolis College, a Bachelor of Engineering degree from the Department of Building, Civil and Environmental Engineering. Mr. Pieper is a member of the Quebec Order of Professional Engineers as well as the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) and the Canada and U.S. Green Building Council (CaGBC & USGBC) and
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
(ASHRAE) and the Canada and U.S. Green Building Council (CaGBC & USGBC) and represents Venmar CES Inc. with the Air-Conditioning, Heating and Refrigeration Institute (AHRI) on the Air-to-Air Energy Recovery Ventilation Equipment Section.
Mr. Pieper is the former Chair of ASHRAE TC 8.12 Desiccant Dehumidification Equipment and Components, is an active member of ASHRAE TC 5.5 Air-to-Air Energy Recovery and is Distinguished Lecturer for ASHRAE. He is also a member of the U.S. delegation for the ISO Working Group developing a “Method of Test for the Performance of Heat Recovery Ventilators and Energy Recovery Ventilators” and a member of the Project Monitoring Subcommittee for the upcoming “ASHRAE Design Guide for Dedicated Outdoor Air Systems”.
Disclaimer
The views and opinions expressed in this presentation are strictly those of the author and do not necessarily reflect the views of
the American Society of Heating
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
the American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE)
Learning Objectives
1. Understand the historical and current market drivers for energy recovery
2. Identify key current and proposed standards and guidelines that relate to energy recovery and determine where and why air to air energy recovery is mandated
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
where and why air-to-air energy recovery is mandated
3. Understand how energy recovery technologies may be used to resolve the seemingly conflicting requirements of current and proposed standards and guidelines
Ventilation Air
• The process of introducing outside air into occupied spaces for dilution of indoor pollutants
• Reduces occupant discomfort d l i t
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
and complaints
• A well-designed and ventilated area will result in high levels of human productivity and health
A Brief History of Energy Recovery
• Until the early 1970s, energy recovery was of little concern; mechanical ventilation rates were lower than today, but were supported by natural ventilation and IAQ was good
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
• The oil embargo, associated energy crisis and rapidly rising costs would have a profound effect on the design and operation of buildings throughout the world
Cause and Effect
Design Decisions• Reduced Amounts of O/A• Increasing Use of Synthetic Results
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
g yMaterials
• Tighter Building Envelopes• Reduced Productivity• Sick Building Syndrome (SBS) and
Building Related Illness (BRI)• Occupant Discomfort• Poor Indoor Environmental Quality (IEQ)
Response from the Market
• Standards were developed to improve IAQ, energy efficiency and human comfort
• Commercial energy recovery was introduced
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
gy yinto the commercial marketplace at this time as it proved to be one of the most economical ways to introduce ventilation air and improve IAQ
AAERV Applications
Pro
cess • Waste heat is
captured from the exhaust airstream & transferred to om
fort • Waste heat
captured from the process exhaust air stream heats the om
fort • Sensible and
latent energy are transferred from the exhaust air stream to the
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Pro
cess
-to-
P the process supply airstream
• Equipment is available to handle exhaust temperatures as high as 1600°F
Pro
cess
-to-
Co
building makeup air during winter
• Typically modulated during warm weather to prevent overheating of makeup air
Com
fort
-to-
Co
supply air stream in summer and winter
• The objective is to temper the O/A with preconditioned air from the space
Energy Recovery VentilationGreen Building is Thriving in a Down Economy
• Climate Change, Energy Efficiency and the Global Economic Crisis
• Seemingly Conflicting and Increasingly Stringent Standards and Guidelines
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Standards and Guidelines
• Net Zero Energy and Sustainability
• Energy Recovery Provides the Most Cost-Effective Way to Recycle Waste Energy and Create Quiet and Comfortable Indoor Environments
The Green EconomyEnergy Efficiency and the Economic Stimulus Package
• Allocation of $22 Billion Towards:
– Modernization of Schools’ Heating and Cooling Systems
– Conversion of Federal Buildings to High Performance Green Buildings
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Green Buildings
– Energy Efficiency Projects, Energy Retrofits and Facility Modernization
• Funding for States is Dependent on Adopting an Energy Code at Least as Stringent as ASHRAE 90.1-2007
Selected Key Standards & Guidelines
• ANSI/ASHRAE Standard 55-2004 Thermal Environmental Conditions for Human Occupancy
• ANSI/ASHRAE Standard 62.1-2007 Ventilation for Acceptable Indoor Air Quality
• ANSI/ASHRAE Standard 84-2008 Method of Test for Air-to-Air Heat/Energy Exchangers
• ANSI/ASHRAE/IESNA Standard 90 1 2007 Energy Standard for Buildings
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
• ANSI/ASHRAE/IESNA Standard 90.1-2007 Energy Standard for Buildings Except Low-Rise Residential Buildings
• Proposed Standard 189.1P Proposed Standard for the Design of High-Performance, Green Buildings Except Low-Rise Residential Buildings
• ARI Standard 1060-2005 Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation
• LEED for New Construction and Major Renovations (LEED 2009)
ANSI/ASHRAE Standard 55-2004Thermal Environmental Conditions for Human Occupancy
PURPOSE:
To specify the combinations of indoor thermal environmental factors and personal factors that will produce thermal environmental conditions acceptable to a majority of the occupants within the space
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
ANSI/ASHRAE Standard 62.1-2007Ventilation for Acceptable Indoor Air Quality
Published in May, Standard 62.1-2007 supersedes Standard 62.1-2004 and incorporates Addenda a, b, c, d, e, f, g and h
PURPOSE:
To specify minimum ventilation rates and other measures intended to provide indoor air quality that is acceptable to human
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
air quality that is acceptable to human occupants and that minimizes adverse health effects
It is intended for regulatory application to new buildings, additions to existing buildings, and those changes to existing buildings that are identified in the body of the standard
It is intended to be used to guide the improvement of indoor air quality in existing buildings
Systems & Equipment Flow Chart
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
§ 5.10 Dehumidification Systems
§ 5.10.1 Relative Humidity
HVAC systems that have dehumidification capability must be designed to limit relative humidity toa maximum of 65% when analyzed under the following simultaneous design conditions:
At the peak outdoor dewpoint
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
At the peak outdoor dewpointdesign conditions and the mean coincident dry-bulb and
At the design indoor latent and sensible loads, and
With solar loads at zero.
This combination is the "dehumidification challenge"condition.
§ 6.1 Procedures
Indoor Air Quality Procedure• The IAQP is performance-
based
• The IAQP allows designers to take credit for source-control
Ventilation Rate Procedure• The VRP is prescriptive
• Outdoor air intake rates are predetermined for various space types (occupancy
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
take credit for source control and removal measures, such as selection of low-emitting materials and gas-phase air cleaning devices
space types (occupancy categories) based on contaminant sources and source strengths that are typical for the space type
Two-Component Approach
• Prescribed rates were expressed as volumetric airflow rate per person for most typical occupancy categories until about 2001
• This was significantly revised by
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
g y yAddendum 62n, approved by ASHRAE in June 2003 and ANSI in January 2004
• Additivity, now prescribes rates based on an occupant-related component and a building-related component
VRP Flow Chart
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Estimating Outdoor Air
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
ASHRAE 62MZCalc
Ventilation Rate Reduction
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Occupancy for outdoor air assumed to be 25 people / 1000 ft2
Ventilation Rate Comparison
Stan
dard
62.
1-20
01 Outside Air Requirements for Classroom Ventilation St
anda
rd 6
2.1-
2007 Outside Air
Requirements for Classroom Ventilation
Outside Air Reduction
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
ASH
RAE
S Ventilation
48,081 CFM
ASH
RAE
Ventilation
39,810 CFM
(17.2%)
§ 5.17 Air Classification & Recirculation
• Classifies air in various types of spaces
• Limits the recirculation of lower quality air into spaces that contain air of higher quality
• This requirement applies when using the
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
• This requirement applies when using the Ventilation Rate Procedure
§ 5.17 Air Classification & Recirculation § 5.17.1 Classification
Class 1: Air with low contaminant concentration and inoffensive odor and sensory-irritation intensity, suitable for recirculation or transfer to any
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
recirculation or transfer to any space.
Examples: Office spaces, classrooms, assembly rooms, churches, corridors
§ 5.17 Air Classification & Recirculation § 5.17.1 Classification
Class 2: Air with moderate contaminant concentration, mildly offensive odors or sensory irritation intensity, suitable for recirculation or transfer to any space with Class 2 or Class 3 air that is utilized for the same or similar purpose and involves the same or
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
similar purpose and involves the same or similar pollutant sources. Class 2 air is not suitable for recirculation or transfer to spaces with Class 1 air, or dissimilar spaces with Class 2 or Class 3 air.
Examples: Rest rooms, swimming pools, dining rooms, locker rooms, warehouses
§ 5.17 Air Classification & Recirculation § 5.17.1 Classification
Class 3: Air with significant contaminant concentration or significant offensive odor or sensory-irritation intensity that is suitable for recirculation with the same space Class 3 air is not
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
same space. Class 3 air is not suitable for recirculation or transfer to any other space.
Examples: Kitchens, dry cleaners, beauty salons, laboratories, pet shops.
§ 5.17 Air Classification & Recirculation § 5.17.1 Classification
Class 4: Air with highly objectionable fumes or gases or potentially containing dangerous particles, bioaerosols, or gases at a concentration high enough to be considered harmful
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
enough to be considered harmful, not suitable for recirculation or transfer to any other space.
Examples: Paint spray booths, laboratory fume exhaust, kitchen grease exhaust
§ 5.17.2 Re-Designation
A mixture is classified with the highest class of its constituents. For example, air returned from both a Class 1 and a Class 2 space served by a common system must be designated as Class 2 air
Formerly Known as Addendum y to 62.1-2004
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
BUT§ 5.17.2.2 Energy Recovery
Energy recovery resulting in 10% or less cross-contamination from Class 2 or 5% or less from Class 3 does not affect the classification of Class 1 air.
ANSI/ASHRAE/IESNA Standard 90.1-2007Energy Standard for Buildings Except Low-Rise Residential Buildings
PURPOSE:
The purpose of this standard is to provide minimum requirements for the energy-efficient design of buildings except low-rise residential buildings.
SCOPE:
This standard provides minimum energy efficiency requirements for the design and construction of
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
requirements for the design and construction of new residential dwelling units and their systems, and where explicitly specified, new portions of residential dwelling units and their systems, and new systems and equipment in existing dwelling units.
This standard applies to the building envelope, heating equipment and systems, air-conditioning equipment and systems, domestic water-heating equipment and systems, and provisions for overall building design alternatives and trade-offs.
90.1 Compliance Paths
§ 6 Heating, Ventilating and Air Conditioning
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
§ 6.5 Prescriptive Path
Economizers
Simultaneous heating and cooling
Air system design and
Heat rejection equipment
Exhaust Air Energy Recovery
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Air system design and control
Hydronic system design and control
y
Exhaust hoods
Radiant heating
Hot gas bypass limitation
§ 6.5.2.3 Simultaneous Heating & Cooling
• Active dehumidification is most often required in humid climates so that air delivered to the space is not overcooled
• Is allowed in 90.1 if at least 75% of the energy for
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
gyreheating comes from site recovered or a site-solar energy source
Pre-Cooler Re-Heater Examples
Fixed Plate Heat Exchanger
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Heat Pipe Heat Exchanger
§ 6.5.6.1 Exhaust Air Energy Recovery
“Individual fan systems that have both a design supply air capacity of 5000 CFM or greater and have a minimum outdoor air supply of 70% or greater of the design supply air quantity shall have an energy recovery system with at least 50% recovery effectiveness. Fifty percent energy
ff ti h ll h i th th l
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
recovery effectiveness shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air at design conditions. Provision shall be made to bypass or control the heat recovery system to permit air economizer operation as required by Section 6.5.1.1.”
§ 6.5.6.1 Exhaust Air Energy Recovery
EXCEPTIONS:
Laboratory systems:
a. Systems serving spaces that are not cooled and that are heated to less than 60°F
b. Systems exhausting toxic, flammable, paint or corrosive fumes or dust
c. Commercial kitchen hoods used for collecting and removing grease vapors and smoke
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
and smoke
d. Where more than 60% of the outdoor air heating energy is provided from site-recovered or site-solar energy
e. Heating systems in climate zones 1 through 3
f. Cooling systems in climates zones 3c, 4c, 5b, 6b, 7 and 8
g. Where the largest exhaust source is less than 75% of the design outdoor air flow
h. Systems requiring dehumidification that employ energy recovery in series with the cooling coil
Proposed Addendum e to 90.1-2007Third Public Review Draft
• This is an ISC to the second public review of addendum e to incorporate changes suggested by the second public review comments
Revises section 6 3 2 and
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
• Revises section 6.3.2, and 6.5.6.1 and deletes a reference to Chapter 12 to include ARI 1060-2005 – Performance Rating Of Air to Air Heat Exchangers For Energy Recovery Ventilation Equipment Standard
Addendum e§ 6.3.2 Criteria and Requirements of § 6.5.6.1
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Addendum eTable 6.5.6.1 & Climate Zones
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Addendum eTable 6.5.6.1B & Normative Reference
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
ANSI/ASHRAE Standard 84-2008Method of Test for Air-to-Air Heat/Energy Exchangers
SPC 84-2008 - Revision project committee authorized 2/01/1995 with revised TPS. Revised TPS approved June 23, 2007 (Long Beach).
PURPOSE:
• To establish a uniform method of test
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
test
• Specify the test conditions, data required, uncertainty analysis to be performed, calculations to be used, and reporting procedures
• Specify the types of test equipment for performing such tests.
• Is NOT a Ratings Program
ARI Standard 1060-2005Performance Rating of Air-to-Air Heat Exchangers
for Energy Recovery Ventilation
PURPOSE:
To establish definitions, test requirements, rating requirements, minimum data requirements for Published Ratings, marking and nameplate data and conformance conditions for Air-to-Air Heat Exchangers intended for use in Air-to-Air Energy Recovery Ventilation Equipment
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Energy Recovery Ventilation Equipment
ARI Certification Program started in Q1 2001
Old New
=
Standard Rating Conditions
Stringently tests for conformance and certifies the following to validate manufacturers claims with airflow at 75% and 100% of rated flow:
1 P D
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
1. Pressure Drop
2. Energy Transfer Effectiveness (Sensible, Latent and Total)
3. EATR (Cross Leakage)
4. OACF
Standard 1060 Key DefinitionsExhaust Air Transfer Ratio (EATR) & Outdoor Air Correction Factor (OACF)
Exhaust Air Transfer Ratio (EATR)
The tracer gas concentration difference between the Leaving Supply Airflow and the Entering Supply Airflow divided by the difference between the Entering Exhaust Airflow and the Entering Supply Airflow
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Outdoor Air Correction Factor (OACF)
The Entering Supply Airflow divided by the measured (gross) Leaving Supply Airflow
Performance MetricsNet Sensible, Latent & Total Effectiveness
Net EffectivenessThe measured Effectiveness adjusted to account for the leakage of Entering Exhaust Airflow rather than exchange
AHRI Standard 1060
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
of heat or moisture between the airstreams
ARI 1060 versus 90.1 Effectiveness
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
ARI 1060-2005 ASHRAE 90.1-2007
Specification Verbiage
Manufacturer
Energy transfer ratings shall be ARI Certified to Standard 1060 and bear the ARI certification seal
Non-ARI Certified Manufacturer
The manufacturer shall provide certified performance data in accordance with ASHRAE
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
and bear the ARI certification seal for ARI Air-to-Air Energy Recovery Ventilation Equipment Program based on ARI 1060. Ratings "in accordance with 1060" without certification shall be deemed unacceptable.
accordance with ASHRAE Standard 84 and ARI 1060. Independent performance test results shall be used to rate the product in accordance with the ARI Air-to-Air Energy Recovery Ventilation Equipment Program .
ARI Certified Componentshttp://www.ahridirectory.org
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Proposed Standard 189.1PStandard for the Design of High-Performance, Green Buildings
• Currently being developed by ASHRAE, IESNA & USGBC
• In 3rd Public review
• Will be written in code language; upon completion it will become an ANSI-accredited standard that
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
an ANSI-accredited standard that can be incorporated into building codes
• A step towards sustainability and a glimpse at the at the future of Standards 90.1 and 62.1
What is 189.1P?
• 189.1P is NOT a design guide or ratings system
• Where LEED operates on a menu-system for compliance, 189.1P will have mandatory criteria in all categories with simple compliance options
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
g p p p
• Creates a baseline for sustainable design, construction and operations in order to drive green building into mainstream building practices
§ 7.4.3.8 Exhaust Air Energy RecoveryTable 7.4.3.8 Energy Recovery Requirement
DOE Climate Zones
189.1P Third Public Review Draft
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
• Mandates 60% Energy Recovery Effectiveness
• Replicates Addendum e but requires energy recovery from as little as 10% of design airflow
U.S. Green Building Council
The U.S. Green Building Council (USGBC) is a non-profit organization committed to expanding sustainable building practices. USGBC is composed of more than 15,000 organizations from across the building industry that are working to advance structures that are environmentally responsible, profitable and healthy places to live and work.
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
USGBC's Mission
To transform the way buildings and communities are designed, built and operated, enabling an environmentally and socially responsible, healthy and prosperous environment that improves the quality of life.
USGBC's Vision
Buildings and communities will regenerate and sustain the health and vitality of all life within a generation.
Energy & Atmosphere
Prereq 2Minimum Energy Performance
Required
ERV sys tems can be des igned or selected to meet
the mandatory (5.4, 6.4, 7.4, 8.4, 9.4 & 10.4) and
prescriptive (5.5, 6.5, 7.5, & 9.5) or performance
(Section 11) requirements of 90.1 ‐2007
Credi t 1Optimize Energy Performance
1 to 19
ERV sys tems can be used to help acheive
improvements over baseline bui ldi ng performance
for maximum energy optimiza tion to maxi mize ava ilabl e credits for this category; DOAS reduces
energy use and demand and results i n
approximately 30% reduction in mechnical system
opera ting costs; additional ai r‐to‐ai r energy recovery strategies and parall el system sel ecti ons
can achieve even more
Indoor Environmental Quality
Energy & Atmosphere
Prereq 2Minimum Energy Performance
Required
ERV sys tems can be des igned or selected to meet
the mandatory (5.4, 6.4, 7.4, 8.4, 9.4 & 10.4) and
prescriptive (5.5, 6.5, 7.5, & 9.5) or performance
(Section 11) requirements of 90.1 ‐2007
Credi t 1Optimize Energy Performance
1 to 19
ERV sys tems can be used to help acheive
improvements over baseline bui ldi ng performance
for maximum energy optimiza tion to maxi mize ava ilabl e credits for this category; DOAS reduces
energy use and demand and results i n
approximately 30% reduction in mechnical system
opera ting costs; additional ai r‐to‐ai r energy recovery strategies and parall el system sel ecti ons
can achieve even more
Indoor Environmental Quality
LEED v3 / LEED 2009
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
Prereq 1 Minimum IAQ Performance Required
ERV sys tems can be des igned or selected to meet
the minimum requirements of Secti ons 4 through
Section 7 of 62.1‐2007
Credi t 2 Increased Ventilation 1
ERV sys tems provide the most cost effective method of delivering 30% more ventila tion ai r while
maximi zing energy performance through the use of
a ir‐to‐a ir energy recovery technol ogies
Credi t 5Indoor Chemical & Pollutant Source Control
1
ERV equipment can be des igned or selected with MERV 13 filters and reduce the potentia l for
potentia l ly hazardous particul ate a gaseous
pollutants
Credi t 6.2Controllability of Systems , Thermal Comfort
1
ERV sys tems conti bute to this credit with
equi pment and controls tha t can provide
individua l comfort controls for 50% of occupants
Credi t 7.1 Thermal Comfort, Design 1
ERV sys tems can be des igned or selected to meet the requirements of ASHRAE Standard 55 ‐2004 for
tempera ture and humi dity that supports
productivity and well‐being quite eas ily wi th the
DOAS approch and appropria te parallel sys tem
selection
Prereq 1 Minimum IAQ Performance Required
ERV sys tems can be des igned or selected to meet
the minimum requirements of Secti ons 4 through
Section 7 of 62.1‐2007
Credi t 2 Increased Ventilation 1
ERV sys tems provide the most cost effective method of delivering 30% more ventila tion ai r while
maximi zing energy performance through the use of
a ir‐to‐a ir energy recovery technol ogies
Credi t 5Indoor Chemical & Pollutant Source Control
1
ERV equipment can be des igned or selected with MERV 13 filters and reduce the potentia l for
potentia l ly hazardous particul ate a gaseous
pollutants
Credi t 6.2Controllability of Systems , Thermal Comfort
1
ERV sys tems conti bute to this credit with
equi pment and controls tha t can provide
individua l comfort controls for 50% of occupants
Credi t 7.1 Thermal Comfort, Design 1
ERV sys tems can be des igned or selected to meet the requirements of ASHRAE Standard 55 ‐2004 for
tempera ture and humi dity that supports
productivity and well‐being quite eas ily wi th the
DOAS approch and appropria te parallel sys tem
selection
EA Credit 1Optimize Energy Performance
OPTION 1 — WHOLE BUILDING ENERGY SIMULATION (1–19 Points)
Demonstrate a percentage improvement in the proposed building performance rating compared to the baseline building performance rating per ASHRAE/IESNA Standard 90.1-2007 (with errata but without addenda*) by a whole building project simulation using the Building
OPTION 2 — PRESCRIPTIVE COMPLIANCE PATH (1 Point)
Comply with the prescriptive measures of the ASHRAE Advanced Energy Design Guide appropriate to the project scope, outlined below. Project teams must fully comply with all applicable criteria as established in the Advanced Energy Design Guide for the climate zone in which
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
project simulation using the Building Performance Rating Method in Appendix G of the Standard.
Design Guide for the climate zone in which the building is located.
OPTION 3 — PRESCRIPTIVE COMPLIANCE PATH: Advanced Buildings™ Core Performance™ Guide (1-3 Points)
Comply with the prescriptive measures identified in the Advanced Buildings™ Core Performance™ Guide developed by the New Buildings Institute.
EQ Credit 2Increased Ventilation
CASE 1 - MECHANICALLY VENTILATED SPACES (1 Point)
Increase breathing zone outdoor air ventilation rates to all occupied spaces by at least 30% above the minimum rates required by ASHRAE Standard
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
62.1-2007 (with errata but without addenda*) as determined by EQ Prerequisite 1.
Ventilation Rate ComparisonEQ Credit 2 - Increased Ventilation (1 Point)
HRA
E St
anda
rd 6
2.1-
2007 Outside Air
Requirements for Classroom Ventilation*
LEED
200
9 /
v3 Outside Air Requirements for Classroom Ventilation
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
ASH
39,810 CFM 51,753 CFM30% Increase
* Based on total square footage of classroom area for the Baseline High School and assuming 25 people per 1000ft2 from the Technical Support Document: Development of the Advanced Energy Design Guide for K-12 Schools—30% Energy Savings
An additional 11,943 CFM of O/A needs to be introduced with 30% less energy!
Conclusions
• The use of air-to-air energy recovery technologies that is mandated in current minimum performance standards is rapidly increasing
• The current economic climate is providing strong incentives to use energy recovery beyond the minimum requirements currently required by codes
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
• Concerns for the environment and high performance building codes and guidelines will require air-to-air energy recovery in order to meet the seemingly conflicting requirements of high performance HVAC systems that are energy efficient and capable of delivering superior IEQ
• Air-to-air energy recovery systems and equipment provide some of the most cost-effective and efficient ways to recycle waste energy while creating quiet and comfortable indoor environments
Beyond this PresentationUseful References
ASHRAE: http://www.ashrae.org/
TC 5.5 Air-to-Air Energy Recovery: http://tc55.ashraetcs.org/
Advanced Energy Design Guides: http://www.ashrae.org/publications/ page/1604
AHRI: http://ari.org/
AHRI Certification
Meeting and Exceeding High Performance Standards, Codes and Guidelines
Air-to-Air Energy Recovery Systems and Equipment
AHRI Certification: http://ari.org/Content/AirtoAirEnergyRecoveryVentilators_81.aspx
• 2004 ASHRAE Handbook – HVAC Systems and Equipment, Chapter 44 Air-to-Air Energy Recovery
• ARI Guideline V: ARI Guideline V: Calculating the Efficiency of Energy Recovery Ventilation and Its Effect on Efficiency and Sizing of Building HVAC Systems
• ARI Guideline W: Selecting, Sizing, & Specifying Packaged Air-To-Air Energy Recovery Ventilation Equipment (2005)