    The IAQ Issue

    People spend a lot of time indoors (90% +)

    People expect the air to be reasonably comfortable,which usually means reasonable temperature and

    humidity; avoiding drafts or stuffiness; and absence ofunpleasant odors or irritation.

    Studies Have Proven That Poor IAQ can effectpeoples

    HealthProductivityHappiness

  • 8/10/2019 ASHRAE D62

    3/27

    How IEQ Affects Health, ProductivitySource of

    Productivity GainPotential AnnualHealth Benefits

    Potential U.S. AnnualSavings or Productivity

    Gain (1996 U.S. $)

    ReducedRespiratory Illness

    16 Million to 37Million Avoided

    Cases of CommonCold or Influenza

    $6 Billion to $14 Billion

    Reduced Allergiesand Asthma

    8% to 25% Decreasein Symptoms within

    53 Million AllergySufferers and 16

    Million Asthmatics

    $1 Billion to $4 Billion

    Reduced SickBuilding Syndrome

    Symptoms

    20% to 50%Reduction in SBSHealth Symptoms

    Experienced

    Frequently at Workby ~ 15 MillionWorkers

    $10 Billion to $30 Billion

    Improved WorkerPerformance from

    Changes inThermal

    Environment andLighting

    Not Applicable $20 Billion to $160 Billion

    Estimated potentialhealth and productivitygains from improved

    IEQ.In many non-industrialworkplaces, workerssalaries and benefits

    exceed energy costs byapproximately 100:1.

    Source: ASHRAE Journal

  • 8/10/2019 ASHRAE D62

    4/27

    A Growing ConcernAn estimated 30 percent of the more than fourmillion U.S. commercial buildings have IAQproblems.

    Although ser ious health problems related to IAQare rare, the percept ion of adverse health effectsassociated with IAQ is common. Since 1991, US courts have seen a markedincrease in cases in which plaintiffs claiminjuries due to IAQ issues.

  • 8/10/2019 ASHRAE D62

    5/27

    Information About IAQ Is

    Everywhere..

  • 8/10/2019 ASHRAE D62

    6/27

    The IAQ Issue What To Do?Comply with building codes

    MandatoryComply with ASHRAE 62.1

    Voluntary unless written into building codesProperly install & maintain building & HVAC equipment

    Education & training

    Stay current on what is happening in the industry

    Docum ent Everyth ing !

  • 8/10/2019 ASHRAE D62

    7/27

    How ASHRAE Standard 62.1-2004Addresses IAQ

    Provides guidelines to designers

    Proper IAQ is more than providing 15 or 20 cfm of OAair per person

    Also addresses other 3 components; contaminantsource control, filtration and managing relativehumidity

    Establishes the standard -of- care of the industry,however is not an all encompassing document.Structured more towards the HVAC industry.

    Lets look at some of the key areas of 62.1 -2004

    You have to look at the s tandard as a w hole!

  • 8/10/2019 ASHRAE D62

    8/27

    Ventilation Control

    A SHRA E 62.1-2004 Req u ires : 5.4 Ventilation System Controls. system shall bedesigned to maintain the minimum outdoor airflow asrequired by Section 6 under any load condition.

    Implies OA should be measured in VAV systems.

    Good idea for CV systems also.Energy savings in multipurpose buildings - movie theaters,classrooms, etc.

    Specify ai r flow m oni tor ing damp ers tha t meetA MCA 610 & 611.

  • 8/10/2019 ASHRAE D62

    9/27

    A SHRAE 62.1-2004 Requ ires:

    5.5.1 Resistance to Mold Growth. Material surfacesshall be determined to be resistant to mold growth inaccordance with a standardized test method, such asUnderwriters Laboratories, Inc. (UL) 181 Mold Growthand Humidity Test, ASTM C 1338 Standard TestMethod for Determining Fungi Resistance of InsulationMaterial and Facings, or other comparable testmethods.

    Exceptio n to 5.5.1. Sheet metal surfaces and metal fastners.

    Note: Even with this resistance, any airstream surface that iscontinuously wetted is still subject to microbial growth.

    Mold

  • 8/10/2019 ASHRAE D62

    10/27

    Double Wall LinerFor Cleanability

    62.1-2004 Implies surface shouldbe cleanable

    Specify double wall solid liners,especially on all interior wetareas

    Make sure you can readily accessareas that will need to beperiodically cleaned

    Make sure specifications call forthe entire unit to be insulated andnot just the panels!

    Double wall solidliner prevents

    mold growth and

    airstream erosion.

    Wet fiberglass insulationunder perforated lineris an ideal medium

    for mold growth!

  • 8/10/2019 ASHRAE D62

    11/27

    Prevent/Manage Water IntrusionA SHRA E 62.1-2004 Requ ires:

    5.6.2 5.6.5 OUTDOOR AIR INTAKES

    Limit rain entrainment by selecting properly sized and/orrated outdoor air louvers or hoods.

    Manage any water that does penetrate outdoor airintakes with drains and/or moisture removal devices.

    Where snow entrainment is likely, provide drains anddoors in outdoor air sections to permit cleaning anddrainage.

    Provide corrosion resistant bird screening over all outdoorair intakes.

  • 8/10/2019 ASHRAE D62

    12/27

    Minimize InfiltrationA SHRA E 62.1-2004 Requ ires:

    5.8 Particulate Matter Removal Minimum MERV 6filters upstream of all cooling coils and wettedsurfaces.

    Specify performance that minimizesinfiltration of contaminants.

    Panel deflection limit of L/240 and 1% leakage at 8 w.c. reduces the chance of dust, dirt andmicrobes bypassing the filters.

    Less bypass reduces maintenance costsassociated with cleaning coils.

    2 - 30%

  • 8/10/2019 ASHRAE D62

    13/27

    Exam ples Of

    Microbial Contamination

    Photos cour tesy of Association of Occupational and Envir onmental Cli ni cs & NI OSH

    http://www.ohb.org/ieq-home.htm

  • 8/10/2019 ASHRAE D62

    14/27

    A SHRA E 62.1-2004 Requ ires:

    5.10.1 Relative Humidity. Occupied space RH shall be limitedto 65% or less at either

    the peak outdoor dew-point design conditions and the peak indoor designlatent load or

    the lowest space sensible heat ratio expected to occur and the concurrentoutdoor condition.

    Occupant comfort is optimal at 30% - 60% RH

    Relative humidity levels outside this range...Support microbial growth & produce unpleasant odorsCause occupant health problemsLead to equipment and furniture damageCan cause building structural damage

    Control the Humidity

  • 8/10/2019 ASHRAE D62

    15/27

    A SHRA E 62.1-2004 Requ ires:

    5.11.4. Drain pan sufficient to collect water droplets acrossthe entire width of the water producing device and extending

    downstream from the leaving face of the device either:(a) one half the installed vertical dimension of the device, or

    (b) as necessary to limit carryover to .0044 oz/ft 2 of face area per hourunder peak sensible and peak dewpoint design conditions,considering both latent load and face velocity.

    Specify corrosion resistant condensate drain pans,sloped a minimum of 1/8 per foot with drain outlet(s) atthe lowest point(s) of the pan and minimum accessunder coil for visual inspection and cleaning.

    Condensate Management

    This drain pan designmakes it difficult to

    clean or inspectunder the coil andthe coil supports

    This drain pan can beeasily visually inspectedand physically cleaned!

  • 8/10/2019 ASHRAE D62

    16/27

    A SHRAE 62.1-2004 Requ ires:

    5.12.2. Finned-Tube Coil Selection for Cleaning

    Air pressure drop of individual finned tube coils, or multiple finned tube coils in

    series without at least 18 between them, is limited to 0.75 in-wc. at 500 fpmdry coil velocity.

    Unless clear and complete instructions for access and cleaning of the coils isincluded.

    5.14.3. Access for Inspection, Cleaning, and Maintenance

    Outside air and mixed air plenums, coils, drain pans, air cleaners,humidifiers and fan sections

    Specify minimum access dimension along with door sizeand specify equipment location for full accessibility.

    Access, Access, Access...

  • 8/10/2019 ASHRAE D62

    17/27

    Coil Spacing Requirements

  • 8/10/2019 ASHRAE D62

    18/27

    Filter Contaminated AirA SHRA E 62.1-2004 Requ ires:

    4.1 4.3 OUTDOOR AIR QUALITY

    Investigation and documentation of outdoor air quality prior to completion of ventilation system design.

    6.2.1.1 Particulate Matter. If outdoor air isunacceptable, minimum MERV 6 filters or aircleaners are required for outside air before it

    reaches occupied spaces.6.2.1.2 Ozone. Air cleaning devices may berequired where high ambient ozone levels arecommon.

  • 8/10/2019 ASHRAE D62

    19/27

    MERV?

  • 8/10/2019 ASHRAE D62

    20/27

    MERV

    MERV: Minim um Eff ic iency Rat ing Value

    Introduced by ASHRAE Standard 52.2.

    Particle Size Based Efficiency - the filters abilityto remove airborne particles in specific sizeranges from 0.3 to 10 microns.

    The dust spot efficiency rating of ASHRAE

    Standard 52.1 does not account for particle sizeand does not use a controlled, repeatable testmedium.

    Range 2 Range 31 to 3 m 3 to 10 m

    9 40 to 45% E2 < 50 85 < E3 1 Nebulizer drops,welding fumes

    Commercial Box filters

    10 50 to 55% 50 < E2 < 65 85 < E3 1 Coal dust,auto emissions

    Superiorresidential

    ResidentialEACs

    11 60 to 65% 65 < E2 < 80 85 < E3 1 Lead dust,milled flour

    Bettercommercial

    Box filters

    12 70 to 75% 80 < E2 90 < E3 1 Legionella,humidifier dust

    Hospitallaboratories

    Bag filters

    Particle size efficiency (PSE) %ASHRAE52.1 dust

    s otMERV

    Min. finalresistance

    in. WG

    Typicalcontrolled

    contaminants A lication Filter t e

  • 8/10/2019 ASHRAE D62

    21/27

    Ventilation Procedures6.2 Ventilation Rate Procedure

    Prescriptive procedure in which outdoor air intake rates arebased on space type, occupancy level and floor area.

    Rates are based on contaminant sources and sourcestrengths that typical for the space type.

    6.3 Indoor Air Quality Procedure

    Alternate design procedure in which outdoor air intake ratesand other parameters are based contaminant sources and

    concentrations.Lower ventilation rates than the Ventilation Rate Proceduremay be required as a result of using filtration or other designtechniques.

  • 8/10/2019 ASHRAE D62

    22/27

    A SHRA E 62.1-2004 Requ ires:

    7.1.3. Protection of Materials. When recommended bythe manufacturer, building materials shall be protected

    from rain and other sources of moisture by appropriatein-transit and on-site procedures.

    Specify shrink-wrapped to protect indoor unitsfrom road dirt & microbial contamination.

    Specify that indoor units without shrink-wrappingshould be fully tarped for shipping or shipped inan enclosed truck and adequately protected fromrain and contamination during storage at the

    jobsite.

    Keep it Clean!

  • 8/10/2019 ASHRAE D62

    23/27

    IOM Requirements

    A SHRAE 62-2001 Requ ires:

    TABLE 8-1 Minimum Maintenance Activity & Frequency

    Visual inspect ion or remo te moni tor ing o f OSA damp ers &actuators every th ree mo nths .

    Cleaning of h um idi f iers every three month s .

    Regular (no less th an on ce/year) v isua l inspect ion ofdehum idi fy ing coi l s and dra inpans , and c leaning w hennecessary.

    Biannual insp ect ion of OSA louv ers , b i rdscreens , etc .

    Specify that IOMs highlight the requirements ofASHRAE 62 and include a maintenanceschedule and recommended procedures.

  • 8/10/2019 ASHRAE D62

    24/27

    ENERGY STAR Label Requires IAQ Compliance ... Then a professional engineer needs to submitverification that the building meets 3 standards forthe indoor environment: ASHRAE Standard 62-2001 ;

    ASHRAE Standard 55-1992 for thermal comfort; andIESNA Lighting Handbook for lighting quality. TheENERGY STAR Label for Buildings is offered to thetop 25% of buildings. The Label recognizes one yearof performance, and encourages facility managers toapply annually. The Label was introduced inJanuary, 1999.

  • 8/10/2019 ASHRAE D62

    25/27

    The Future ofASHRAE Standard 62.1

    ASHRAE Standard 62-2004 is under continuousmaintenance:

    Addenda are considered on a semi-annual basis and regularlysubmitted for Public Review (check www.ashrae.org).

    All approved addenda will now be published simultaneously ina periodic supplement to the standard rather than as soon asthey are approved as they were in the past.

    Ap pro ved addend a are available for f ree do w nlo adon the ASHRAE w ebsi te and are essent ia l for acom ple te & accura te und ers tanding o f the s tand ard .

  • 8/10/2019 ASHRAE D62

    26/27

    Summary

    ASHRAE 62.1-2004 provides sound direction andestablishes the standard-of-care for ventilation systemdesign, however, there are many factors that contribute topoor IAQ that are not addressed in 62-2004!

    Specify equipment and systems which do not compromisethe requirements of ASHRAE 62.1

    Stay current on IAQ news in the industry

    Remember that IAQ applies to the entire building, not just

    the HVAC systemLook for updates to the standard

    Contact indu stry leaders for h elp