AS 1674.2-2007 Safety in welding and allied processes ...
Transcript of AS 1674.2-2007 Safety in welding and allied processes ...
LICENCE for
Licensee:
Date:
To read the full licence agreement, simply click within the red box above and scroll through with your cursor
Learn about LexConnect, All Jurisdictions, Standards referenced in Australian legislation
Know when a Standard has changed
Visit our store to find more Publications
AS 1674.2—2007 (Incorporating Amendment No. 1)
Australian Standard®
Safety in welding and allied processes
Part 2: Electrical
AS
16
74
.2—
20
07
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
This Australian Standard® was prepared by Committee EL-019, Electrical Welding Plant. It was approved on behalf of the Council of Standards Australia on 2 February 2007. This Standard was published on 16 April 2007.
The following are represented on Committee EL-019:
• Australian Chamber of Commerce and Industry • Australian Industry Group • Australian Manufacturing Workers Union • Electrical Regulatory Authorities Council • Welding Technology Institute of Australia
This Standard was issued in draft form for comment as DR 05498. Standards Australia wishes to acknowledge the participation of the expert individuals that contributed to the development of this Standard through their representation on the Committee and through the public comment period.
Keeping Standards up-to-date Australian Standards® are living documents that reflect progress in science, technology and systems. To maintain their currency, all Standards are periodically reviewed, and new editions are published. Between editions, amendments may be issued. Standards may also be withdrawn. It is important that readers assure themselves they are using a current Standard, which should include any amendments that may have been published since the Standard was published. Detailed information about Australian Standards, drafts, amendments and new projects can be found by visiting www.standards.org.au Standards Australia welcomes suggestions for improvements, and encourages readers to notify us immediately of any apparent inaccuracies or ambiguities. Contact us via email at [email protected], or write to Standards Australia, GPO Box 476, Sydney, NSW 2001.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 (Incorporating Amendment No. 1)
Australian Standard®
Safety in welding and allied processes
Part 2: Electrical
Originated in part as AS CC5—1947 and MP 17—1965. AS CC5—1965 and MP 17—1965 revised, amalgamated and redesignated as AS 2745—1984. AS 2745—1984 revised and redesignated as AS 1674.2—1990. Third edition 2007. Reissued incorporating Amendment No. 1 (February 2011).
COPYRIGHT
© Standards Australia Limited
All rights are reserved. No part of this work may be reproduced or copied in any form or by
any means, electronic or mechanical, including photocopying, without the written
permission of the publisher, unless otherwise permitted under the Copyright Act 1968.
Published by SAI Global Limited under licence from Standards Australia Limited, GPO Box
476, Sydney, NSW 2001, Australia
ISBN 0 7337 8142 X
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 2
PREFACE
This Standard was prepared by the Standards Australia Committee EL-019, Electrical
Welding Plant, to supersede AS 1674.2—2003.
This Standard incorporates Amendment No. 1 (February 2011). The changes required by
the Amendment are indicated in the text by a marginal bar and amendment number against
the clause, note, table, figure or part thereof affected.
The objective of this Standard is to provide a significant improvement in the safety of
welding in hazardous environments, where, in recent years, there have been a number of
deaths by electrocution.
The major changes from the 2003 edition of this Standard are as follows:
(a) Clarifications have been made that control measures are required to remove water
from category C environments.
(b) The scope has been modified to ensure that high ripple current d.c. welding power
sources are to be treated as a.c. power sources and to specifically exclude welding
underwater.
(c) A Table has been added to Section 5 detailing minimum insulation resistances for
routine inspection and testing of welding power sources.
The term ‘informative’ has been used in this Standard to define the application of the
appendix to which is applies. An ‘informative’ appendix is only for information and
guidance.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
3 AS 1674.2—2007
CONTENTS
Page
SECTION 1 SCOPE AND GENERAL
1.1 SCOPE ........................................................................................................................ 4
1.2 REFERENCED DOCUMENTS .................................................................................. 4
1.3 DEFINITIONS ............................................................................................................ 5
SECTION 2 RISK ASSESSMENT AND PERSONAL SAFETY
2.1 GENERAL .................................................................................................................. 9
2.2 CLASSIFICATION OF WELDING ENVIRONMENT............................................... 9
2.3 CONTROL MEASURES............................................................................................. 9
2.4 PARTICULAR HAZARDS WITH PLASMA-ARC PROCESSES ........................... 11
SECTION 3 EQUIPMENT
3.1 HELMETS, HANDSHIELDS, GOGGLES, FACE MASKS AND GLOVES............ 12
3.2 POWER SOURCES................................................................................................... 12
3.3 ANCILLARIES ......................................................................................................... 16
SECTION 4 ELECTRICAL CONNECTIONS
4.1 CONNECTION TO ELECTRICITY SUPPLY.......................................................... 17
4.2 WELDING CIRCUIT CONNECTIONS.................................................................... 17
4.3 EARTHING............................................................................................................... 19
4.4 CONNECTING MULTIPLE POWER SOURCES TO A COMMON WORKPIECE 19
SECTION 5 INSPECTION AND MAINTENANCE
5.1 POWER SOURCE..................................................................................................... 24
5.2 ACCESSORIES......................................................................................................... 25
APPENDICES
A TYPICAL ELECTRICAL HAZARDS ...................................................................... 26
B FATAL ELECTRICAL ACCIDENTS....................................................................... 34
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 4
© Standards Australia www.standards.org.au
STANDARDS AUSTRALIA
Australian Standard
Safety in welding and allied processes
Part 2: Electrical
S E C T I O N 1 S C O P E A N D G E N E R A L
1.1 SCOPE
This Standard sets out safety requirements for arc welding and allied processes, to reduce
the possibility of electric shock and minimize associated hazards. It includes requirements
for cable connections for alternating and direct current power sources, as well as
requirements for hazard-reducing devices and other ancillary equipment. It also describes
practices and safeguards that should be adopted by welders and provides examples of
situations that present an increased risk of electric shock.
For the purposes of this Standard the term ‘direct current’ (d.c.) is considered to be a direct
current with a sinusoidal ripple content of not more than 10% r.m.s. Any d.c. power source
with a sinusoidal ripple content of more than 10% shall be considered as an a.c. power
source (eg. a single phase unfiltered full wave rectified d.c. power source has a nominal
sinusoidal ripple content of 48%).
This Standard does not cover electrical safety requirements when welding is carried out
underwater.
NOTES:
1 Other aspects of welding safety are covered in other Standards.
2 Typical electrical hazards are described in Appendix A.
3 Some fatal electrical accidents are reported in Appendix B.
1.2 REFERENCED DOCUMENTS
The following documents are referred to in this Standard:
AS
1674 Safety in welding and allied processes
1674.1 Part 1: Fire precautions
2812 Welding, brazing and cutting of metals—Glossary of terms
60529 Degrees of protection provided by enclosures (IP Code)
60974 Arc welding equipment
60974.1 Part 1: Welding power sources (IEC 60974-1, Ed.2.2 (2000) MOD)
60974.6 Part 6: Limited duty portable arc welding and allied process power
sources (IEC 60974-6, Ed. 1.0 (2003) MOD)
60974.11 Part 11: Electrode holders (IEC 60974-11, Ed.2.0 (2004))
AS/NZS
1336 Recommended practices for occupational eye protection
1337 Eye protectors for industrial applications
1338 Filters for eye protectors
1338.1 Part 1: Filters for protection against radiation generated in welding and
allied operations
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
5 AS 1674.2—2007
www.standards.org.au © Standards Australia
AS/NZS
1995 Welding cables
2161 Occupational protective gloves
2161.4 Part 4: Protection against thermal risks (heat and fire)
2865 Safe working in a confined space
3000 Electrical installations (known as the Australian/New Zealand Wiring Rules)
3100 Approval and test specification—General requirements for electrical
equipment
60479 Effects of current on human beings and livestock
60479.1 Part 1: General aspects
IEC
60974 Arc welding equipment
60974-2 Part 2: Liquid cooling systems
60974-5 Part 5: Wire feeders
60974-7 Part 7: Torches
60974-12 Part 12: Coupling devices for welding cables
WTIA [The Welding Technology Institute of Australia]
Tech. Note 7 Technical Note No.7: Health and safety in welding
Tech. Note 22 Technical Note No.22: Welding electrical safety
1.3 DEFINITIONS
For the purpose of this Standard, the definitions given in AS 2812 and those below apply.
NOTE: Diagrams for the purpose of illustrating some definitions relating to arc welding
installations are given in Figure 1.3.
1.3.1 Allied process
An electric arc process that is not used for joining, such as air arc gouging, air arc cutting,
metal arc cutting, arc spraying and plasma spraying.
1.3.2 Authorized
1.3.2.1 Authorized inspector
A person authorized by an authority administering acts of Parliament or regulations under
such acts or, in the absence of such acts and regulations, any person appointed by the Fire
and Accident Underwriters’ Association or the electricity supply or other authority, to
inspect installations.
1.3.2.2 Authorized person
A person in charge of a premises or a licensed electrical contractor, electrician or other
person appointed or selected by the person in charge of a premises, to perform certain
duties.
1.3.3 Conductor
1.3.3.1 Electrode conductor
Fixed wiring between a machine electrode or work terminal and the corresponding output
terminal.
1.3.3.2 Work (or return) conductor
Fixed wiring between a machine work or return terminal and the corresponding output
terminal.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 6
© Standards Australia www.standards.org.au
1.3.4 Control lead
A lead that connects the power source to ancillary devices, for control or regulating
purposes, but is not part of the welding circuit.
1.3.5 Distribution box
A multi-operator arrangement of connections, sockets or terminals that is enclosed in a box
or covered space, dividing a welding circuit into two or more branches that are suitable for
use by two or more welders.
1.3.6 Environment
1.3.6.1 Category A environment (see Clause 2.2(a))
An environment where—
(a) the risk of an electric shock or electrocution by arc welding is low;
(b) normal work practice is used; and
(c) it is not possible for a welder or any other worker to be in contact with the workpiece,
in the event of being in contact with a live part of the welding circuit.
1.3.6.2 Category B environment (see Clause 2.2(b))
An environment where there is a significant risk of the welder contacting the workpiece or
other parts of the welding circuit.
NOTE: Such an environment may be found where the ambient temperature is less than 32°C
and—
(a) freedom from movement is restricted, so that an operator is forced to perform welding
in a cramped position (e.g., kneeling, sitting, lying), with physical contact with
conductive parts (e.g., the workpiece); or
(b) there is a high risk of accidental or unavoidable contact by the operator with
conductive elements, which may or may not be in a confined space as defined in
AS/NZS 2865.
1.3.6.3 Category C environment (see Clause 2.2(c))
An environment where the risk of an electric shock or electrocution by arc welding is
greatly increased due to low body impedance of the welder and a significant risk of the
welder contacting the workpiece or other parts of the welding circuit.
NOTE: Low body impedance is likely in the presence of water, moisture or heat, particularly
where the ambient temperature is above 32°C. In wet, moist or hot locations, humidity or
perspiration considerably reduces the skin resistance of human bodies and the insulating
properties of personal protective equipment accessories and clothing.
1.3.7 FCAW
Flux-cored arc welding.
1.3.8 GMAW
Gas metal-arc welding.
1.3.9 GTAW
Gas tungsten-arc welding.
1.3.10 Hazard-reducing device (HRD)
A device designed to reduce the hazard of electric shocks from a welding circuit.
1.3.11 Licensed electrical worker
A person who holds an appropriate licence or approval to carry out electrical work in
accordance with AS/NZS 3000.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
7 AS 1674.2—2007
www.standards.org.au © Standards Australia
1.3.12 Mains installation (electrical)
Wiring systems, switchgear, control gear, accessories, appliances, luminaires and fittings
associated with wiring situated on any premises to which electricity is supplied or is to be
supplied through any one service to a consumer.
1.3.13 MMAW
Manual metal-arc welding.
1.3.14 Observer
A person whose sole responsibility is to monitor the welder(s) activity, and who is capable
of responding appropriately in an emergency.
1.3.15 Open-circuit voltage (OCV) or no-load voltage
The voltage between output terminals of a power source, while it is switched on, but not
delivering any current.
1.3.16 Output lead (or cable)
1.3.16.1 Electrode lead (or cable)
A lead between an electrode holder or torch and an electrode output terminal of an electrode
conductor, distribution box, choke or power source.
1.3.16.2 Work (or return) lead (or cable)
A lead between work and a return or work output terminal of a return conductor,
distribution box or power source.
NOTE: The term ‘earth lead’ is often incorrectly used to refer to a return lead or a work lead.
1.3.17 Power source (also known as welding machine)
A device that supplies welding current and output characteristics that are suitable for arc
welding or allied processes.
1.3.18 SAW
Submerged arc welding.
1.3.19 Shall
Indicates that a statement is mandatory.
1.3.20 Should
Indicates a recommendation.
1.3.21 Terminal
1.3.21.1 Power source terminal
A terminal of a welding or cutting power source, for the connection of conductors or leads
of a welding circuit (see Figure 1.1).
1.3.21.2 Output terminal
A terminal in a welding circuit to which an output lead is connected.
1.3.22 Voltage-reducing device (VRD)
A type of hazard-reducing device (either internally or externally fitted to a welding power
source) that is designed to automatically reduce the open-circuit voltage to a safer level.
1.3.23 Welder
A person who performs welding (including tack welding) or cutting operations.
NOTE: The term ‘welder’ is often used incorrectly to refer to a welding power source.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 8
© Standards Australia www.standards.org.au
1.3.24 Welding
The making of a joint between parts, by means of heat or pressure or both, in such a way
that there is continuity in the nature of the material of the parts.
NOTE: A filler material may or may not be used.
1.3.25 Welding circuit (also known as output circuit)
A circuit that includes the conductive material through which a welding current is intended
to flow.
NOTES:
1 An arc is part of a welding circuit.
2 In certain welding processes, an arc may be established between two electrodes. In such a
case, the workpiece is not necessarily part of the welding circuit.
1.3.26 Welding current
Current delivered by a power source during welding.
NOTE: These diagrams are for purposes of illustration and do not embrace all the possible combination of
circumstances.
FIGURE 1.3 ILLUSTRATION OF SOME ARC WELDING TERMS
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
9 AS 1674.2—2007
www.standards.org.au © Standards Australia
S E C T I O N 2 R I S K A S S E S S M E N T A N D
P E R S O N A L S A F E T Y
2.1 GENERAL
Parts of welding circuits, including workpieces and current return paths, have to be
considered electrically alive. Consequently, welders shall follow the precautions and
requirements in this Section, to minimize the risk of current passing through their body.
Before use, equipment shall be examined for soundness and proper maintenance in
accordance with Section 5.
2.2 CLASSIFICATION OF WELDING ENVIRONMENT
Before welding commences, the work area shall be assessed and the welding environment
classified for risk of electric shock in accordance with Clause 1.3.6. Also the following
apply:
(a) Category A environment (see Clause 1.3.6.1) In Category A environments,
considerable effort is required to insulate the welder and others from the workpiece,
such as bench-top welding where the workpiece is small and there is a low risk of the
welder becoming part of the circuit; or where both the welder and any assistants are
prevented from being in contact with conductive parts. For repetitive operations, such
an environment is usually limited to carefully designed workstations, as well as
welder training and welding procedure qualification test bays.
NOTE: AS 60974.1 and AS 60974.6 classify a Category A environment as ‘an environment
without increased hazard of electric shock’.
(b) Category B environment (see Clause 1.3.6.2) Category B environments include
general fabrication activities, large workpieces, steel building structures, inside
pressure vessels, processing tanks, storage tanks, conductive confined spaces and
onboard ships.
NOTES:
1 AS 60974.1 and AS 60974.6 classify Category B environments as ‘environment with
increased hazard of electric shock’.
2 When the weather is hot, when high preheat temperature is employed or when the vessel
is exposed to the sun, many Category B environments become Category C environments.
(c) Category C environment (see Clause 1.3.6.3) Category C environments include, but
are not limited to, coffer dams, trenches, underground mines, in rain, partially
submerged areas, splash zones (see also Appendix B).
NOTE: It may be possible to derate Category B and Category C environments, where
effective control measures are taken to reduce or eliminate the risk (e.g., airconditioning,
special insulating clothing).
2.3 CONTROL MEASURES
2.3.1 Category A environments
For welding in Category A environments (defined by Clause 1.3.6.1), Clause 2.2(a) and the
following apply:
(a) The electrode and workpiece shall be regarded as electrically live.
NOTE: The welder should take care to avoid contact with them.
(b) Welding gloves shall be sound, dry and used on both hands while welding or
changing electrodes.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 10
© Standards Australia www.standards.org.au
(c) Welders should wear appropriate dry fireproof clothing that covers the legs and arms,
and footwear should be rubber soled and not have bare steel toecaps.
(d) Leather cushions, wooden duckboards or other means shall be used to insulate the
welder from damp concrete floors and any exposed parts of the workpiece.
(e) Leads and equipment shall be inspected for damage. Damaged equipment and leads
shall not be used, but removed from service for repair or discarded.
NOTE: A system of tagging for defective equipment is recommended.
(f) While tacking two pieces together, the arc shall be struck on the piece connected to
the return lead.
NOTE: Trying to tack weld on an unconnected piece will expose any person holding a piece
not connected to the return lead to the risk of electric shock.
(g) The work area shall be kept tidy and free from tangled leads, discarded cut-offs and
electrode stubs.
(h) The electrode holder or gun shall not be placed on the workpiece, where it may short
circuit.
NOTE: An insulated container should be provided.
(i) The power shall be turned off and MMAW electrodes and stub ends removed from the
electrode holder, before the welder leaves the work area and whenever the leads have
to be moved.
NOTE: Further detailed advice may be obtained from WTIA Tech. Notes 7 and 22.
2.3.2 Category B environments
While welding in Category B environments (see Clause 1.3.6.2), Clauses 2.2(b) and 2.3.1
and the following apply:
(a) Where practicable, care shall be taken to convert to a Category A environment.
NOTE: Insulating cushions, sheets, blankets, duckboards and other suitable protection should
be used to insulate the welder, if practical.
(b) The open-circuit voltage in a Category B environment shall not exceed 113 V d.c
peak or 68 V a.c. peak and 48 V a.c. r.m.s.
The open circuit voltage shall be measured, to ensure it is within the specified limits.
If necessary, the power source shall be fitted with a hazard-reduction device
complying with Clause 3.2.7, in order to comply with this requirement.
NOTE: Power sources complying with AS 60974.1 should have been marked with the letter S
in a square on the compliance plate, to indicate its safety in such an environment (see
Table 3.2.2). Many a.c. MMAW power sources, particularly older machines, do not meet this
requirement and should not be used in a Category B environment.
(c) Whenever the welder works without an observer, the open circuit voltage shall not
exceed 35 V d.c. peak or 35 V a.c. peak and 25 V a.c. r.m.s. (i.e., the same as in Item
2.3.3(e) for a Category C environment).
NOTE: The use of a HRD may be required.
(d) Where the environment is a confined space, the provisions of AS/NZS 2865 shall also
apply, which specifies requirements for access to the space, egress from the space in
an emergency, avoiding asphyxiation and avoiding entanglement or entrapment.
Where access to the space is restricted, an observer, as described in Clause 1.3.14,
shall be required.
NOTES:
1 These control measures should be included in the hot work permit described in AS 1674.1.
2 Further detailed advice may be obtained from WTIA Tech. Notes 7 and 22.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
11 AS 1674.2—2007
www.standards.org.au © Standards Australia
2.3.3 Category C environments
For welding in Category C environments (defined by Clause 1.3.6.3), Clauses 2.2(c) 2.3.2
and the following apply:
(a) Where it is determined that the welder or welding equipment can become wet from
rain, splashing, partial submersion or other external sources, then adequate control
measures shall be implemented before welding commences.
(b) Every effort shall be made to make the environment as cool as possible to minimize
perspiration.
(c) An observer shall be appointed to monitor the welder. The observer or a third person
working close by shall be trained in rescue and emergency procedures. The observer
may monitor more than one welder, provided that the welders being monitored can be
observed at the same time.
(d) Maintenance of welding equipment shall not be undertaken in this environment.
(e) The voltage between the electrode holder and the workpiece while an arc is not
present shall not exceed 35 V d.c. peak or 35 V a.c. peak and 25 V a.c. r.m.s.
NOTES:
1 The use of covers to protect from water exposure (e.g., rain or a dripping roof),
air-conditioning and frequent changes of clothing (particularly cotton glove liners) should
minimize the risk.
2 Most equipment for GMAW, FCAW and GTAW complies with this requirement, because the
current is switched with a trigger switch.
3 For MMAW or similar processes, such as carbon-arc gouging, the power source may require
an additional hazard-reducing device.
4 Further detailed advice may be obtained from WTIA Tech. Notes 7 and 22.
2.4 PARTICULAR HAZARDS WITH PLASMA-ARC PROCESSES
Plasma-arc processes can produce fumes, gases, noise, radiation and heat, and explosion
when cutting aluminium, which can present greater hazards than typical arc welding
processes.
Plasma-arc cutting equipment presents a greater risk of electric shock than arc welding
equipment, due to the higher voltages.
NOTE: Reference should be made to the supplier’s recommendations for guidance on protection
from these potential hazards.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 12
© Standards Australia www.standards.org.au
S E C T I O N 3 E Q U I P M E N T
3.1 HELMETS, HANDSHIELDS, GOGGLES, FACE MASKS AND GLOVES
Helmets, hand shields, goggles and face masks shall be designed so that no
injury to the wearer can arise through conduction of electricity through the
material, and any metal parts which might touch the head or face shall be
electrically insulated.
NOTE: Helmets, hand shields, goggles and facemasks should comply with AS/NZS 1336,
AS/NZS 1337 or AS/NZS 1338.1. Gloves should comply with AS/NZS 2161.4.
3.2 POWER SOURCES
3.2.1 General
In addition to the requirements specified herein, power sources shall comply with the
relevant requirements of AS 60974.1, AS/NZS 3100 and AS 60974.6.
3.2.2 Degree of protection
The power source shall have a degree of protection that suits the environment in which it is
to be used.
NOTES:
1 Box 22 on the rating plate of power sources should show the degree of protection in
accordance with AS 60974.1.
2 Table 3.2.2 shows a typical rating plate.
3 Power sources rated with an IP21 degree of protection, as designated by AS 60529, are for
indoor use only.
4 Power sources rated with a minimum of IP23 degree of protection, as designated by
AS 60529, may be used outdoors.
5 The design and testing of power sources for use in Category B and Category C environments
should be agreed between the manufacturer and the purchaser. Examples of such conditions
include high humidity, unusually corrosive fumes, steam, excessive oil vapour, abnormal
vibration, abnormal shock, excessive dust, severe weather conditions, unusual coastal
conditions, shipboard conditions, vermin infestation and atmospheres conducive to the growth
of fungus.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
13 AS 1674.2—2007
www.standards.org.au © Standards Australia
TABLE 3.2.2
BOX NUMBERS
3.2.3 Terminals
Output terminals on the welding power source shall be enclosed, covered or otherwise
protected, to prevent inadvertent contact. Covers shall be of a robust design, with adequate
mechanical properties, and effectively maintained.
Terminals remote from the power source shall be marked in accordance with the relevant
requirements of AS 60974.1.
The words EARTH or GROUND shall not be marked on the output circuit. The welding
circuit cable shall not be coloured or tagged green and/or yellow.
3.2.4 Internal insulation
Power sources designated Class I Protection, as designated by AS/NZS 3000, shall be
connected to the power supply earth system.
Power sources designated Class II protection, as designated by AS/NZS 3000, do not
require connection to the power supply earth system.
NOTE: Where a power source has a Class II Protection, Box 23 of its rating plate will contain a
symbol consisting of two concentric squares.
3.2.5 Control
The power source shall be controlled by a switch that is incorporated in its primary circuit.
The switch shall have a designated OFF position and be mounted on or adjacent to the
power source framework. Where the power source is connected to the supply by means of a
power supply cord and plug, any switch mounted on the power source shall open all live
conductors, including the neutral.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 14
© Standards Australia www.standards.org.au
3.2.6 Maximum open-circuit voltage
Except as provided for in Clauses 3.2.7 and 3.2.8, the maximum open-circuit voltage shall
not exceed the values specified in Table 3.2.6.
TABLE 3.2.6
MAXIMUM PERMITTED OPEN CIRCUIT VOLTAGE
Working conditions Maximum permitted open circuit voltage
Category A environment (Clause 2.2(a)) d.c. 113 V peak, or
a.c. 113 V peak and 80 V rms
Category B environment (Clauses 1.3.6.2 and 2.2(b)) d.c. 113 V peak, or
a.c. 68 V peak and 48 V rms
Category C environment (Clauses 1.3.6.3 and 2.2(c)) d.c. 35 V peak, or
a.c. 35 V peak and 25 V rms
Mechanically held torches with increased protection
for the operator
d.c. 141 V peak, or
a.c. 141 V peak and 100 V rms
Plasma cutting d.c. 500 V peak
NOTES:
1 Each power source, complying with AS 60974.1, that is suitable for a Category B environment should be
marked with a symbol comprising the letter ‘S’ in a square box. This symbol can be found in Box 7 of the
rating plate or sometimes on the front panel.
2 MMAW power sources to old Standards may supply excessively high a.c. voltages for Category B and
Category C environments. It is necessary to measure the open-circuit voltage to determine suitability and,
if necessary, fit a hazard-reduction device.
3 Power sources to be used in Category C environments may require a hazard-reducing device (see
Clauses 2.3.3 and 3.2.7).
Conformity shall be checked by measurement and by analysis of the circuit or by the failure
simulation or both.
Measurement shall be as follows:
(a) RMS values A true r.m.s meter is used with a resistance of the external welding
circuit of 5 kΩ with a maximum tolerance of ±5%.
(b) Peak values To obtain reproducible measurements of peak values, omitting impulses
which are not dangerous, a circuit is used as shown in Figure 3.2.6.
1 = Diode 1N4007 or similar
FIGURE 3.2.6 MEASUREMENT OF PEAK VALUES
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
15 AS 1674.2—2007
www.standards.org.au © Standards Australia
The voltmeter shall indicate mean values. The measurement range chosen shall be as near
as possible to the actual value of the no-load voltage. The voltmeter shall have an internal
resistance of at least 1 MΩ.
The tolerance of the component values in the measurement circuit shall not exceed ±5%.
During the measurement, the potentiometer is varied from 0 Ω to 5 kΩ in order to obtain
the highest peak value of the voltage measured with these loads of 200 Ω to 5.2 kΩ. This
measurement is repeated with the two connections to the measuring apparatus reversed.
3.2.7 Hazard-reducing devices
3.2.7.1 General
Hazard-reducing devices shall reduce electrical-shock hazards originating from no-load
voltages that exceed the values in Table 3.2.6.
The hazard reducing devices shall comply with the relevant requirements of AS 60974.1.
3.2.7.2 Voltage-reducing devices
The voltage reducing devices shall comply with the relevant requirements of AS 60974.1.
3.2.7.3 Hand-piece trigger switches
Where a hand-piece trigger switch is used as a hazard-reducing device⎯
(a) the voltage of its control circuit shall be not more than d.c. 35 V peak or a.c. 25 V
rms; and
(b) its switching mechanism shall⎯
(i) return to the OFF position, immediately the welder releases pressure on the
switch;
(ii) be easy to hold in the closed position, enabling the welder to carry out normal
welding operations, without muscle strain;
(iii) for MMAW and carbon-arc gouging have a two-stage operation to move to the
ON position, so that there is a low probability of accidental closure of the
switch during any hazardous operations (for example, changing electrodes); and
(iv) automatically latch in the OFF position, on release of pressure by the welder.
3.2.7.4 Indication of satisfactory operation of voltage-reducing devices
Each voltage-reducing device shall be provided with a reliable device that indicates that it
is operating satisfactorily. Where a lamp is used, it shall light when the voltage has been
reduced.
3.2.8 Ancillary devices
The welding power source cabinet may contain additional equipment, which may be
separate devices, such as a high-frequency arc-initiating device, a smoke removal device, a
wire feeder or a water cooler. If these devices are used, they should be made to appropriate
Standards, such as the IEC 60974 series of Standards.
Any additional equipment shall be connected to the power source in accordance with the
manufacturer’s recommendations. They shall either have their own isolation switches or be
isolated by the power source switch.
Users should be made aware that high-frequency arc-starting devices deliver up to 6500 V
at a current up to 100 mA, which is imposed over the welding current. It can give a severe
and painful electric shock. It may cause damage to electronic devices, such as heart
pacemakers, computers, electrical meters in the vicinity, even if they are not directly
connected to the same power supply.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 16
© Standards Australia www.standards.org.au
Where it is necessary to earth any conductor of a high-frequency circuit, the earthing
connection shall be made to an earthing electrode driven into the ground and not under any
circumstances in contact with water or gas pipes or a building structure. The earthing
conductor to an earthing electrode shall have a cross-sectional area of not less than
2.5 mm2, be of stranded copper and be insulated with not less than 250 V grade insulation.
The earthing electrode and its connections shall be effectively shielded from personal
contact. (See also Figure 3.2.8 and AS/NZS 3000).
Any power source fitted with high-frequency arc-initiating equipment shall carry a warning
in a prominent position stating the following:
HIGH-FREQUENCY EQUIPMENT IS INSTALLED
VOLTAGES UP TO 6500 V MAY BE PRESENT WITHIN THE CABINET
DISCONNECT FROM POWER SUPPLY BEFORE REMOVING COVERS
FIGURE 3.2.8 INTERLOCK BETWEEN POWER SOURCE AND HIGH-FREQUENCY
ARC-INITIATING EQUIPMENT
3.3 ANCILLARIES
3.3.1 Electrode holders for MMAW
Electrode holders used for MMAW shall comply with AS 60974.11.
Where welding is carried out in a Category B or Category C environment or a position
where the welder may be injured by a fall, the electrode holder shall be a Type A as
specified in AS 60974.11.
Electrode holders shall have sound and crack-free insulation.
3.3.2 Plasma torches
Plasma torches shall comply with the relevant requirements of AS 60974.1.
3.3.3 Wire feeders
Whenever a welding circuit is energized, the wire feed mechanism, the wire path and the
welding wire are at electrode potential; thus, electric shock may result from contact with
any part.
Should welding wire short internally to the workpiece during welding, the welding wire will
become overheated and severe burns may follow inadvertent contact.
Covers should not be removed, as control voltages up to 115 V a.c. may be present.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
17 AS 1674.2—2007
www.standards.org.au © Standards Australia
S E C T I O N 4 E L E C T R I C A L C O N N E C T I O N S
4.1 CONNECTION TO ELECTRICITY SUPPLY
Power sources shall be connected to the electricity supply—
(a) via an approved supply flexible cord with plug and socket; or
(b) by a licensed electrical worker, if the power source is permanently connected to the
supply.
Power supply cords should be kept as short as possible.
Electrical wiring connecting a power source to an electricity supply, wiring connecting a
frame of a power source to earth and any permanent wiring connected to terminals to which
output leads are connected shall comply with the relevant requirements of AS/NZS 3000.
4.2 WELDING CIRCUIT CONNECTIONS
4.2.1 General
The connection of output leads is the responsibility of the welder. The power shall be
switched off when making such connections.
4.2.2 Welding leads
The following apply to welding leads:
(a) Welding leads shall conform to AS/NZS 1995.
(b) Welding leads should be kept as short as practicable.
(c) Welding leads shall be insulated and the insulation shall be in good repair. Where
high-frequency or similar devices are used, the insulation of the welding leads shall
be suitable for the high voltage.
(d) Welding leads longer than 9 m should not be used, unless the voltage drop of the
current used does not exceed the values in Clause 4.2.3.
(e) The nominal cross-sectional area of welding lead conductors needs to be increased as
the length is increased to compensate for cable voltage drop (see Clause 4.2.3).
NOTE: AS/NZS 1995 and WTIA Tech. Note 22 give guidance on the method of calculating
voltage drop and selection of an appropriate welding lead cross-section.
(f) Welding leads shall be fitted with appropriate terminals for connection to the
remainder of the welding circuit. The connection joint shall be clean and tight to
provide electrical continuity.
(g) Terminals and connections shall be fitted to welding leads by a competent person.
NOTE: It is highly recommended that the person’s competence for this task is assessed by a
licensed electrician. If the cables operate at 50 V a.c. or higher, the relevant State legislation
may require that this work be undertaken by a licensed electrician.
4.2.3 Voltage drop
The voltage drop in the leads and conductors comprising a welding circuit, with the
exception of an MMAW electrode lead attached to the electrode holder, should not exceed
1 V for each 7.6 m of cable, while carrying the rated-output current of the power source to
which they are connected.
The overall voltage drop of the conductors, leads and connections comprising a welding
circuit, while carrying output current, but excluding separately mounted current-limiting
devices, should not exceed 10% of the voltage at the power source terminals.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 18
© Standards Australia www.standards.org.au
4.2.4 Electrode leads for MMAW
Electrode leads for MMAW may consist of two or more sections, to provide for quick
disconnection in case of emergency. The first section should have the electrode holder
connected to one end and a suitable insulated plug connected to the other end. The length of
this lead should not exceed 9 m. The second section should have a terminal at one end for
connection to the welding terminal and a corresponding insulated socket at the other end.
The length of this lead should be kept as short as possible, in order to avoid voltage drop
and the risk of cable damage.
4.2.5 Permanently installed welding circuit wiring
In most cases, the welding circuit is connected by flexible leads, which are exposed and
constantly moved. Any welding circuit that is permanently fixed (that is, using cabling in
ducts, cable trays or rigid electrical conductors) shall be designed and fitted by a licensed
electrical worker in accordance with AS/NZS 3000.
4.2.6 Work lead and work conductor
The workpiece shall be soundly connected to the welding power source by an insulated
cable complying with Clause 4.2.2, or by permanently installed wiring complying with
Clause 4.2.5.
Both the work lead and the work conductor should be kept clear of conducting materials,
such as earth and metallic structures.
The work lead shall be soundly connected to the workpiece, as close to the welding as
possible. The current should not be routed through uninsulated conductors, such as the
workpiece, the bench or bare metal strips. It shall never be routed through gas or water
pipes. The work lead may carry the current from multiple power sources, in which case its
capacity shall be determined by a competent electrician, having in mind the duty cycle of
the welding process.
NOTE: Failure to connect the work lead properly will lead to stray current problems, which are
discussed in Paragraph A6, Appendix A.
The current-carrying capacity of the work lead and work conductor shall be not less than
that of the electrode lead and electrode conductor.
4.2.7 Welding circuit connections
The welder is normally responsible for connecting the welding circuit, except for the fitting
of permanently fixed parts of the circuit and the fitting of terminals to leads, which shall be
as detailed in Clauses 4.2.2 and 4.2.5.
The power source shall be switched off or otherwise isolated from the supply, before
making any connections to it.
Water-cooled torches shall not be connected to water mains. An isolated water circulation
system shall be used.
4.2.8 Confined spaces
Where welding is performed in a confined space as defined by AS/NZS 2865, provision
shall be made in close proximity to the observer, to allow the welding circuit to be quickly
broken. This shall be by one of the following methods, in order of priority:
(a) Switching off primary power to the welding machine either at the supply outlet or on
the welding machine.
(b) A whole current switch that breaks the circuit when activated (for example, a stop
button) in the electrode lead.
(c) A twist-lock connector in the electrode lead.
The chosen method shall be tested prior to the commencement of work.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
19 AS 1674.2—2007
www.standards.org.au © Standards Australia
4.3 EARTHING
A licensed electrical worker shall ensure the frame of the power source is earthed in
accordance with AS/NZS 3000.
Wherever possible, all parts of the welding circuit shall be insulated from earth. The work
leads shall be connected in accordance with Clause 4.2.6. Failure to do so could seriously
compromise the integrity of the surrounding electrical installation or surrounding
mechanical componentry.
Under no circumstances shall any earthing conductor of the mains electrical installation be
used in place of the work or return conductor or lead.
4.4 CONNECTING MULTIPLE POWER SOURCES TO A COMMON
WORKPIECE
4.4.1 General
The diagrams shown in this Section are illustrated guides that do not show all possible
connections or the equipment that controls and protects the power sources.
The voltage between the electrode holders or torches of power sources connected to the
same workpiece can be up to twice the normal open-circuit voltage. This occurs where any
of the following apply:
(a) d.c. power sources of different polarity are connected.
(b) a.c. power sources are connected with primary leads opposed or out of phase.
(c) a.c. power sources are connected with secondary leads opposed and primary leads in
phase.
Where primary circuits on any adjacent machines are in phase, the output terminal of a.c.
welding power sources shall be connected in phase.
Where practicable, adjacent power sources should be connected to minimize voltage
between electrode holders or torches. It is the duty of authorized personnel to ensure that an
electric shock due to simultaneous contact with two electrode holders will not occur. The
open-circuit potential difference between the electrode holders or torches of adjacent
welding power sources should not exceed the values specified in Clause 3.2.6, unless
positive means, such as screens or barriers, are provided to prevent physical contact
between the welding circuits. It is desirable that screens and barriers be constructed of
electrically insulating materials.
A voltmeter should be used to determine whether an excessive voltage exists between
adjacent electrode holders. Alterations to connections between a.c. power sources and the
power supply can correct this problem, but only a licensed electrical worker is permitted to
carry out these changes.
4.4.2 Installation of single-phase power sources to two-wire a.c. supply circuits
Where power sources are installed adjacent to each other or where welders are required to
work in close proximity to one another, the power sources shall be connected for similar
instantaneous polarity and have similar connections onto the supply circuit. This results in
zero voltage with no load (open circuit) between output terminals or between electrode
holders or torches, assuming each power source to have the same open circuit voltage (see
Figure 4.4.2(a)). Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 20
© Standards Australia www.standards.org.au
NOTE: Supply connections 1 and 2 are either active and neutral respectively of a single-phase supply, or two phases
of a three-phase supply, depending on the voltage for which the power sources are designed.
FIGURE 4.4.2 TWO-WIRE a.c. SUPPLY
Where two power sources of the same polarity are connected in a reverse manner to the
supply circuit (see Figure 4.4.2(b)), the open-circuit voltage between electrode holders or
torches will be twice the open-circuit power source voltage.
The voltage between two such power sources may be readily checked by a voltmeter or a
test lamp, while both power sources are switched on and both work leads connected
together. If there is a potential difference significantly higher than zero between output
terminals or electrode holders or torches of adjacent power sources, the polarity of one of
the power sources shall be reversed by reversing the supply lead connections (see C and D
in Figure 4.4.2(b)).
4.4.3 d.c. welding circuits
Where direct-current welding power sources are connected to their respective electrode
terminals and electrode holders with opposite polarity, the power source open-circuit
voltages are additive and the potential difference between the electrode holders could equal
twice the normal open-circuit voltage of each power source.
Where the power sources are installed adjacent to each other or where welders using the
power sources are required to work in close proximity to one another, either the power
sources shall be connected for similar polarity of electrode holders or screens, or barriers
shall be provided to prevent physical contact between the welders.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
21 AS 1674.2—2007
www.standards.org.au © Standards Australia
4.4.4 Installations on three-phase supply circuits
The following precautions should be observed for installations supplying a.c. connected on
three-phase supply circuits:
(a) Where welders using single-phase power sources are required to work in close
proximity to each other, it is preferable for their power sources to be of the same
polarity and connected to the same two phases of the three-phase supply circuit. The
voltage between two such power sources may be readily checked by a voltmeter or a
test lamp, while the power sources are switched on. (See Figure 4.4.4.)
(b) Where two welders using single-phase power sources are required to work in close
proximity to each other and the capacity of the supply circuit makes it necessary to
connect their respective power sources to different phases of the three-phase supply
circuit, terminals of similar polarity on each of the power sources should be
connected to the common phase. A check shall be made with a voltmeter to ensure
that the potential difference between the electrode holders or torches connected to the
respective power sources does not exceed the open-circuit voltage of the individual
power sources. If the terminals of the power sources are not of the same polarity, or
connections to the primary or secondary windings are reversed, a potential difference
of 1.73 times the open-circuit power source voltage may be obtained. (See
Figure 4.4.4(b).)
(c) Where three single-phase power sources are each connected to a different phase of a
three-phase supply circuit and any two of the power sources are close to one another
or the welders using these power sources form a group working adjacent to each
other, if the capacity of the circuit permits, the safe connections as shown in
Figure 4.4.4(c) should be observed. For power sources of similar polarity, these
connections result in—
(i) zero voltage between power sources 1 and 2;
(ii) open-circuit power source voltage between power sources 2 and 3; and
(iii) open-circuit power source voltage between power sources 3 and 1.
(d) Where three single-phase power sources (or multiples of three) are each connected to
a different phase of three-phase supply-circuit and it is desired to balance the load
over the three phases, the safest connections are as shown in Figure 4.4.4(d). For
power sources of similar polarity, these connections result in—
(i) open-circuit power source voltage between power sources 1 and 2;
(i) open-circuit power source between power sources 1 and 3; and
(ii) 1.73 times the open-circuit power source voltage between power sources 2 and
3, in which case screens or barriers should be provided to prevent physical
contact between welders using the power sources 2 and 3.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 22
© Standards Australia www.standards.org.au
FIGURE 4.4.4 (in part) CONNECTIONS TO THREE-PHASE SUPPLY CIRCUITS
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
23 AS 1674.2—2007
www.standards.org.au © Standards Australia
FIGURE 4.4.4 (in part) CONNECTIONS TO THREE-PHASE SUPPLY CIRCUITS
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 24
© Standards Australia www.standards.org.au
S E C T I O N 5 I N S P E C T I O N A N D
M A I N T E N A N C E
5.1 POWER SOURCE
5.1.1 Routine inspection and testing
An inspection of the power source, an insulation resistance test and an earthing resistance
test shall be carried out—
(a) for transportable equipment, at least once every 3 months; and
(b) for fixed equipment, at least once every 12 months.
The owners of the machine shall keep a suitable record of the periodic tests and a system of
tagging, including the date of the most recent inspection.
NOTE: A transportable power source is any equipment that is not permanently connected and
fixed in the position in which it is operated.
5.1.2 Insulation resistance
Minimum insulation resistance for in-service welding power sources shall be measured at a
voltage of 500 V between the parts referred to in Table 5.1.2. Power sources with an
insulation resistance less than that specified, shall be withdrawn from service and not
returned until repairs have been made.
TABLE 5.1.2
MINIMUM INSULATION RESISTANCE
Parts to be tested Minimum insulation
resistance (MΩ)
Input circuit (including control
circuits connected to it)
To Welding circuit (including control
circuits connected to it)
5
All circuits To Exposed conductive parts 2.5
Welding circuit (including control
circuits connected to it)
To Any auxiliary circuit which operates at
a voltage exceeding extra low voltage
10
Welding circuit (including control
circuits connected to it)
To Any auxiliary circuit which operates at
a voltage not exceeding extra low
voltage
1
Separate welding circuit To Separate welding circuit 1
Any control or auxiliary circuit connected to the protective conductor terminal shall be
considered as an exposed conductive part for the purpose of this test.
Conformity shall be checked by the stabilized measurement of the insulation resistance
without interference suppression or protection capacitors by application of a d.c. voltage of
500 V at room temperature.
NOTE: Solid state electronic components and their protective devices may be short-circuited
during the measurement.
A1
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
25 AS 1674.2—2007
www.standards.org.au © Standards Australia
5.1.3 Earthing
The resistance shall not exceed 1 Ω between any metal of a power source, where such metal
is required to be earthed, and—
(a) the earth terminal of a fixed power source; or
(b) the earth terminal of the associated plug of a transportable power source; or
(c) the neutral terminal, if applicable (e.g. to confirm the integrity of the MEN link in
engine driven power sources).
NOTE: Because of the dangers of stray output currents damaging fixed wiring, every 12 months
the integrity of fixed wiring should be inspected by a licensed electrical worker in accordance
with Clause 5.1.1.
5.1.4 Repairs
Electrical work inside a welding power source shall be undertaken by a licensed electrical
worker.
5.2 ACCESSORIES
Accessory equipment, including output leads, electrode holders, torches, wire feeders and
the like, shall be inspected at least monthly by a competent person, to ensure that the
equipment is in a safe and serviceable condition. Unsafe and unserviceable accessories shall
not be used.
A1
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 26
© Standards Australia www.standards.org.au
APPENDIX A
TYPICAL ELECTRICAL HAZARDS
(Informative)
A1 SCOPE
This Appendix sets out to—
(a) create an understanding as to how electric shocks are received, so that welders may
be able to avoid them;
(b) describe the conditions that increase or decrease the severity of electric shocks; and
(c) explain the dangers of stray welding currents and how to avoid them.
A2 COURSES OF INSTRUCTION
Welding personnel should be given appropriate training in first aid.
Courses of instruction are available, including those provided by the following
organizations:
(a) Ambulance authorities.
(b) Australian Red Cross.
(c) National Heart Foundation Australia.
(d) Royal Life Saving Society Australia.
(e) St John Ambulance Australia.
(f) Surf Life Saving Australia.
NOTE: Further information about the physiological affects of electric shock on the human body is
given in WTIA Tech. Note 22.
A3 GENERAL
The operation of electric arc welding and allied process equipment is comparatively safe;
however, there are a number of electrical hazards that may cause electric shock and fire.
These hazards should be recognized by welders, to ensure safe operation.
Most welders have experienced electric shocks from welding circuits. Fortunately, the
majority of these shocks are only an unpleasant experience. Some electric shocks may cause
temporary injury, such as difficulty in breathing, heart rhythm disturbances, increase in
blood pressure or nerve damage. Often, shock is enough to cause secondary injury, such as
a fall from a height or a striking injury as a result of a sudden muscle spasm. In a few cases,
the result is death by electrocution. The most usual cause of such deaths is ventricular
fibrillation, when the heart rhythm is disrupted or stopped. Very small currents in the region
of the heart can cause this effect. Some deaths result from asphyxia, due to paralysis of the
lung or diaphragm muscles.
All parts of welding circuits, including output leads and work return paths, should be
considered electrically alive. Consequently, welders should ensure that no part of their body
is placed in such a position as would complete a conductive path for the passage of electric
current.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
27 AS 1674.2—2007
www.standards.org.au © Standards Australia
A4 POWER SOURCES
A4.1 General
Power sources include transformers, rectified transformers, inverters and electric motor
generators that are connected to a 415 V supply and diesel or petrol motor generators. They
may be designed for MMAW and similar processes with a drooping characteristic or for
GMAW and FCAW with a flat characteristic. Power source for SAW may have a flat or a
drooping characteristic.
Power sources should be in sound condition, properly installed, regularly inspected and
maintained in good working order.
A4.2 Open-circuit voltage
Although arc welding power sources are capable of supplying a wide range of current, they
generally operate within the following voltage ranges:
(a) For a.c. power sources, 40 V to 80 V.
(b) For d.c. power sources, 20 V to 100 V.
Power sources for MMAW and similar processes supply a higher open-circuit voltage
between the electrode and the work, when the welding power source is switched on and
ready to commence welding. These power sources have a drooping characteristic, with the
open-circuit voltage higher (often 60 V to 80 V) than when the arc is established and
welding current is drawn (20 V to 35 V). Consequently, the greatest danger occurs while
handling electrodes and the electrode holder between welding operations, such as while
changing electrodes.
Power sources for GMAW and FCAW have a flat characteristic, generally with a lower
open-circuit voltage (30 V to 50 V). Also, the current is turned on and off by a gun trigger,
which also controls the wire feed. Therefore, the welder is not exposed to open-circuit
voltage, unless the trigger is turned on and the wire is feeding. Also, electrodes are not
changed as frequently as for MMAW.
A4.3 Plasma welding and cutting
Plasma-arc welding is relatively safe, as the voltages are similar to other welding processes.
However in plasma-arc cutting, open-circuit voltages generally range up to 500 V d.c.
Plasma cutting equipment is designed so that the operator is not exposed to these voltages.
Welders and maintenance personnel should be aware that if plasma-arc cutting equipment is
mishandled, the higher voltages present a high risk.
Connecting the work cable to the workpiece as close as possible to the area being worked
upon and never touching the workpiece whilst cutting, minimizes the risk of electric shock
during the plasma cutting process.
A5 SECONDARY CIRCUITS
A5.1 General
An electric shock can be received when a person’s body is simultaneously in contact with
any exposed part of a secondary circuit electrode conductor and any metal or conducing
material connected to the work terminal. Figure A1(a) shows a safe situation, as well as an
unsafe situation with possible current paths through the welder’s body, while making
simultaneous contact with the electrode and the return circuit connection. This situation can
be fatal and can be avoided by observing safe working procedures.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 28
© Standards Australia www.standards.org.au
The most exposed point of the electrode conductor in MMAW is the electrode tip, but
electrode coatings may also conduct electricity and should not be considered as safe
insulation. Damaged electrode holders, cables, connections and electrode core wire that is
bared by bending the electrode may also expose the welder to the circuit. GMAW, GTAW
and FCAW guns are generally better protected; however, the electrode tip may still be live.
Handling the gun and electrode with dry, hole-free gloves is essential.
Contacting the workpiece may be almost unavoidable. Usually the workpiece is in contact
with earth, either directly or via building structures and concrete floors. Floors (especially
when damp) and any other conducting materials with which the work is in contact may
become part of the welding circuit. Often the workpiece is a large structure, in which case
the welder and sometimes the welding power source are in direct contact with it.
The severity of an electric shock depends upon the following interrelated factors:
(a) The magnitude of the current flowing through the body.
(b) The path of the current passing through the body.
(c) The duration of the shock.
(d) The type of voltage supply (i.e., a.c. or d.c.).
(e) The reaction to shock by the victim.
A5.2 The magnitude of current flowing through a body
The amount of current that flows in an electrical circuit depends upon the applied voltage
and the electrical resistance of the circuit. The higher the voltage, the greater the amount of
current that will flow through any given resistance. Conversely, for a given voltage the
higher the resistance, the lower will be the flow of current.
In the event of a person touching an active conductor or electrode at the same time as
touching the work or return conductor with another part of the body, a circuit is completed
through the body and the amount of current that will flow depends upon the resistance that
the body offers to the applied voltage. The amount of current necessary to kill is only of the
order of 0.02 A. Welding circuits are designed to operate at thousands of times this level.
No protection is offered to welders in contact with the secondary circuit, by residual current
devices, fuses or earth leakage contact breakers fitted to the primary circuit of a welding
power source.
In general, the wetter the person’s skin and the larger the surface area of body contact, the
higher will be the current flowing through the body and, therefore, the greater will be the
risk of electrocution. In a Category B situation, voltages of the order of 48 V a.c. or more
may cause fatal shocks. Where there is dampness or perspiration, 25 V a.c. may be enough
to give a fatal shock.
The severity of electric shock is minimized by wearing dry gloves, rubber-soled shoes and
dry clothing, even if the body is damp and perspiring. The use of cotton liners that are
frequently changed to avoid welding gloves becoming saturated with perspiration is highly
recommended. Standing or sitting on a dry wooden floor, a dry rubber mat or similar
insulating material further enhances safety. Wherever practicable, insulating material
should be of a flame retardant type. The combined high resistance of insulating materials
offers a high degree of protection against shock; however, if body contact is made through
wet clothing, wet footwear or direct skin contact, with metal or other good conducting
material, the risk of electrocution is greatly increased. Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
29 AS 1674.2—2007
www.standards.org.au © Standards Australia
FIGURE A1 TRANSFORMER TYPE WELDING CIRCUIT
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 30
© Standards Australia www.standards.org.au
A5.3 The path of current through a body
The most likely cause of death by electrocution is ventricular fibrillation (a disruption of
electrical stimulus of the heart muscle) causing its failure or muscle paralysis, leading to
respiratory arrest. Consequently, an electric shock through any part of the torso or the head
is regarded as serious. Where the entry and exit positions are remote from the torso or head,
there is a greater chance of survival.
A5.4 The duration of shock
The time during which current continues to flow through the body has a most important
bearing on survival. When breathing is disrupted or ventricular fibrillation occurs, death is
not instantaneous, but a few minutes delay may be fatal. The immediate isolation of the
power source is vital and prompt removal from the danger and treatment may save the
person’s life.
A5.5 The type of voltage supply
Alternating voltages are much more likely to cause serious shocks than direct voltages of
similar or higher magnitudes. The minimum direct current necessary to cause ventricular
fibrillation is three to five times the minimum level of alternating current at 50 Hz. Even
comparatively small currents are found to exercise a paralyzing effect on muscles, causing a
victim’s grip to tighten and make self-release difficult or impossible.
The threshold of perception and the threshold of reaction are significantly higher for d.c.
currents. AS/NZS 60479.1 uses an average value of 10 mA as the threshold of let-go for a.c.
currents. The threshold of let-go is defined as the maximum value of current at which a
person holding electrodes can let go of the electrodes. This means that in consideration of
the hazards associated with the use of a.c. power sources vs d.c. power sources it is a.c.
currents that approach the threshold of let-go that could lead to fatalities, rather than the
considerably higher currents that are considered to be the threshold of ventricular
fibrillation.
The threshold of let-go depends on several parameters, such as the contact area, the shape
and size of the electrodes and also on the physiological characteristics of the individual.
An average value of about 10 mA is assumed.
Unlike a.c. there is no definable threshold of let-go for d.c. Only the making and breaking
of current lead to painful and cramp-like contractions of the muscles.
A5.6 The reaction to shock
Reaction to a shock may make a victim suffer an instinctive muscle spasm, causing the
victim to move involuntarily. This can lead to a victim striking a nearby object or falling
from a height. Electric shocks can cause nerve damage and internal burns. The physical
condition of a victim has a bearing on the severity of a shock; however, even young
physically-healthy people have suffered electrocution from welding equipment.
A6 STRAY CURRENT
Where a welding circuit has a high electrical resistance, voltages are created, which may
cause currents to stray. This often occurs if leads, and in particular the return lead, are
poorly connected or become disconnected. In such a case, when a welder tries to strike the
arc, but it fails to ignite, the voltage of the workpiece is raised. This may cause a current to
find an alternate path back to the power source. The path it takes depends on the
circumstances and strange effects can occur, particularly if the workpiece is large, such as a
steel building or a ship.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
31 AS 1674.2—2007
www.standards.org.au © Standards Australia
Stray currents can cause the following problems:
(a) The current can track through other equipment not intended to carry welding current
and cause it to overheat and be damaged. Damage to lifting chains, wire-rope slings,
motor bearings, gearboxes and similar equipment has occurred in this way.
(b) The current can cause rapid corrosion to pipelines if it tracks through earth or water
containing these components. Rapid corrosion of a ship’s structure or of any structure
in contact with wet areas may occur in the same way.
(c) The current can cause burning out of electric wiring of equipment connected to the
workpiece, including the earth wiring, which may leave the equipment unprotected.
Destruction of the primary earth lead of power sources, power tools, lighting and
other equipment that is in contact with the workpiece has occurred.
(d) The current exposes others in contact with the workpiece to electric shocks, such as
the assistant holding a piece that is being tacked in place, or another worker at a
remote location.
(e) Poor connections in the circuit may overheat, which can cause overheating of
flammable materials, resulting in a fire. Electric wiring insulation in contact with
these hot spots can melt, allowing persons to contact mains voltages. Hoses
containing flammable gas or oxygen can melt, causing a hazardous leakage.
(f) Stray arc strikes at poor connection points can cause cracking of some metals.
A7 ELECTROMAGNETIC FIELDS AND PACEMAKERS
A7.1 General
Safe practices are particularly important to people wearing implanted pacemakers. Welders
who have been fitted with an implanted pacemaker and have decided to continue to cut or
weld should minimize their exposure to electric fields and magnetic fields and should
follow additional procedures (see Paragraphs A7.2 and A7.3), including adhering to any
advice from a doctor.
Some researchers have reported that exposure to electric fields or magnetic fields may
cause leukaemia or other illnesses. These claims originally arose in relation to high-voltage
electric power lines, but are very much in dispute in the medical and scientific arena. The
best precaution is to minimize any exposure to electric fields and magnetic fields. Any
advice by doctors should be heeded.
These procedures will not eliminate exposure to electric fields and magnetic fields or the
possibility of arc welding or plasma cutting having an effect on a pacemaker; however, they
will significantly reduce exposure to electric fields and magnetic fields.
It is not clear whether exposure to electric fields and magnetic fields can affect a person’s
health. Electric fields and magnetic fields have the following properties:
(a) They are created when electric current flows through a conductor.
(b) The field strength of direct current (d.c.) is relatively constant and does not change.
(c) The field strength of alternating current (a.c.) constantly changes.
(d) The greater the current flow (‘amps’), the stronger the field created by the current.
(e) The closer the conductor or electrical device is to the body, the greater the exposure
to the field.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 32
© Standards Australia www.standards.org.au
A7.2 Minimizing exposure
Welders should use the following procedures to minimize exposure to electric fields and
magnetic fields:
(a) Position the torch or electrode and work cables together. Secure them with tape if
possible.
(b) Do not coil any torch or electrode lead around the body.
(c) Do not place the body between the torch or electrode and the work cables. Where the
torch or electrode cable is on the right side, position the work cable on the right side.
(d) Connect the work cable to the workpiece as close as possible to the area being worked
on. This is also good practice that will reduce the occurrence of poor work
connections, which is a common problem in welding and plasma cutting.
(e) Do not work next to a power source.
A7.3 Welders with pacemakers
Electrical fields in plasma cutting and arc welding can interfere with a pacemaker’s
function. Generally, such interference does not permanently damage the pacemaker. Once a
wearer leaves an arc welding environment or stops cutting or welding, the pacemaker
should operate normally. Welding arcs have little or no affect on the operation of some
types of pacemaker, especially designs that are bi-polar or designed to filter out such
interference.
Anyone who works near to electrical equipment and is going to be fitted with a pacemaker,
particularly a welder who wishes to continue plasma cutting or arc welding, should seek
advice from a doctor as to which would be an appropriate type of pacemaker to select. This
and any other questions should be discussed with a doctor, whose advice should be
followed. The doctor may wish to contact the manufacturer of the pacemaker for a
recommendation.
The design of pacemakers significantly affects the degree to which they are subject to
interference by a plasma or a welding circuit. The pacemaker should be insensitive to
interference from arcs, while still being medically suitable for the welder.
In addition to normal safety precautions, welders fitted with a pacemaker should adopt the
following additional procedures.
(a) Use gas cutting or gas welding where such a process is appropriate.
(b) Use the lowest current setting suitable for the application. Do not weld with more
than 400 A. Low (75 A to 200 A) direct current (d.c.) welding should be used if arc
welding is necessary. Do not use GTAW welding with a high frequency.
(c) Do not use repeated short cuts or welds. Wait about 10 s after stopping one cut or
weld, before starting the next. If having difficulty starting, do not re-strike repeatedly.
Find out the problem, then try again.
(d) If feeling light headed, dizzy or faint, immediately stop work, lay the torch or
electrode holder down so that it does not contact the work and move away from any
arcs. Work should be arranged in advance, so that, should dizziness develop and the
torch or electrode holder is dropped, the electrode will not fall on the body or strike
the work.
(e) Do not work on a ladder or other elevated position or in a cramped or confined place.
(f) Do not work alone. Work only in the presence of a person who understands the
precautions that should be observed and the possible effect that welding may have on
a pacemaker.
(g) Do not work near spot welding equipment.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
33 AS 1674.2—2007
www.standards.org.au © Standards Australia
A welder should not rely on the fact that another welder with a pacemaker had gone on for
years without experiencing a problem. That person and pacemaker may have operated in a
different situation, which may not be relevant.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 34
© Standards Australia www.standards.org.au
APPENDIX B
FATAL ELECTRICAL ACCIDENTS
(Informative)
B1 INTRODUCTION
Open circuit voltages of less than 80 V a.c. are generally considered safe when working
under Category A environments.
When working in a Category B or a Category C environment, the risk is substantially
increased. Unfortunately, under these conditions, fatal accidents have occurred, even
though the welders have been in good health. The possibility of coming into contact with a
higher voltage on the supply side of a mains-operated power source should also be
considered. The circumstances of some fatal accidents are described below.
NOTES:
1 Many of these incidents involve a.c. power sources and MMAW in circumstances that do not
comply with this Standard.
2 It should be stressed that in most cases the equipment was examined and found to be in good
working condition.
B2 BOILER WELDING
The following three fatal accidents occurred to welders while they were working inside a
boiler, which would now be regarded as a Category C environment:
(a) Figure B1 shows a welder leaning against a boiler wall while fitting a new electrode.
While being fitted, the electrode slipped and touched the welder’s neck. After the
accident, current marks were found on the neck, back and soles of the feet.
Consequently, the current flow would have been from the neck through the torso to
the back and feet. While working in the closed room, the welder’s working clothes
had become soaked with perspiration, thus establishing a very good electric
connection to the boiler wall. The total resistance was estimated as being
approximately 250 Ω at the moment of the accident, and with a no-load voltage of
65 V at the transformer, the current would have been approximately 260 mA.
Currents of this magnitude can only be endured for up to 0.5 s but as the influence
would seem to have been of longer duration, the welder died.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
35 AS 1674.2—2007
www.standards.org.au © Standards Australia
FIGURE B1 ELECTRODE TOUCHING WELDER’S NECK ALLOWING
CURRENT TO PASS THROUGH THE TORSO TO THE BACK AND FEET
(b) Figure B2 shows a welder leaning back on a boiler wall, holding the electrode holder
under the arm. The perspiring back and armpit, in connection with an uninsulated
welding handle, caused current to flow from the armpit to the back. Because of the
small resistance at the contact points and the short current path, the resistance was
estimated at some 250 Ω at the moment of the accident. At a no-load voltage of 70 V
to 80 V, the current would have been approximately 300 mA. This proved fatal.
FIGURE B2 ELECTRODE UNDER WELDER’S ARM
CAUSING CURRENT FLOW FROM ARMPIT TO BACK
(c) A faulty cable caused this accident. Figure B3 shows a welder leaning a perspiring
back against the boiler wall. While touching the faulty cable, the welder received a
cramp and pressed the cable against the chest. Thus a chest-to-back electric contact
was established. The resistance was estimated to have been approximately 200 Ω and,
at a voltage of 70 V, the current was approximately 350 mA at the moment of the
accident. This proved fatal.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 36
© Standards Australia www.standards.org.au
FIGURE B3 FAULTY CABLE CAUSING CURRENT
FLOW FROM CHEST TO BACK
B3 WORKING ON BOARD A SHIP
The following two fatal accidents occurred to welders while working on board a ship, in a
Category C environment (see Clause 1.3.6.3):
(a) Figure B4 shows a welder working in a vent shaft of a ship being built, while
kneeling at the bottom of the vent shaft where pools of rainwater collected after it had
rained. While fitting a new electrode, the electrode slipped and hit near one eye. After
the accident, current marks were found on the welder’s knees and in the eye region.
Since the knees presented a comparatively small area, a comparatively large pressure
(approximately 85 percent of the body weight) had been pressed down against the
moist metal base. The contact resistance was low and the total resistance was
estimated at approximately 600 Ω at the moment of the accident.
At a no-load voltage at the welding transformer of 75 V, the current was calculated at
approximately 125 mA at the moment of the accident.
NOTE: A current of 125 mA is dangerous to life if it flows for more than 0.8 s.
FIGURE B4 ELECTRODE MAKES CONTACT WITH FACE CAUSING CURRENT FLOW
THROUGH TORSO TO KNEES
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
37 AS 1674.2—2007
www.standards.org.au © Standards Australia
(b) Figure B5 shows a welder lying on a raft, carrying out repair work on the outside of a
ship’s hull. To assist the welder and ensure that no accident would occur, an assistant
had been placed on a ladder close to the welder. The welder was finishing the work
when a large wave flooded the raft and the welder. The startled welder dropped the
electrode and holder onto the chest, causing an electric contact to be established
through the body and the salt water. The welder fell into the water, but was soon
pulled out onto the raft by the assistant, who immediately administered artificial
respiration; however, the welder could not be saved. The resistance in the circuit was
estimated at approximately 700 Ω and, at a no-load voltage of 70 V, the current was
approximately 100 mA. This was sufficient to cause a fatality.
FIGURE B5 WELDER ON RAFT FLOODED BY WAVE
B4 WELDING OUTDOORS
Figure B6 shows an accident during outdoor welding work. The welder and the assistant
were both standing on a base that was electrically connected to the welding transformer
work return lead. It was raining, so it was a Category C environment (see Clause 1.3.6.3).
The assistant handed a metal object to the welder and, at the moment the welder touched it,
both received an electric shock. Through analysis of the current marks, it was found that the
current had passed through the assistant’s footwear, the assistant’s body, the metal object
and the welder’s body to the electrode where the insulation was poor. Due to the many
contact resistances and the comparatively long current path, the total resistance was
estimated at 1900 Ω. Since the transformer no-load voltage was 67 V, the current would
have been approximately 35 mA. Currents of this magnitude are usually regarded as being
harmless. In this case, the assistant got off with a shock, whereas the welder died. This
demonstrates that two people may react differently to the same current influence and that
consideration should be given to the varying body build and health condition of different
people. The welder may have had a non-recognized heart condition, which proved decisive
to the course of the accident when exposed to the current.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 38
© Standards Australia www.standards.org.au
FIGURE B6 WELDER HOLDING ELECTRODE IS HANDED METAL OBJECT BY
ASSISTANT CAUSING CURRENT FLOW THROUGH THEM BOTH
B5 PULLING A CABLE
Figure B7 shows a welder pulling a live cable up to the welding point by putting it over the
shoulder. Due to a faulty cable insulation and poor footwear insulation, the welder received
an electric shock and fell. Thus, contact was established from the head and chest to the
cable on the shoulder. The resistance was estimated at approximately 200 Ω at the moment
of the accident and, at a no-load voltage of 67 V, the current would have been
approximately 335 mA. This proved fatal.
FIGURE B7 WELDER PULLED FAULTY CABLE OVER SHOULDER AND RECEIVED
FATAL SHOCK
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
39 AS 1674.2—2007
www.standards.org.au © Standards Australia
B6 FATAL ELECTRICAL ACCIDENT INVOLVING MAINS VOLTAGE
Figure B8 shows the power supply cord resting on an overhead terminal of a power source.
The PVC insulation of the power supply cord melted, allowing the active conductor of the
cord to contact the work terminal, thus energizing the welding circuit and the work at mains
voltage.
The welder, who was barefooted, touched the work with the hand, and a circuit was
completed through the body to earth.
At a voltage to earth of approximately 240 V, the current that flowed through the body
proved fatal.
FIGURE B8 MAINS SUPPLY ELECTROCUTES WELDER THROUGH HOT TERMINAL
ON POWER SOURCE MELTING INSULATION
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
AS 1674.2—2007 40
AMENDMENT CONTROL SHEET
AS 1674.2—2007
Amendment No. 1 (2011)
CORRECTION
SUMMARY: This Amendment applies to Clauses 5.1.2 and 5.1.3.
Published on 15 February 2011.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
Standards Australia Standards Australia develops Australian Standards® and other documents of public benefit and national interest. These Standards are developed through an open process of consultation and consensus, in which all interested parties are invited to participate. Through a Memorandum of Understanding with the Commonwealth Government, Standards Australia is recognized as Australia’s peak non-government national standards body. Standards Australia also supports excellence in design and innovation through the Australian Design Awards. For further information visit www.standards.org.au Australian Standards® Committees of experts from industry, governments, consumers and other relevant sectors prepare Australian Standards. The requirements or recommendations contained in published Standards are a consensus of the views of representative interests and also take account of comments received from other sources. They reflect the latest scientific and industry experience. Australian Standards are kept under continuous review after publication and are updated regularly to take account of changing technology. International Involvement Standards Australia is responsible for ensuring the Australian viewpoint is considered in the formulation of International Standards and that the latest international experience is incorporated in national Standards. This role is vital in assisting local industry to compete in international markets. Standards Australia represents Australia at both the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC). Sales and Distribution Australian Standards®, Handbooks and other documents developed by Standards Australia are printed and distributed under license by SAI Global Limited.
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing
For information regarding the development of Standards contact: Standards Australia Limited GPO Box 476 Sydney NSW 2001 Phone: 02 9237 6000 Fax: 02 9237 6010 Email: [email protected] Internet: www.standards.org.au For information regarding the sale and distribution of Standards contact: SAI Global Limited Phone: 13 12 42 Fax: 1300 65 49 49 Email: [email protected]
ISBN 0 7337 8142 X
Lice
nsed
to D
awso
ns E
ngin
eerin
g on
16-
Oct
-201
7. 1
con
curr
ent u
ser
netw
ork
licen
ses.
Cop
ying
of 5
0% o
nly
for
inte
rnal
use
doc
umen
ts p
erm
itted
.G
et p
erm
issi
on to
cop
y fr
om o
r ne
twor
k th
is p
ublic
atio
n w
ww
.sai
glob
al.c
om/li
cens
ing