AIR CORE REACTORS
Shunt Reactorsin Power Systems
Tech News
AREVA T&D’s Expertise
FORWARD
During normal operation of an electrical power system, the transmission and distribution voltages must be maintained within a small range, typically, from 0.95 to 1.05 pu of rated value. Due to the load variations, shunt reactors and capacitors have been applied in power systems to compensate excess reactive power (inductive for heavy load conditions, and capacitive for light load conditions). Shunt reactors are commonly used to compensate the capacitive reactive power of transmission and distribution systems and thereby to keep the operating voltages within admissible levels.
The purpose of this document is to present some information about the application and specifi cation of shunt reactors for electrical power systems.
AREVA T&D’S TECHNOLOGY AND
EXPERIENCE
AREVA T&D has more than 30 years of experience in designing and manufacturing air-core dry-type reactors (ACR) for various market segments around the world, including power generation, transmission and distribution systems, industrial plants, OEM and electrical test laboratories. Reactive shunt compensation is one of the most common applications of air-core reactors.
Air-core shunt reactors are applicable to system voltages up to 72,5 kV and typically they are connected to tertiary winding of large power transformers. Due to the required ratings, the ACR for this application are designed in fi berglass encapsulated technology.
In fi berglass encapsulated technology, the reactor’s winding consists of numerous insulated aluminum connected in parallel. These conductors are mechanically immobilized and encapsulated in epoxy impregnated fi berglass fi laments forming cylinders. Depending on the reactor’s ratings, one or more of these cylinders are connected in parallel between the aluminium spiders. The individual cylinders are separated by fi berglass spacers, which form the cooling ducts of the coil.
The benefi ts in using AREVA T&D air-core shunt reactors are:
> Maintenance free and environmentally friendly > Conservative temperature rise for extended service life > Customized space saving solutions for installation in
compact areas > Surface treatment for protection against UV radiation
and pollution > High mechanical strength to withstand elevated
short-circuit forces > Low noise level for sensitive applications
In the following sections general information will be presented about the application of shunt reactors to electrical power systems and two different ways to specify the required ratings of the equipment(MVAr ratings).
APPLICATION OF SHUNT REACTORS
The calculation of optimum ratings and points of connection of shunt reactors is generally done by means of extensive load fl ow studies, taking into account all possible system confi gurations. One approach for a single line is presented below.
Depending on system voltage, shunt reactors may be inserted directly connected to station busbars (Pos. 1), to transmission line terminations (Pos. 2) or connected to tertiary winding of large power transformers (Pos. 3), as shown in the picture 1.
The majority of shunt reactors for system voltages of 72,5 kV or above are in the 30 to 300 MVAr range (threephase power) and they are normally connected directly to high voltage busbar or transmission line ending. For these voltage levels, reactors are most commonly oil-fi lled type. Future reactors in the range 72,5 to 145 kV will tend to be air-core dry-type coil units.
Shunt reactors rated below 72,5 kV are either oil-fi lled or air-core dry-type units and they are normally connected to the tertiary winding of large power transformers. The range of reactive power varies from a few MVAr to 100 MVAr.
The winding connection of three-phase reactors or a bank of three single-phase units can be either wye (most common confi guration) or delta. Typically, for system voltages of 72,5 kV or above, the reactors are wye connected with the neutral grounded directly or through a neutral reactor (also named “four reactor scheme”). For system voltages below 72,5 kV, thereactors are wye connected with the neutral ungrounded.
Picture 1 – Shunt reactor application in power systems
Picture 2 – Winding connection of shunt reactors
Pos. 2 Pos. 2
Pos. 1
Pos. 3
)emehcSrsotcaeR ruoF( noitcennoc eyW
XR
XNEUTRAL
noitcennoc atleD
XR
MAIN CALCULATION OF SHUNT REACTORS
For the calculation of the positive sequence reactance and the current requirements of a shunt reactor, it is necessary to know only the rated three-phase reactive power and the rated system voltage and frequency, as summarized in the table below.
The zero sequence reactance (X0) depends on the winding connection and grounding of the shunt reactor. For air-core dry-type units, it can be calculated as follow:
Neutral reactors generally are used in shunt reactors installed in transmission line terminations to provide a faster extinguishing of the secondary arc current and, therefore, to allow the automatic reclosing of the transmission line after a fault elimination (typically, the reclosing time varies from 0.5 to 1.5 seconds).
OPEN-CIRCUIT OPERATION OF RADIAL
TRANSMISSION LINES
The operation of a lossless radial transmission line, which is energized by a generator at the sending ending (V1) and is open-circuited at the receiving ending (V2), can be represented in the matrix form by the ABCD parameters, where I2 = 0.
Inserting shunt reactors at the receiving ending, the ABCD parameters of the line are changed, as described below:
So, the relation between the ending voltages of the transmission line is given by:
Application Example
Consider a lossless radial transmission line, frequency 60 Hz, length ℓ = 350 km, and parameters z = j 0,32886 Ω/km and bC = j 5,097 µS/km. To estimate the reactive power of shunt reactors to be installed in the transmission line to provide a maximum operating voltage of 1.05 pu at the open-circuited terminal (receiving ending), when the line is energized with 1.0 pu in the sending ending.
Solution:
> Total impedance and admittance of the non-compensated transmission line
RATING WYE CONNECTION DELTA CONNECTION
Reactance
Rated Current
Maximum Continuous Current(Design Current)
Parameters > rated reactance per phase (positive sequence) > rated three-phase reactive power > rated reactive power per phase > rated system voltage > maximum system operating voltage > rated current > maximum continuous current
> Wye connection with neutral directly grounded
> Wye connection with neutral grounded through a reactor
> Wye connection with neutral ungrounded
> Delta connection
+
Pro
duc
ts-L
4PS
-Shu
nt r
eact
or-7
1695
-V1-
EN
- ©
- A
RE
VA -
200
7. A
RE
VA, t
he A
RE
VA lo
go a
nd a
ny a
ltern
ativ
e ve
rsio
n th
ereo
f are
tra
dem
arks
and
ser
vice
mar
ks o
f AR
EVA
.A
ll tr
ade
nam
es o
r tr
adem
arks
men
tione
d h
erei
n w
heth
er r
egis
tere
d o
r no
t, a
re t
he p
rop
erty
of t
heir
owne
rs. -
389
1919
82 R
CS
PA
RIS
Our
pol
icy
is o
ne o
f con
tinuo
us d
evel
opm
ent.
Acc
ord
ingl
y th
e d
esig
n of
our
pro
duc
ts m
ay c
hang
e at
any
tim
e. W
hils
t ev
ery
effo
rt is
mad
e to
pro
duc
e up
to
dat
e lit
erat
ure,
thi
s b
roch
ure
shou
ld o
nly
be
rega
rded
as
a gu
ide
and
is in
tend
ed fo
r in
form
atio
n p
urp
oses
onl
y. It
s co
nten
ts d
o no
t co
nstit
ute
an o
ffer
for
sale
or
advi
se o
n th
e ap
plic
atio
n of
any
pro
duc
t re
ferr
ed t
o in
it. W
e ca
nnot
be
held
res
pon
sib
le fo
r an
y re
lianc
e on
any
dec
isio
ns t
aken
on
its c
onte
nts
with
out
spec
ifi c
advi
ce.
> Parameter A:
> Operating voltage at the receiving ending of the non- compensated transmission line
> Calculation of the shunt reactor reactance:
> Calculation of the three-phase reactive power of the shunt reactor:
> Calculation of the compensation degree of the transmission line:
In order to make possible line energization on both sides, it is recommended to install shunt reactors with similar ratings in their two terminations.
> The line charging of the transmission line is:
So, compensation degree is:
BUSBAR VOLTAGE VARIATION AFTER
SWITCHING OF SHUNT REACTORS
Typically, the voltage variation at the high voltage busbar after switching of a shunt reactor shall not be higher than 2 to 3% of rated voltage. A practical circuit is used to simplify the analysis of voltage control (see picture 3). The determination of the shunt
reactor to provide a required voltage variation in the busbar can calculated through the short-circuit power of system at the busbar where the reactor will be connected.
The shunt reactor rating is given by:
Application Example
To estimate the reactive power of shunt reactors to installed in the 34.5 kV busbar in order to reduce the voltage level from 1.02 to 0.99 pu, considering a fault current of 25 kA (or short-circuit power of 1495 MVA).
Solution:
> Calculation of the three-phase reactive power of the shunt reactor:
Remark:
> In the analysis above, it is not considered the on tap changer (OLTC) operation of power transformers near to the point of connection of the shunt reactors, which occurs in a few minutes after the shunt reactor switching.
CONCLUSIONS
AREVA T&D is able to supply air-core shunt reactors to provide reactive power compensation for electrical systems with rated voltages up to 72,5 kV and three-phase ratings up to 100 MVAr.
AREVA T&D’s air-core shunt reactors are maintenance free, environmentally friendly and maintain a conservative temperature rise offering an extended service life.
To request technical information, please contact us by e-mail:[email protected]
Picture 3 – Practical circuit for voltage control analysis
V1
V2S CC
S R3Ø
MVAr
MVAr
MVAr
AREVA T&D Worldwide Contact Centre:
www.areva-td.com/contactcentre/
Tel. : +44 (0) 1785 250 070
www.areva-td.com